Plan Review Details - Permit 05100635
Plan Review Stops For Permit 05100635
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-08-16 Cont ID  
Sent By pkrauss Date 2006-08-16 Time 15:18 Rev Time 0.00
Received By pkrauss Date 2006-08-16 Time 15:18 Sent To  
Notes
2006-08-11 00:00:00NEEDS SUITE #

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-09-29 Cont ID  
Sent By jwitmer Date 2006-09-29 Time 11:06 Rev Time 0.77
Received By jwitmer Date 2006-09-29 Time 08:38 Sent To PC
Notes
2006-09-29 00:00:00REVISION# 3 & 4.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-06-20 Cont ID  
Sent By jwitmer Date 2006-06-20 Time 07:28 Rev Time 1.11
Received By jwitmer Date 2006-06-20 Time 07:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-03-01 Cont ID  
Sent By jwitmer Date 2006-03-01 Time 17:45 Rev Time 0.55
Received By jwitmer Date 2006-03-01 Time 17:45 Sent To  
Notes
2006-03-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05100635
 ADD: 1661 WORTHINGTON RD
 CONT: "PLAN REVIEW"
 TEL: (954)689-6905
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 1) OK!
  
 2)OK!
 2A)OK!
 2B) FL ADMINISTRATIVE CODE 481.219
 REQUIRES THE ARCHITECTURAL FIRM TO HAVE
 THEIR CERTIFICATE OF AUTHORIZATION
 NUMBER IN TITLEBLOCK.
 2C) 471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING
 ENGINEERING SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
  
 BUILDING PLANS APPEAR TO BE CODE
 COMPLIANT!!!
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-01-19 Cont ID  
Sent By jwitmer Date 2006-01-19 Time 08:59 Rev Time 0.77
Received By jwitmer Date 2006-01-19 Time 08:59 Sent To PC
Notes
2006-01-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05100635
 ADD: 1661 WORTHINGTON RD
 CONT: "PLAN REVIEW"
 TEL: (954)689-6905
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1) 106.1.2 ADDITIONAL DATA. THE BUILDING
 OFFICIAL MAY REQUIRE ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 ASSEMBLED INTO PERMIT READY SETS OF
 PLANS. PLANS ARE LOOSE AND UNORGANIZED.
  
 2)SEE THE VARIOUS REVIEWERS COMMENTS ON:
 2A) ORIGINAL PLANS STILL HAVE RUBBER
 STAMP SEAL, NOT THE REQUIRED RAISED
 EMBOSSED SEAL.
 2B) FL ADMINISTRATIVE CODE 481.219
 REQUIRES THE ARCHITECTURAL FIRM TO HAVE
 THEIR CERTIFICATE OF AUTHORIZATION
 NUMBER IN TITLEBLOCK.
  
 3)COMMENT# 3 FROM THE PREVIOUS REVIEW
 DELT WITH NO INFORMATION ON THE KITHEN
 CABINETS AND SINK.
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-21 Cont ID  
Sent By jwitmer Date 2005-11-21 Time 13:20 Rev Time 2.22
Received By jwitmer Date 2005-11-21 Time 13:20 Sent To  
Notes
2005-11-21 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05100635
 ADD: 1661 WORTHINGTON RD
 CONT: "PLAN REVIEW"
 TEL: (954)689-6905
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS DO NOT INDICATE AS TO WHAT CODE
 THEY WERE DESIGNED TOO?SEE 110.2
 INFORMATION REQUIRED FOR CERTIFICATE OF
 OCCUPANCY, SEE 12 ITEMS THAT WILL BE
 REQUIRED FOR PERMIT ISSUANCE AND C.O.
  
 2)SHEET A-200 FLOOR PLAN HAS VARIOUS
 DOORS THAT DOESN'T COMPLY WITH THE
 MANEUVERING CLEARENCES AT DOORWAYS.
 SEE THE REQUIRED 18" AT THE LATCH ON THE
 PULL SIDE OF THE DOOR.
 11-4.13.6 MANEUVERING CLEARANCES AT
 DOORS. MINIMUM MANEUVERING
 CLEARANCES AT DOORS THAT ARE NOT
 AUTOMATIC OR POWER-ASSISTED SHALL BE AS
 SHOWN IN FIGURE 11-25.THE FLOOR OR
 GROUND AREA WITHIN THE REQUIRED
 CLEARANCES SHALL BE LEVEL AND CLEAR.
 DOORS 106, 107,108,KITCHEN CLOSET DOOR
 109, 114B, 115 & 119.
  
