| Plan Review Stops For Permit 05100902 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2005-10-22 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2005-10-22 |
Time |
22:04 |
Rev Time |
0.30 |
| Received By |
jleahy |
Date |
2005-10-22 |
Time |
22:04 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2005-11-16 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2005-11-16 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2005-11-16 |
Time |
15:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-11-14 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2005-11-14 |
Time |
12:40 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2005-11-14 |
Time |
12:29 |
Sent To |
E |
|
| Notes |
| 2005-11-14 00:00:00 | DENIED: | | | | | | 1) THE CUT SHEETS AND SPEC'S NOTES UNDER | | | OPERATION STATES THAT WHEN POWER FAILS | | | THE DOORS WILL BE LOCKED AND SECURED. | | | | | | 2) THESE LOCKING DEVICES ON THE DOORS | | | MUST COMPLY WITH NFPA 101 LIFE SAFETY | | | CODE CHAPTER 7.2.1.6 SPECIAL LOCKING | | | ARRANGEMENTS. | | | | | | NATE MCCRAY, ASSISTANT FIRE MARSHAL | | | 561-804-4754 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-10-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-10-20 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-10-20 |
Time |
09:22 |
Sent To |
E |
|
| Notes |
| 2005-10-20 00:00:00 | TO "E" BOX |
|
|
|