Plan Review Details - Permit 05110189
Plan Review Stops For Permit 05110189
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-08-21 Cont ID  
Sent By mjacobs Date 2007-08-21 Time 07:25 Rev Time 0.00
Received By mjacobs Date 2007-08-16 Time 12:25 Sent To  
Notes
2007-08-17 06:04:20 
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 05110189
 ADD: 2025 N. DIXIE HWY
 CONT: GR CONCEPTS
 TEL: (561)743-0066
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 3RD
 ACTION: DENIED
  
 --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 AT THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) OK
  
 3) OK
  
 4) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 -------------------------------------
 ) NUMBER OF FLOORS
 ) SPACE/ FL
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
 ) FLOOD ZONE
 ) FLOOD ELEVATION
 )L.O.M.R.
  
 5) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 PRODUCTS WITH STATEWIDE APPROVAL ARE
 REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE.SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG. NOTE: THE
 PRODUCT APPROVALS FOR THE DOORS AND WINDOWS ARE
 EXPIRED. SUBMIT NEW AND
 UP-DATED PRODUCT APPROVALS FOR THE
 DOORS/WINDOWS/SHUTTERS/ROOFING MATERIALS
 ETC.
 NEW*** TWO SETS OF PRODUCT APPROVALS SHALL BE SUBMITTED
 FOR EACH PRODUCT.THE PRODUCT APPROVAL FOR THE
 ROOFING.
 FBC 1609.6.2.2 THE SYSTEM SELECTED
 FROM THE SUBMITTED FLAT ROOF PRODUCT
 APPROVAL NOA HAS A MAXIMUM DESIGN
 PRESSURE OF LESS THAN -89 PSF AND CITES
 GENERAL LIMITATION #9 (SEE PAGE 12_ OF
 _41_).GENERAL LIMITATION #9 PROHIBITS
 RATIONAL ANALYSIS OR EXTRAPOLATION TO
 ENHANCE THE UPLIFT PRESSURE AT PERIMETER
 AND CORNER AREAS BY REDUCING THE
 FASTENER SPACING IN THESE AREAS.EITHER
 SELECT AN ALTERNATIVE SYSTEM (OR PRODUCT
 APPROVAL) THAT DOES NOT CITE GENERAL
 LIMITATION #9.ALTERNATIVELY IF THE
 SELECTED SYSTEM DOES CITE GENERAL
 LIMITATION #9, IT MUST HAVE A MAXIMUM
 DESIGN PRESSURE THAT EXCEEDS THE
 PRESSURE IN ROOF ZONE 3 (TYPICALLY -89
 PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR
 LESS).
  
 6) OK
  
 7) 13-103.1.2 THE BUILDING OWNER, THE OWNER'S
 ARCHITECT, OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED
 BY THE OWNER SHALL CERTIFY THAT THE BUILDING IS IN
 COMPLIANCE WITH THE CODE, AS PER SECTION 553.907,
 FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION OR RENOVATION.
 IF, DURING THE BUILDING'S CONSTRUCTION OR RENOVATION,
 ALTERATIONS ARE MADE IN THE BUILDING?S DESIGN OR IN
 MATERIALS OR EQUIPMENT INSTALLED IN THE BUILDING WHICH
 WOULD DIMINISH ITS ENERGY PERFORMANCE, AN AMENDED COPY
 OF THE COMPLIANCE CERTIFICATION SHALL BE SUBMITTED TO
 THE BUILDING OFFICIAL ON OR BEFORE THE DATE OF FINAL
 INSPECTION BY THE BUILDING OWNER OR HIS OR HER LEGALLY
 AUTHORIZED AGENT.
 BEFORE A BUILDING PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE SIGNED BY THE
 BUILDING OWNER, THE
 OWNER?S ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY
 DESIGNATED BY THE OWNER.
  
 8) OK
  
 9) OK
  
 10) OK
  
 NO RESPONSE****
 11) EXPLAIN WHAT TYPE OF WORK IS CARRIED OUT IN THE
 WORKSHOP AREA. WHAT TYPE OF MATERIAL WILL BE DISPLAYED
 IN THE SHOW ROOMS? THE BUILDING OCCUPANCY MAY CHANGE
 DUE TO THE USE OF THE WORKSHOP AND OTHER AREAS IN THE
 BUILDING.
  
 12) OK
  
 13) OK
  
 14) OK
  
 NEW************
  
 A)SHEET 3.1 THE DIMENTIONS FOR F-I ON THE FOUNDATION
 LEGEND DO NOT MATCH DETAIL #3 ON SHEET 8.2. CLARIFY.
  
 B)GEOTECHNICAL TESTING LAB RECOMEND THAT THE MINIMUM
 CONTINOUS FOOTING WIDTH BE 30". THE CONTINOUS FOOTING
 ON SHEET 3.1 SHOWS A 20" WIDTH. THE TESTING LAB REPORTS
 SHALL NOT BE IGNORED.
  
 C)A FRAMING HEADDER DETAIL FOR THE NEW 3 FOOT OPENING
 CONNECTING THE BUILDINGS IS REQUIRED. SEE SHEET 4.1
  
 D)HOW CAN THE FOUNDATION /FLOOR AND ROOF PLAN HAVE
 THE SAME DETAIL? #3 SHEETS 8.1. SEE PAGES 3.1 / 4.1 AND
 6.1. FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOACTION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
  
 E)FBC TABLE 1607.1 IF THE MEZZANINE IS USED AS OFFICE
 SPACE THE DESIGN FLOOR LOAD SHALL BE 50 PSF. INDICATE
 THE STAIRS FLOOR LOAD ON THE PLANS.
  
 F)FBC 903.2.6 IF THE BUILDING IS DECLEARED AS GROUP M
 THERE IS A POSSIBILITY IT WILL REQUIRE A SPRINKLER
 SYSTEM ACCORDING TO THIS SECTION.
  
 G)FBC. 302.3WHEN A BUILDING IS OCCUPIED BY TWO OR
 MORE USES NOT INCLUDED IN THE SAME OCCUPANCY
 CLASSIFICATION, THE BUILDING OR PORTION THEREOF SHALL
 COMPLY WITH SECTION 302.3.1 OR 302.3.2.
  
 H)FBC. 1607.7.1 HANDRAIL ASSEMBLIES AND GURADS SHALL
 BE DESIGNED TO RESIST A LOAD OF 50 PLF APPLIED IN ANY
 DIRECTION AT THE TOP AND TO TRANSFER THIS LOAD THROUGH
 THE STRUCTURE.
  
 I)FBC. 1607.7.1.1 THE GUARD RAIL SHALLBE ABLE TO
 RESIST A SINGLE CONCENTRATED LOAD OF 200 POUNDS. SHOW
 IN DETAIL HOW THESE REQUIREMENTS WILL BE MET.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-06 Cont ID  
Sent By mjacobs Date 2006-07-06 Time 18:35 Rev Time 0.00
Received By mjacobs Date 2006-07-06 Time 09:35 Sent To  
Notes
2006-07-05 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05110189
 ADD: 2025 N. DIXIE HWY
 CONT: GR CONCEPTS
 TEL: (561)743-0066
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) OK
  
 3) OK
  
 4) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 -------------------------------------
 ) NUMBER OF FLOORS
 ) SPACE/ FL
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
 ) FLOOD ZONE
 ) FLOOD ELEVATION
 )L.O.M.R.
  
 5) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
 PRODUCTS WITH STATEWIDE APPROVAL ARE
 REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE.SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG. NOTE: THE
 PRODUCT APPROVALS FOR THE DOORS AND
 WINDOWS ARE EXPIRED. SUBMIT NEW AND
 UP-DATED PRODUCT APPROVALS FOR THE
 DOORS/WINDOWS/SHUTTERS/ROOFING MATERIALS
 ETC.
  