 3) KITCHEN(109) PROVIDE ELEVATIONS OF
 COUNTER W/ SINK, COMPLY WITH:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
 4)PROVIDE THE MINIMUM INTERIOR FINISH
 CLASSIFICATION.TABLE 803.5
 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASED ON INTERIOR
 FINISH REQUIREMENTS BASED ON OCCUPANCY.
  
 5) FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,VARIOUS
 SHEETS INDICATE DIFFERENT TYPES OF
 STRUCTURAL COMPONENTS ABOVE THE FINISH
 CEILING A003 INDICATES DECK WITH NO TYPE
 DECLARED, A9.10 INDICATES A CONCRETE
 DECK AND P2.01 INDICATES BAR JOIST.
 SHEET A-400 INDICATES VARIOUS DROPPED
 DRYWALL CEILINGS BUT NO MENTION AS TO
 TYPE OF DECK ABOVE, TYPE OF FASTENER,
 SPACING OF FRAMING, TYPE OF FRAMING,
 IF STIFF BACKS ARE REQUIRED NOR THE
 THICKNESSS OF DRYWALL?
  
 6)A006 WALL FINISH SCHEDULE DOESN'T
 INDICATE EALL FINISH IN RESTROOMS, SEE
 REQUIREMENTS 1210.2 FOR A SMOOTH,HARD
 AND NONABSORBANT SURFACE TO A HEIGHT OF
 4'-0" AT WATERCLOSETS & URINALS.
  
 7) CORRECT ENERGY FORM TO THE FORM 400A
 2004 EDITION.
  
 8) LETTER OF AUTHORIZATION FROM BANK
 INDICATES EXTERIOR MODIFICATIONS?
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2006-11-13 Cont ID  
Sent By dpalmer Date 2006-11-13 Time 11:59 Rev Time 0.00
Received By dpalmer Date 2006-11-13 Time 11:41 Sent To PC
Notes
2006-11-13 12:00:52*** REV #9,,,
  
  
  
 STILL REDLINED TRANSFORMER LOCATION AS PLANS ONLY
 MENTION TO BE MOUNTED ABOVE PANEL. THIS SIZE OF
 TRANSFORMER MUST NOT BE ABOVE CEILING. 450.13B.
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-09-22 Cont ID  
Sent By dpalmer Date 2006-09-22 Time 19:32 Rev Time 0.00
Received By dpalmer Date 2006-09-22 Time 19:18 Sent To PC
Notes
2006-09-22 00:00:00REV, LOCATIONS AND SOME CIRCUITING.
 REDLINED TRANSFORMER TO BE SURE IT IS
 NOT ABOVE CEILING PER 450.13

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-08-11 Cont ID  
Sent By dpalmer Date 2006-08-11 Time 20:32 Rev Time 0.00
Received By dpalmer Date 2006-08-11 Time 20:02 Sent To M
Notes
2006-08-11 00:00:00ELECTRICAL STAMPED.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-07-27 Cont ID  
Sent By dpalmer Date 2006-07-27 Time 18:21 Rev Time 0.00
Received By dpalmer Date 2006-07-27 Time 17:19 Sent To  
Notes
2006-07-27 00:00:00***UNSAT ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW.
  
