Plan Review Details - Permit 05100637
Plan Review Stops For Permit 05100637
Review Stop AD ADDRESSING
Rev No 2 Status N Date 2006-02-08 Cont ID  
Sent By dpalmer Date 2006-02-08 Time 19:55 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2006-02-08 00:00:00OK, ADDRESS WAS CORRECTED IN SYSTEM.

Review Stop AD ADDRESSING
Rev No 1 Status N Date 2006-01-23 Cont ID  
Sent By ptjomsto Date 2006-01-23 Time 11:13 Rev Time 0.00
Received By ptjomsto Date 2006-01-23 Time 11:13 Sent To  
Notes
2006-01-23 00:00:00ADDRESS ON APP READS 2130
 CENTREPARK/PAPA ALSO/CP READS 2100
 CENTREPARK

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2006-11-15 Cont ID  
Sent By jwitmer Date 2006-11-15 Time 10:39 Rev Time 0.77
Received By jwitmer Date 2006-11-15 Time 10:39 Sent To PC
Notes
2006-11-15 10:40:08REVISIONS A201,A202& A210

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-10-12 Cont ID  
Sent By jwitmer Date 2006-10-12 Time 13:39 Rev Time 0.66
Received By jwitmer Date 2006-10-12 Time 13:39 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-09-29 Cont ID  
Sent By jwitmer Date 2006-09-29 Time 08:11 Rev Time 0.77
Received By jwitmer Date 2006-09-29 Time 08:10 Sent To PC
Notes
2006-09-29 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05100637
 ADD: 2130 CENTREPARK DR
 CONT: TURNER CONSTRUCTION
 TEL: (786)229-4036
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW
 ACTION: DENIED
  
 1) ARCHITECTURAL PLANS INDICATE IN THE
 TITLEBLOCK A FICTIUOS NAME INTERARCH
 PLEASE PROVIDE THE FIRMS CERTIFICATE OF
 AUTHORIZATIONNUMBER.
 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ARCHITECTURAL SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
 IF THE FIRM DOESN'T HAVE THE
 CERTIFICATE OF AUTHORIZATION, THIS
 FICTIOUS NAME IS TO BE RMOVED.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-06-27 Cont ID  
Sent By jwitmer Date 2006-06-15 Time 15:21 Rev Time 1.11
Received By jwitmer Date 2006-06-15 Time 15:21 Sent To  
Notes
2006-06-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05100637
 ADD: 2100 CENTREPARK WEST
 CONT:PLAN REVIEW
 TO BE DETERMINED
 TEL: ()###-####
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
 ADMINISTRATIVE CODE
  
 3RD REVIEW
 ACTION: PROVISO
 FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-03-02 Cont ID  
Sent By jwitmer Date 2006-03-02 Time 07:44 Rev Time 0.66
Received By jwitmer Date 2006-03-02 Time 07:44 Sent To  
Notes
2006-03-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05100637
 ADD: 2100 CENTREPARK WEST
 CONT:PLAN REVIEW
 TO BE DETERMINED
 TEL: ()###-####
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
 ADMINISTRATIVE CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) COMMENT# 6 FROM THE PREVIOUS
 REVIEW,A-910 PLANS INDICATE DROPPED
 CEINGS OR SOFFITS WITH THE USE OF
 FRAMING HUNG FROM THE STRUCTURE ABOVE.
 PROVIDE WHAT TYPE OF MATERIAL THIS IS
 AND HOW OFTEN THE FRAMING IS TO BE
 ATTACHED, TO THE DECK ABOVE.
  
 *****COMMENT UNDERCONSIDERATION*******
 8) RESTROOMS:1210.2 WALLS.
 WALLS WITHIN 2 FEET (610 MM) OF URINALS
 AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT
 OF 4 FEET (1219 MM) ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTURAL ELEMENTS, THE
 MATERIALS USED IN SUCH WALLS SHALL BE OF
 A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE.
  
