Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-01-26 Cont ID  
Sent By btrobaug Date 2006-01-26 Time 11:24 Rev Time 1.00
Received By btrobaug Date 2006-01-26 Time 07:47 Sent To Z
Notes
2006-01-26 00:00:00 
 PROVISO
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW PRIOR TO CALLING INSPECTION.
  
  
 1} 445.13 AMPACITY OF CONDUCTORS.
 THE AMPACITY OF THE CONDUCTORS FROM THE
 GENERATOR TERMINALS TO THE FIRST
 DISTRIBUTION DEVICE(S) CONTAINING
 OVERCURRENT PROTECTION SHALL NOT BE LESS
 THAN 115 PERCENT OF THE NAMEPLATE
 CURRENT RATING OF THE GENERATOR.
  
 2} THE FEEDER FROM THE ATS TO THE
 "EMERGENCY" PANEL ALSO MUST COMPLY WITH
 310.15. THE OCP MUST BE DECREASED OR THE
 CONDUCTOR SIZE INCREASED.I FTHERE ARE
 ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2005-11-18 Cont ID  
Sent By btrobaug Date 2005-11-18 Time 12:03 Rev Time 0.50
Received By btrobaug Date 2005-11-18 Time 11:29 Sent To PC
Notes
2005-11-18 00:00:00 
 A RESIDENTIAL GENERATOR PERMIT MUST BE
 APPLIED FOR BEFORE THE ELECTRICAL OR
 FUEL PERMITS CAN BE ISSUED.
  
 PLEASE SUBMIT MANUFACTURERS
 SPECIFICATIONS FOR THE EQUIPMENT BEING
 INSTALLED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-02 Cont ID  
Sent By adarroug Date 2006-02-02 Time 14:45 Rev Time 0.00
Received By adarroug Date 2006-02-02 Time 14:44 Sent To M
Notes
2006-02-02 00:00:00TO "GEN-RES" BOX "M"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-22 Cont ID  
Sent By adarroug Date 2005-10-22 Time 12:18 Rev Time 0.00
Received By adarroug Date 2005-10-22 Time 12:18 Sent To E
Notes
2005-10-22 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-02-07 Cont ID  
Sent By tgordon Date 2006-02-07 Time 08:47 Rev Time 0.20
Received By tgordon Date 2006-02-07 Time 08:47 Sent To E
Notes
2006-02-07 00:00:00*** PROVISO ***
 1)GENERATOR EXHUST MUST BE TEN FEET AWAY
 FROM ANY BUILDING OPENINGS (WINDOWS,
 DOORS, ROOF & EAVE VENTS), AND TEN FEET
 AWAY FROM ADJECENT BUILDING OPENS. PER
 2004 FBC/M 401.5.1 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-01-31 Cont ID  
Sent By mmclean Date 2006-01-31 Time 17:42 Rev Time 0.00
Received By mmclean Date 2006-01-31 Time 17:42 Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved