Plan Review Details - Permit 05101201
Plan Review Stops For Permit 05101201
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-08-03 Cont ID  
Sent By shill Date 2006-08-03 Time 17:09 Rev Time 0.00
Received By shill Date 2006-08-03 Time 17:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-05-02 Cont ID  
Sent By shill Date 2006-05-02 Time 17:12 Rev Time 0.00
Received By shill Date 2006-05-02 Time 17:12 Sent To  
Notes
2006-05-02 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 FROM PREVIOUS LISTS:
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 THE NOC PROVIDED IS EXPIRED, OVER 90
 DAYS WITHOUT COMMENCING WORK
 FS713.13(2).
  
 2.)PROVIDE BUILDING MEAN ROOF HEIGHT.
 DESIGN PRESSURES FOR BUILDINGS OVER
 60FEET ARE REQUIRED TO BE DESIGNED USING
 ASCE7, FBC1609.1.1.DOCUMENTS PREPARED
 BY AN ENGINEER AND SUBMITTED FOR PUBLIC
 RECORD ARE TO BE SIGNED SEALED ORIGINALS
 FAC61G15-23.002.
  
 (SECOND REVIEW) THE SCHEDULE GIVES
 DESIGN PRESSURES OF -13.5 AND -14.1, BUT
 -45 IS CIRCLED ON SHEET 9 OF THE PRODUCT
 APPROVAL.DESIGN PRESSURES ARE TO BE
 DETERMINED BY FBC TABLE 1609.6B AND
 1609.6D.
  
 (THIRD REVIEW) A NEW SCHEDULE GIVES THE
 WORST CASE PRESSURE AS -54.5 BUT PAGE 9
 HAS -45 CIRCLED.NO ANCHORING IS
 SPECIFIED ON EITHER THE INSTALLATION
 SCHEDULE OR ON THE TABLES ON THE PRODUCT
 APPROVALS.
  
 3.)ADDRESSED.
  
 4.)COMPLETE THE ATTACHED INSTALLATION
 SCHEDULE, OR PROVIDE REQUIRED
 INFORMATION IN A SIMILAR FORMAT.SEE
 ATTACHED POLICY.
  
 (SECOND REVIEW) THE FORM WAS NOT FILLED
 OUT CORRECTLY (ALL COLUMNS BLANKEXCEPT
 FOR DPS WHICH ARE INCORRECT).NO ANCHOR
 SPACING INDICATED ON PRODUCT APPROVAL.
 NOT ENOUGH INFORMATION PROVIDED TO
 DETERMINE CODE COMPLIANCE.
  
 (THIRD REVIEW) SAME PAPERWORK SUBMITTED.
 NO ANCHORING SPECIFIED.
  
 NEW COMMENT:
  
 5.)ONLY ONE PRODUCT APPROVAL WAS
 SUBMITTED. SUBMIT TWO COPIES OF ALL
 DOCUMENTS FOR PERMITTING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-02-17 Cont ID  
Sent By shill Date 2006-02-17 Time 14:38 Rev Time 0.00
Received By shill Date 2006-02-17 Time 14:38 Sent To  
Notes
2006-02-17 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 FROM PREVIOUS LIST:
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 THE NOC PROVIDED IS EXPIRED, OVER 90
 DAYS WITHOUT COMMENCING WORK
 FS713.13(2).
  
 2.)PROVIDE BUILDING MEAN ROOF HEIGHT.
 DESIGN PRESSURES FOR BUILDINGS OVER
 60FEET ARE REQUIRED TO BE DESIGNED USING
 ASCE7, FBC1609.1.1.DOCUMENTS PREPARED
 BY AN ENGINEER AND SUBMITTED FOR PUBLIC
 RECORD ARE TO BE SIGNED SEALED ORIGINALS
 FAC61G15-23.002.
  
 THE SCHEDULE GIVES DESIGN PRESSURES OF
 -13.5 AND -14.1, BUT -45 IS CIRCLED ON
 SHEET 9 OF THE PRODUCT APPROVAL.DESIGN
 PRESSURES ARE TO BE DETERMINED BY FBC
 TABLE 1609.6B AND 1609.6D.
  
 3.)ADDRESSED.
  
 4.)COMPLETE THE ATTACHED INSTALLATION
 SCHEDULE, OR PROVIDE REQUIRED
 INFORMATION IN A SIMILAR FORMAT.SEE
 ATTACHED POLICY.
  
 THE FORM WAS NOT FILLED OUT CORRECTLY
 (ALL COLUMNS BLANKEXCEPT FOR DPS WHICH
 ARE INCORRECT).NO ANCHOR SPACING
 INDICATED ON PRODUCT APPROVAL.NOT
 ENOUGH INFORMATION PROVIDED TO DETERMINE
 CODE COMPLIANCE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-06 Cont ID  
Sent By shill Date 2005-12-06 Time 09:10 Rev Time 0.00
Received By shill Date 2005-12-06 Time 09:10 Sent To  
Notes
2005-12-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)PROVIDE BUILDING MEAN ROOF HEIGHT.
 DESIGN PRESSURES FOR BUILDINGS OVER
 60FEET
 ARE REQUIRED TO BE DESIGNED USING ASCE7,
 FBC1609.1.1.DOCUMENTS PREPARED BY AN
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD
 ARE TO BE SIGNED SEALED ORIGINALS
 FAC61G15-23.002.
  
 3.)PROVIDE A COPY OF THE CONDO
 ASSOCIATION APPROVAL.
  
 4.)COMPLETE THE ATTACHED INSTALLATION
 SCHEDULE, OR PROVIDE REQUIRED
 INFORMATION IN A SIMILAR FORMAT.SEE
 ATTACHED POLICY.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-24 Cont ID  
Sent By adarroug Date 2006-07-24 Time 11:33 Rev Time 0.00
Received By adarroug Date 2006-07-24 Time 11:33 Sent To B
Notes
2006-07-24 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-20 Cont ID  
Sent By adarroug Date 2006-04-20 Time 15:32 Rev Time 0.00
Received By adarroug Date 2006-04-20 Time 15:32 Sent To B
Notes
2006-04-20 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-14 Cont ID  
Sent By adarroug Date 2006-02-14 Time 09:06 Rev Time 0.00
Received By adarroug Date 2006-02-14 Time 09:06 Sent To B
Notes
2006-02-14 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-22 Cont ID  
Sent By adarroug Date 2005-10-22 Time 12:03 Rev Time 0.00
Received By adarroug Date 2005-10-22 Time 12:03 Sent To B
Notes
2005-10-22 00:00:00TO "MISC" BOX#1