Plan Review Details - Permit 05100915
Plan Review Stops For Permit 05100915
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2006-06-22 Cont ID  
Sent By rbrown Date 2006-06-22 Time 20:15 Rev Time 0.00
Received By rbrown Date 2006-06-22 Time 20:15 Sent To  
Notes
2006-06-22 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 STRUCTURAL REVISION SUBMITTED ON 6/19/06
 FOR FUEL TANK BRACKET ANCHOR DETAIL
  
 1) FBC 1604.1WELDED BRACKET.SHEET
 T-1 DOES NOT SHOW THE SIZE OF THE WELD
 BETWEEN THE TWO BRACKET LEGS.
 AMEND/ANNOTATE THE PLAN.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-03-28 Cont ID  
Sent By rbrown Date 2006-03-28 Time 09:09 Rev Time 0.00
Received By rbrown Date 2006-03-28 Time 09:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-03-25 Cont ID  
Sent By rbrown Date 2006-03-25 Time 18:10 Rev Time 0.00
Received By RBROWN Date 2006-03-26 Time 17:47 Sent To  
Notes
2006-03-25 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 THE COMMENTS FROM THE PREVIOUS
 BUILDING/STRUCTURAL PLAN REVIEW DATED
 1/17/06 WERE NOT ADDRESSED.THE KAMM
 CONSULTING COMMENT RESPONSE LETTER DATED
 2/6/06 STATES THAT IT DOES NOT ADDRESS
 THE STRUCTURAL COMMENTS.THE STRUCTURAL
 ENGINEER'S SHEETS S-1 AND S-2, SUBMITTED
 FOR THIS LATEST REVIEW, WERE SIGNED AND
 SEALED ON 11/23/05 WHICH IS BEFORE THE
 DATE OF THE LAST REVIEW (1/17/06).THEY
 ARE THE SAME SHEETS REVIEWED LAST TIME
 AND FOUND TO BE MISSING INFORMATION AS
 STATED ON THE LAST REVIEW.ALSO, THE
 DOCUMENT "OUTSTANDING DEPARTMENT
 REVIEWS' HAND CARRIED TO THIS OFFICE BY
 MR MARTY BISHOP, LISTS AND ADDRESSES THE
 MECHANICAL COMMENTS UNDER THE INCORRECT
 HEADING OF BUILDING (STRUCTURAL).
 CONSEQUENTLY, THAT DOCUMENT ALSO DOES
 NOTHING TO ADDRESS THE BUILDING
 (STRUCTURAL) REVIEW COMMENTS.
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE PREVIOUS
 BUILDING (STRUCTURAL) PLAN REVIEW OF
 1/17/06:
  
 2) FBC 1603.1.4WIND DESIGN DATA.THIS
 COMMENT HAS NOT BEEN ADDRESSED.THE
 FUEL TANK AND IT'S COMPONENTS ARE
 EXTERIOR. THE LOUVER AND SCREEN, AND THE
 ALTERATIONS TO THE CONCRETE BLOCK
 MASONRY WALL AROUND THE LOUVER, ARE ALL
 EXTERIOR 'COMPONENTS AND CLADDING'.THE
 PLANS MUST STATE THE BASIC WIND SPEED,
 WIND IMPORTANCE FACTOR, WIND EXPOSURE
 CATEGORY, INTERNAL PRESSURE COEFFICIENT,
 AND EXTERIOR COMPONENT AND CLADDING
 DESIGN WIND PRESSURES.ADD THIS
 INFORMATION TO THE PLANS.THE PLANS
 HAVE BEEN SEARCHED AND SCOURED LOOKING
 FOR THIS CODE REQUIRED INFORMATION SO,
 IF THE INFORMATION IS SOMEWHERE ON THESE
 PLANS, PLEASE CALL OR EMAIL TO TELL ME
 WHERE.
  