 6) OK
  
 7) 13-103.1.2 CODE COMPLIANCE
 CERTIFICATION.
 THE BUILDING'S OWNER, THE OWNER'S
 ARCHITECT, OR OTHER AUTHORIZED AGENT
 LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN
 COMPLIANCE WITH THE CODE, AS PER SECTION
 553.907, FLORIDA STATUTES , PRIOR TO
 RECEIVING THE PERMIT TO BEGIN
 CONSTRUCTION OR RENOVATION.
 IF, DURING THE BUILDING?S CONSTRUCTION
 OR RENOVATION, ALTERATIONS ARE MADE IN
 THE BUILDING?S DESIGN OR IN MATERIALS OR
 EQUIPMENT INSTALLED IN THE BUILDING
 WHICH WOULD DIMINISH ITS ENERGY
 PERFORMANCE, AN AMENDED COPY OF THE
 COMPLIANCE CERTIFICATION SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL ON OR
 BEFORE THE DATE OF FINAL INSPECTION BY
 THE BUILDING OWNER OR HIS OR HER LEGALLY AUTHORIZED
 AGENT.
  
 8) OK
  
 9) SHEET 3.1 REFERS TO DETAIL #3 ON PAGE
 8.1, HOWEVER, THERE IS NO DETAIL #3 ON
 SHEET 8.1. THERE IS ALSO A REFERENCE TO
 DETAIL #1 ON SHEET 8.2 BUT THERE IS NO
 #1 DETAIL ON SHEET 8.2. ALL THESE
 REFERENCES NEEDS TO CORRESPOND WITH THE
 REFERENCE PAGES INDICATED. AN ARROW
 POINTING IN THE DIRECTION OF THE CROSS
 SECTION WILL INDICATE CLEARLY WHICH
 ELEVATION WILL BE SHOWN. CHECK ALL PAGES
 FOR CORRECT REFERENES. SEE SHEET 4.1/7.1
 ETC. FOR SIMULAR ERRORS.
  
 10) THE DESCRIPTION ON THE APPLICATION
 INDICATE ADDITION TO EXISTING BUILDING
 ONLY. HOWEVER THE PLANS SHOWS MAJOR
 REMODELING OF THE EXISTING BUILDING. THE APPLICATION
 STATES :DESCRIBE PROJECT IN
 DETAIL: ADJUST THE APPLICATION ACCORDINGLY.
  
 11) INDICATE THE USE OF THE MEZZANINE
 AREA AND THE WORKSHOP AREAS. THE
 OCCUPANT LOAD IS ALSO REQUIRED FOR THESE
 AREAS.
  
 12) THE NEW H/C TOILETS SHALL MEET THE REQUIREMENTS OF
 11-4.16/11-4.19/11-4.24ETC ALSO SEE
 FIG.30E CH.11.
  
 13) SHEET 4.1 REFERENCE CERTAIN DETAILS
 AND PAGES WHICH CANNOT BE LOCATED ON THE
 DRAWINGS. MODIFY THE DRAWINGS
 ACCORDINGLY.
  
 14) ONCE AGAIN PROVIDE THE ELEVATIONS OF
 THE FLOORS SHOWING THE CEILING HEIGHTS.
 MEZZANINES ARE REQUIRED TO HAVE CEILING
 HEIGHT OF NOT LESS THA 7' AND THE
 CEILING HEIGHT BELOW THE MEZZANINE MUST
 ALSO BE 7'.FBC.505.1
  
 NOTE: WHEN RESUBMITTING PLANS, INDICATE
 THE REVISION AND REMOVE AND REPLACE THE
 OLD SHEETS. SUBMIT TWO COMPLETE NEW SETS
 OF DRAWINGS AND ONE OLD SET FOR REVIEW.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-01 Cont ID  
Sent By mjacobs Date 2006-03-01 Time 17:19 Rev Time 12.00
Received By mjacobs Date 2006-03-01 Time 07:12 Sent To PC
Notes
2006-02-28 00:00:00 
 1)ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 2)THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. THE CITY
 WPB AMMENDMENT TO FBC 106.3.3. EACH
 PRODUCT APPROVAL NEEDS ITS OWN STATE
 COVER SHEET WITH THE FL#.
  
 3) THE SCALE ON PAGE 1.1 SHOWS 1"=1'
 HOWEVER WHEN SCAILING THE DRAWINGS, THIS
 SCALE WON'T WORK. PLEASE CLARIFY.
  
 4) ON PAGE 3.1 INDICATE THE SLOPE OF THE
 NEW RAMP.SEE F.B.C. 11-4.8. ALSO, IN
 REFERENCE TO THE DETAILS OF SHEET 8.3,
 WHERE IS SHEET 8.3?
  
 5) THE ADDRESS ON THE PAGES NEED TO
 MATCH NEED TO MATCH. SOME INDICATE 2025
 N.DIXIE HIGHWAY AS THE ADDRESS AND
 OTHERS HAVE 2025 S.DIXIE HIGHWAY. MAKE
 SURE ALL SHEETS SHOW THE SAME ADDRESS.
  
 6) (2004 FBC) 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND REVELENT
 LAWS, ORDINANCES, AND RULES AND
 REGULATIONS AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 7) 109.3.10* IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS
 CODE SHALL BE PERMORMED IN A MANNER SO
 AS NOT TO ADVERSLY IMPACT THE CONDITION
 OF ADJACENT PROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS
 &CONDITIONS AGREEABLE TO THE APPLICABLE
 PROPERTY OWNER.THIS INCLUDES BUT IS NOT
 LIMITED TO THE CONTROL OF DUST, NOISE,
 WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS.
 NEW CONSTRUCTION ACTIVITY SHALL NOT
 ADVERSELY IMPACT HISTORIC SURFACE WATER
 DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, & MAY REQUIRE SPECIAL
 DRAINAGE DESIGNCOMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED
 SITES.ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENET, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCELL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9)11-4.6.2 LOCATION.
 ACCESSIBLE PARKING SPACES SERVING A
 PARTICULAR BUILDING SHALL BE LOCATED ON
 THE SHORTEST SAFELY ACCESSIBLE ROUTE OF
 TRAVEL FROM ADJACENT PARKING TO AN
 ACCESSIBLE ENTRANCE. IN PARKING
 FACILITIES THAT DO NOT SERVE A
 PARTICULAR BUILDING, ACCESSIBLE PARKING
 SHALL BE LOCATED ON THE SHORTEST
 ACCESSIBLE ROUTE OF TRAVEL TO AN
 ACCESSIBLE PEDESTRIAN ENTRANCE OF THE
 PARKING FACILITY. IN BUILDINGS WITH
 MULTIPLE ACCESSIBLE ENTRANCES WITH
 ADJACENT PARKING , ACCESSIBLE PARKING
 SPACES SHALL BE DISPERSED AND LOCATED
 CLOSEST TO THE ACCESSIBLE ENTRANCES.
 EACH PARKING SPACE MUST BE NO LESS THAN
 12 FEET (3658 MM) WIDE.
 (1)ALL SPACES MUST BE LOCATED ON AN
 ACCESSIBLE ROUTE NO LESS THAN 44 INCHES
 (1118 MM)WIDE SO THAT USERS WILL NOT BE
 COMPELLED TO WALK OR WHEEL BEHIND PARKED
 VEHICLES. SEE ADDITIONAL INFORMATION IN
 PACKAGE.
  
 10) SHEET 4.1. STATE THE MEAN ROOF
 HEIGHT ON THE DRAWINGS. ALSO WHAT IS THE
 LIVE AND DEAD LOAD FOR THE MEZZANINE
 AREA? WHAT WILL THE MEZZANINE BE USE FOR
 STORAGE OR WILL THERE BE WORK TAKING
 PLACE ON THE MEZZANINE.
 SEE FBC 11-4.1.3 (1-5) FOR
 ACCESSIBILITY.
  
