Plan Review Details - Permit 05100943
Plan Review Stops For Permit 05100943
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-02-08 Cont ID  
Sent By alange Date 2006-02-08 Time 11:30 Rev Time 1.50
Received By alange Date 2006-02-07 Time 10:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-01-03 Cont ID  
Sent By alange Date 2006-01-03 Time 11:22 Rev Time 0.75
Received By alange Date 2006-01-03 Time 10:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2005-12-02 Cont ID  
Sent By alange Date 2005-12-02 Time 13:47 Rev Time 1.00
Received By alange Date 2005-12-02 Time 13:31 Sent To  
Notes
2005-12-02 00:00:00DENIED
  
 1.PLANS SUBMITED AFTER OCTOBER 1, 2005
 SHALL BE DESIGNED TO THE 2004 FBC.
  
 2.FBC 2004 EXISTING BUILDING 301.5
 A DESIGN PROFESSIONAL OR AN OWNER MUST
 ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PERSUANT TO SECTIONS 303,
 304, 305 OF THIS CODE.SHOW HOW
 ALTERATION WILL BE DESIGNED TO LEVEL
 SELECTED.
  
 3.CHECK DETAILS WHEN DESIGNING TO THE
 2004 FBC. FOR EXAMPLE, THE IS NO TYPE 6
 CONSTRUCTION, CODE SECTIONS SITED WILL
 BE CHANGED.
 **CHECK PLANS SEVERAL DESIGN AND CODE
 SECTIONS STILL REFERENCE THE 2001 FBC.
  
 A. ENERGY EFFIENCY FORM SHOULD BE FORM
 400D-04.BE SURE TO ALSO SIGN OWNER
 AGENT ON FORM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-16 Cont ID  
Sent By alange Date 2005-11-16 Time 07:47 Rev Time 2.25
Received By alange Date 2005-11-16 Time 07:26 Sent To  
Notes
2005-11-16 00:00:00DENIED
  
 1.PLANS SUBMITED AFTER OCTOBER 1, 2005
 SHALL BE DESIGNED TO THE 2004 FBC.
  
 2.FBC 2004 EXISTING BUILDING 301.5
 A DESIGN PROFESSIONAL OR AN OWNER MUST
 ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PERSUANT TO SECTIONS 303,
 304, 305 OF THIS CODE.SHOW HOW
 ALTERATION WILL BE DESIGNED TO LEVEL
 SELECTED.
  
 3.CHECK DETAILS WHEN DESIGNING TO THE
 2004 FBC. FOR EXAMPLE, THE IS NO TYPE 6
 CONSTRUCTION, CODE SECTIONS SITED WILL
 BE CHANGED.
  
 4.CLEARLY SHOW EXISTING AREAS AND
 WALLS ALONG WITH ANY NEW WALLS AND
 DETAILS FOR THEM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-02-07 Cont ID  
Sent By jleahy Date 2006-02-07 Time 16:35 Rev Time 0.00
Received By jleahy Date 2006-02-07 Time 16:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-01-03 Cont ID  
Sent By dpalmer Date 2006-01-03 Time 07:40 Rev Time 0.00
Received By dpalmer Date 2006-01-03 Time 07:29 Sent To  
Notes
2006-01-03 00:00:00******* PROVISO/ REVISON NEEDED *******
  
  
  
 1)NOTE: PLEASE SEE 210.62, 220.12 FIR
 MIN SHOW WINDOW RECEPTS REQUIRED FOR
 RETAIL/MERCHANTILE OCCUPANCY.
 PLEASE REVISE WITH ANY OTHER REVISIONS
 BEFORE ROUGH ELECTRICAL INSPECTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELCTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-12-07 Cont ID  
Sent By jleahy Date 2005-12-07 Time 06:44 Rev Time 0.30
Received By jleahy Date 2005-12-07 Time 06:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-11-10 Cont ID  
Sent By jleahy Date 2005-11-10 Time 20:49 Rev Time 0.45
Received By jleahy Date 2005-11-10 Time 20:49 Sent To  
Notes
2005-11-10 00:00:00NO LOW VOLTAGE SYSTEMS SHOWN ON
 DRAWINGS, SEPARATE PERMIT(S) REQUIRED

