| 2006-02-15 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | FROM PREVIOUS LIST, NUMBERING REMAINING |
| | THE SAME FOR CONSISTENCY |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)ADDRESSED. |
| | |
| | 3.)ADDRESSED. |
| | |
| | 4.)SHEET S2, STRUCTURAL NOTES CODES |
| | AND STANDARDS HAS REFERENCES WHICH ARE |
| | OUTDATED AND IN CONFLICT WITH OTHER |
| | SPECIFICATIONS ON THIS SHEET.CHECK ALL |
| | REFERENCES, ALL SECTIONS. |
| | |
| | STILL HAS OUTDATED REFERENCED.SOME |
| | YEARS REFERENCED ARE 1992, 1997, 1995. |
| | THESE ARE OVER TEN YEARS OLD.SEE |
| | FBC35. |
| | |
| | 5.)A NEW FIXED GLASS WINDOW IS SHOWN |
| | ON THE PLAN.PROVIDE PRODUCT APPROVAL. |
| | SEE ATTACHED POLICY IN REGARDS TO IMPACT |
| | PROTECTION.IF YOU PROPOSE THE USE OF |
| | REMOVABLE SHUTTERS, APPROVAL FROM THE |
| | BUILDING OFFICIAL IS REQUIRED. |
| | |
| | NOT ADDRESSED.NO PRODUCT APPROVAL |
| | SUBMITTED.S1 GENERAL NOTE 9 REFERS TO |
| | SHUTTERS.THIS CAN BE DONE ONLY WITH A |
| | PLAN APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | 6.)THE TRUSS PLACEMENT PLAN AND TRUSS |
| | DRAWINGS PREPARED BY JULIUS LEE'S |
| | CONSULTING ENGINEERING, PA ARE |
| | PHOTOCOPIES (ONE COPY).DOCUMENTS |
| | PREPARED BY AN ENGINEER AND SUBMITTED |
| | FOR PUBLIC RECORD ARE TO BE SIGNED, |
| | SEALED ORIGINALS. |
| | |
| | NOT ADDRESSED.SUBMIT TWO ORIGINAL, |
| | SIGNED, SEALED AND DATED SETS. |
| | |
| | 7.)THE SPECIFICATION FOR HURRICANE |
| | STRAP H16 CONFLICTS WITH THE CATALOG. |
| | IF YOU WANT TO SPECIFY A DIFFERENT |
| | NUMBER OF FASTENERS, LOCAL PRODUCT |
| | APPROVAL REQUIRED, FAC9B72. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | THIS WAS CHANGED TO MST30, WHICH I WAS |
| | UNABLE TO LOCATE IN THE CATALOG.MST IN |
| | THE CATALOG IS A WOOD-TO-WOOD STRAP. |
| | PROVIDE A TECHNICAL BULLETIN FROM THE |
| | MANUFACTURER IF YOU ARE SPECIFYING A |
| | PRODUCT TO BE USED IN A DIFFERENT MANNER |
| | THAN SPECIFIED IN THE CATALOG. |
| | |
| | 8.)FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVAL REQUIRED FOR THE GAF SHINGLES, |
| | FAC9B72.WWW.FLORIDABUILDING.ORG |
| | |
| | NOT ADDRESSED.THIS IS ALSO REQUIRED |
| | FOR THE WINDOW PRODUCT APPROVAL WHEN |
| | SUBMITTED. |
| | |
| | 9.)PROVIDE WIND DESIGN DATA |
| | FBC1603.1.4. |
| | |
| | SOME BUT NOT ALL OF THE INFORMATION WAS |
| | SUPPLIED. |
| | |
| | 10.)ROOF PERMIT REQUIRED (STRUCTURAL |
| | PERMIT ONLY WAS APPLIED FOR). |
| | |
| | NEW COMMENTS: |
| | |
| | 11.)SHEET S1 ALSO HAS OUTDATED |
| | REFERENCES.CHECK AND CORRECT ALL |
| | REFERENCES. |
| | |
| | 12.)ALL CHANGES ARE TO BE CLOUDED AND |
| | NUMBERED.THIS IS AN INDUSTRY STANDARD. |
| | FAILURE TO DO SO RESULTS IN DELAYS IN |
| | PLAN REVIEW. |
| | |
| | 13.)S2, THE HI RIB LATH IS TO BE |
| | FASTENED AT EVERY RIB, FBC2510.3, |
| | ASTM7.9. |
| | |
| | 14.)FAC61G15-23.002, THE PRINTED |
| | LICENSE NUMBER OF THE PERSON SEALING THE |
| | DOCUMENT IS TO BE ON EACH SHEET.THIS |
| | REQUIREMENT IS CURRENTLY SATISFIED BY |
| | THE INK SEAL.AS THIS HAS NOT BEEN |
| | INCORPORATED INTO THE ENGINEER'S TITLE |
| | BLOCK, CONFIRM THAT THIS INFORMATION IS |
| | ON THE RESUBMITTED PLAN. |
| | |
| | 15.)THE IMPRESSED SEAL IS NOT LEGIBLE |
| | DUE TO THE OVERLAPPING OF THE INK SEAL. |
| | ALL PLANS ARE TO BE SUBMITTED IN |
| | CONFORMANCE OF ALL STATUTORY |
| | REQUIREMENTS. |
| | |
| | 16.)SEE ATTACHED FS553.80(2)(B).A 4X |
| | PLAN REVIEW FEE WILL BE CHARGED IF |
| | COMMENTS ARE NOT PROPERLY ADDRESSED. |