 11) EXPLAIN WHAT TYPE OF WORK IS CARRIED
 OUT IN THE WORKSHOP AREA. WHAT WILL BE
 DISPLAYED IN THE SHOW ROOMS?
  
 12) ADDITIONAL INFORMATION IS REQUIRED
 FOR THE BRACING AROUND THE HOLES FOR THE
 A/C UNITS. A DETAIL DRAWING IS REQUIRED
 SHOWING ALL BRACING.
  
 13) SHEET 4.1 REFERENCE CERTAIN DETAIL
 AND PAGES WHICH CANNOT BE LOCATED ON THE
 DRAWINGS. MODIFY DRAWINGS ACCORDINGLY TO
 SHOW CORRECT DETAILS.
  
 14) PROVIDE AN FRONT ELEVATION OF THE
 MEZZANINE SHOWING THE FIRST FLOOR HEIGHT
 AND THEMEZZANINE. ALSO SHOW THE
 GUARDRAIL. A DETAIL DRAWING OF THE
 GUARDRAIL IS ALSO REQUIRED. WHAT IS THE
 HEIGHT OF THE WALL? IS IT 42" OR 4'?
 WILL THERE BE AHY OPENING IN THIS WALL?
 IF SO SHOW ON ELEVATION DRAWINGS.
  
 15) 713.13 F.S.A NOTICE OF
 COMMENCEMENT SHALL BE RECORDED AT PALM
 BEACH COUNTY COURTHOUSE AND A COPY
 SUBMITTED TO THIS OFFICE BEFORE A PERMIT
 CAN BE ISSUED. BLANK FORMS ARE AVAILABLE
 FROM THIS OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-08-12 Cont ID  
Sent By dpalmer Date 2007-08-12 Time 15:05 Rev Time 0.00
Received By dpalmer Date 2007-08-12 Time 14:20 Sent To  
Notes
2007-08-12 15:05:57** DENIED 3RD REVIEW **
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEWS WHICH STILL
 NEED TO BE ADDRESSED.
  
  
 1) NOTE: PLEASE SEE COMPLIANCE WITH FBC CHAPTER 13 HAS
 STILL NOT BEEN ACHIEVED.
 PLEASE SEE MISSING TIME SCHEDULING.
 PLEASE SEE NO OVER RIDE DEVICES AS REQUIRED PER CODE.
 PLEASE SEE MISSING MAXIMUM OVER RIDE TIMES.
 PLEASE SEE MISSING CONTROLS/SYSTEM FOR EACH LEVEL AS
 ONE SYSTEM MAY NOT FEED MULTIPLE LEVELS.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE NOW
 UNDER THE NEW CODE WHICH WAS ADOPTED DECEMBER 8TH,
 2006. THIS PROJECT WAS APPLIED FOR IN NOVEMBER OF 05
 WHICH PLACES THE ENERGY CALCULATIONS UNDER A DIFFERENT
 VERSION. *MAY NOT USE CALCULATIONS FROM ONE ADOPTED
 CODE AND PLANS DESIGNED UNDER ANOTHER*
 PLEASE CLARIFY HOW NO EXTERIOR LIGHTING IS ENTERED INTO
 THE ENERGY CALCULATIONS WHEN THE PLANS CLEARLY SHOWS
 LIGHTING?13-415.2.ABC.1.3
 THIS HAS BEEN CONFIRMED WITH THE STATE OF FLORIDA
 BUILDING COMMISSION.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DOES NOT
 CORRELATE WITH PLANS FOR THE METHOD OF CONTROLS,
 FIXTURES, WATTAGE ETC.
 PLEASE SEE THE CALCULATIONS ARE REQUIRED TO BE SIGNED,
 DATED AND SEALED PER 13-103.1.1.1
 FS 481.221/471.025
  
 PLEASE SEE 13-415.2.ABC.1, 13-415.1.A,
 13-415.2.ABC.1.1, 13-415.2.ABC.1FOR PERFORMANCE
 CALCULATIONS/ENERGY CALCULATIONS TO BE SHOWN FOR
 COMPLIANCE WHICH IS NOT DONE AT THIS TIME.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3FOR LIGHTING
 CONTROLS, FIXTURES, SCHEDULING , OVER-RIDES, MORE THAN
 ONE FLR, LOCATIONS OF OVER-RIDE DEVICES AND TIME
 LIMITS.
  
 2) NOTE: PLEASE SUBMIT A FIXTURE LEGEND WHICH
 CORRELATES WITH THE CALCULATIONS FOR CHAPTER 13 AS
 SUBMITTED.
 FBC 106.3.5.1.2, 106.1.2
  
 3) NOTE: PLEASE SEE THE TWO PREVIOUS REVIEWS REQUESTED
 PHOTO-METRICS FOR STAIRS FOR EGRESS HOWEVER THESE ARE
 STILL NOT SUBMITTED.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-33.004 AS
 THIS IS REQUIRED AS A PART OF MINIMUM LIGHTING DESIGNS
 FOR ENGINEER.
 NFPA-101 2003 7.8.1.3,7.9.2.2
 ** PLEASE SHOW AND INDICATE ALL OTHER EM/EXT LTS NEW OR
 EXISTING ON PLANS .
  
 4) NOTE:THIS IS THE SAME NOTE AS PREVIOUS REVIEW.
 PLEASE SEE LOADS SHOWN ON PANEL "D" DO NOT SEEM TO
 CORRELATE WITH THE LOADS INDICATED ON PANEL "E". PANEL
 *E* IS SHOWN BEING FED FROM PANEL *D*. PLEASE
 COORDINATE.
 PLEASE STILL CLARIFY SERVICE AS THIS IS STILL BEING
 SHOWN AS 120/240 ON PANELS AND RESPONSE AND NOTE
 MENTIONS DELTA SERVICE WITH HIGH-LEG YET THE NOTE ALSO
 MENTIONS THIS IS A 208V SERVICE. HOW IS THIS POSSIBLE?
 PLEASE ADJUST AND CLARIFY SERVICE AS SHOWN.
 PLEASE ADJUST LOAD CALCULATIONS AS NEEDED.
 NEC 220, 230, 310, 408 ETC THERE ARE MANY ITEMS TO
 REVIEW FOR COMPLIANCE, HOWEVER AS SERVICE IS NOT CLEAR
 NOT PARTICULAR REVIEW OF THIS EQUIPMENT CAN BE DONE.
 FBC 106.3.5.1.2
  
 5) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTORS FROM GUTTER TO EACH DISCONNECT A, B AND C.
 250.110, 250.122 ETC.
  
