Plan Review Details - Permit 05100675
Plan Review Stops For Permit 05100675
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-02-15 Cont ID  
Sent By shill Date 2006-02-15 Time 16:26 Rev Time 0.00
Received By shill Date 2006-02-15 Time 14:32 Sent To  
Notes
2006-02-15 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST, NUMBERING REMAINING
 THE SAME FOR CONSISTENCY
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)ADDRESSED.
  
 3.)ADDRESSED.
  
 4.)SHEET S2, STRUCTURAL NOTES CODES
 AND STANDARDS HAS REFERENCES WHICH ARE
 OUTDATED AND IN CONFLICT WITH OTHER
 SPECIFICATIONS ON THIS SHEET.CHECK ALL
 REFERENCES, ALL SECTIONS.
  
 STILL HAS OUTDATED REFERENCED.SOME
 YEARS REFERENCED ARE 1992, 1997, 1995.
 THESE ARE OVER TEN YEARS OLD.SEE
 FBC35.
  
 5.)A NEW FIXED GLASS WINDOW IS SHOWN
 ON THE PLAN.PROVIDE PRODUCT APPROVAL.
 SEE ATTACHED POLICY IN REGARDS TO IMPACT
 PROTECTION.IF YOU PROPOSE THE USE OF
 REMOVABLE SHUTTERS, APPROVAL FROM THE
 BUILDING OFFICIAL IS REQUIRED.
  
 NOT ADDRESSED.NO PRODUCT APPROVAL
 SUBMITTED.S1 GENERAL NOTE 9 REFERS TO
 SHUTTERS.THIS CAN BE DONE ONLY WITH A
 PLAN APPROVED BY THE BUILDING OFFICIAL.
  
 6.)THE TRUSS PLACEMENT PLAN AND TRUSS
 DRAWINGS PREPARED BY JULIUS LEE'S
 CONSULTING ENGINEERING, PA ARE
 PHOTOCOPIES (ONE COPY).DOCUMENTS
 PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED,
 SEALED ORIGINALS.
  
 NOT ADDRESSED.SUBMIT TWO ORIGINAL,
 SIGNED, SEALED AND DATED SETS.
  
 7.)THE SPECIFICATION FOR HURRICANE
 STRAP H16 CONFLICTS WITH THE CATALOG.
 IF YOU WANT TO SPECIFY A DIFFERENT
 NUMBER OF FASTENERS, LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 THIS WAS CHANGED TO MST30, WHICH I WAS
 UNABLE TO LOCATE IN THE CATALOG.MST IN
 THE CATALOG IS A WOOD-TO-WOOD STRAP.
 PROVIDE A TECHNICAL BULLETIN FROM THE
 MANUFACTURER IF YOU ARE SPECIFYING A
 PRODUCT TO BE USED IN A DIFFERENT MANNER
 THAN SPECIFIED IN THE CATALOG.
  
 8.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED FOR THE GAF SHINGLES,
 FAC9B72.WWW.FLORIDABUILDING.ORG
  
 NOT ADDRESSED.THIS IS ALSO REQUIRED
 FOR THE WINDOW PRODUCT APPROVAL WHEN
 SUBMITTED.
  
 9.)PROVIDE WIND DESIGN DATA
 FBC1603.1.4.
  
 SOME BUT NOT ALL OF THE INFORMATION WAS
 SUPPLIED.
  
 10.)ROOF PERMIT REQUIRED (STRUCTURAL
 PERMIT ONLY WAS APPLIED FOR).
  
 NEW COMMENTS:
  
 11.)SHEET S1 ALSO HAS OUTDATED
 REFERENCES.CHECK AND CORRECT ALL
 REFERENCES.
  
 12.)ALL CHANGES ARE TO BE CLOUDED AND
 NUMBERED.THIS IS AN INDUSTRY STANDARD.
 FAILURE TO DO SO RESULTS IN DELAYS IN
 PLAN REVIEW.
  
 13.)S2, THE HI RIB LATH IS TO BE
 FASTENED AT EVERY RIB, FBC2510.3,
 ASTM7.9.
  
 14.)FAC61G15-23.002, THE PRINTED
 LICENSE NUMBER OF THE PERSON SEALING THE
 DOCUMENT IS TO BE ON EACH SHEET.THIS
 REQUIREMENT IS CURRENTLY SATISFIED BY
 THE INK SEAL.AS THIS HAS NOT BEEN
 INCORPORATED INTO THE ENGINEER'S TITLE
 BLOCK, CONFIRM THAT THIS INFORMATION IS
 ON THE RESUBMITTED PLAN.
  