 9)PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 (RAISED)TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 PLANS STILL HAVE SHEETS THAT ARE NOT
 RAISED SEAL BUT EMBOSSED.
 2ND ISSUE INTERARCH DOES NOT HAVE
 ANY ARCHITECTURAL NOR INTERIOR DESIGN
 CERTIFICATE OF AUTHORIZATION NUMBER
 LISTED ON THEIR HEADER SHEET. IF THEY DO
 HAVE A CERTIFICATE OF AUTHORIZATION THE
 ADDRESS LISTED WITH STATE TO BE THE ONE
 USED IN FL.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-23 Cont ID  
Sent By jwitmer Date 2005-12-23 Time 11:34 Rev Time 3.30
Received By jwitmer Date 2005-12-23 Time 11:34 Sent To  
Notes
2005-12-23 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05100637
 ADD: 2100 CENTREPARK WEST
 CONT:PLAN REVIEW
 TO BE DETERMINED
 TEL: ()###-####
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
 ADMINISTRATIVE CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2)110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.ALSO HEIGHT
 OF BUILDING.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 3) PROVIDE INTERIOR WALL & CEILING
 FINISH REQUIEMENTS BY OCCUPANCY:803.5
 INTERIOR FINISH REQUIREMENTS BASED ON
 GROUP.
 INTERIOR WALL AND CEILING FINISH SHALL
 HAVE A FLAME SPREAD INDEX NOT GREATER
 THAN THAT SPECIFIED IN TABLE 803.5 FOR
 THE GROUP AND LOCATION DESIGNATED.
 INTERIOR WALL AND CEILING FINISH
 MATERIALS, OTHER THAN TEXTILES, TESTED
 IN ACCORDANCE WITH NFPA 286 AND MEETING
 THE ACCEPTANCE CRITERIA OF SECTION
 803.2.1 , SHALL BE PERMITTED TO BE USED
 WHERE A CLASS A CLASSIFICATION IN
 ACCORDANCE WITH ASTM E 84 IS REQUIRED.
  
 4) (2004 FBC) 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND REVELENT
 LAWS, ORDINANCES, AND RULES AND
 REGULATIONS AS DETERMINED BY THE
 BUILDING OFFICIAL.
 SHEET A201 INDICATES A STAIR TOWER
 HEIGHT OF BUILDING UNKOWN, THE STAIR
 TOWER IS UNIDENTIFIABLE EXCEPT FOR DOOR#
 123. IN THIS STAIR TOWER THERE IS A
 OPENING BLOCKED BUT NO DETAIL GIVING THE
  
 UL LISTING AND FIRE RESISTANCE RATING.
  
 5) A202 INDICATES DOOR# 119 MISSING 18"
 LATCH SIDE OF DOOR,SEE,11-4.13.6
 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARENCES AT DOORS THAT ARE
 NOT AUTOMATIC OR POWER-ASSISTED SHALL BE
 AS SHOWN IN FIG. 25. THE FLOOR OR GROUND
 AREA WITH IN THE REQUIRED CLEARENCES
 SHALL BE CLEAR & LEVEL.
  
 6)-910 PLANS INDICATE DROPPED CEINGS OR
 SOFFITS WITH THE USE OF FRAMING HUNG
 FROM THE STRUCTURE ABOVE. PROVIDE WHAT
 TYPE OF MATERIAL THIS IS AND HOW OFTEN
 THE FRAMING IS TO BE ATTACHED, AND BY
 WHAT METHOD.
  
 7) A963 INDICATES (2) KITCHEN UNITS BUT
 NO INFORMATION AS TO:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 8) RESTROOMS:1210.2 WALLS.
 WALLS WITHIN 2 FEET (610 MM) OF URINALS
 AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT
 OF 4 FEET (1219 MM) ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTURAL ELEMENTS, THE
 MATERIALS USED IN SUCH WALLS SHALL BE OF
 A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE.
  
