Plan Review Details - Permit 05101241
Plan Review Stops For Permit 05101241
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-10-23 Cont ID  
Sent By kconrad Date 2006-10-21 Time 09:48 Rev Time 0.00
Received By kconrad Date 2006-10-21 Time 09:48 Sent To I
Notes
2006-10-23 09:56:39SEE FRC SECTION R310.4: WHILE HURRICANE PROTECTECTION
 IS PROVIDED, AT LEAST ONE MEANS OF ESCAPE MUST BE
 PROVIDED WITHIN THE FIRST FLOOR OF THE DWELLING OR
 DWELLING UNIT AND SHALL NOT BE LOCATED WITHIN THE
 GARAGE. OCCUPANTS IN ANY PART OF THE DWELLING OR
 DWELLING UNIT SHALL BE ABLE TO ACCESS THE MEANS OF
 ESCAPE WITHOUT PASSING THROUGH A LOCKABLE DOOR NOT
 UNDER THEIR CONTROL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-04-04 Cont ID  
Sent By jgomez Date 2006-04-04 Time 15:48 Rev Time 3.00
Received By jgomez Date 2006-04-04 Time 15:48 Sent To  
Notes
2006-04-04 00:00:00BUILDING REVIEW PROVISO:
 *1- SHEET A-3: A) REVISE TYPE OF
 CONSTRUCTION. SEE FBC 2004. THERE IS NOT
 CONSTRUCTION TYPE VI ON 2004 FBC.
 B) MEAN ROOF HEIGHT IS +/-21'-3", NOT
 15'-0. REVISE AS REQUIRED.
 C) REVISE BUILDING HEIGHT. SEE
 DEFINITION ON SEC. 502 FBC 2004.
 D) REVISE/CLARIFY REFERENCE TABLE USED
 FOR WIND ANALYSIS. WHICH ONE IS TABLE
 R301.2?. SEE TABLES AND REVISE AS REQ'D.
 *2- TRUSS DESIGN PACKAGE: A) ENGINEER TO
 USE CURRENT APPROVED SEAL THAT SAYS
 "LICENSE" INSTEAD OF "CERTIFICATE" AS
 REQUIRED BY FLORIDA ADMINISTRATIVE CODE.
 B) ALL GENERAL DETAILS SUBMITTED WITH
 TRUSS PACKAGE NEED TO HAVE ENGINEER'S
 ORIGINAL SEAL, SIGNATURE AND DATE AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE
 AND FLORIDA ADMINISTRATIVE CODE
 61G15-23.002.
 *3- CONNECTOR SPECIFIED FOR GIRDER TRUSS
 N1G DOESN'T RESIST THE CALCULATED UPLIFT
 LOADS. ARCHITECT TO REVISE CONNECTOR.
 *4- RE-SUBMIT COMPLETE PRODUCT APPROVAL
 PACKAGE. NEED TO PROVIDE 2004 FLORIDA
 PRODUCT APPROVAL VERSION, NOT 2001.
 *5- PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS UNDER A SEPARATE PERMIT.
 *6- NEED SURVEY WITH ORIGINAL SIGNATURE
 AS REQUIRED BY CHAPTER 472 FL. STATUTE.
 *7- ARCHITECT'S REVIEW STAMP USED TO
 APPROVE PRODUCT APPROVALS DOESN'T HAVE
 THE ARCHITECT'S NAME OR COMPANY'S NAME
 ON IT. NEED STAMP THAT IDENTIFIES
 COMPANY OR ARCHITECT REVIEWING THE
 PRODUCTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-27 Cont ID  
Sent By jgomez Date 2005-12-27 Time 17:56 Rev Time 3.00
Received By jgomez Date 2005-12-27 Time 17:17 Sent To Z
Notes
2005-12-27 00:00:00BUILDING REVIEW CHECKLIST:
 1- ALL PLANS SUBMITTED AFTER OCTOBER 1ST
 2005 ARE REQUIRED TO COMPLY WITH FBC
 2004. REVISE ALL PLANS, GENERAL NOTES,
 DESIGN PARAMETERS, CONSTRUCTION TYPE AND
 ALL PERTINENT ITEMS SHOWN ON PLANS AS
 REQUIRED TO COMPLY WITH FBC 2004.
  
 2- ENERGY CALCS SUBMITTED ARE DONE USING
 FBC 2001 FORMS. NEED TO REVISE CALCS
 USING FBC 2004 FORMS.
  
 3- TRUSS DESIGN DRAWINGS NEED TO BE
 PROVIDED TO THE BUILDING OFFICIAL FOR
 APPROVAL PRIOR TO INSTALLATION. SEC.
 R802.10.1 OF RESIDENTIAL FLORIDA
 BUILDING CODE 2004. (REMAINDER: DESIGNER
 OF RECORD TO REVIEW ALL TRUSSES PRIOR TO
 SUBMITTAL TO THIS OFFICE).
  
 4- DESIGNER OF RECORD TO REVIEW ALL
 PRODUCT APPROVALS PRIOR TO SUBMITTAL TO
 THIS OFFICE AS REQUIRED BY SEC. 106.3.3
 CITY AMENDMENTS TO FBC 2004.
 ***NOTE: PLEASE, DON'T PUT THE REVIEW
 STAMP ON THE BACK OF THE PAGE OF THE
 PRODUCT APPROVAL BECAUSE IT CAN'T BE
 SCANNED FOR FILING PURPOSES.
  
