Plan Review Details - Permit 05100953
Plan Review Stops For Permit 05100953
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-17 Cont ID  
Sent By alange Date 2005-11-17 Time 15:56 Rev Time 3.00
Received By alange Date 2005-11-17 Time 10:47 Sent To  
Notes
2005-11-17 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.PLANS IN FOR PERMITTING AFTER
 OCTOBER 1ST 2005 SHALL BE DESIGNED TO
 THE 2004 FLORIDA BUILDING CODE.
  
 3.CONTSTRUCTION TYPE V IS NOT CORRECT.
  
 4.SHOW TRAVEL DISTANCE ALONG THE PATH
 OF TRAVEL.2004 FBC 1015
  
 5.URINALS SHALL BE A MAX OF 17" 2004
 FBC 11-4 18.2
  
 6.FBC 2004 EXISTING BUILDINGS.A
 DESIGN PROFESSIONAL MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION
 PURSUANT TO SECTIONS 303,304,AND 305 OF
 THIS CODE.SHOW HOW PLANS WILL COMPLY
 WITH THE LEVEL SELECTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-11-10 Cont ID  
Sent By jleahy Date 2005-11-10 Time 21:00 Rev Time 0.45
Received By jleahy Date 2005-11-10 Time 21:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-11-15 Cont ID  
Sent By mwennerg Date 2005-11-15 Time 13:14 Rev Time 0.00
Received By mwennerg Date 2005-11-15 Time 13:14 Sent To  
Notes
2005-11-15 00:00:00******PROVISO******
  
 1) PLEASE SEE POSSIBLE COMMENTS BY
 BUILDING REVIEW REF: FBC EDITION.
  
 2) IF BUILDING HAS EXISTING FIRE
 SPRINKLER AND OR FIRE ALARM SYSTEMS,
 SEPARATE SHOP DRAWINGS AND PERMITS ARE
 REQUIRED FOR REMODEL.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-11-17 Cont ID  
Sent By alange Date 2005-11-17 Time 15:57 Rev Time 0.00
Received By alange Date 2005-10-19 Time 10:10 Sent To  
Notes
2005-10-19 00:00:00TO "BOB"#6

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-11-15 Cont ID  
Sent By prafter Date 2005-11-15 Time 09:44 Rev Time 1.00
Received By prafter Date 2005-11-15 Time 09:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-10-20 Cont ID  
Sent By jleech Date 2005-10-20 Time 14:46 Rev Time 1.00
Received By jleech Date 2005-10-20 Time 14:46 Sent To  
Notes
2005-10-20 00:00:00DENIED;
 1.DRINKING FOUNTAIN REQUIRED. FBC-2004
 PLUMBING TABLE 403.1 (2).
 2.RISER DIAGRAM, OFFSET W/C'S FROM
 BUILDING DRAIN, NOT VENTED AS DRAWN.
 3.SHT. 10.1 (6) BREAK SINK, TOE KICK
 PLATE MUST BE REMOVED FOR A FRONTAL
 APPROACH. REFURE TO FBC-2004 CHAPTER 11
 SEC. 11-4.24.1 THRU 11-4.24.7.
 4.PLEASE SHOW SHOWER DETAIL TO COPLY
 WITH FBC-2004 SEC. 11-4.21.1 THRU
 11-4.21.8.
 5.PLEASE SHOW CLEAR FLOOR SPACE FOR ALL
 H/C FIXTURES ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695