 ** PLEASE KNOW ANY "EARLY WORK RELEASE"
 GRANTED BY THE BUILDING OFFICAL WAS AT
 CONTRACTOR'S OWN RISK.
  
  
 1 NOTE: PLEASE SEE REQUIREMENTS FOR
 FBC CHAPTER 13 ARE REQUIRED TO BE MET
 FOR ALL LIGHTING.
 13-415.1.ABC.1.1, 13-415.1.ABC.1.2 ETC
 PLEASE SEE THE OVER RIDE SWITCHES
 MUST STATE A MAXIMUM OF 4HRS AND A MAX
 OF 30 MINS FOR MOTION SENSORS FOR
 DEVICES AND LOCATIONS.
 PLEASE SEE WORST CASE VD COULD NOT BE
 LOCATED FOR ANY ONE BRANCH CIRCUIT. OR
 FEEDER? 13-413
 PLEASE KNOW, A "SWITCH" IS NOT A DEVICE
 FOR CONTROL. IT MUST BE PART OF THE
 SYSTEM AND SHALL HAVE LIMITS TO TIME
 ETC. PLEASE BE SURE TO LIST THE TIMES
 FOR MAX OVER RIDE.
 ** PLEASE SEE CALCS FOR 13-415.1.AB.1,
 13-415.2.ABC.1, TABLES 415.2.C.1,
 415.2.B.1.
 PLEASE SEE CALCULATIONS SUBMITTED ARE
 THE SAME ONES FROM 2/27/06 AND HAVE NOT
 BEEN REVISED TO INCLUDE LIGHITNG DESIGN
 (DESIGN WATTAGE) DESIGN MAX ALLOWANCE(
 PERMITTED LPD'S PER TABLES) ETC.,
 PLEASE ALSO SEE IT WAS NOTED ON PREVIOUS
 REVIEW FROM THE MECHANICAL REVIEWER THAT
 THE CALCULATIONS WERE SEALED
 "PHOTO-COPIES" OF SIGNED DOCUMENTS.
 PLEASE SEE FS 471.025, FBC CHAPTER 13 AS
 THESE ARE REQUIRED TO CONTAIN THE
 "ORIGINAL" SIGNATURE , DATE AND RAISED
 SEAL FOR THE DESIGNER OF RECORD. MAY NOT
 PLACE A "RAISED SEAL" OVER PHOTO-COPIED
 SIGNATURES.
  
 PLACED TWO PHONE CALLS TO CONTRACTOR ETC
 WITH RESPECT TO CALCULATIONS.
  
 2) NOTE: PLEASE COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 PLEASE SEE THAT ALL OLD/VOIDED SHEETS
 WERE LEFT IN SETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.ONCE AGAIN IF THERE ARE ANY
 QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-06-09 Cont ID  
Sent By dpalmer Date 2006-06-09 Time 17:42 Rev Time 0.00
Received By dpalmer Date 2006-06-09 Time 17:27 Sent To  
Notes
2006-06-09 00:00:00***UNSAT ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEWS AND NOTES PER NEW FBC 2004
 CHAPTER 13.
  
 ** PLEASE KNOW, EARLY WORK RELEASE WHICH
 WAS GRANTED BY THE BUILDING OFFICIAL WAS
 AT OWNER/CONTRACTORS OWN RISK.
  
  
 1) NOTE: PLEASE SEE PREVIOUS NOTE WITH
 RESPECT TONEC 645, NFPA-75.
 PLEASE SEE MEANS OF SHUTTING DOWN ALL
 ELECTRICAL, A/C SYSTEMS AND SEPARATIONS
 COULD NOT BE LOCATED ON PLANS.
 645.1-645.16 NFPA-75 PLEASE SEE ALL
 CHAPTERS
 ** PLEASE SEE THIS REVIEW COMMENT HAS
 BEEN REPEATED THREE TIMES AND A NOTICE
 TO FS 553.80(2)(B) WAS GIVEN ON THE
 PREVIOUS REVIEWS WITH RESPECT TO REPEAT
 COMMENTS THREE OR MORE TIMES. PLEASE
 KNOW AS THE FIRST TWO REVIEWS WERE "PLAN
 REVIEW"ONLY, IF THIS COMMENT IS NOT
 ADDRESSED ON THE FOLLOWING REVIEW A 4X
 PLAN REVIEW FEE WILL BE ASSESSED.
  
