Plan Review Details - Permit 05101119
Plan Review Stops For Permit 05101119
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-12-20 Cont ID  
Sent By amorse Date 2005-12-20 Time 09:24 Rev Time 0.50
Received By amorse Date 2005-12-20 Time 09:24 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-11-28 Cont ID  
Sent By amorse Date 2005-11-28 Time 09:29 Rev Time 0.50
Received By amorse Date 2005-11-28 Time 09:29 Sent To PC
Notes
2005-11-28 00:00:00DENIED
  
  
  
  
 1) CONTRACTOR FAILED TO PROVIDE THE
 FLORIDA STATE APPROVAL COVER SHEETS THEY
 MUST BE SUPPLIED WITH THE NOA'S (2
 COPIES)
 THESE ARE THE PAGES WITH THE FL #'S ON
 THEM. (EG.) GAF BUILT UP ROOF IS
 FL618-R1
  
 2) IN THE NOA FOR POLYGLASS USA INC.
 THE ONLY PRODUCT THAT CAN BE USED ON A
 ROOF SLOPE ABOVE 5/12 IS POLYSTICK TU
 (SEE LIMITATION 7)
 YOUR APPLICATION SPECIFIES TU PLUS AND
 CANNOT BE USED ABOVE A 5/12 SLOPE
  
 3) ALMAR (USA), INC. IS NOT IN THE
 FLORIDA STATE APPROVAL SYSTEM BUT
 ALTUSA TILE IS UNDER THE 2001 VERSION WE
 WILL ACCEPT THIS APPROVAL WITH THE
 ACCOMPANING SBCCI/ICC ES LEGACY REPORT #
 9914
  
 NOTE: AN UPDATED COPY OF THIS REPORT IS
 AVAILABLE ON THE WEB SITE
 WWW.ICC-ES.ORG/EVALUATION_REPORTS/INDEX.
 SHTML
  
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 (561)805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-10-20 Cont ID  
Sent By jgomez Date 2005-10-20 Time 10:59 Rev Time 0.33
Received By jgomez Date 2005-10-20 Time 10:58 Sent To PC
Notes
2005-10-20 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- PROVIDE FLORIDA PRODUCT APPROVAL OR
 LOCAL PRODUCT APPROVAL FOR A) FLAT ROOF
 SYSTEM. B) CLAY ROOF TILE. C) POLYFOAM
 AS REQUIRED BY RULE 9B-72 OF DCA. SEE
 WWW.FLORIDABUILDING.ORG.
 DADE COUNTY NOA ALONE IS NOT
 AUTOMATICALLY AN STATE WIDE FLORIDA
 PRODUCT APPROVAL. IF THERE IS NOT
 FLORIDA PRODUCT APPROVAL, MANUFACTURER
 MAY APPLY FOR LOCAL PRODUCT APPROVAL
 USING THE DADE COUNTY NOA AND COMPLETING
 THE LOCAL PRODUCT APPROVAL FORM
 DOWNLOADED FROM WWW.FLORIDABUILDING.ORG.
  
 3- POLISTICK CAN NOT BE USED FOR ROOF
 TILE UNDERLAYMENT. SEE LIMITATION #2 ON
 PAGE 4 OF 5 OF DADE COUNTY NOA SUBMITTED
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-19 Cont ID  
Sent By adarroug Date 2005-12-19 Time 16:56 Rev Time 0.00
Received By adarroug Date 2005-12-19 Time 16:56 Sent To B
Notes
2005-12-19 00:00:00TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-11-28 Cont ID  
Sent By adarroug Date 2005-11-28 Time 08:29 Rev Time 0.00
Received By adarroug Date 2005-11-28 Time 08:29 Sent To B
Notes
2005-11-28 00:00:00TO "AMORSE" DESK