 3) THE FOLLOWING COMMENT WAS IGNORED.
 THERE ARE NUMEROUS OLD 'VOID' SHEETS
 LEFT IN THE SUBMITTED PLAN SETS.PLEASE
 READ THE FOLLOWING TEXT CAREFULLY AND
 FOLLOW THE DIRECTIONS:TO EXPEDITE
 REVIEW OF A RESUBMITTAL WHICH REQUIRES
 NEW PLANS IN ORDER TO ADDRESS THE ABOVE
 COMMENTS, THE OLD SHEETS SHALL BE
 REMOVED AND THE NEW SHEETS INSERTED.
 ONE COPY OF EACH OLD SHEET SHOULD BE
 STAPLED/CLIPPED TO THE REMAINING OLD
 SHEETS, TO FORM A SET OF 'OLD/VOID
 SHEETS', FOR COMPARISON OF REVISIONS
 WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-01-17 Cont ID  
Sent By rbrown Date 2006-01-17 Time 15:15 Rev Time 0.00
Received By rbrown Date 2006-01-17 Time 15:14 Sent To  
Notes
2006-01-17 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) THE PLANS HAVE BEEN REVISED TO SHOW A
 5000 GALLON ABOVE GROUND DIESEL FUEL
 TANK.ALSO, STRUCTURAL SHEETS S-1 AND
 S-2 WERE NOT SUBMITTED FOR THE FIRST
 PLAN REVIEW.THE FOLLOWING COMMENTS
 APPLY TO THESE SHEETS.
  
 2) FBC 1603.1.4WIND DESIGN DATA.THE
 PLANS SHALL STATE THE BASIC WIND SPEED,
 WIND IMPORTANCE FACTOR, WIND EXPOSURE
 CATEGORY, INTERNAL PRESSURE COEFFICIENT,
 AND EXTERIOR COMPONENT AND CLADDING
 DESIGN WIND PRESSURES.ADD THIS
 INFORMATION TO THE PLANS.
  
 3) TO EXPEDITE REVIEW OF A RESUBMITTAL
 WHICH REQUIRES NEW PLANS IN ORDER TO
 ADDRESS THE ABOVE COMMENTS, THE OLD
 SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHOULD BE STAPLED/CLIPPED TO THE
 REMAINING OLD SHEETS, TO FORM A SET OF
 'OLD/VOID SHEETS', FOR COMPARISON OF
 REVISIONS WHEN REVIEWING THE RESUBMITTED
 PLANS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-11-04 Cont ID  
Sent By rbrown Date 2005-11-04 Time 13:40 Rev Time 0.00
Received By rbrown Date 2005-11-04 Time 13:40 Sent To FIRE
Notes
2005-11-04 00:00:00SEE MECHANICAL PLAN REVIEW FOR COMMENTS
 ON GENERATOR EXHAUST TERMINAL AND VENT
 REQUIREMENTS.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-06-22 Cont ID  
Sent By jleahy Date 2006-06-22 Time 10:01 Rev Time 1.30
Received By jleahy Date 2006-06-23 Time 10:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-03-28 Cont ID  
Sent By rbrown Date 2006-03-28 Time 12:23 Rev Time 0.00
Received By rbrown Date 2006-03-28 Time 12:23 Sent To  
Notes
2006-03-28 00:00:00PLANS NOW HAVE THE SIGNATURE OF LON T.
 CARTER P.E.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-03-28 Cont ID  
Sent By rbrown Date 2006-03-28 Time 12:23 Rev Time 0.00
Received By rbrown Date 2006-03-28 Time 10:04 Sent To  
Notes
2006-03-28 00:00:00PLANS ARE SEALED BUT HAVE ONLY THE
 INITIALS (LTC) OF THE THE ENGINEER.
 LON T. CARTER P.E. IS REQUIRED TO USE
 HIS FULL SIGNATURE AS REQUIRED BY
 FLORIDA BOARD OF PROFESSIONAL ENGINEER'S

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-03-28 Cont ID  
Sent By jleahy Date 2006-03-28 Time 08:14 Rev Time 0.45
Received By jleahy Date 2006-03-28 Time 08:14 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-03-26 Cont ID  
Sent By jleahy Date 2006-03-26 Time 17:24 Rev Time 3.00
Received By jleahy Date 2006-03-26 Time 17:24 Sent To  
Notes
2006-03-26 00:00:00THE SIZE OF THE TAP BOX 38 X 38 X 24
 HOW DOES THIS MEET THE REQUIREMENTS OF
 314.28(A2) 12 - 4" PIPES? PLEASE
 INDICATE CODE SECTION FOR SIZING?
  
