| 2005-11-09 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05110180 | | | ADD: 8403 IRONHORSE COURT | | | CONT: GUSTAFSON | | | TEL: (561)732-0656 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW: | | | ACTION: DENIED | | | | | | 1) PROVIDE THE MEAN ROOF HEIGHT | | | | | | 2) ENTEGRA ROOF TILE: | | | REPORT SUBMITTED IS UNDER THE 2001 CODE | | | HIGHLIGHT WHICH TILE WILL BE INSTALLED. | | | HIGHLIGHT WHICH FASTENING SYSTEM TO BE | | | USED, MECHANICAL, IF MORTAR OR ADHESIVE | | | SET, PROVIDE THE ADDITIONAL REPORTS | | | REQUIRED SBCCI, PST ESI OR NES. | | | | | | 3) THE TARCO REPORT SUBMITTED IS FOR THE | | | 2001 CODE NOT THE 2004. SECOND HIGHLIGHT | | | WHERE THIS REPORT CAN BE USED FOR 140 | | | MPH WIND ZONES WITH NEGATIVE PRESSURES | | | OF -89.0 FOR ZONE 3 OF ROOF. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
|