 15.)THE IMPRESSED SEAL IS NOT LEGIBLE
 DUE TO THE OVERLAPPING OF THE INK SEAL.
 ALL PLANS ARE TO BE SUBMITTED IN
 CONFORMANCE OF ALL STATUTORY
 REQUIREMENTS.
  
 16.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE WILL BE CHARGED IF
 COMMENTS ARE NOT PROPERLY ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-19 Cont ID  
Sent By shill Date 2005-12-19 Time 11:26 Rev Time 1.00
Received By shill Date 2005-12-19 Time 11:26 Sent To  
Notes
2005-12-19 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)PROVIDE A SITE PLAN SHOWING THE
 PROPOSED IMPROVEMENT (TWO COPIES).
  
 3.)SHEET S2 STRUCTURAL NOTES REFERS TO
 FBC2001; GOVERNING CODE IS FBC2004.
  
 4.)SHEET S2, STRUCTURAL NOTES CODES
 AND STANDARDS HAS REFERENCES WHICH ARE
 OUTDATED AND IN CONFLICT WITH OTHER
 SPECIFICATIONS ON THIS SHEET.CHECK ALL
 REFERENCES, ALL SECTIONS.
  
 5.)A NEW FIXED GLASS WINDOW IS SHOWN
 ON THE PLAN.PROVIDE PRODUCT APPROVAL.
 SEE ATTACHED POLICY IN REGARDS TO IMPACT
 PROTECTION.IF YOU PROPOSE THE USE OF
 REMOVABLE SHUTTERS, APPROVAL FROM THE
 BUILDING OFFICIAL IS REQUIRED.
  
 6.)THE TRUSS PLACEMENT PLAN AND TRUSS
 DRAWINGS PREPARED BY JULIUS LEE'S
 CONSULTING ENGINEERING, PA ARE
 PHOTOCOPIES (ONE COPY).DOCUMENTS
 PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED,
 SEALED ORIGINALS.
  
 7.)THE SPECIFICATION FOR HURRICANE
 STRAP H16 CONFLICTS WITH THE CATALOG.
 IF YOU WANT TO SPECIFY A DIFFERENT
 NUMBER OF FASTENERS, LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 8.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED FOR THE GAF SHINGLES,
 FAC9B72.WWW.FLORIDABUILDING.ORG
  
 9.)PROVIDE WIND DESIGN DATA
 FBC1603.1.4.
  
 10.)ROOF PERMIT REQUIRED (STRUCTURAL
 PERMIT ONLY WAS APPLIED FOR).
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-30 Cont ID  
Sent By adarroug Date 2006-01-30 Time 14:09 Rev Time 0.00
Received By adarroug Date 2006-01-30 Time 14:09 Sent To B
Notes
2006-01-30 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-01-20 Cont ID  
Sent By adarroug Date 2006-01-20 Time 08:14 Rev Time 0.00
Received By adarroug Date 2006-01-20 Time 08:13 Sent To Z
Notes
2006-01-20 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-06 Cont ID  
Sent By adarroug Date 2005-12-06 Time 11:22 Rev Time 0.00
Received By adarroug Date 2005-12-06 Time 11:22 Sent To Z
Notes
2005-12-06 00:00:00TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-19 Cont ID  
Sent By adarroug Date 2005-10-19 Time 11:56 Rev Time 0.00
Received By adarroug Date 2005-10-19 Time 11:56 Sent To B
Notes
2005-10-19 00:00:00TO "JGOMEZ" DESK

Review Stop Z ZONING
Rev No 2 Status N Date 2006-01-28 Cont ID  
Sent By mmclean Date 2006-01-28 Time 10:13 Rev Time 0.00
Received By mmclean Date 2006-01-28 Time 10:13 Sent To I
Notes
2006-01-28 00:00:00NOTE: NEW PLANS S-1 SHOWS THE CANOPY
 PORCH REMOVED (NO CANOPY PORCH).NO
 ZONING REVIEW REQUIRED.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-12-06 Cont ID  
Sent By mmclean Date 2005-12-06 Time 11:27 Rev Time 0.00
Received By mmclean Date 2005-12-06 Time 11:27 Sent To B
Notes
2005-12-06 00:00:00DENIED,
 1. MUST SHOW THE LOCATION OF THE NEW
 CANOPY ON TWO CURRENT SITE PLAN/SURVEY
 WITH SETBACK (THE DISTANCE OF THE NEW
 CANOPY FROM PROPERTY LINE).
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720