Plan Review Details - Permit 05101187
Plan Review Stops For Permit 05101187
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-01-03 Cont ID  
Sent By nmccray Date 2006-01-03 Time 14:43 Rev Time 0.00
Received By nmccray Date 2006-01-03 Time 14:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-11-21 Cont ID  
Sent By nmccray Date 2005-11-21 Time 16:14 Rev Time 0.00
Received By nmccray Date 2005-11-21 Time 16:14 Sent To  
Notes
2005-11-21 00:00:00DENIED:
  
 1) NEW FIRE ALARM SYSTEMS SHALL BE
 LISTED FOR CENTRAL STATION SERVICE.
  
 2) ALL FIRE ALARM SYSTEMS THAT SUPERVISE
 FIRE SPRINKLER SYSTEMS SHALL BE UL
 CERTIFICATED AND HAVE DOCUMENT ATTESTING
 TO THIS CERTIFICATION PRIOR TO FINAL
 APPROVAL OF THE FIRE ALARM SYSTEM.
  
 3) THE FIRE ALARM SYSTEM SHALL BE CLASS
 "A" OR FULLY ADDRESSABLE.
  
 4) THE CITY OF WEST PALM BEACH FIRE
 MARSHAL OFFICE REQUIRED DUCT DETECTORS
 TO INITIATE A GENERAL FIRE ALARM.
  
 5) PLEASE EXPLAIN WHY THERE ARE TWO (2)
 PERMIT APPLICATION FOR FIRE ALARM SYSTEM
 FOR THIS BUILDING. (05100244)
  
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-20 Cont ID  
Sent By adarroug Date 2005-12-20 Time 15:12 Rev Time 0.00
Received By adarroug Date 2005-12-20 Time 15:12 Sent To FIRE
Notes
2005-12-20 00:00:00TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-22 Cont ID  
Sent By adarroug Date 2005-10-22 Time 11:39 Rev Time 0.00
Received By adarroug Date 2005-10-22 Time 11:39 Sent To FIRE
Notes
2005-10-22 00:00:00TO "F" BOX