 9)PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 (RAISED)TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-12-22 Cont ID  
Sent By btrobaug Date 2006-12-22 Time 11:08 Rev Time 0.50
Received By btrobaug Date 2006-12-22 Time 10:42 Sent To PC
Notes
2006-12-18 20:09:21ROUTED TO BILL TROBAUGH'S DESK AS HE IS THE PREVIOUS
 REVIEWER FOR ISSUANCE OF PROJECT

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-11-21 Cont ID  
Sent By btrobaug Date 2006-11-21 Time 11:45 Rev Time 1.00
Received By btrobaug Date 2006-11-20 Time 12:15 Sent To PC
Notes
2006-11-20 12:16:31ROUTED TO BILL TROBAUGH AS HE WAS THE PREVIOUS
 REVIEWER. DVPALMER.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-07-12 Cont ID  
Sent By btrobaug Date 2006-07-12 Time 09:25 Rev Time 1.00
Received By btrobaug Date 2006-07-12 Time 07:34 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-06-09 Cont ID  
Sent By dpalmer Date 2006-06-09 Time 15:03 Rev Time 0.00
Received By dpalmer Date 2006-06-09 Time 11:04 Sent To  
Notes
2006-06-09 00:00:00****UNSAT ****
  
 ** PLEASE KNOW, ANY WORK DONE UNDER
 EARLY WORK RELEASE WAS AT CONTRACTORS
 RISK AND ANY CHANGES WILL BE THE
 RESPONSIBILTY OF THE CONTRACTORS ETC.
 PLEASE SEE NOTES BELOW AS COMMENTS WITH
 RESPECT THE 2004 FBC CHAPTER 13.
  
 PLEASE SEE THE OLD PLANS SUBMITTED BACK
 FOR REFERENCE FOR THIS PROJECT WERE FROM
 THE 1661 WORTHINGTON SITE AND OLD PLANS
 CAN NOT BE VERIFIED AT THIS TIME.
  
 1) NOTE: PLEASE SEE REQUIREMENTS FOR FBC
 CHAPTER 13 ARE REQUIRED TO BE MET FOR
 ALL LIGHTING.
 13-415.1.ABC.1.1, 13-415.1.ABC.1.2 ETC
 PLEASE CLARIFY AS SOME OF THIS IS BEING
 SHOWN, BUT UNCLEAR AS MANY LIGHTING
 CIRCUITS DO NOT INDICATE ANY CONTROL?
 PLEASE ALSO SEE THE OVER RIDE SWITCHES
 MUST STATE A MAXIMUM OF 4HRS AND A MAX
 OF 30 MINS FOR MOTION SENSORS.
 PLEASE SEE THE OVER RIDING SWITCHES
 SHALL BE LOCATED IN THE AREAS FO
 LIGHTING WHICH CAN BE SEEN BY THE
 OCCUPANT.
 PLEASE SHOW LOCATIONS OF ALL OVER RIDES
 AND OCC SENSORS.
 ** PLEASE SEE A WORST CASE SCENARIO
 SHALL BE SHOWN FOR VOLTAGE DROP PER 13-413.1.ABC.1
 **PLEASE ALSO SEE 13-415.1.ABC.1.3 FOR
 OTHER LIGHTING IN AREAS.
 ** PLEASE SEE CALCS FOR 13-415.1.AB.1
  
 2) NOTE: PLEASE SEE RISER SEEMS TO SHOW
 NEW FEEDERS FROM GUTTER TO METER ON THE
 EXISTING RISER AND THE NEW RISER SEEMS
 TO INDICATE EXISTING FEEDERS ??
 SEEMS TO BE A MISPRINT?
 215.5
  
 3) NOTE: PLEASE CLARIFY IT ROOM AND
 PLEASE SEE PART WALLS THAT DO NOT SEEM
 TO INDICATE THE 1 HR RATING ALL THE WAY
 AROUND? THIS SHOULD BE IN BUILDING
 REVIEW COMMENTS ALSO.
 PLEASE SEE NEC 645 FOR MEANS OF
 DISCONNECTS AND DETECTION SYSTEMS WHICH
 NEED TO BE SHOWN FOR THE IT ROOM.
 PLEASE INDICATE THE SHUT OFF DEVICE AND
 SHUT OFF FOR AHU.
 PLEASE INDICATE ANY RAISED FLR AND SD'S
 ABOVE AND BELOW.
 PLEASE SEE NFPA-75 , CHAPTER 6 ETC.
  
