Plan Review Details - Permit 05101193
Plan Review Stops For Permit 05101193
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-06-27 Cont ID  
Sent By jwitmer Date 2006-06-27 Time 07:05 Rev Time 0.55
Received By jwitmer Date 2006-06-27 Time 07:05 Sent To PC
Notes
2006-06-27 00:00:00REVISION# 1 MEZZANINE LEVEL TO BE
 STORAGE OCCUPANCY, NO OFFICE SPACE ON
 THIS LEVEL. JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-01-10 Cont ID  
Sent By jwitmer Date 2006-01-10 Time 08:57 Rev Time 0.77
Received By jwitmer Date 2006-01-10 Time 08:57 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-29 Cont ID  
Sent By jwitmer Date 2005-11-29 Time 16:38 Rev Time 0.88
Received By jwitmer Date 2005-11-29 Time 16:38 Sent To PC
Notes
2005-11-29 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05101193
 ADD: 1335 OKEECHOBEE RD # 700
 CONT: PALM BEACH COPY SERVICE INC.
 TEL: (561)714-4265
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
  
 1) PERMIT APPLICATION INDICATES PALM
 BEACH COPY SERVICE INC HAS APPLIED FOR
 AN OWNER BUILDER PERMIT. SEE FL S S 489
 OWNER BUILDERS CAN NOT BE A CORPORATION,
 THEY CAN NOT BE A TRUSTEE OR A TRUST.
 OWNER BUILDERS ARE A INDIVIDUAL THAT CAN
 BE LEGALLY RESPONSIBLE. A CONTRACTOR
 WILL BE REQUIRED TO HAVE THE PERMIT,
 FEES AND PLANS TRANSFERRED TO THE
 CONTRACTING BUSSINESS. THE QUALIFIER
 WILL HAVE TO FILL OUT A NEW PERMIT
 APPLICATION AND PAY A $100.00 TRANSFER
 FEE BEFORE ISSUANCE OF PERMIT.
  
 PLEASE HAVE THE CONTRACTOR FILL OUT NEW
 APPLICATION & CORRECT THE ADDRESS TO
 1335 OKEECHOBEE RD, SUITE# 700, THERE IS
 NO OLD OKEECHOBEE RD IN THE CITY.WEST
 SIDE OF FL MANGO RD THE COUNTY NAMED THE
 SAME STREET OLD OKEECHOBEE.
  
 2) FBC 104.2.1ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.PLEASE COMPLY.
  
 3A) PLANS DO NOT INDICATE TO WHICH CODE
 THEY ARE DESIGNED NOR WHICH EDITION.
 3B) THE INFORMATIONAL ITEMS THAT NEED TO
 BE ADDRESSED FOR RECORD KEEPING PURPOSES
 MISSING UNDER 110.2*ARE AS FOLLOWS:
 3B(1)A DESCRIPTION OF THAT PORTION
  
 OF THE STRUCTURE FOR WHICH THE
  
 CERTIFICATE IS ISSUED.
 3B(2) THE NAME OF THE BUILDING
 OFFICIAL.
 3B(3) THE EDITION OF THE CODE UNDER
 WHICH THE PERMIT WAS ISSUED.
 3B(4) THE USE AND OCCUPANCY, IN
 ACCORDANCE WITH THE PROVISIONS
  
 OF CHAPTER 3 .
 3B(5) THE TYPE OF CONSTRUCTION AS
 DEFINED IN CHAPTER 6 .
 3B(6) THE DESIGN OCCUPANT LOAD.
 3B(7) IF AN AUTOMATIC SPRINKLER
 SYSTEM IS PROVIDED, WHETHER THE
  
 SPRINKLER SYSTEM IS REQUIRED.
 3B(8) ANY SPECIAL STIPULATIONS AND
 CONDITIONS OF THE BUILDING
 PERMIT.
  