 THE LISTING I ASKED FOR WAS A LISTING
 AGENCY SUCH AS "UL" "ETL" ??? 110.2
  
 WHO IS THE MANUFACTURER OF THE TAP
 BOX????? 110.3A CUT SHEETS!
  
 PLEASE INDICATE HOW LOAD SHEADING IS TO
 BE ACCOMPLISHED??? WHAT IS TO BE SHEADED
 THE WHOLE DISTRIBUTION TIED TO
 THOSE SWITCHES PLEASE INDICATED LOADS TO
 BE SHEAD. 215.2(A)
  
 IF TAP BOX IS NOT LISTED PLEASE HAVE
 SWITCH GEAR MANUFACTURER RE-LIST GEAR
 WITH TAP BOX INSERTED.
 110.3 (A)(B)
  
  
 ALSO IN NOTES BACK TO CITY PG.E0.5
 NOT ONE OF THE PAGES SUBMITTED.
  
 NOTES ON PAGE E5.1 DO NOT LIST TESTING/
 LISTING AGENCY OR MANUFACTURER!

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-01-18 Cont ID  
Sent By jleahy Date 2006-01-18 Time 20:50 Rev Time 3.00
Received By jleahy Date 2006-01-18 Time 20:17 Sent To M
Notes
2006-01-18 00:00:00PG. E0.1 GENERATOR SPECS SHOW 480/277V
  
 PG. E0.5 TAP BOX SHOW SIZE ON PAGE
 ACCORDING TO THE CODE.
 PLEASE SHOW SIZE ON DRAWINGS.
 IS TAP BOX LISTED FOR USE WITH
 GEAR?
  
 PG. E6.1 SWITCHBOARD "G1A" LOAD IS
 834.6 GENERATOR IS 800???
  
 SPEC BOOK FOR GENERATOR AND TRANSFER
 SWITCHES NEED TO BE GONE OVER PAGE BY
 PAGE THEY DO NOT MATCH THE DRAWINGS
 ONE PAGE SAYS 480, NEXT PAGE SAYS 208.
 PLEASE FIX. IF YOU CAN NUMBER EACH PAGE
 IT WILL MAKE IT EASIER TO SHOW YOU WHERE
 THE MISTAKES ARE!!!
  
 PG. E6.1 COMMENT IS NEW SORRY I MISSED
 IT ON LAST REVIEW.
 PLEASE ADDRESS THE TAP BOX ISSUE ON THE
 DRAWINGS.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-11-04 Cont ID  
Sent By jleahy Date 2005-11-04 Time 07:13 Rev Time 3.30
Received By jleahy Date 2005-11-04 Time 07:13 Sent To M
Notes
2005-11-04 00:00:00SPEC BOOK SHOWS ON COVER 120/208
 EQUIPMENT, BUT INSIDE BOOK UNDER
 TRANSFER SWITCHES THE VOLTAGES LISTED
 ARE 277/480.
  
 SPECS FOR GENERATOR SHOW 277/480V????
  
 PAGE E0.1 LIGHTING FIXTUR SCHEDULE SHOWS
 277 VOLT LIGHTING.PANEL SCHEDULE SHOWS
 120/208 VOLTS.
  
 PAGE E5.1 SHOWS NEW TAP BOXES ON MAINS
 FOR TOWER PLEASE SIZE BOX ON DRAWINGS
 PER CODE. 314.28
  
 ON FEEDER SCHEDULE FEEDERS NT-1A,
 NT-1B,NT-!, NT-2DO NOT SPECIFY TYPE OF
 MATERIALCOPPER OR ALUMINUM.
  
 PAGE E6.1 SWITCHBOARD G2A HAS A LOAD OF
 564 KVA GENERATRO IS RATED FOR 500 KVA.
  
 SWITCHBOARD G1A SHOWS 277/480V ???
  