 4) NOTE: PLEASE CLARIFY EXISTING
 TRANSFORMER ON RISER AND THE LOCATION OF
 THIS TRANSFORMER. IT IS IN THE MAIN
 ELECTRICAL ROOM ? AS PLANS DO NOT SHOW.
 PLEASE SEE 450.13B, 450.21
 IF IN THE MAIN ELECTRICAL ROOM THIS
 SHOULD BE OK.
  
 5) NOTE: PLEASE SUBMIT THE SPECS ON THE
 WATT STOPPER EQUIPMENT WHICH WILL BE
 INSTALLED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRCAIL PLAN REVIEW.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-02-08 Cont ID  
Sent By dpalmer Date 2006-02-08 Time 20:16 Rev Time 0.00
Received By dpalmer Date 2006-02-08 Time 19:54 Sent To I
Notes
2006-02-08 00:00:00********* UNSAT 2ND REVIEW ********
  
  
 COMMERACE BANK: SUBMITTED FOR PERMIT ON
 JAN 23,2006
  
 1)NOTE: PLEASE SEE SOME NOTES FROM
 PREVIOUS REVIEW WHICH STILL NEED TO BE
 ADDRESSED. PLEASE SEE NOTES BELOW WHICH
 WERE TAKEN DIRECTLY FROM PREVIOUS REVIEW
 AND NEW NOTE FOR REPEAT COMMENTS.
  
 ** PLEASE SEE NO FORMAL RESPONSE WAS
 GENERATED FROM THE DESIGNER OR ONE
 SUBMITTED.
  
 ******** UNSAT ********
  
  
  
 1)NOTE: OK.
  
 2)NOTE: OK.
  
 3)NOTE: PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE (FAC) 61G1-16.004
 WHICH REQUIRES THE PRINTED FIRM LICENSE
 NUMBER ON SAID TITLE BLOCK FOR
 ARCHITECTUAL FIRM NAME.
 PLEASE SEE FS 481.219 WHICH REQUIRES A
 "CERTIFICATE OF AUTHORIZATION"/ FIRM #
 NUMBER FOR SAID ARCHITECTUAL COMPANY.
 PLEASE SEE THE ABOVE TWO COMMENTS IS
 REQUIRED OF ALL SHEETS AND FOR ALL TRADE
 SHEETS WHETHER OR NOT COMMENTS ARE MADE
 BY OTHER REVIEWER(S).
 THIS COMMENT IS NOT FOR ENGINEERING
 FIRM, HOWEVER DOES AFFECT PM&E SHEETS.
  
 4)NOTE: OK
  
 5)NOTE:PLEASE VERIFY ALL EMERGENCY AND
 EXT LTS, AS THESE COULD NOT BE LOCATED
 ON PLANS TO MATCH UP WITH THE FIXTURE
 SCHEDULE AND SHOWING THESE AS CONTAINING
 THE MIN BATTERY BACK UP.
 NEW , EXISTING?
 PLEASE SEE NFPA-101 7.8 AND 7.9.
  
 6)NOTE: OK.
  
  
 7)NOTE: PLEASE VERIFY TAPPED CONDUCOTRS
 FROM MAIN GUTTER. PLEASE SEE 3/0'S ARE
 RATED AT 200A'S ONLY AND OCP FOR SERVICE
 IS SHOWN AT 210A'S.
 240.4,310.16
 PLEASE ALSO SEE 240.21 FOR "TAPPED"
 CONDUCTORS AND MIN SIZES. PLEASE SEE
 CONDUCTORS ARE TAPPED IN GUTTER AND THEN
 AGAIN IN METER, WHERE AS THE 3/0'S
 CONTINUE THROUGH, BUT #2'S ARE TAPPED
 FROM THOSE EXISITNG TAPS?
 PLEASE VERIFY LENGTH.
 ALL THIS IS SHOWN AS EXISTING, HOWEVER,
 PLEAS KNOW DUE TO THE EXTENT OF WORK AND
 POSSIBILITY OF NON-CODE COMPLIANCE, THE
 ABOVE WOULD NEED TO BE CORRECTED AT THIS
 TIME.
  
 *** NEW NOTES***
  
 1)NOTE: PLEASE SEE NOTE #5, NO FIXTURE
 LEGEND WAS SUBMITTED.
  