 4A) PLANS INDICATE DRAWN TO 1/8" SCALE,
 BUT NOT ACCURATE, 106.1.3*QUALITY OF
 PLANS, BUILDING PLANS SHALL BE DRAWN TO
 A MINIMUM OF 1/8" SCALE.
 4B) BOTH PAGES INDICATE THAT IT IS THE
 BASE FLOOR PLAN BUT DEPICTS TWO
 DIFFERENT SCENARIO ONE A STORAGE CLOSET
 AND THE SECOND AND OFFICE LEADING TO THE
 EXTERIOR OF THE BUILDING, BUT NEITHER
 ARE DRAWN ON THE SAME PAGE?
 4C) THE THIRD INCONSISTANCY IS THE RIGHT
 SIDE OF THE DRAWING, ONE INDICATES A
 LANDING AND THEN STAIRS, THE SECOND
 DEPICT WHAT APPEARS TO BE A STAIRWAY
 THAT STARTS AGAINST A WALL AND ENDS
 AT WHAT APPEARS TO BE A SECOND STORY
 OFFICE?NOT A MEZZANINE BECAUSE IT IS
 2/3RD THE SPACE OF THE ROOM.
 PLEASE PROVIDE A VERTICAL CUT
 SECTION THROUGH THE MEZZANINE LEVEL
 INDICATING NEW WORK FROM THE FRONT OF
 THE BUILDING TO THE REAR.
 THE NEW STORAGE ROOM PLANS ARE DRAWN
 TO APPEARS TO HAVE DRYWALL ONLY ON ONE
 SIDE? ALSO WHAT WILL BE STORED IN THIS
 ROOM? WILL THIS ROOM BE FIRE
 SPRINKLERED?
  
 5) DEPENDING ON THE ANSWER TO 3B(4)
 OCCUPANCY AND SUB-CLASSIFICATION THERE
 MAY BE A PROBLEM WITH THE COMMON PATH OF
 TRAVEL FOR THE ANCILLARY USE OF THE
 OFFICE. SEE 1013.3 FOR COMMON PATH OF
 TRAVEL.
 5A) INDICATE WHAT THE USE OF THE FIRST
 FLOOR WILL BE, THE USE OF THE REMAINDER
 OF THE MEZZANINE, INDICATE ALLOWABLE
 SAFE FLOOR LOADS FOR EACH USE TABLE
 1607.1 FOR LIVE LOADS.
 5B) IF THE REMAINDER OF THE MEZANINE IS
 TO BE USED FOR STORAGE:
 5B)(1) 110.4.2 STORAGE & FACTORY- INDUS-
 TRIAL OCCUPANCIES. IT SHALL BE THE
 RESPONSIBILITY OF THE OWNER, AGENT,
 PROPIETOR OR OCCUPANT OF GROUP S AND
 GROUP F OCCUPANCIES, OR ANY OCCUPANCY
 WHERE EXCESSIVE FLOOR LOADING IS LIKELY
 TO OCCUR, TO EMPLOY A COMPETENT ARCHI-
 TECT OR ENGINEER IN COMPUTING THE SAFE
 FLOOR LOAD CAPACITY. ALL SUCH COMPUTA-
 TIONS SHALL BE ACCOMPANIED BY AN AFFA-
 DAVIT FROM THE ARCHITECT OR ENGINEER
 STATING THE SAFE ALLOWABLE FLOOR LOADS
 ON EACH FLOOR IN POUNDS PER SQ FT.THE
 COMPUTATIONS & AFFADAVIT SHALL BE FILED
 AS A PERMANENT RECORD OF THE BLDG DEPT.
  
 5B)(2) 110.4.3.SIGNS REQUIRED. IN EVERY
 BUILDING OR PART OF A BUILDING USED FOR
 STORAGE, INDUSTRIAL OR HAZARDOUS PUR-
 POSES, THE SAFE FLOOR LOADS, AS REVIEWED
 BY THE BUILDING OFFICIAL ON THE PLAN,
 SHALL BE MARKED ON PLATES OF APPROVED DE
 SIGN WHICH SHALL BE SUPPLIED & SECURELY
 AFFIXED BY THE OWNER OF THE BUILDING IN
 A CONSPICUOUS PLACE IN EACH STORY TO
 WHICH THEY RELATE. SUCH PLATES SHALL NOT
 BE REMOVEDOR DEFACED, & IF LOST,
 REMOVED THE OWNER OF THE BUILDING SHALL
 REPLACE THEM.
  
 6) THE OFFICE LOCATED ON THE MEZZANINE
 LEVEL INDICATE COMPLIANCE WITH:
 1203.1 GENERAL.
 BUILDINGS SHALL BE PROVIDED WITH NATURAL
 VENTILATION IN ACCORDANCE WITH SECTION
 1203.4 , OR MECHANICAL VENTILATION IN
 ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, MECHANICAL .
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-12-29 Cont ID  
Sent By dpalmer Date 2005-12-29 Time 06:05 Rev Time 0.00
Received By dpalmer Date 2005-12-29 Time 05:58 Sent To  
Notes
2005-12-29 00:00:00IN ELEC
 ******** PROVISO/REVISION NEEDED *****
  
  
 1)NOTE: PLEASE PROVIDE A PANEL SCHEDULE
 WHICH WILLL CORRELATE WITH ALL
 CIRCUITING ON PLANS AS REQUESTED ON
 ORIGINAL REVIEW.
 ** PLEASE SUBMIT THE REVISION ALONG WITH
 ANYOTHER CHANGES WHICH MAY BE MADE
 BEFORE ANY ROUGH ELECTRICAL INSPECTION.
  