 6) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS.
 FBC ADMIN SECTION 106.1
  
 7) NOTE:PLEASE SEE PREVIOUS REVIEW WHICH GAVE NOTICE
 TO FLORIDA STATUTES 553.80(2)(B) DUE TO REPEAT CODE
 COMPLIANCE COMMENTS.
 PLEASE SEE THIS FEE HAS NOW BEEN ASSESSED AS REQUIRED
 BY THE FLORIDA STATUES. THIS IS A REQUIRED STATUTE.
 THIS FEE OF $9,788.82 IS DUE BEFORE NEXT RE-SUBMITTAL
 OF PLANS. ELECTRICAL PLANS AND CALCULATIONS SUBMITTED
 ARE RETAINED AT THIS TIME.
 PLEASE SEE NOTICE TO FS553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS.
 TO DATE NO ONE HAD CONTACTED THIS OFFICE TO GO OVER
 THESE COMMENTS.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-15 Cont ID  
Sent By dpalmer Date 2006-06-15 Time 08:49 Rev Time 0.00
Received By dpalmer Date 2006-06-15 Time 07:32 Sent To  
Notes
2006-06-15 00:00:00A
 ********* UNSAT 2ND REVIEW ********
  
 ** PLEASE SEE SOME NOTES FROM PREVIUOUS
 REVIEW AND SOME NEW NOTES DUE TO ITEMS
 ON PLANS NOT ON ORIGINAL.
  
 1) NOTE: PLEASE SEE PREVIOUS NOTE #1
 MENTIONED PLANS CAME IN DESIGNED UNDER
 THE 2001 FBC WHERE THE DESIGNS AFTER OCT
 1ST 2005 REQUIRED CHANGE TO THE 2004
 FBC.
 PLEASE SEE ENERGY CODE COMPLIANCE FORMS
 ARE STILL BEING SHOWN UNDER THE 2001.
 PLEASE SEE THERE ARE NUMEROUS CHANGES
 UNDER THE 2004 FBC CHAPTER 13 AND
 LIGHTING DENSITIES ETC.
 PLEASE SEE 13-415.2.ABC.1 FOR
 PERFORMANCE CALCULATIONS TO BE SHOWN FOR COMPLIANCE
 WHICH IS NOT DONE AT THIS
 TIME.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3
 FOR LIGHTING CONTROLS, FIXTURES,
 SCHEDULING , OVER-RIDES, MORE THAN ONE
 FLR, LOCATIONS OF OVER-RIDE DEVICES AND
 TIME LIMITS.
 PLEASE SEE MIN VOLTAGE DROP INFORMATION
 FOR WORST CASE SHALL BE SHOWN PER
 13-413.1.ABC.1
 PLEASE SEE 13-415.1.ABC.3 ETC
  
 2) NOTE: PLEASE SEE MISSING
 PHOTO-METRICS FOR STAIRSAS NOTED ON
 PREVIOUS REVIEW. PLEASE SEE THIS DETAIL
 CAN BE TYPICAL FOR EACH IF APPLICABLE
 FOR SAME TYPE OF FIXTURES ANDLAYOUT.
 NFPA-101 2003 7.8.1.3,7.9.2.2
 ** PLEASE SHOW AND INDICATE ALL OTHER
 EM/EXT LTS NEW OR EXISTING ON PLANS .
  
 3) NOTE: PLEASE SEE LOADS SHOWN ON PANEL
 "D" DO NOT SEEM TO CORRELATE WITH THE
 LOADS INDICATED ON PANEL "E".
 PLEASE CLARIFY.
 PLEASE ALSO VERIFY LOAD CALCULATION AS
 SERVICE IS BEING SHOWN AS 3-PHASE YET IT
 SEEM ONLY THE A/C LOADS ARE BEING
 FIGURED AT 3-PHASE.
 PLEASE SEE NEC 220,
  
 4) NOTE: PLEASE SEE ARCHITECTURAL PLANS
 WHICH INDICATE NEW WORK IN OTHER AREAS ,
 YET THE ELECTRICAL PLANS DO NOT
 CORRELATE WITH THIS.
 PLEASE SEE NEW LIGHTING IS MENTIONED AND
 AREAS TO BE REMODELED, YET NONE IS
 SHOWN??
 PLEASE COMPLETE.
  
 5) NOTE: PLEASE SEE NOTICE TO FS
 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 ** PLEASE SUBMIT ONLY ONE COPY OF THE
 OLD/VOIDED SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
2006-06-14 00:00:00PLANS IN ELECTRICAL FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-24 Cont ID  
Sent By dpalmer Date 2005-12-24 Time 09:14 Rev Time 0.00
Received By dpalmer Date 2005-12-24 Time 08:31 Sent To  
Notes
2005-12-24 00:00:00*********** UNSAT **********
  
 ** PLEASE SEE PLANS REFERENCE THE 2001
 FBC, HOWEVER AS OF OCT 1ST, 2005, THE
 CODE HAS CHANGED TO THE 2004 FBC.
 PLEASE ADJUST DESIGNS REQUIRED.
 THIS IS REQUIRED FOR ALL TRADES WHETHER
 OR NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
 ALL PLANS ARE TO DICTATE CURRENT
 RELEVANT CODES.
  
 1)NOTE: PLEASE SEE TWO COMPLETELY
 DIFFERENT RISER DIAGRAMS WERE SUBMITTED.
 IT IS ASSUMED, THE RISER SHOWN ON 10.2
 IS THE ONE FOR REVIEW , AS THE PREVIOUS
 RISER IS INCOMPLETE AND WOULD HAVE
 NUMEROUS COMMENTS.
 THIS REVIEW IS FOR THE ONE ON 10.2,
  
 A) PLEASE CONDUCTORS FROM GUTTER TO THE
 RELOCATED EXISTING MAINS.
  
 B)NOTE: PLEASE INCLUDE THOSE EXISTING
 DISCONNECTS SIZES.
  
 2)NOTE: PLEASE SEE PANEL SCHEDULE "D"
 INDICATE DEDICATED BATHROOM CIRCUIT,
 HOWEVER ONLY TWO BATHROOMS ARE SHOWN AND
 NEITHER OF THOSE CONTAIN ELECTRICAL GFI
 RECEPTS???
  
 3)NOTE: PLEASE VERIFY SIGN CIRCUIT PER
 600.5.
  
 4)NOTE: PLEASE INDICATE LOADING FOR
 SHYOW WINDOW CIRCUIT. 220.12A
 PLEAS ADJUST THE # OF CIRCUITS OF
 NEEDED.
  
 5)NOTE: PLEASE SEE LOADS FOR RTU'S
 APPEAR TO BE ROUNDED DOWN?
 PLEASE SEE EACH IS SHOWN AS 10,800VA,
 HOWEVER THE TOTAL VA SHOWN ON LOAD CALCS
 DOES NOT CORRELATE.
 PLEASE ALSO SEE 43KW + IS MORE THAN
 104A'S.
 215.5
  
 6)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125% ALONG WITH ANY LARGEST MOTOR
 LOADS.
 215.3,230.42 ETC.
  
 7)NOTE: PLEASE SEE NOTE ON 10.2 MENTIONS
 TO SEE MEZZ PLANS FOR ELECTRICLA AND
 EGRESS LTS, HOWEVER THIS COULD NOT BE
 LOCATED ON ELECTRICAL SHEETS SUBMITTED.
 PLEASE SEE NFPA-101 7.8,7.9.
 PLEASE SEE A MIN OF 10FT CANDLES IS NOW
 REQUIRED FOR EGRESS STAIRS UNDER NORMAL
 POWER AND A MIN OF 1FT CANDLE UNDER
 EMERGENCY POWER.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FORM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE REMOVE ANY OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF ANY OLD/VOIDED
 SHEETS FOR REFERENCE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THEREARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2007-08-23 Cont ID  
Sent By rchokshi Date 2007-08-23 Time 13:36 Rev Time 0.00
Received By rchokshi Date 2007-08-23 Time 13:28 Sent To  
Notes
2007-08-23 13:36:37***FAILED**** PLEASE PROVIDE THE FOLLOWING:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON DRAWINGSTHE LOCATION OF DUMPSTER &
 ITS ENCLOSURE PER CITY OF WPB, LOCATION MUST BE
 ACCESSIBLE FOR PICKUP TRUCK.
 3. PLEASE SHOW ON YOUR CALCULATIONS, HOW DID YOU
 CALCULATE FIRST FLOOR ELEVATION, DID YOU CONSIDER
 CENTER LINE OF ROAD , SIDEWALK ELEVATION,FLOOD ZONE
 AREA,5,10, 25, 100 YEAR FLOOD CRITERIATO DETERMINE
 THE FIRST FLOOR ELEVATION??PLEASE SHOWTHESE IN YOUR
 STORM WATER CALS.
 4. MAKE SURE THESE SITE AREAS SHOWN ON DRAWINGS MUST
 MATCH WITH AREAS USED IN STORM WATER QUALITY
 CALCULATIONS.
 5. PLEASE SHOW ON YOUR DRAWINGS ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE LAYOUT OF STORM
 WATER PIPES.PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, DO YOU HAVE EXFILTRATION
 TRENCHES. PLEASE SHOW DRY DETENTION/WET DETENTION AREAS
 IN YOURWATER QUALITY CALCULATIONS
 6. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST AROUND
 YOUR SITE EVENTHOUGH THEY ARE NOT IN YOUR SITE.
 7. PLEASE PROVIDE A COPY OF SFWMD PERMIT,,PLEASE
 RESUBMIT A COPY OF GEO-TECH REPORT AND A LATESTEST COPY
 OF STORM STORM WATER QUALITY CALCULATIONS .
 8. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT ETC., PLANS SHOWING SILT
 FENCE AROUND THE SITE & CATCH BASINS.HEIGHT OF FENCE
 SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST &
 PARTICLES.
 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED
 10. PLEASE PROVIDE LATEST COPY OF CIVIL DRAWINGS THAT
 WERE APPROVED AT 45TH STREET.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2006-07-28 Cont ID  
Sent By rchokshi Date 2006-07-28 Time 13:56 Rev Time 0.00
Received By rchokshi Date 2006-07-28 Time 13:55 Sent To  
Notes
2006-07-28 00:00:00PASS 7-28-06