 2)NOTE: PLEASE SEE PLANS WHICH WERE
 REDLIEND ON PREVIOUS REVIEW FOR 210.8B3
 FOR KITCHENS IN OTHER THAN DWELLING
 UNITS FOR REQUIRED GFI PROTECTION.
  
 3)NOTE: PLEASE SEE FLORIDA STATUES
 553.80(2)(B) WITH RESPECT TO THE DESIGN
 PROFESSIONAL AND REPEAT COMMENTS THREE
 OR MORE TIMES.
 ** PLEASE KNOW, THIS IS ONLY A NOTICE
 GIVEN AT THIS TIME AND DOES NOT APPLY
 FOR THIS REVIEW.
  
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENT(S) FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 ONE COPY OF ANY OLD/VOIDED SHEETS SHOULD
 BE SUBMNITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-22 Cont ID  
Sent By dpalmer Date 2005-12-22 Time 14:56 Rev Time 0.00
Received By dpalmer Date 2005-12-22 Time 12:07 Sent To  
Notes
2005-12-22 00:00:00******** UNSAT ********
  
 COMMERACE BANK TENAT REMODEL
 "PLAN REVIEW ONLY"
  
 1)NOTE: PELASE SEE PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW" AND HAVE NOT
 BEEN SUBMITTED FOR PERMIT.
  
 2)NOTE: PLEASE SEE FS 481.221, FAC
 61G1-16.003 WHICH REQUIRES THE SEALING
 OF PLANS TO BE DONE WITH AN "IMPRESSION
 TYPE" "RAISED" SEAL.
 PLEASE SEE "A" SHEETS CONTAIN A "RUBBER
 STAMP" FOR THE ARCHITECT'S SEAL.
  
 3)NOTE: PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE (FAC) 61G1-16.004
 WHICH REQUIRES THE PRINTED FIRM LICENSE
 NUMBER ON SAID TITLE BLOCK FOR
 ARCHITECTUAL FIRM NAME.
 PLEASE SEE FS 481.219 WHICH REQUIRES A
 "CERTIFICATE OF AUTHORIZATION"/ FIRM #
 NUMBER FOR SAID ARCHITECTUAL COMPANY.
 PLEASE SEE THE ABOVE TWO COMMENTS IS
 REQUIRED OF ALL SHEETS AND FOR ALL TRADE
 SHEETS WHETHER OR NOT COMMENTS ARE MADE
 BY OTHER REVIEWER(S).
 THIS COMMENT IS NOT FOR ENGINEERING
 FIRM, HOWEVER DOES AFFECT PM&E SHEETS.
  
 4)NOTE: PLEASE SEE PLANS SHOW AN ADDRESS
 OF 2130 CENTREPARK, HOWEVER WHEN APPLIED
 FOR "PLAN REVIEW" , THE PARCEL CONTROL
 NUMBER (PCN) USED ON APPLICATION MATCHES
 UP TO AN ADDRESS OF 2100 CENTREPARK ,
 PLEASE VERIFY AND ADJUST EITHER AS
 NEEDED.
  
 5)NOTE: PLEASE VERIFY ALL EMERGENCY AND
 EXT LTS, AS THESE COULD NOT BE LOCATED
 ON PLANS TO MATCH UP WITH THE FIXTURE
 SCHEDULE AND SHOWING THESE AS CONTAINING
 THE MIN BATTERY BACK UP.
 NEW , EXISTING?
 PLEASE SEE NFPA-101 7.8 AND 7.9.
  
 6)NOTE: PLEASE SEE "A" SHEETS REFERENCE
 A 2004 NEC.
 PLEASE SEE AS OF JULY 1ST , 2003 THE
 STATE ADOPTED THE 2002 NEC. WE ARE
 CURRENTLY UNDER THAT CODE.
 PLEASE ALSO KNOW THE NEXT CODE THAT WILL
  
 COME INTO AFFECT FOR FUTURE KNOWLEDGE
 WILL BE THE 2005.
  
