Plan Review Details - Permit 05110191
Plan Review Stops For Permit 05110191
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-12-21 Cont ID  
Sent By alange Date 2005-12-21 Time 14:08 Rev Time 1.66
Received By alange Date 2005-12-21 Time 12:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-01 Cont ID  
Sent By alange Date 2005-12-01 Time 15:43 Rev Time 2.00
Received By alange Date 2005-12-01 Time 14:50 Sent To  
Notes
2005-12-01 00:00:00DENIED
  
 1.ALL PLANS SUBMITTED AFTER OCTOBER 1,
 2005 SHALL BE DESIGNED TO THE 2004
 BUILDING, PLUMBING, MECHANICAL AND
 ACCESSABILITY CODES.SHOW ALL CODE
 REFERENCES ON PLANS TO COMPLY WITH THESE
 CODES.
  
 2. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 3.SHOW BUILDING CONSTRUCTION
 CLASSIFICATION TYPE OF BUILDING 2004 FBC
 602.
  
 4.SHOW EXIT ACCESS PATH OF TRAVEL
 COMPLYING WITH FBC 2004 1015.1.
  
 5.A DESIGN PROFESSIONAL MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION
 PURSUANT TO SECTIONS 303, 304 AND 305 OF
  
 THE 2004 FBC EXISTING BUILDING.
 SHOW HOW BUILDING WILL COMPLY WITH THE
 SECTIONS SELECTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-12-21 Cont ID  
Sent By jleahy Date 2005-12-21 Time 09:05 Rev Time 0.45
Received By jleahy Date 2005-12-21 Time 09:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-12-05 Cont ID  
Sent By jleahy Date 2005-12-03 Time 13:30 Rev Time 0.45
Received By jleahy Date 2005-12-03 Time 13:26 Sent To  
Notes
2005-12-03 00:00:00LIGHTING PLAN SHOWS CIRCUITS AS L2, THIS
 WAS NOT SHOWN FOR PANEL SCHEDULE.
  
 IF PANEL EXISTS PLEASE SHOW LOAD CALC,
 AND PANEL SCHEDULE.
  
 IF NOT HAVE LETTER SENT STATING ALL
 LOADS ARE LOCATED IN PANEL L1.
  
  
 JAKE 644-7291

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-12-19 Cont ID  
Sent By nmccray Date 2005-12-19 Time 10:48 Rev Time 0.00
Received By nmccray Date 2005-12-19 Time 10:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-12-06 Cont ID  
Sent By mcarsill Date 2005-12-06 Time 11:00 Rev Time 0.00
Received By mcarsill Date 2005-12-06 Time 10:34 Sent To  
Notes
2005-12-06 00:00:001. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED FROM THE
 SITE DAILY.
  
 3. SEPERATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM REMODEL.
  
 4. SEPERATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM REMODEL.
  
 5. COULD NOT LOCATE ANY EMERGENCY LIGHT
 FIXTURES ON ELECTRICAL SHEETS.
  
 6. PLEASE EXPLAIN PROPOSED KEY LOCK
 HARDWARE SHOWN ON PAGE A-6. HOW DOES
 THESE DEVICES INTERFACE WITH EXITING.
  
 7. GENERAL HARDWARE NOTES ON PAGE A-2
 IS INCORRECT. CHAPTER 7 OF THE LIFE
 SAFETY CODE SHALL BE REFERENCED INSTEAD
 OF CHAPTER 5.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-06 Cont ID  
Sent By adarroug Date 2006-02-06 Time 08:19 Rev Time 0.00
Received By adarroug Date 2006-02-06 Time 08:19 Sent To M
Notes
2006-02-06 00:00:00TO "HMOSER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-13 Cont ID  
Sent By adarroug Date 2005-12-13 Time 19:01 Rev Time 0.00
Received By adarroug Date 2005-12-13 Time 19:01 Sent To  
Notes
2005-12-13 00:00:00TO "BOB"#15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-08 Cont ID  
Sent By tgordon Date 2005-12-08 Time 09:43 Rev Time 0.00
Received By tgordon Date 2005-11-15 Time 14:43 Sent To  
Notes
2005-11-29 00:00:00TO "BOB"#5
2005-11-15 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-02-06 Cont ID  
Sent By hmoser Date 2006-02-06 Time 08:35 Rev Time 0.00
Received By hmoser Date 2006-02-06 Time 08:35 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-12-08 Cont ID  
Sent By jleahy Date 2005-12-05 Time 14:59 Rev Time 0.45
Received By tgordon Date 2005-12-08 Time 09:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-12-16 Cont ID  
Sent By jleech Date 2005-12-16 Time 08:28 Rev Time 1.00
Received By jleech Date 2005-12-16 Time 08:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-12-06 Cont ID  
Sent By jleech Date 2005-12-06 Time 09:14 Rev Time 1.00
Received By jleech Date 2005-12-06 Time 09:14 Sent To  
Notes
2005-12-06 00:00:00DENIED;
 1.SHOW COMPLIANCE TO FBC-2004 TABLE
 403.1 (3)
 2.DRINKING FOUNTAINS CANNOT INTRUDE INTO
 THE HALLWAY. FBC-2004 CHAPTER 11
 SEC.11-4.4.1.
 3.DELETE REFERENCE TO AIR CHAMBERS.
 WATER HAMMER ARRESTORS ARE REQUIRED. SEE
 SEC 604.9. MANUFACTURE SPECIFICATIONS
 REQUIRE REQUIRE WHA'SCLOSE TO SORCE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695