Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-12-13 Cont ID  
Sent By alange Date 2005-12-13 Time 08:50 Rev Time 0.66
Received By alange Date 2005-12-13 Time 08:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-02-01 Cont ID  
Sent By btrobaug Date 2006-02-01 Time 17:56 Rev Time 0.50
Received By btrobaug Date 2006-02-01 Time 17:32 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-11-18 Cont ID  
Sent By btrobaug Date 2005-11-18 Time 10:41 Rev Time 0.50
Received By btrobaug Date 2005-11-18 Time 10:23 Sent To B
Notes
2005-11-18 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE A RISER DIAGRAM OF THE
 PROPOSED SERVICE, INCLUDE:
 A) CONDUDIT AND CONDUCTOR SIZES.
  
 B) AIC RATING OF EQUIPMENT, 110.9.
  
 C) GROUNDING ELECTRODE SYSTEM PER250.50
  
  
 D) GEC SIZE PER 250.66.
  
 E) AMPERE AND DISCONNECT RATING OF
 MAIN.
  
 PLEASE SEE 110.26 FOR CLEARANCE
 REQUIREMENT
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-01-31 Cont ID  
Sent By adarroug Date 2006-01-31 Time 16:37 Rev Time 0.00
Received By adarroug Date 2006-01-31 Time 16:37 Sent To E
Notes
2006-01-31 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-16 Cont ID  
Sent By adarroug Date 2005-11-16 Time 13:05 Rev Time 0.00
Received By adarroug Date 2005-11-16 Time 13:05 Sent To E
Notes
2005-11-16 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2005-12-13 Time   Rev Time 0.00
Received By adarroug Date 2005-10-22 Time 10:36 Sent To  
Notes
2005-10-22 00:00:00TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2005-11-15 Cont ID  
Sent By mmclean Date 2005-11-15 Time 08:12 Rev Time 0.20
Received By mmclean Date 2005-11-15 Time 08:12 Sent To I
Notes
2006-02-01 00:00:002/1/06
 NOTE: MUST CONVERT BACK TO A CABANA,
 ZONED SF7. NO RENTAL ALLOWED.
  
  
2005-11-15 00:00:00APPROVING THE 48" HEIGHT FENCE FOR THE
 REAR PROPERTY AND RENOVATION OF CABANA
 (ONLY ONE COOKING FACILITY ALLOWED).