 7)NOTE: PLEASE VERIFY TAPPED CONDUCOTRS
 FROM MAIN GUTTER. PLEASE SEE 3/0'S ARE
 RATED AT 200A'S ONLY AND OCP FOR SERVICE
 IS SHOWN AT 210A'S.
 240.4,310.16
 PLEASE ALSO SEE 240.21 FOR "TAPPED"
 CONDUCTORS AND MIN SIZES. PLEASE SEE
 CONDUCTORS ARE TAPPED IN GUTTER AND THEN
 FAIN IN METER, WHERE AS THE 3/0'S
 OCNTINUE THROUGH, BUT #2'S ARE TAPPED
 FROM THOSE EXISITNG TAPS?
 PLEASE VERIFY LENGTH.
 ALL THIS IS SHOWN AS EXISTING, HOWEVER,
 PLEAS KNOW DUE TO THE EXTENT OF WORK AND
 POSSIBILITY OF NON-CODE COMPLIANCE, THE
 ABOVE WOULD NEED TO BE CORRECTED AT THIS
 TIME.
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENT(S) FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 ONE COPY OF ANY OLD/VOIDED SHEETS SHOULD
 BE SUBMNITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-06-22 Cont ID  
Sent By mwennerg Date 2006-06-22 Time 14:14 Rev Time 0.00
Received By mwennerg Date 2006-06-22 Time 14:14 Sent To  
Notes
2006-06-22 00:00:00***APPROVED***
  
 SEPARATE SHOP DRAWINGS AND PERMITS ARE
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL PRIOR TO ANY WORK BEING
 DONE ON SYSTEMS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-03-03 Cont ID  
Sent By mwennerg Date 2006-03-03 Time 10:19 Rev Time 0.00
Received By mwennerg Date 2006-03-03 Time 10:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-11-23 Cont ID  
Sent By nmccray Date 2005-11-23 Time 15:42 Rev Time 0.00
Received By nmccray Date 2005-11-23 Time 14:42 Sent To  
Notes
2005-11-23 00:00:00PLAN REVIEW ONLY
  
 1) DEMOLITION, RENOVATION, AND
 CONSTRUCTION SHALL COMPLY WITH NFPA 241.
  
 2) THERE APPEARS TO BE NO FIRE SPRINKLER
 PROTECTION IN TELLER CASH ROOM 109.
  
 3) THE CITY OF WEST PALM BEACH FIRE
 MARSHAL OFFICE REQUIRES HVAC DUCT SMOKE
 DETECTORS TO ACTIVATE A GENERAL FIRE
 ALARM.
  
 4) THE FIRE ALARM SYSTEM IS REQUIRED TO
 BE CLASS A OR FULLY ADDRESSABLE.
  
 5) SEPARATE PERMIT APPLICATIONS AND SHOP
 DRAWINGS ARE REQUIRED FOR THE FIRE ALARM
 AND FIRE SPRINKLER SYSTEM REMODEL.
  
 6) THE INTERIOR WALLS AND CEILINGS
 FINISH MATERIAL COMPLYING WITH SECTION
 10.2 SHALL BE CLASS A OR CLASS B, IN
 EXITS AND IN EXIT ACCESS CORRIDORS. IN
 ALL OTHER AREAS, INTERIOR WALL AND
 CEILING FINISHES SHALL BE CLASS A, CLASS
 B, OR CLASS C.
  