 21) NOTE: PLEASE SEE REQUIREMENTS FOR
 FBC CHAPTER 13 ARE REQUIRED TO BE MET
 FOR ALL LIGHTING.
 13-415.1.ABC.1.1, 13-415.1.ABC.1.2 ETC
 PLEASE CLARIFY AS SOME OF THIS IS BEING
 SHOWN, BUT UNCLEAR AS MANY LIGHTING
 CIRCUITS DO NOT INDICATE ANY CONTROL?
 PLEASE ALSO SEE THE OVER RIDE SWITCHES
 MUST STATE A MAXIMUM OF 4HRS AND A MAX
 OF 30 MINS FOR MOTION SENSORS.
 PLEASE SEE THE OVER RIDING SWITCHES
 SHALL BE LOCATED IN THE AREAS FOR
 LIGHTING WHICH CAN BE SEEN BY THE
 OCCUPANT. A NOTE ON THE PLAN MENTIONS AN
 OVER RIDE SWITCH IN THE ELECTRICAL
 CLOSET WHICH WILL NOT BE ACCEPTED.
 PLEASE SHOW LOCATIONS OF ALL OVER RIDES
 AND OCC SENSORS.
 ** PLEASE SEE A WORST CASE SCENARIO
 SHALL BE SHOWN FOR VOLTAGE DROP PER
 13-413.1.ABC.1
 **PLEASE ALSO SEE 13-415.1.ABC.1.3 FOR
 OTHER LIGHTING INSEPARATE SPACES
 /ROOMS AREAS.
 PLEASE KNOW, A "SWITCH" IS NOT A DEVICE
 FOR CONTROL. IT MUST BE PART OF THE
 SYSTEM AND SHALL HAVE LIMITS TO TIME
 ETC.
 ** PLEASE SEE CALCS FOR 13-415.1.AB.1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-02-08 Cont ID  
Sent By dpalmer Date 2006-02-08 Time 19:47 Rev Time 0.00
Received By dpalmer Date 2006-02-08 Time 19:38 Sent To I
Notes
2006-02-08 00:00:00********* UNSAT 2ND REVIEW *******
  
 1)NOTE: PLEASE SEE ALMOST ALL COMMENTS
 FROM PREVIOUS REVIEW STILL APPLY.
 PLEASE SEE IT SEEMS ONLY COMMENTS #1 AND
 #3 WERE ADDRESSED.
  
 ** PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW. PLEASE
 ALSO SEE ONE NEW NOTE WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
  
  
 ******** UNSAT *********
  
  
  
  
 1)NOTE: OK
  
  
 *************************************
 2)NOTE: PLEASE SEE MISSING LICENSE
 INFORMATION REQUIRED FOR ARCHITECTUAL
 FIRM ON TITLE BLOCKS.
 PLEASE SEEFLORIDA ADMINISTRATIVE CODE
 61G1-16.004 AND FS 481.219.
 PLEASE KNOW, THIS IS REQUIRED FOR ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 ***************************************
 3)NOTE: OK
  
  
  
  
  
 ***************************************
  
 4)NOTE: PLEASE SEE 645.2,645.10,645.15
 ETC FOR MISSING REQUIRED INFORMATION FOR
 "IT" ROOM.
 PLEASE SEE ELECTRICAL REQUIREMENTS PER
 NFPA-70 AND NFPA-75
  
 PLEASEALSO SEEMISSING FIRE RATING OF
 RM, FIRE/SMOKE DAMPERS ETC REQUIRED.
  
 5)NOTE: PLEASE SEE PLANS INCLUDING
 A-SHEETS REFERENCE A 2004 ELECTRICAL
 CODE.
 PLEASE SEE AS OF JULY 1ST,2003 WE ARE
 UNDER THE 2002 NEC.
 **NOTE, THE NEXT ELECTRICAL CODE WILL BE
 THE 2005 NOT YET ADOPTED BY THE STATE.
  
 6)NOTE: PLEASE PROVIDE LOAD CALCULATIONS
 FOR NEW ADDED LOADS TO EXISTING SERVICE.
 NONE SUBMITTED.
 220,220.3,220.10,220.11,220.13, ETC
 CONTINUOUS LOADS 215.3, 230.42
  
 7)NOTE: PLEASE SEE 210.8B3 FOR KITCHENS
 IN OTHER THAN DWELLING UNITS.
  
 ***************************************
 NEW NOTE:
  
 1)NOTE: PLEASE SEE COPY OF FLORIDA
 STATUES 553.80(2)(3) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS
 THREE OR MORE TIMES. PLEASE BE SURE ALL
 COMMENTS ARE ADDRESSED.
  