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2006-01-27 Cont ID  
Sent By mamini Date 2006-01-27 Time 15:13 Rev Time 1.00
Received By mamini Date 2006-01-27 Time 15:13 Sent To  
Notes
2006-01-27 00:00:00FAILED:
  
 1. PLEASE PROVIDE STORM WATER
 CALCULATION FOR THE PROPOSED IMPROVMENT
 ON THE ENTIRE SITE.
 2. SHEET C1, SHOWS TWO C.S. STRUCTURE,
 PLEASE VERIFY.
 3. SHEET C1 SHOWS A POWER POLE AT THE
 PROPOSED CURB CUT, IS THIS A FPL POLE OR
 BELONG TO THE CITY? NOTE THAT, IT SHOULD
 BE RELOCATED BY THE DEVELOPER WITH A
 PERMIT ISSUED FROM PUBLIC UTILITY
 DEPARTMENT AND FPL.
 4. ANY WORK WITHIN PUBLIC R.O.W WOULD
 REQUIRED A PERMIT FROM PUBLIC UTILITIES,
 THE PROPOSED 15 IN. STORM PIPE SHOULD BE
 RCP TYPE(IN PUBLIC R.O.W.), CONTACT
 494-1086, WINDEL PALMER.
 5. ARE THERE NEW CONNECTIONS FOR WATER
 AND SEWER OR THE EXISTING WILL BE USED?
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-09-06 Cont ID  
Sent By mwennerg Date 2007-09-06 Time 15:32 Rev Time 0.00
Received By mwennerg Date 2007-09-06 Time 15:32 Sent To  
Notes
2007-09-06 15:36:59***PROVISO***
  
 1) THIS SUBMITTAL WAS PASSED DURING PREVIOUS REVIEWS.
 PLANS WILL BE STAMPED WHEN PASSED BY OTHER REVIEWERS.
  
 2) PROJECT DATA INDICATES THAT THIS PROJECT IS
 UNSPRINKLERED. LIFE SAFETY NOTE INDICATES PROPOSED FIRE
 SPRINKLER SYSTEM. PLEASE ADVISE AND CORRELATE SHEETS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-07-18 Cont ID  
Sent By mwennerg Date 2006-07-18 Time 13:22 Rev Time 0.00
Received By mwennerg Date 2006-07-18 Time 13:22 Sent To  
Notes
2006-06-15 00:00:00NEEDS, SEE ELEC COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-12-06 Cont ID  
Sent By mcarsill Date 2005-12-06 Time 13:27 Rev Time 0.00
Received By mcarsill Date 2005-12-06 Time 13:05 Sent To  
Notes
2005-12-06 00:00:001. SEPERATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM INFORMATION SHOWN
 ON PAGE 10.2.
  
 2. ALL GUARDRAILS AND HANDRAILS ARE TO
 MEET THE PRESCRIPTIVE STRENGTH
 REQUIREMENTS OF THE FLORIDA BUILDING AND
 FIRE CODE.
  
 3. THE NEW ADDITION SHALL COMPLY WITH
 THE LATEST EDITION OF THE CODE.
  
 4. BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION. A MINIMUM OF AT LEAST 6" HIGH
 NUMBERS ARE REQUIRED.
  
 5. ALL NEW STAIRS AND RAMPS SHALL BE
 EQUIPPED WITH HANDRAILS ON BOTH SIDES OF
 THEM.
  
 6. ALL EXIT DOORS ARE TO REMAIN CLEAR
 AND UNOBSTRUCTED WHILE THE ADDITION IS
 BEING CONSTRUCTED.
  
 7. COMPLIANCE WITH NFPA 241 IS REQUIRED.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-20 Cont ID  
Sent By adarroug Date 2007-07-20 Time 09:42 Rev Time 0.00
Received By adarroug Date 2007-07-20 Time 09:42 Sent To  
Notes
2007-08-01 13:30:28TO "COMM" BD#27
2007-07-20 09:43:14WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-24 Cont ID  
Sent By adarroug Date 2006-05-24 Time 15:58 Rev Time 0.00
Received By adarroug Date 2006-05-24 Time 15:58 Sent To  
Notes
2006-06-12 00:00:00TO "COMM" BD#42
2006-05-24 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2006-03-01 Time   Rev Time 0.00
Received By adarroug Date 2005-11-14 Time 15:57 Sent To  
Notes
2005-11-22 00:00:00TO "COMM" BD#35
2005-11-14 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-08-09 Cont ID  
Sent By rregueir Date 2007-08-09 Time 13:44 Rev Time 0.00
Received By rregueir Date 2007-08-08 Time 19:54 Sent To  
Notes
2007-08-09 12:14:25---------------DENIED-----------------
  
 FBC 2004 CODE FAMILY
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS COMMENTS FOR THE PURPOSE OF CONTINUITY.
  
 NOTE: NO WRITTEN RESPONSE TO PREVIOUS REVIEW COMMENTS
 WAS FOUND IN THIS SUBMITTAL PACKAGE.
  
 1. OK
  
 2. OK
  
 3. RELOCATING CONDENSER STANDS: IS THIS NO LONGER PART
 OF THE SCOPE OF THIS PERMIT? NO INFORMATION WAS FOUND
 ON PLANS OR IN SUBMITTAL PACKAGE. PLEASE CLARIFY. A
 NARRATIVE OR WRITTEN RESPONSE TO PREVIOUS RVIEW
 COMMENTS WILL HELP IN EXPEDITING THE REVIEW PROCESS.
  
 4. PG 6.2: DRAWING OF "SHIP'S LADDER" SHOWS THE LATTER
 STARTING AT 6 FEET ABOVE GRADE. THE EXTENT OF THE
 LADDER SHALL BE FROM GRADE OR FLOOR LEVEL TO THE
 EQUIPMENT'S LEVEL SERVICE SPACE. SEE FBC,M 306.5.
  
 5. NO OUTDOOR AIR INFORMATION COULD BE FOUND ON PLANS.
 PROVIDE OCCUPANCY CLASSIFICATION, OCCUPANT LOAD,
 OUTDOOR AIR REQUIRED PER OCCUPANT AND THE AMOUNT OF
 OUTDOOR AIR TO BE PROVIDED IN ACCORDANCE WITH FBC,M
 TABLE 403.3. ALSO, PROVIDE INFORMATION FOR TOILET ROOM
 EXHAUST FANS SUCH AS MODEL # AND CFM.
  