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2005-12-23 Cont ID  
Sent By mcarsill Date 2005-12-23 Time 12:54 Rev Time 0.00
Received By mcarsill Date 2005-12-23 Time 12:46 Sent To  
Notes
2005-12-23 00:00:001. ON SHEET A.1. IT INDICATES THAT AN
 EXISTING FIRE SPRINKLER HEAD IS TO BE
 RELOCATED WITH A PERMIT. A PERMIT WILL
 NOT BE REQUIRED FOR A SINGLE FIRE
 SPRINKLER HEAD RELOCATION. A LICENSED
 FIRE SPRINKLER CONTRACTOR MUST BE USED.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-12-14 Cont ID  
Sent By mwennerg Date 2005-12-14 Time 15:08 Rev Time 0.00
Received By mwennerg Date 2005-12-14 Time 15:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-11-15 Cont ID  
Sent By mwennerg Date 2005-11-15 Time 13:35 Rev Time 0.00
Received By mwennerg Date 2005-11-15 Time 13:35 Sent To  
Notes
2005-11-15 00:00:00******DENIED******
  
 1) NO EXIT SIGNS OR EMERGENCY LIGHTING
 SHOWN ON PLANS. NEW OR EXISTING?
  
 2) PLANS INDICATE THAT THE BUILDING IS
 FIRE SPRINKLERED. SEPRATE SHOP DRAWINGS
 AND PERMIT ARE REQUIRED FOR FIRE
 SPRINKLER REMODEL.
  
  
 MIKE WENNERGREN, CAPTAI/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-03-24 Cont ID  
Sent By dpalmer Date 2006-03-24 Time 14:41 Rev Time 0.00
Received By dpalmer Date 2006-03-24 Time 14:41 Sent To M
Notes
2006-03-24 00:00:00TO MECH INBOX

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-02-07 Cont ID  
Sent By adarroug Date 2006-02-07 Time 14:59 Rev Time 0.00
Received By adarroug Date 2006-02-07 Time 14:59 Sent To  
Notes
2006-02-07 00:00:00TO "BOB"#5

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-19 Cont ID  
Sent By adarroug Date 2006-01-19 Time 11:29 Rev Time 0.00
Received By adarroug Date 2006-01-19 Time 11:29 Sent To B
Notes
2006-01-19 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-23 Cont ID  
Sent By adarroug Date 2005-12-23 Time 09:20 Rev Time 0.00
Received By adarroug Date 2005-12-23 Time 09:20 Sent To  
Notes
2005-12-23 00:00:00TO "BOB#1

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-01 Cont ID  
Sent By adarroug Date 2005-12-01 Time 16:55 Rev Time 0.00
Received By adarroug Date 2005-12-01 Time 16:55 Sent To  
Notes
2005-12-01 00:00:00TO "BOB"#11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-11-16 Cont ID  
Sent By alange Date 2005-11-16 Time 07:47 Rev Time 0.00
Received By alange Date 2005-10-20 Time 10:29 Sent To  
Notes
2005-10-20 00:00:00TO "BOB"#8

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-03-24 Cont ID  
Sent By tgordon Date 2006-03-24 Time 15:59 Rev Time 0.30
Received By tgordon Date 2006-03-24 Time 15:59 Sent To  
Notes
2006-03-24 00:00:00REV. TO MECH. PLANS .