  
  
 QUESTIONS CALL JAKE LEAHY 561-644-7291.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-03-06 Cont ID  
Sent By nmccray Date 2006-03-06 Time 13:26 Rev Time 0.00
Received By nmccray Date 2006-03-06 Time 10:17 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-01-18 Cont ID  
Sent By nmccray Date 2006-01-18 Time 15:27 Rev Time 0.00
Received By nmccray Date 2006-01-18 Time 15:25 Sent To M
Notes
2006-01-18 00:00:00DENIED:
  
 1) THE TANK STORAGE SHALL COMPLY WITH
 NFPA 30, NFPA 80, NFPA 90A, AND NFPA 91.
  
 2) THE TANK STORAGE ROOM SHALL BE 2 HOUR
 FIRE RATED.
  
 3) THE TANK STORAGE ROOM SHALL BE FIRE
 SPRINKLER PROTECTED.
  
 4) THE EXHAUST SYSTEM SHALL BE INSTALL
 IN ACCORDANCE WITH THE PROVISIONS OF
 NFPA 91.
  
 5) IS THIS TANK STORAGE AREA SUBJECTED
 TO FLOODING, IF SO CERTAIN REQUIREMENTS
 MUST BE MET OF NFPA 30.
  
 6) EACH STORAGE TANK BUILDING AND EACH
 TANK WITHIN THE BUILDING SHALL BE
 ACCESSIBLE FROM AT LEAST TWO SIDES FOR
 FIREFIGHTING AND FIRE CONTROL.
  
 7) APPROPRIATE SIGNAGE MAY BE REQUIRED.
  
 8) PLEASE SEE OTHER REVIEW COMMENTS.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-11-07 Cont ID  
Sent By mwennerg Date 2005-11-07 Time 08:03 Rev Time 0.00
Received By mwennerg Date 2005-11-07 Time 08:03 Sent To  
Notes
2005-11-07 00:00:00******DENIED******
  
 1) PLEASE PROVIDE FURTHER INFORMATION
 REF: CAPACITY OF FUEL TANK.
  
 2) APPROPRIATE SIGNAGE MAY BE REQUIRED.
  
 3) PLEASE SEE OTHER REVIEW COMMENTS
 REGARDING MAX. INSIDE FUEL STORAGE.
  
 4) PLEASE PROVIDE INFORMATION REGARDING
 OPENINGS LEADING TO ANOTHER ROOM OR
 OUTSIDE THE BUILDING.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status P Date 2006-03-27 Cont ID  
Sent By jleahy Date 2005-11-04 Time 10:21 Rev Time 0.00
Received By hmoser Date 2006-03-27 Time 08:33 Sent To  
Notes
2005-11-04 00:00:001)PROVIDE CAPACITY OF THE FUEL TANK
  
 2) PLEASE PROVIDE DRAWINGS OF THE FUEL
 LINE FRON THE TANK TO THE GENERATOR ON
 THE PLANS
  
 3) PLEASE REFER TO SECTION 1301.2.2 FOR
 MAXIMUM INSIDE FUEL STORAGE FBC (M)
  
 4) PLEASE REFER TO NFPA 30 FOR VENT
 PIPING AND EXHAUST TERMINATION.
  
 QUESTIONS CALL HAROL MOSER 805-6732
 ALL COMMENTS FOUND IN BINDER.

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2006-06-23 Cont ID  
Sent By pschmitz Date 2006-06-23 Time 09:44 Rev Time 0.00
Received By pschmitz Date 2006-06-23 Time 09:44 Sent To  
Notes
2006-06-23 00:00:00RE-SUB, AS BUILT

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2006-03-23 Cont ID  
Sent By pschmitz Date 2006-03-23 Time 09:30 Rev Time 0.00
Received By pschmitz Date 2006-03-23 Time 09:30 Sent To  
Notes
2006-03-23 00:00:00SEE REVISED PLANS, AND SUBMITTALS IN
 THREE RING BINDER.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-01-18 Cont ID  
Sent By pschmitz Date 2006-01-18 Time 13:17 Rev Time 0.00
Received By pschmitz Date 2006-01-18 Time 13:17 Sent To  
Notes
2006-01-18 00:00:00PAUL SCHMITZ
 FBC2001 FUEL GAS CODEPLAN REVIEW
 DENIED
 1) INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 2) SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 TYPE OF REGULATOR,INCLUDE INFORMATION
 FOR REGULATOR VENT, MATERIAL
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2005-11-04 Cont ID  
Sent By pschmitz Date 2005-11-04 Time 09:27 Rev Time 0.00
Received By pschmitz Date 2005-11-04 Time 09:27 Sent To  
Notes
2005-11-04 00:00:00SEPERATE PERMIT FOR NATURAL GAS