 6. ENERGY CALCULATIONS:
 A) ON THE PROJECT SUMMARY PAGE, PLEASE INCLUDE ALL
 AVAILABLE INFORMATION IN THE GIVEN FIELDS. MISSING ON
 THIS FORM ARE THE OWNER NAME AND THE PERMIT NUMBER.
 B) CALCULATION PROCEDURES SHALL BE PREPARED, SIGNED AND
 SEALED BY AN ARCHITECT OR ENGINEER REGISTERED IN
 FLORIDA PER FBC 13-400.3.ABC.1.
 C) THE BUILDING?S OWNER, THE OWNER?S ARCHITECT, OR
 OTHER AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER
 SHALL CERTIFY TO THE BUILDING OFFICIAL THAT THE
 BUILDING IS IN COMPLIANCE WITH THE REQUIREMENTS OF
 CHAPTER 13 OF THIS CODE PRIOR TO RECEIVING THE PERMIT
 TO BEGIN CONSTRUCTION OR RENOVATION. THE PARTY
 RESPONSIBLE UNDER SUBSECTIONS 471.003 AND 481.228 AND
 CHAPTER 489, FLORIDA STATUTES, FOR THE DESIGN AND
 SPECIFICATION OF EACH BUILDING SYSTEM SHALL CERTIFY
 THAT THE PLANS AND SPECIFICATIONS FOR THAT SYSTEM
 COMPLY WITH THE REQUIREMENTS OF CHAPTER 13 OF THIS CODE
 (SEE ALSO SECTION 13-103.2).
 D) WALL TYPE ON INPUT DATA REPORT CALLS FOR 8 INCH
 LIGHTWEIGHT CONCRETE BLOCK. IF THIS TYPE OF BLOCK IS TO
 BE USED FOR AN ENERGY CREDIT IT MUST BE SPECIFIED ON
 PLANS.
 E) PG 4.1 GENERAL NOTE #22 CALLS FOR MINIMUM R-5
 INSULATION ON ALL CBS WALLS. ADJUST CALCULATIONS TO
 CORRESPOND WITH PLANS.
 F) PG 4.1 GENERAL NOTE #22 CALLS FOR R-19 BATT
 INSULATION ON CEILINGS IN ALL CONDITIONED SPACES. DOES
 THIS SPACE HAVE A CEILING? WHERE AND HOW WILL THIS
 INSULATION BE INSTALLED? ADJUST INPUT DATA REPORT TO
 CORRESPOND WITH THE ACTUAL ROOF/INSULATION TYPE TO BE
 USED. PLA DOES NOT SHOW A BUILT-UP GRAVEL ROOF.
  
 7. OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-07-19 Cont ID  
Sent By pkrauss Date 2006-07-19 Time 06:57 Rev Time 0.00
Received By pkrauss Date 2006-07-19 Time 06:57 Sent To  
Notes
2006-07-19 00:00:00DENIED:2004 FBC
 COMMENTS FROM REVIEW DATED 1-25-06
  
 COMMENT #1:OK
 COMMENT #2:PLAN SHEET 9.1 ROOF CURB
 DETAIL INDICATES 8" FROM THE BAR JOIST
 FLANGE TO THE FLASHING.PER THE 2004
 FBC 1509.7, ROOF CURBS SHALL EXTEND 8"
 ABOVE THE ROOF SURFACE NOT THE BAR
 JOIST.
  
 COMMENT #3:PLEASE PROVIDE A DETAIL FOR
 THE RELOCATED CONDENSING UNIT STANDS.
 PLEASE SHOW COMPLIANCE WITH 2004 FBC
 TABLE 1509.7.
  
 COMMENT #4:PLAN SHEET 6.2 INDICATES A
 SHIPS LADDER WILL BE INSTALLED ON THE
 WALL WHERE THE LOWER EXISTING ROOF MEETS
 THE NEW HIGHER ROOF.PLAN DOES NOT
 INDICATE ACCESS TO EXISTING ROOF.
 PLEASE ANNOTATE EXISTING ROOF ACCESS.
  
 COMMENT #5: PLEASE PROVIDE OUTSIDE AIR
 CALUCALTIONS IN ACCORDANCE WITH 2004 FMC
 TABLE 403.3.
  
 *****************NEW COMMENTS***********
 6.ENERGY CALCULATION FORM SUBMITTED IS
 NOT THE PROPER FORM.COMPLIANCE
 CALCULATIONS ARE THOSE UTILIZED IN THE
 ENERGY GAUGE FLA/COM COMPUTER PROGRAM.
  
 7.PLEASE PROVIDE DUCT AND GRILL SIZES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-01-25 Cont ID  
Sent By pkrauss Date 2006-01-25 Time 06:32 Rev Time 0.00
Received By pkrauss Date 2006-01-25 Time 06:24 Sent To  
Notes
2006-01-25 00:00:00DENIED:2004 FLORIDA BUILDING CODE
  
 1.PLAN SHEET 9.1 GENERAL HVAC NOTE #2
 INDICATES 2001 FBC.WE ARE CURRENTLY IN
 THE 2004 FBC.
  
 2.PLAN SHEET 6.2, DETAIL FOR THE CURB.
 PLANS DO NOT INDICATE ATTACHMENT TO THE
 ROOF DECK.PLEASE NOTE, ROOF CURBS
 SHALL BE A MINIMUM OF 8" ABOVE THE ROOF
 SURFACE PER 2004 FBC 1509.7.
  
 3.PLANS DO NOT PROVIDE A DETAIL FOR
 THE STANDS FOR THE EXISTING CONDENSING
 UNITS THAT WERE RELOCATED TO THE
 EXISTING ROOF.HEIGHT OF THE STANDS
 SHALL COMPLY WITH TABLE 1509.7 OF THE
 2004 FBC.
  
 4.PLEASE INDICATE HOW THE EQUIPMENT
 LOCATED ON THE ROOF WILL BE ACCESSED FOR
 SERVICE, MAINENTANCE OR REPLACEMENT.
 SHOW COMPLIANCE WITH 2004 FMC 306.5,
 EQUIPMENT LOCATED ON ROOFS WITH AN
 ELEVATION OF 16FT OR GREATER SHALL HAVE
 A PERMANENT MEANS OF ACCESS.
  
 5.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2004 FMC
 TABLE 403.3.
  
 6.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS PER 2004 FMC
 606.4.1 EXCEPTION #2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-08-30 Cont ID  
Sent By kstevens Date 2007-08-30 Time 17:42 Rev Time 0.00
Received By kstevens Date 2007-08-30 Time 17:42 Sent To  
Notes
2007-08-30 17:53:57DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****FROM PREVIOUS REVIEWS:
  
 1. APPLICATION DESCRIPTION OF PROJECT
 INDICATES "ADDITION ONTO EXISTING BLDG."
 PLANS INDICATE ALTERATION OF EXISTING
 BLDG. ALSO. PLEASE DESCRIBE PROJECT IN
 DETAIL ON APPLICATION AS REQUIRED.
 ****NEW APPLICATION INDICATES "NEW BUILDING" AND NO
 MENTION OF EXTERIOR REMODEL AS INDICATED ON SHT 2.1 (3
 OF 4 SHEETS). PLEASE DESCRIBE THE PROJECT IN DETAIL AS
 REQUIRED ON APPLICATION.
  