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-11-29 Cont ID  
Sent By dpalmer Date 2005-11-29 Time 15:39 Rev Time 0.00
Received By dpalmer Date 2005-11-29 Time 15:29 Sent To  
Notes
2005-11-29 00:00:00********* UNSAT ***********
  
  
 1)NOTE: PLEASE SEE FS 489 WHICH WILL
 ONLY ALLOW AN OWNER OF A COMMERCIAL BLDG
 TO DO THE INTERIOR WORK AS AN INDIVIDUAL
 OWNER. THE O/B MAY NOT BE A COMPANY,
 CORPORATION ETC.
 PLEASE OBTAIN A CONTRACTOR TO APPLY FOR
 PERMIT.
  
 2)NOTE: PLEASE SEE PERMIT APPLICATION
 AND "PLANS" SUBMITTED ARE REQUIRED TO
 CONTAIN THE ADDRESS OF "OKEECHOBEE RD".
 "OLD OKEECHOBEE" IS NOT A STREET.
  
 3)NOTE: PLEASE PROVIDE CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED.
 215.5
  
 4)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 AND ANY OTHER REVIEW COMMENTS WITH
 RESPECT TO THE STORAGE USE.
  
 5)NOTE: PLEASE THAT ALL PLANS MUST
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONESIBLE FOR PLANS OR
 DESIGN. FBC 104.2.1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-12-29 Cont ID  
Sent By mwennerg Date 2005-12-29 Time 15:55 Rev Time 0.00
Received By mwennerg Date 2005-12-29 Time 15:55 Sent To  
Notes
2005-12-29 00:00:00******PROVISO******
  
 SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL IF APPLICABLE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-11-23 Cont ID  
Sent By nmccray Date 2005-11-23 Time 14:32 Rev Time 0.00
Received By nmccray Date 2005-11-23 Time 13:57 Sent To  
Notes
2005-11-23 00:00:00DENIED:
  
 1) DOES THE RENOVATION AFFECTS THE FIRE
 SPRINKLER PROTECTION COVERAGE?
  
 2) DOES THE RENOVATION AFFECTS THE FIRE
 ALARM DEVICES?
  
 3) SEPARATE PERMITS APPLICATIONS AND
 SHOP DRAWINGS ARE REQUIRED FOR FIRE
 ALARM AND FIRE SPRINKLER SYSTEMS.
  
  
 4) WHAT WILL BE STORED IN THIS NEW
 STORAGED ROOM?
  
 5) WHAT IS THE INTERIOR FINISH FOR WALLS
 AND CEILINGS?
  
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-22 Cont ID  
Sent By adarroug Date 2006-06-22 Time 16:12 Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 16:12 Sent To B
Notes
2006-06-22 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-13 Cont ID  
Sent By adarroug Date 2005-12-13 Time 14:01 Rev Time 0.00
Received By adarroug Date 2005-12-13 Time 14:01 Sent To  
Notes
2005-12-28 00:00:00TO "BOB"#12
2005-12-13 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-11-30 Cont ID  
Sent By jwitmer Date 2005-11-30 Time 10:37 Rev Time 0.00
Received By jwitmer Date 2005-11-08 Time 08:39 Sent To  
Notes
2005-11-22 00:00:00TO "COMM" BD#13
2005-11-08 00:00:00WAITING FOR "COMM"BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-01-06 Cont ID  
Sent By tgordon Date 2006-01-06 Time 14:14 Rev Time 0.15
Received By tgordon Date 2006-01-06 Time 14:14 Sent To  
Notes
2006-01-06 00:00:00PREVIOUS REVIEW COMMENTS HAVE BEEN
 CORRECTED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-01-04 Cont ID  
Sent By tgordon Date 2006-01-04 Time 14:50 Rev Time 0.45
Received By tgordon Date 2006-01-04 Time 14:50 Sent To  
Notes
2006-01-04 00:00:00*** DENIED ***
 1)ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 2) NEED TO SHOW TRANSFER AIR GRILL SIZE
 AND SUPPLY AIR DUCT SIZE. PLEASE NOTE
 TRANSFER GRILL MUST BE 50 SQUARE INCHES
 PER 100 CFM'S OF SUPPLY AIR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
2005-12-29 00:00:00NEW MECH SHEETS.