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-06-20 Cont ID  
Sent By adarroug Date 2006-06-20 Time 16:38 Rev Time 0.00
Received By adarroug Date 2006-06-20 Time 16:38 Sent To B
Notes
2006-06-20 00:00:00TO "RBROWN" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-15 Cont ID  
Sent By adarroug Date 2006-06-15 Time 11:34 Rev Time 0.00
Received By adarroug Date 2006-06-15 Time 11:34 Sent To  
Notes
2006-06-21 00:00:006/21/06-TO "JLEAHY" DESK-WILL BRING BACK
 AFTER HIS REVIEW
2006-06-15 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-25 Cont ID  
Sent By adarroug Date 2006-02-25 Time 13:21 Rev Time 0.00
Received By adarroug Date 2006-02-25 Time 13:21 Sent To  
Notes
2006-03-21 00:00:00TO COMM BOARD #53
2006-02-25 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-05 Cont ID  
Sent By adarroug Date 2005-12-05 Time 09:25 Rev Time 0.00
Received By adarroug Date 2005-12-05 Time 09:25 Sent To  
Notes
2005-12-27 00:00:00TO "COMM" BD#55
2005-12-05 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-11-07 Cont ID  
Sent By mmclean Date 2005-11-07 Time 09:38 Rev Time 0.00
Received By mmclean Date 2005-10-20 Time 11:22 Sent To  
Notes
2005-10-20 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-06-23 Cont ID  
Sent By hmoser Date 2006-06-23 Time 14:02 Rev Time 0.00
Received By hmoser Date 2006-06-23 Time 14:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-03-23 Cont ID  
Sent By hmoser Date 2006-03-22 Time 09:46 Rev Time 0.00
Received By hmoser Date 2006-03-23 Time 09:54 Sent To  
Notes
2006-03-23 00:00:00ALL COMMENTS FOUND IN THREE RING BINDER
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
2006-03-22 00:00:00 
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-01-19 Cont ID  
Sent By pkrauss Date 2006-01-19 Time 10:49 Rev Time 0.00
Received By pkrauss Date 2006-01-19 Time 10:49 Sent To B
Notes
2006-01-19 00:00:00DENIED:
 1.PLEASE SUBMIT PLANS FOR REVIEW AND
 APPROVAL TO THE DEPARTMENT OF
 ENVIRONMENTAL PROTECTION LOCATED AT;
 3323 BELVEDERE RD BUILDING #502,
 ATTENTION CHIP GREEN.TELEPHONE
 (561)233-2504.
  
 2.PER 2001 FMC 1301.2.1, MAXIMUM
 AMOUNT OF FUEL OIL STORAGE ALLOWED
 WITHOUT ADDITIONAL PROTECTION SHALL BE
 660 GALLONS.FUEL OIL STORAGE GREATER
 THAN 660 GALLONS SHALL COMPLY WITH NFPA.
  
 3.PLEASE PROVIDE ANCHORING DETAIL OR
 TIE DOWN FOR FUEL TANK.
  
 4.SHOW COMPLIANCE WITH 2001 FMC 301.14
 FOR REQUIREMENTS MANDATED BY THE FLOOD
 ZONE.PLEASE PROVIDE SLAB ELEVATION.
  
 5.PLAN SHEET M2.1, PLEASE CLARIFY
 TERMINATION OF EF1 INTO WHAT APPEARS TO
 BE ANOTHER "ENCLOSED" ROOM.PER 2001
 FMC 501.3, ALL MECHANICAL EXHAUST SHALL
 DISCHARGE TO THE OUTDOORS.
  
 6.PLAN SHEET M2.1, THE PRIMARY &
 EMERGENCY VENTS ARE WITHIN 10FT OF THE
 SHEET METAL HOOD.IS THIS AN INTAKE?
 PER 2001 FMC 401.5.1 INTAKE OPENINGS
 SHALL BE LOCATED A MINIMUM OF 10 FT FROM
 ANY HAZARDOUS CONTAMINANT.
  