 2. OK
 3. OK
 4. SHT 8.2 RESTROOM ELEVATIONS. SHOW
 COMPLIANCE WITH THE FOLLOWING:
 FOR W/C'S:
 A. 11-4.16.2 OK
 B. 11-4.16.3 OK
 C. 11-4.16.4 OK
 D. 11-4.16.5 FLUSH CONTROLS ****NOT ADDRESSED
 FOR LAVS:
 A. 11-4.19.2 OK
 B. 11-4.19.3 OK
 FOR TOILET ROOMS:
 A. OK
 5. OK - NO WORK IN BREAKROOM
 6. SUBMIT A DETAIL FOR THE DRINKING
 FOUNTAIN SHOWING THE FOLLOWING:
 A. 11-4.15.2 OK
 B. 11-4.15.3 OK
 C. 11-4.15.4 OK
 D. 11-4.15.5 OK
 E. 11-4.1.3(10)(A) OK
 7. OK
 8. OK
  
 9. SUBMIT A WATER RISER DIAGRAM SHOWING
 ALL PIPE SIZES, VALVES AND WATER HAMMER
 ARRESTORS IF REQUIRED BY SECTION 604.9.
 (AIR CHAMBERS ARE NOT APPROVED). SECTION 106.3.5.1.3.
 ****RESPONSE NOTED, BUT THE HOSE BIBB IS NOT INDICATED
 ON THE WATER RISER DIAGRAM, AND THE RISER DIAGRAM DOES
 NOT REFLECT THE PIPE SIZE REQUIRED FOR THE W/C'S
 INDICATED IN THE FIXTURE CONNECTION SCHEDULE SHOWN ON
 SHT 11.1. PLEASE CORRELATE INFORMATION. (SHUT OFF VALVE
 REQUIRED ON SUPPLY LINE TO HOSE BIBB PER SECTION
 606.2(2)).
  
 10. OK
 11. OK
 12. OK
 13. OK
 14. SEPARATE IRRIGATION PLANS AND PERMIT
 REQUIRED. SECTION 106.3.5.1.3. (INFORMATIONAL).
 15. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 REMOVE ALL VOIDED SHEETS AND RESUBMIT
 ONE SET FOR COMPARISON.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-07-02 Cont ID  
Sent By pschmitz Date 2006-07-02 Time 08:09 Rev Time 0.00
Received By pschmitz Date 2006-07-02 Time 08:09 Sent To  
Notes
2006-07-02 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
  
 1) SHT 6.2 ROOF DRAINS SEC. 1107.2
 SEPERATE SYSTEMS.SECONDARY ROOF DRAIN
 SYSTEMS SHALL HAVE THE END POINT OF
 DISCHARGE, SEPERATE FROM THE PRIMARY
 SYSTEM.
  
 2) SHT 11.1 RTU A/C CONDENSATE,REFERENCE
 TO CIVIL DRAWINGS. PROVIDE A DETAIL
 SHOWING POINT OF DISPOSAL.
  
 3) SHT 11.1 WATER RISER: SEC 606.1 (4)
 FULLY OPEN VALVES, SHALL BE LOCATED AT
 THE TOP OF EVERY WATER DOWN FEED PIPE.
  
 4)SHT 4.1 PRIVATE BATH: SEC 11-4.1.3
 TOILET FACILITIES, PRIVATE TOILET ROOM
 FOR THE OCCUPANT OF A PRIVATE OFFICE,
 SHALL BE ADAPTABLE.
  
 5) NOTES FROM PREVIOUS PLAN REVIEW DATED
 2-11-06 NOT ADDRESSED.
  
 1. APPLICATION DESCRIPTION OF PROJECT
 INDICATES "ADDITION ONTO EXISTING BLDG."
 PLANS INDICATE ALTERATION OF EXISTING
 BLDG. ALSO. PLEASE DESCRIBE PROJECT IN
 DETAIL ON APPLICATION AS REQUIRED.
  
 3. INDICATE THE USE OF THE MEZZANINE,
 AND INDICATE THE USE OF THE WORKSHOP TO
 DETERMINE OCCUPANCY. SECTION 106.1.1.
  
 5. SUBMIT A DETAIL FOR THE BREAK ROOM
 SINK SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD
 APPROACH REQUIED)
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 F. 11-4.24.7 FAUCETS
  
 7. SHOW PIPE ROUTING FOR THESTORM, AND
 CONDENSATE. SECTIONS 106.1.1, AND
 106.3.5.1.3.
  
 10. SUBMIT A STORM RISER DIAGRAM SHOWING
 ALL PIPE SIZES AND INDICATE THE SQUARE
 FOOTAGE DRAINED BY EACH DRAIN. SECTION
 106.3.5.1.3.
  
 14. SEPARATE IRRIGATION PLANS AND PERMIT
 REQUIRED. SECTION 106.3.5.1.3.
  
 15. CODE ADOPTED IN FBC-2004 IN EFFECT
 SINCE 10-01 2005. PLEASE CHANGE
 REFERENCES TO CODE TO REFLECT THIS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 REMOVE ALL VOIDED SHEETS AND RESUBMIT
 ONE SET FOR COMPARISON.
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-02-11 Cont ID  
Sent By kstevens Date 2006-02-11 Time 13:06 Rev Time 2.88
Received By kstevens Date 2006-02-11 Time 13:06 Sent To  
Notes
2006-02-11 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. APPLICATION DESCRIPTION OF PROJECT
 INDICATES "ADDITION ONTO EXISTING BLDG."
 PLANS INDICATE ALTERATION OF EXISTING
 BLDG. ALSO. PLEASE DESCRIBE PROJECT IN
 DETAIL ON APPLICATION AS REQUIRED.
 2. SHT P4.1 PER TABLE A DRINKING
 FOUNTAIN IS REQUIRED.
 3. INDICATE THE USE OF THE MEZZANINE,
 AND INDICATE THE USE OF THE WORKSHOP TO
 DETERMINE OCCUPANCY. SECTION 106.1.1.
 4. SHT 8.2 RESTROOM ELEVATIONS. SHOW
 COMPLIANCE WITH THE FOLLOWING:
 FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.4 GRAB BARS (SHOW LENGTH OF
 GRAB BAR BEHIND THE W/C)
 D. 11-4.16.5 FLUSH CONTROLS
 FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 FOR TOILET ROOMS:
 A. TURNING AREA TO BE UNOBSTRUCTED, W/C
 SHALL NOT BE IN TURNING AREA. SECTION
 11-4.22.3
 5. SUBMIT A DETAIL FOR THE BREAK ROOM
 SINK SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD
 APPROACH REQUIED)
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 F. 11-4.24.7 FAUCETS
 6. SUBMIT A DETAIL FOR THE DRINKING
 FOUNTAIN SHOWING THE FOLLOWING:
 A. 11-4.15.2 SPOUT HEIGHT
 B. 11-4.15.3 SPOUT LOCATION
 C. 11-4.15.4 CONTROLS
 D. 11-4.15.5 CLEARANCES/CLEAR FLOOR
 SPACE
 E. 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
 7. SHOW PIPE ROUTING FOR THE SANT.
 SYSTEM, WATER PIPING, STORM, AND
 CONDENSATE. SECTIONS 106.1.1, AND
 106.3.5.1.3.
 8. SUBMIT A SANITARY RISER DIAGRAM
 ISOMETRIC SHOW ALL PIPE SIZES, TRAPS,
 VENTS REQUIRED. SECTION 106.3.5.1.3.
 9. SUBMIT A WATER RISER DIAGRAM SHOWING
 ALL PIPE SIZES, VALVES AND WATER HAMMER
 ARRESTORS IF REQUIRED BY SECTION 604.9.
 (AIR CHAMBERS ARE NOT APPROVED). SECTION 106.3.5.1.3.
 10. SUBMIT A STORM RISER DIAGRAM SHOWING
 ALL PIPE SIZES AND INDICATE THE SQUARE
 FOOTAGE DRAINED BY EACH DRAIN. SECTION 106.3.5.1.3.
 11. SUBMIT A CONDENSATE RISER DIAGRAM
 SHOWING ALL PIPE SIZE, TRAPS ETC. IN
 ISOMETRIC FORM.
 12. SHT 6.2 INDICATES 6" ROOF DRAINS
 WITH SCUPPERS IN PARAPET NEXT TO THE
 DRAINS. SHT 8.2 INDICATES DOWNSPOUTS
 OUTSIDE BLDG WALL. PLEASE CLARIFY. IF
 ROOF DRAINS ARE DOWNSPOUTS, DOWNSPOUTS
 SHALL DISCHARGE AT LEAST 1 FOOT AWAY
 FROM THE STRUCTURE SIDEWALL. PLEASE
 INDICATE HOW THIS WILL BE ACCOMPLISHED.
 SECTION 1503.6.
 13. RPZV BACKFLOW REQUIRED ON THE WATER
 SERVICE TO BLDG.
 14. SEPARATE IRRIGATION PLANS AND PERMIT
 REQUIRED. SECTION 106.3.5.1.3.
 15. CODE ADOPTED IN FBC-2004 IN EFFECT
 SINCE 10-01 2005. PLEASE CHANGE
 REFERENCES TO CODE TO REFLECT THIS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 REMOVE ALL VOIDED SHEETS AND RESUBMIT
 ONE SET FOR COMPARISON.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status F Date 2007-08-16 Cont ID  
Sent By jroach Date 2007-08-16 Time 08:47 Rev Time 0.00
Received By jroach Date 2007-08-16 Time 08:47 Sent To  
Notes
2007-08-16 08:51:14***FAILED***
  