 5- PROVIDE ALL INFORMATION ON PLANS
 REGARDING THE GARAGE SEPARATION AS
 REQUIRED BY SEC. R309 OF THE RESIDENTIAL
 FBC 2004.
  
 6- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) FIXED WINDOWS.
 ***NOTE: CHECK SIZES SHOWN ON PLANS. EG:
 SEE BREAKFAST AREA.
 B) CASEMENT WINDOWS: NOA SUBMITTED
 DOESN'T MATCH NOA SUBMITTED FOR FLORIDA
 APPROVAL. ALSO, CLARIFY IF USING IMPACT
 WINDOWS OR NOT.
  
 7- PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS. THERE WAS NOT
 INFORMATION SUBMITTED WITH THIS PACKAGE.
 SEE ATTACHED INSTALLATION SCHEDULE
 SAMPLE THAT HELPS TO PROVIDE ALL
 REQUIRED INFORMATION FOR PLAN REVIEW.
  
 8- AREA CALCS SHOWN ON SHEET A3 DON'T
 ADD UP. REVISE AS REQUIRED. ALSO, AREA
 SHOWN ON PERMIT APPLICATION DOESN'T
 MATCH PLANS. REVISE AS REQUIRED.
  
 9- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-09-11 Cont ID  
Sent By btrobaug Date 2006-09-11 Time 17:56 Rev Time 0.50
Received By btrobaug Date 2006-09-11 Time 17:56 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-07-24 Cont ID  
Sent By dpalmer Date 2006-07-24 Time 18:41 Rev Time 0.00
Received By dpalmer Date 2006-07-24 Time 18:41 Sent To PC
Notes
2006-07-24 00:00:00REV FOR AS BUILTS

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-03-23 Cont ID  
Sent By btrobaug Date 2006-03-23 Time 17:17 Rev Time 0.50
Received By btrobaug Date 2006-03-23 Time 17:01 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-11-21 Cont ID  
Sent By btrobaug Date 2005-11-21 Time 11:08 Rev Time 0.50
Received By btrobaug Date 2005-11-17 Time 08:07 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-25 Cont ID  
Sent By adarroug Date 2006-08-25 Time 09:35 Rev Time 0.00
Received By adarroug Date 2006-08-25 Time 09:35 Sent To E
Notes
2006-08-25 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-24 Cont ID  
Sent By adarroug Date 2006-07-24 Time 09:52 Rev Time 0.00
Received By adarroug Date 2006-07-24 Time 09:52 Sent To E
Notes
2006-07-24 00:00:00TO "E" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-21 Cont ID  
Sent By dpalmer Date 2006-03-21 Time 12:03 Rev Time 0.00
Received By dpalmer Date 2006-03-21 Time 12:03 Sent To E
Notes
2006-03-21 00:00:00TO BT'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-03 Cont ID  
Sent By adarroug Date 2006-03-03 Time 10:12 Rev Time 0.00
Received By adarroug Date 2006-03-03 Time 10:12 Sent To Z
Notes
2006-03-03 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-03 Cont ID  
Sent By adarroug Date 2006-01-03 Time 14:31 Rev Time 0.00
Received By adarroug Date 2005-11-14 Time 11:24 Sent To  
Notes
2005-11-14 00:00:00TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2006-03-24 Cont ID  
Sent By tgordon Date 2006-03-24 Time 09:34 Rev Time 0.15
Received By tgordon Date 2006-03-24 Time 09:34 Sent To P
Notes
2006-03-24 00:00:00NO MECHANICAL PLANS SUBMITTED, AND
 CUSTOMER VOIDED MECHANICAL PERMIT NUMBER
 05101244 AND WILL APPLY FOR LATER AND
 SUBMIT MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-11-21 Cont ID  
Sent By tgordon Date 2005-11-21 Time 11:11 Rev Time 0.15
Received By tgordon Date 2005-11-21 Time 11:11 Sent To P
Notes
2005-11-21 00:00:00*** DENIED ***
 NO MECHANICAL PLANS SUBMITTED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-03-24 Cont ID  
Sent By jleech Date 2006-03-24 Time 10:42 Rev Time 0.00
Received By jleech Date 2006-03-24 Time 10:42 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-11-21 Cont ID  
Sent By jleech Date 2005-11-21 Time 18:30 Rev Time 0.33
Received By jleech Date 2005-11-21 Time 18:30 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-03-17 Cont ID  
Sent By lfranco Date 2006-03-17 Time 12:16 Rev Time 0.00
Received By lfranco Date 2006-03-17 Time 12:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-01-03 Cont ID  
Sent By lfranco Date 2006-01-03 Time 14:00 Rev Time 0.00
Received By lfranco Date 2006-01-03 Time 13:35 Sent To  
Notes
2006-01-03 00:00:00ZONING REVIEW COMMENTS:
 1.ORIENTATION OF BUILDING FOOTPRINT ON
 SURVEY DOES NOT MATCH ACTUAL FLOOR PLAN.
 REVISE DRAWINGS ACCORDINGLY.
  
 2. PROVIDE A LOCATION MAP ON BOTH SURVEY
 AND ARCHITECTURAL CONSTRUCTION
 DOCUMENTS' COVER PAGE. (I.E INCLUDE WHAT
 "POD", TRACT OF IBIS GOLF & COUNTRY CLUB
 MASTER PLAN THIS LOT 21 BELONGS TO).