 7) RENOVATION SHALL COMPLY WITH NFPA 101
 LIFE SAFETY CODE, 2003 EDITION.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-12-15 Cont ID  
Sent By adarroug Date 2006-12-15 Time 16:04 Rev Time 0.00
Received By adarroug Date 2006-12-15 Time 16:04 Sent To E
Notes
2006-12-15 16:04:40TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-11-14 Cont ID  
Sent By adarroug Date 2006-11-14 Time 16:33 Rev Time 0.00
Received By adarroug Date 2006-11-14 Time 16:33 Sent To E
Notes
2006-11-14 16:33:45TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-10-23 Cont ID  
Sent By adarroug Date 2006-10-23 Time 13:45 Rev Time 0.00
Received By adarroug Date 2006-10-23 Time 13:45 Sent To B
Notes
2006-10-23 13:45:46TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-10-10 Cont ID  
Sent By adarroug Date 2006-10-10 Time 18:08 Rev Time 0.00
Received By adarroug Date 2006-10-10 Time 18:08 Sent To B
Notes
2006-10-10 18:08:28TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-09-12 Cont ID  
Sent By adarroug Date 2006-09-12 Time 08:35 Rev Time 0.00
Received By adarroug Date 2006-09-12 Time 08:35 Sent To B
Notes
2006-09-12 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-16 Cont ID  
Sent By adarroug Date 2006-08-16 Time 10:51 Rev Time 0.00
Received By adarroug Date 2006-08-16 Time 10:51 Sent To M
Notes
2006-08-16 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-11 Cont ID  
Sent By shill Date 2006-07-11 Time 16:12 Rev Time 0.00
Received By shill Date 2006-07-11 Time 16:12 Sent To  
Notes
2006-07-11 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-12 Cont ID  
Sent By adarroug Date 2006-05-12 Time 14:27 Rev Time 0.00
Received By adarroug Date 2006-05-12 Time 14:27 Sent To  
Notes
2006-06-06 00:00:00TO "COMM' BD#6/1 ROLL ON RACK
2006-05-12 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-22 Cont ID  
Sent By adarroug Date 2006-01-26 Time 10:39 Rev Time 0.00
Received By adarroug Date 2006-01-26 Time 11:26 Sent To  
Notes
2006-02-22 00:00:00TO "COMM" BD#57
2006-01-26 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-09 Cont ID  
Sent By pschmitz Date 2006-01-09 Time 11:41 Rev Time 0.00
Received By adarroug Date 2005-10-14 Time 11:49 Sent To  
Notes
2005-11-14 00:00:00TO "COMM" BD#19
2005-10-18 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2006-11-14 Cont ID  
Sent By hmoser Date 2006-11-14 Time 09:00 Rev Time 0.00
Received By hmoser Date 2006-11-14 Time 09:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-08-17 Cont ID  
Sent By tgordon Date 2006-08-17 Time 08:26 Rev Time 0.25
Received By tgordon Date 2006-08-17 Time 08:26 Sent To  
Notes
2006-08-17 00:00:00REVISION TO MECHANICAL PLANS PAGE M1.01

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-07-12 Cont ID  
Sent By pkrauss Date 2006-07-12 Time 12:44 Rev Time 0.00
Received By pkrauss Date 2006-07-12 Time 10:24 Sent To B
Notes
2006-07-12 00:00:00PROVISO ADDRESSED

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-07-03 Cont ID  
Sent By pkrauss Date 2006-07-03 Time 13:38 Rev Time 0.00
Received By pkrauss Date 2006-07-03 Time 13:38 Sent To  
Notes
2006-07-03 00:00:00PROVISO:
 PLAN SHEET M1.01 ROOM 112 DUCT
 PENETRATION SHALL HAVE A FIRE DAMPER OR
 COMPLY WITH THE EXCEPTIONS UNDER
 607.5.3.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-02-27 Cont ID  
Sent By pkrauss Date 2006-02-27 Time 10:14 Rev Time 0.00
Received By pkrauss Date 2006-02-27 Time 09:13 Sent To  
Notes
2006-02-27 00:00:00PLEASE NOTE, PLAN SHEET M2.01 ON THE
 EXHAUST FAN SCHEDULE, FAN EF-1 IS NOT
 INDICATED ON THE PLAN.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-12-22 Cont ID  
Sent By tgordon Date 2005-12-22 Time 11:05 Rev Time 1.00
Received By tgordon Date 2005-12-22 Time 11:28 Sent To  
Notes
2005-12-22 00:00:00*** FAILED ***
 1) PLEASE MAKE NOTE, MATERIALS
 EXPOSED WITHIN PLENUMS SHALL BE NON -
 COMBUSTIBLE OR SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND SMOKE -
 DEVELOPED INDEX OF NOT MORE THAN 50 WHEN
 TESTED IN ACCORDANCE WITH ASTM E 84.
  
