Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-11-16 Cont ID  
Sent By pkrauss Date 2005-11-16 Time 12:42 Rev Time 0.35
Received By pkrauss Date 2005-11-16 Time 12:17 Sent To  
Notes
2005-11-16 00:00:00ENERGY CALCS SUBMITTED WITH BUILDING
 PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-10-20 Cont ID  
Sent By tgordon Date 2005-10-20 Time 14:20 Rev Time 0.30
Received By tgordon Date 2005-10-20 Time 14:20 Sent To  
Notes
2005-10-20 00:00:00*** DENIED ***
 1) NEED MANUAL J CALCULATIONS SHOWING
 A/C EQUIP. SIZE REQUIRED, PER 2004 FBC/R
 M1401.3 .
 2) NEED A/C SYSTEM MANUFACTURE'S NAME,
 MODEL NUMBER, SIZE, & SEER, SHOWING ON
 PLANS.
 3) SHOW LOCATION OF CONDENSER UNIT, &
 DRAIN LINE ON PLANS.
 4) NEED A NOTICE OF COMMENCEMENT.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.