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-02-10 Cont ID  
Sent By hmoser Date 2006-02-10 Time 08:10 Rev Time 0.00
Received By hmoser Date 2006-02-10 Time 07:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2005-12-29 Cont ID  
Sent By tgordon Date 2005-12-29 Time 12:15 Rev Time 0.30
Received By tgordon Date 2005-12-29 Time 12:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-12-09 Cont ID  
Sent By tgordon Date 2005-12-09 Time 08:11 Rev Time 0.25
Received By tgordon Date 2005-12-09 Time 08:10 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-11-15 Cont ID  
Sent By prafter Date 2005-11-15 Time 10:45 Rev Time 1.00
Received By prafter Date 2005-11-15 Time 10:45 Sent To  
Notes
2005-11-15 00:00:00MECH. PLAN REVIEW:
  
 PROVISO: PROVIDE FOR AUTO. FAN SHUT
 DOWN BY DUCT SMOKE DETECTOR.
  
 2004 FBC/M 606.2.1.
  
 PAT RAFTER 561/6728 OR 6719 PATTY
 KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.
  
  
  
  
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-02-16 Cont ID  
Sent By mperson Date 2006-02-16 Time 10:01 Rev Time 0.33
Received By mperson Date 2006-02-16 Time 10:01 Sent To  
Notes
2006-02-16 00:00:00REVISION:"3" IN CLOUDS, BATHROOM WITH
 AIR ADMITTANCE VALVES AND TANKLESS WATER
 HEATER
  
 PASSED PER PHONE CONVERSATION WITH JOHN
 LEECH

Review Stop P PLUMBING
Rev No 4 Status F Date 2006-02-08 Cont ID  
Sent By jleech Date 2006-02-08 Time 17:15 Rev Time 1.00
Received By jleech Date 2006-02-08 Time 17:15 Sent To  
Notes
2006-02-08 00:00:00REVISION DENIED;
 1.SHOW THE 3 MECHANICAL VENTS TO BE
 USED.
 2.MOP SINK REQUIRES HOT WATER. SEE
 FBC-2004 PLUMBING SEC.607.1 MOP SINK IS
 FOR BUILDING MAINTENANCE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-01-03 Cont ID  
Sent By jleech Date 2006-01-03 Time 09:43 Rev Time 0.33
Received By jleech Date 2006-01-03 Time 09:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2005-12-12 Cont ID  
Sent By jleech Date 2005-12-12 Time 08:38 Rev Time 0.50
Received By jleech Date 2005-12-12 Time 08:38 Sent To  
Notes
2005-12-12 00:00:00DENIED;
 1.DRINKING FOUNTAIN REQUIRED NOT BOTTLE
 WATER FBC-2004 PLUMBING SEC. 410.1.
 2.PAGE LS.1 DETAIL 4, HIGHT OF TOILET
 SEAT TO BE 17 - 19" SEE FBC-2004 CHAPTER
 11, SEC 11-4.16.3.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-11-16 Cont ID  
Sent By pschmitz Date 2005-11-16 Time 11:45 Rev Time 0.00
Received By pschmitz Date 2005-11-16 Time 11:45 Sent To  
Notes
2005-11-16 00:00:00PAUL SCHMITZ
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 DENIED
 1) THIS PLAN ISREVIEWED UNDER 2004
 FLORIDA BUILDING CODE.
 NOTES ON PLANS SHOULD REFELECT THE SAME.
  
 2)SEC 403 MINIMUM PLUMBING FACILITIES
 TABLE 403.1 BUSINESS OUCPANCY
 ONE DRINKING FOUNTAIN REQUIRED.
 3)SHT LS.1 DETAIL "3" WATER CLOSET IS
 REQUIRED TO BE 1'6" OFF THE WALL
 4)SHT M.1 PLUMBING NOTES # 10 AIR
 CHAMBER.
 SEC 604.9 WATER HAMMER
 WATER HAMMER ARRESTORS SHALL CONFORM TO
 ASSE 1010
 5) SHT M.1 WATER ISOMETRIC
 WATER PIPE SIZE TO COMPLY WITH
 TABLE 604.3
 END OF COMMENTS QUESTIONS 561-805-6692
  
  