Plan Review Details - Permit 05101140
Plan Review Stops For Permit 05101140
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-04-28 Cont ID  
Sent By shill Date 2006-04-19 Time 15:56 Rev Time 0.00
Received By shill Date 2006-04-19 Time 15:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-06 Cont ID  
Sent By shill Date 2006-04-06 Time 13:29 Rev Time 0.00
Received By shill Date 2006-04-06 Time 13:29 Sent To  
Notes
2006-04-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)YOU HAVE SUBMITTED TWO PRODUCT
 APPROVALS FOR PANELS.CLARIFY; ARE YOU
 INSTALLING TWO DIFFERENT TYPES OF
 PANELS?
  
 2.)THE INSTALLATION SCHEDULE STATES
 THAT YOU ARE INSTALLING FL#358, BUT THIS
 IS NOT ONE OF THE PRODUCT APPROVALS
 SUBMTITED.
  
 3.)TWO COPIES OF ALL DOCUMENTS
 REQUIRED.ONLY ONE FLOOR
 PLAN/INSTALLATION SCHEDULE WAS
 SUBMITTED.
  
 4.)YOU HAVE SPECIFIED 1" FASTENERS,
 BUT THERE IS A 7/8" EMBEDMENT
 REQUIREMENT.THIS LEAVES ONLY 1/8" FOR
 STUCCO.PLEASE ADDRESS.
  
 5.)IT IS NOT CLEAR HOW YOU HAVE
 ARRIVED AT THE DESIGN PRESSURES.FOR
 INSTANCE, OPENING 3 IS 18SF, SHOULD BE
 -47.3 EXPOSURE C, 19' MRF AS YOU HAVE
 DECLARED ON THE INSTALLATION SCHEDULE.
 SEE FBC TABLE 1609.6B, 1606.2D.PLEASE
 CONTACT ME IF YOU NEED ASSISTANCE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-06 Cont ID  
Sent By shill Date 2005-12-06 Time 09:40 Rev Time 0.50
Received By shill Date 2005-12-06 Time 09:40 Sent To  
Notes
2005-12-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)ADDITIONAL FEES DUE, VALUATION
 ADJUSTMENT USING MARSHALL & SWIFT.
  
 3.)THE INSTALLATION SCHEDULE ANCHOR
 SPACING IS BLANK.PLEASE COMPLETE ALL
 REQUIRED INFORMATION.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-17 Cont ID  
Sent By adarroug Date 2006-04-17 Time 09:59 Rev Time 0.00
Received By adarroug Date 2006-04-17 Time 09:59 Sent To B
Notes
2006-04-17 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-28 Cont ID  
Sent By adarroug Date 2006-03-28 Time 12:04 Rev Time 0.00
Received By adarroug Date 2006-03-28 Time 12:04 Sent To B
Notes
2006-03-28 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-22 Cont ID  
Sent By adarroug Date 2005-10-22 Time 12:19 Rev Time 0.00
Received By adarroug Date 2005-10-22 Time 12:19 Sent To B
Notes
2005-10-22 00:00:00TO "MISC" BOX#1