 PAVING AND DRAINAGE PLANS WERE NOT RESUBMITTED...SOME
 WERE MADE AT THE TIME OF THE LAST REVIEW AND COULD NOT
 BE VERIFIED IF THEY HAD BEEN ADDRESSED.ARE THE PAVING
 AND DRAINAGE PLANS BEING REMOVED FROM THE PACKAGE?
 PLEASE CLARIFY.
  
 1) THE SITE PLAN AND PAVING AND DRAINAGE
 PLANS DO NOT CORRESPOND WITH EACH OTHER.
  
 1A) THE SITE PLAN SHOWS 16 PARKING
 SPACES WHILE THE PANDD PLANS SHOW 15.
  
 1B) THE LOCATION OF THE HC PARKING SPACE
 DIFFERS BETWEEN THE PLANS.
  
 1C) THE PANDD PLANS SHOW LANDSCAPING IN
 THE SW CORNER OF THE PARKING LOT, THE
 SITE PLAN DOES NOT.
  
 THE FOLLOWING COMMENTS HAVE NOT BEEN ADDRESSED...
  
 2) THE PARKING DETAIL ON THE SITE PLAN
 DOES NOT CONFORM TO SECTION 94-485 OF
 THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (I.E. DOUBLE STRIPING,
 ETC.). NO DIMENSIONS WERE SHOWN BETWEEN THE STRIPING.
 SEE THE ATTACHED DETAIL FOR REFERENCE.
  
 4) PLEASE PROVIDE PROOF OF ACCEPTANCE OF
 THE DUMPSTER LOCATION FROM THE CITY'S
 SANITATION DEPARTMENT.
  
 8) PLEASE PROVIDE EVIDENCE OF OBTAINING
 TRAFFIC CONCURRENCY (TRAFFIC CONCURRENCY
 LETTER) FROM PALM BEACH COUNTY.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 SENIOR PLANNER, AT (561) 822-1435.

Review Stop Z ZONING
Rev No 3 Status F Date 2007-07-18 Cont ID  
Sent By rbrown Date 2007-07-18 Time 14:17 Rev Time 0.00
Received By rbrown Date 2007-07-18 Time 14:17 Sent To  
Notes
2007-07-18 14:18:37THE FOLLOWING IS A NOTE ABOUT PERMIT EXPIRATION.IT IS
 NOT A ZONING PLAN REVIEW:
  
 6/1/07 MET WITH OWNERS AND CRA.CHANGED STATUS FROM
 EXPIRED TO OPEN BECAUSE SOME OF THE ZONING COMMENTS
 WERE ADDRESSED IN MEETINGS AND CORRESPONDENCE BETWEEN
 THE OWNERS AND PLANNING DEPT.AS CONFIRMATION OF THAT,
 JOHN ROACH IS TO UPDATE ZONING PLAN REVIEW NOTES TO
 REFLECT THE FACT THAT SOME OF THE ZONING REVIEW
 COMMENTS WERE ADDRESSED ON 10/11/06. RB

Review Stop Z ZONING
Rev No 2 Status F Date 2006-07-17 Cont ID  
Sent By jroach Date 2006-07-17 Time 11:40 Rev Time 0.00
Received By jroach Date 2006-07-17 Time 11:40 Sent To  
Notes
2006-07-17 00:00:007/17/06 ***FAILED***
  
 1) THE SITE PLAN AND PAVING AND DRAINAGE
 PLANS DO NOT CORRESPOND WITH EACH OTHER.
  
 1A) THE SITE PLAN SHOWS 16 PARKING
 SPACES WHILE THE PANDD PLANS SHOW 15.
  
 1B) THE LOCATION OF THE HC PARKING SPACE
 DIFFERS BETWEEN THE PLANS.
  
 1C) THE PANDD PLANS SHOW LANDSCAPING IN
 THE SW CORNER OF THE PARKING LOT, THE
 SITE PLAN DOES NOT.
  
 1D) THE SITE PLAN DOES NOT SHOW A FIVE
 (5) FOOT LANDSCAPE TERMINAL ISLAND, WITH
 SHADE TREE, AT THE NE CORNER OF THE
 PARKING LOT.THIS IS REQUIRED.
  
 1E) NO DRIVEWAY APPROACH IS SHOWN ON THE
 SITE PLANS.
  
 2) THE PARKING DETAIL ON THE SITE PLAN
 DOES NOT CONFORM TO SECTION 94-485 OF
 THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (I.E. DOUBLE STRIPING,
 ETC.).
  
 3) THE SITE PLAN DOES NOT PROVIDE A DATA
 TABLE INDICATING PARKING CALCULATIONS,
 IMPERVIOUS, PERVIOUS, BUILDING SQUARE
 FOOTAGE, ETC.
  
 4) PLEASE PROVIDE PROOF OF ACCEPTANCE OF
 THE DUMPSTER LOCATION FROM THE CITY'S
 SANITATION DEPARTMENT.
  
 5) THE SE CORNER OF THE PARKING LOT
 SHALL BE CURBED AND LANDSCAPED WITH AT
 LEAST ONE (1) SHADE TREE.
  
 6) THE PROPOSED BUILDING ENCROACHES INTO
 THE VISIBILITY TRIANGLE (20 FEET X 20
 FEET) AT THE CORNER.
  
 7) PLEASE PROVIDE PHOTOMETRIC PLAN OF
 THE EXTERIOR LIGHTING.PHOTOMETRIC
 LEVELS SHALL NOT EXCEED 0.5 FOOTCANDLES
 WHEN MEASURED IN A RESIDENTIAL ZONING
 DISTRICT (I.E. WEST PROPERTY LINE).
  
 8) PLEASE PROVIDE EVIDENCE OF OBTAINING
 TRAFFIC CONCURRENCY (TRAFFIC CONCURRENCY
 LETTER) FROM PALM BEACH COUNTY.
  
 9) A SCREEN WALL SHALL BE BUILT ALONG
 THE WEST PROPERTY LINE, SEPARATING THE
 NONRESIDENTIAL USE FROM THE ADJACENT
 RESIDENTIAL ZONING DISTRICT.
  
 10) LANDSCAPE PLANS SHALL BE SUBMITTED
 AN SHALL BE CONSISTENT WITH THE SITE
 PLAN.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 SENIOR PLANNER, AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-01-12 Cont ID  
Sent By gjoyce Date 2006-01-12 Time 09:52 Rev Time 0.00
Received By gjoyce Date 2006-01-12 Time 09:52 Sent To  
Notes
***NONE***