 7.PLAN SHEET P0.1 INDICATES BOTH
 GENERATORS WILL HAVE THE OPTION OF BEING
 POWERED BY DIESEL FUEL OR NATURAL GAS.
 PLEASE PROVIDE COMBUSTION AIR
 CALCULATIONS FOR BOTH GENERATOR ROOMS.
  
 8.PLANS INDICATE THE EXISTING
 GENERATOR WILL NOW HAVE THE OPTION TO
 RUN WITH NATURAL GAS.PLEASE PROVIDE
 SUBMITTAL DATA FOR THE EXISTING
 GENERATOR.
  
 9.PLEASE CLARIFY INTAKE LOUVERS FOR
 OUTSIDE AIR FROM THE ENCLOSED GARAGE?
  
 10. PLEASE SPECIFY PIPING MATERIAL FOR
 THE FUEL OIL PIPING & METHOD OF
 INSTALLATION IN ACCORDANCE WITH 2001 FMC
 TABLE 1302.3 & 1303.1 RESPECTIVELY.
  
 11. PLEASE NOTE FUEL OIL PIPING SHALL BE
 TESTED IN ACCORDANCE WITH NFPA 31.
  
 12. PLEASE PROVIDE DETAIL FOR PIPE
 SUPPORTS PER 2001 FMC 305.PLEASE NOTE,
 CORROSION PROTECTION REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-11-04 Cont ID  
Sent By jleahy Date 2005-11-04 Time 10:03 Rev Time 0.00
Received By hmoser Date 2006-01-18 Time 13:42 Sent To  
Notes
2005-11-04 00:00:00PLAN DENIED
 1) PLEASE PROVIDE CAPACITY OF THE FUEL
 TANK.
 2) PLEASE PROVIDE DROWINGS OF THE FUEL
 LINES FROM THE FUEL TANK TO THE
 GENERATOR ON THE PLANS.
 3) PLEASE REFER TO SECTION 1301.2.2
 MAXIMUM INSIDE FUEL OIL STORAGE.FBC(M)
 4) PLEASE REFER TO NFPA 30 FOR VENT
 PIPING AND EXHAUST TERMINATION.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-01-18 Cont ID  
Sent By pschmitz Date 2005-11-04 Time 09:26 Rev Time 0.00
Received By pschmitz Date 2005-11-04 Time 09:26 Sent To  
Notes
2005-11-04 00:00:00SEPERATE PERMIT FOR NATURAL GAS

Review Stop Z ZONING
Rev No 4 Status P Date 2006-03-02 Cont ID  
Sent By aaponte Date 2006-03-02 Time 17:07 Rev Time 0.00
Received By aaponte Date 2006-03-02 Time 17:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2006-01-23 Cont ID  
Sent By aaponte Date 2006-01-23 Time 08:13 Rev Time 0.00
Received By aaponte Date 2006-01-23 Time 08:13 Sent To  
Notes
2006-01-23 00:00:00PLEASE PROVIDE INFORMATION THAT
 DEMONSTRATES THE TANK WILL NOT BE SEEN
 FROM THE STREET.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-01-20 Cont ID  
Sent By mmclean Date 2006-01-20 Time 13:17 Rev Time 0.00
Received By mmclean Date 2006-01-20 Time 13:17 Sent To  
Notes
2006-01-20 00:00:00DENIED,
 1. NEED TO PROVIDE A COMPLETE SITEPLAN
 OF PROPERTY SHOWING THE LOCATION OF THE
 PROPOSED 5000GAL TANK WITH SETBACKS FROM
 PROPERTY LINE.
 2. INFORMATION PROVIDED IS INCOMPLETE
 FOR A COMPLETE REVIEW.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status N Date 2005-11-04 Cont ID  
Sent By rbrown Date 2005-11-04 Time 14:44 Rev Time 0.00
Received By rbrown Date 2005-11-04 Time 14:44 Sent To  
Notes
2005-11-04 00:00:00INTERIOR INSTALLATION.ALSO, DOES NOT
 REDUCE THE NUMBER OF SPACES IN THE
 PARKING GARAGE.