| 2006-01-06 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05100946 |
| | ADD: 430 HIBISCUS ST |
| | CONT: THE TOWER GROUP CGCA38309 |
| | TEL: (954)474-3111 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | NOTE: 713.13.(2) IF WORK HASN'T STARTED |
| | WITHIN 90 DAYS OF THE NOC BEING RECORDED |
| | SUCH NOTICE WILL BE VOID AND NO FURTHER |
| | IN EFFECT CAUSING IT TO BE RE-RECORDED. |
| | |
| | 2) THERE SEEMS TO BE A DISCREPANCY |
| | BETWEEN THE PERMIT APPLICATION AND PLANS |
| | AS TO THE ADDRESS AS WELL AS THE |
| | PROPERTY CONTROL NUMBER. |
| | 2A) PERMIT APPLICATION INDICATES 430 |
| | HIBISCUS WHERE AS THE PLANS INDICATE 480 |
| | HIBISCUS. |
| | 2B) THE PCN SUPPLIED ON THE PERMIT |
| | APPLICATION INDICATES A SINGLE LOT. A0.2 |
| | APPEARS TO TAKE MOST OF THE BLOCK AND |
| | CROSSING THE ALLEYWAY. PROVIDE A REPLAT |
| | INDICATING A SINGLE LOT AND NEW PCN. |
| | 2C) BEFORE THE FOUNDATION PLAN IS |
| | RESUBMITTED CORRALATE ALL PLANS INTO |
| | THREE COMPLETE SETS AND STAPLED. |
| | 106.1.2 ADDITIONAL DATA. THE BUILDING |
| | OFFICIAL MAY REQUIRE DETAILS, |
| | COMPUTATIONS, STRESS DIAGRAMS, AND OTHER |
| | DATA NECESSARY TO DESCRIBE THE |
| | CONSTRUCTION OR INSTALLATION AND THE |
| | BASIS OF CALCULATION. ALL DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA |
| | REQUIRED BY THE BUILDING OFFICIAL TO BE |
| | PREPARED BY AN ARCHITECT OR ENGINEER |
| | SHALL BE AFFIXED WITH THIER OFFICIAL |
| | SEAL, SIGNATURE AND DATE AS STATE LAW |
| | REQUIRES. |
| | |
| | 3A) 104.4.5. SPECIAL FOUNDATION PERMIT |
| | WHEN APPLICATION FOR A PERMIT TO ERECT |
| | OR ENLARGE A BUILDING HAS BEEN FILED, & |
| | PENDING ISSURANCE OF SUCH PERMIT, THE |
| | BUILDING OFFICIAL MAY, AT HIS/ HER |
| | DISCRETION, ISSUE A SPECIAL PERMIT FOR |
| | THE FOUNDATION ONLY, UPON WRITTEN RE- |
| | QUEST OF THE OWNER AND CONTRACTOR. THE |
| | HOLDER OF SUCH A SPECIAL PERMIT IS PRO- |
| | CEEDING AT HIS OR HER OWN RISK AND WITH- |
| | OUT ASSURANCE THAT A PERMIT FOR THE |
| | REMAINDER OF THE WORK WILL BE GRANTED |
| | AND THAT CORRECTIONS WILL NOT BE RE- |
| | QUIRED IN ORDER TO MEET THE PROVISIONS |
| | OF THE TECHNICAL CODE. |
| | 3B) WHEN A FOUNDATION PERMIT IS APPLIED |
| | FOR IT IS UNDERSTOOD THAT INCLUDES FLOOR |
| | SLABS REQUIRING MEP PLANS. IF LOOKING |
| | FOR A PERMIT TO START WORK WITHOUT THE |
| | REQUIRED MEP SHEETS INDICATE WHAT WORK |
| | WILL BE COMPLETED UNDER THIS PERMIT. |
| | THE PERMIT APPLICATION BOX DESCRIPTION |
| | OF PROJECT SHOULD INCLUDE WHAT TYPE OF |
| | WORK IS TO BE COMPLETED UNDER THIS |
| | FOUNDATION PERMIT. |
| | |
| | 4)FL S. S. 553.71(7) " THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN |
| | CY CLASSIFICATION AS DEINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS |
| | 5,000 SQ FT IN AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. |
| | 105.13.1 THE ENFORCING AGENCY SHALL |
| | REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| | SRUCTURAL INSPECTIONS ON A THRESHOLD |
| | BUILDING PURSUANT TO A STRUCTURAL INSPEC |
| | TION PLAN PREPARED BY THE ENGINEER OF |
| | RECORD. THE STRUCTURAL INSPECTION PLAN |
| | MUST BE SUBMITTED TO THE ENFORCING AGEN- |
| | CY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESH- |
| | OLD BUILDING. THE PURPOSE OF THE SRUCTUR |
| | AL INSPECTION PLAN IS TO PROVIDE SPECIF- |
| | IC INSPECTION PROCEDURES AND SCHEDULES |
| | SO THAT THE BUILDING CAN BE ADEQUATELY |
| | INSPECTED FOR COMPLIANCE WITH THE |
| | PERMITTED DOCUMENTS. |
| | |
| | 5) WPB AMENDMENT 105.13.6. W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A |
| | SPECIAL INSPECTOR AS REQUIRED BY S. |
| | 553.79(5) FLORIDA STATUTES TO THE MIN- |
| | IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| | CONTACT HAROLD PISKURA MANAGER OF THE |
| | SPECIAL INSPECTOR PROGRAM AT (561) |
| | 805-6711 FOR FURTHER INFORMATION BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | 6) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS |
| | FOR THE BUILDING WHICH ARE REQUIRED TO |
| | BE SIGNED AND SEALED BY THE ARCHITECT OR |
| | ENGINEER OF RECORD CON- TAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR |
| | ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS |
| | DETERMINED BY THE LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 7)106.1.2 ADDITIONAL DATA. THE |
| | BUILDING OFFICIAL MAY REQUIRE DETAILS, |
| | COMPUTATIONS, STRESS DIAGRAMS, AND OTHER |
| | DATA NECESSARY TO DESCRIBE THE |
| | CONSTRUCTION OR INSTALLATION AND THE |
| | BASIS OF CALCULATION. ALL DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA |
| | REQUIRED BY THE BUILDING OFFICIAL TO BE |
| | PREPARED BY AN ARCHITECT OR ENGINEER |
| | SHALL BE AFFIXED WITH THIER OFFICIAL |
| | SEAL, SIGNATURE AND DATE AS STATE LAW |
| | REQUIRES. |
| | THE STRUCTURAL PLANS START WITH |
| | SHEET S-1.0 BUT THE STRUCTURAL NOTES |
| | START WITH NUMBER (4). |
| | THERE IS NO MENTION OF SOILS |
| | REQUIREMENTS, SOILS REPORTS, |
| | DENSEIFICATION, NOR AUGER PILE GRADE |
| | BEAMS, ETC?S1.1 SOIL NOTE SOIL TO BE |
| | DENSIFIED TO 8,000 BY VIBROFLOTATION, |
| | PROVIDE REPORT. |
| | |
| | 8) SEE SHEET S-1.0 FOR IMPORTANCE |
| | FACTOR, ASCE 7-98 TABLE 1-1/ TABLE 6-1, |
| | BUILDINGS AND OTHER STRUCTURES WHERE |
| | MORE THAN 300 PEOPLE CONGREGATE IN ONE |
| | AREA WILL REQUIRE THE BUILDING CATEGORY |
| | BE A III AND THE IMPORTANCE FACTOR OF |
| | 1.15. SEE POOL DECK AND WALKWAYS OF |
| | 11,697 SQ FT / 30= 390 OCCUPANT LOAD. |
| | |
| | 9) SHEET S1.1 FOOTING# 440140 NOT ON |
| | FOOTING SCHEDULE.STEEL? |
| | |
| | 10) SHEET S1.1 FOOTING 200160 NOT ON |
| | FOOTING SCHEDULE. STEEL? THERE ARE |
| | NUMEROUS FOOTERS THAT ARE NOT ON THE |
| | SCHEDULE AND WILL REQUIRE STEEL PLEASE |
| | PROVIDE INFORMATION. |
| | |
| | 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |
| | |
| | |