 2) BATHROOM EXHAUST FANS ARE SHOWING AS
 EF-2 THERE IS NO EF-2 LISTED ON EXHAUST
 FAN DATA.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-07-01 Cont ID  
Sent By pschmitz Date 2006-07-01 Time 07:58 Rev Time 0.00
Received By pschmitz Date 2006-07-01 Time 07:33 Sent To  
Notes
2006-07-01 00:00:00RE-SUB

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-03-18 Cont ID  
Sent By pschmitz Date 2006-03-18 Time 13:19 Rev Time 0.00
Received By pschmitz Date 2006-03-18 Time 13:18 Sent To  
Notes
2006-03-18 00:00:00PAUL SCHMITZ
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 DENIED
 1) SHT 963 BREAK RM SINK RM #114
 DOORS NOT APPROVED ON SINK BASE.
  
 ?11-4.24.3 KNEE CLEARANCE. KNEE
 CLEARANCE THAT IS AT LEAST 27 IN. (685
 MM) HIGH, 30 IN. (760 MM) WIDE, AND 19
 IN (485 MM) DEEP SHALL BE
 PROVIDED UNDERNEATH SINKS.
 ?11-4.24.4 DEPTH. EACH SINK SHALL BE A
 MAXIMUM OF 6-1/2 IN (165 MM)
 DEEP.
 ?11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30 IN. BY 48
 IN. (760 MM BY 1220 MM) COMPLYING WITH
 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.THE CLEAR FLOOR SPACE SHALL
 BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 IN. (485 MM)
 UNDERNEATH THE SINK (SEE FIGURE
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-01-09 Cont ID  
Sent By pschmitz Date 2006-01-09 Time 09:41 Rev Time 0.00
Received By pschmitz Date 2006-01-09 Time 09:40 Sent To  
Notes
2006-01-09 00:00:00PAUL SCHMITZ
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 DENIED
  
 1) SHT 1-100 DEMOLITION
 SEPERATE PERMIT REQUIRED.
 SEC.704.5 DEAD ENDS.ADD NOTE ON PLANS.
 IN THE INSTALLATION OR REMOVAL OF ANY
 PART OF A DRAINAGE SYSTEM, DEAD ENDS
 SHALL BE PROHIBITED.
  
 2) SHT-P1.01 RM #114 BREAK ROOM SINK
 PROVIDE A DETAIL, ?11-4.24 SINKS.
 ?11-4.24.1 GENERAL. SINKS REQUIRED TO
 BE ACCESSIBLE BY ?11-4.1 SHALL
 COMPLY WITH ?11-4.24.
 ?11-4.24.2 HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER OR RIM NO
 HIGHER THAN 34 IN. (865 MM) ABOVE THE
 FINISH FLOOR.
 ?11-4.24.3 KNEE CLEARANCE. KNEE
 CLEARANCE THAT IS AT LEAST 27 IN. (685
 MM) HIGH, 30 IN. (760 MM) WIDE, AND 19
 IN (485 MM) DEEP SHALL BE
 PROVIDED UNDERNEATH SINKS.
 ?11-4.24.4 DEPTH. EACH SINK SHALL BE A
 MAXIMUM OF 6-1/2 IN (165 MM)
 DEEP.
 ?11-4.24.5 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE AT LEAST 30 IN. BY 48
 IN. (760 MM BY 1220 MM) COMPLYING WITH
 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD
 APPROACH.THE CLEAR FLOOR SPACE SHALL
 BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 IN. (485 MM)
 UNDERNEATH THE SINK (SEE FIGURE
 11-32).
 ?11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED
 UNDER SINKS SHALL BE INSULATED OR
 OTHERWISE CONFIGURED SO AS TO PROTECT
 AGAINST CONTACT.THERE SHALL BE NO
 SHARP OR ABRASIVE SURFACES UNDER
 SINKS.
 ?11-4.24.7 FAUCETS. FAUCETS SHALL
 COMPLY WITH ?11-4.27.4.LEVER-
 OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS
 ARE ACCEPTABLE DESIGNS.
 3) TAB 403 MINIMUM FACILITIES.
 ONE DRINKING FOUNTAIN REQUIRED.
 SEC. 404 ACCESSIBLE PLUMBING FIXTURES
 PROVIDE A DETAIL, SEE FIG. 404.2.2
 END OF COMMENTS, QUESTIONS 561-805-6692
  