  
 2)NOTE: PLEASE COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING.
 PLEASE BE SURE TO SUBMIT ONE COPY OF
 OLD/VOIDED SHEETS FOR REFERENCE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-01-03 Cont ID  
Sent By dpalmer Date 2006-01-03 Time 08:15 Rev Time 0.00
Received By dpalmer Date 2006-01-03 Time 07:48 Sent To  
Notes
2006-01-03 00:00:00******** UNSAT *********
  
  
 ** PLANS ONLY SUBMITTED FOR "PLAN
 REVIEW" AND NOT FOR PERMIT.
  
 1)NOTE: PLEASE SUBMIT COMPLETE ATTACHED
 SETS FOR REVIEW AND STAMPING.
 PLEASE SEE EACH SET CONTAINS ALL LOSE
 SHEETS AND NOTHING IS ATTACHED.
 PLEASE REMOVE ALL OLD/VOIDED SHEETS FROM
 SETS AND ONLY INSERT NEW REVISED SHEETS
 INTO COMPLETED SETS.
 ONE SET OF OLD/VOIDED SHEETS SHOULD BE
 SEPARATE FOR REFERENCE.
  
  
 *************************************
 2)NOTE: PLEASE SEE MISSING LICENSE
 INFORMATION REQUIRED FOR ARCHITECTUAL
 FIRM ON TITLE BLOCKS.
 PLEASE SEEFLORIDA ADMINISTRATIVE CODE
 61G1-16.004 AND FS 481.219.
 PLEASE KNOW, THIS IS REQUIRED FOR ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 ***************************************
 3)NOTE: PLEASE SEE MANY ARCHITECTUAL
 SHEETS CONTAIN A "RUBBER STAMP" FOR THE
 ARCHITECT'S REQUIRED "RAISED/IMPRESSION"
 TYPE SEAL.
 PLEASE SEE FS 481.221
 THIS IS REQUIRED OF ALL SHEETS. PLEASE
 SEE SOME SHEETS DO CONTAIN THE REQUIRED
 "RAISED SEAL".
 ***************************************
  
 4)NOTE: PLEASE SEE 645.2,645.10,645.15
 ETC FOR MISSING REQUIRED INFORMATION FOR
 "IT" ROOM.
 PLEASE SEE ELECTRICAL REQUIREMENTS PER
 NFPA-70 AND NFPA-75
  
 PLEASEALSO SEEMISSING FIRE RATING OF
 RM, FIRE/SMOKE DAMPERS ETC REQUIRED.
  
 5)NOTE: PLEASE SEE PLANS INCLUDING
 A-SHEETS REFERENCE A 2004 ELECTRICAL
 CODE.
 PLEASE SEE AS OF JULY 1ST,2003 WE ARE
 UNDER THE 2002 NEC.
 **NOTE, THE NEXT ELECTRICAL CODE WILL BE
 THE 2005 NOT YET ADOPTED BY THE STATE.
  
 6)NOTE: PLEASE PROVIDE LOAD CALCULATIONS
 FOR NEW ADDED LOADS TO EXISTING SERVICE.
 NONE SUBMITTED.
 220,220.3,220.10,220.11,220.13, ETC
 CONTINUOUS LOADS 215.3, 230.42
  
 7)NOTE: PLEASE SEE 210.8B3 FOR KITCHENS
 IN OTHER THAN DWELLING UNITS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-11-14 Cont ID  
Sent By jleahy Date 2005-11-14 Time 20:24 Rev Time 1.30
Received By jleahy Date 2005-11-14 Time 20:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-06-21 Cont ID  
Sent By mwennerg Date 2006-06-21 Time 11:10 Rev Time 0.00
Received By mwennerg Date 2006-06-21 Time 11:10 Sent To  
Notes
2006-06-21 00:00:00***APPROVED***
  
 PLEASE SHOW LOCATION OF FACP WHEN
 SUBMITTING FOR FIRE ALARM PERMIT. SMOKE
 DETECTOR IS REQUIRED IN AREA OF PANEL.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2005-12-30 Cont ID  
Sent By nmccray Date 2005-12-30 Time 10:00 Rev Time 0.00
Received By nmccray Date 2005-12-30 Time 09:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-11-16 Cont ID  
Sent By mwennerg Date 2005-11-16 Time 14:03 Rev Time 0.00
Received By mwennerg Date 2005-11-16 Time 14:03 Sent To  
Notes
2005-11-16 00:00:00******DENIED******
  
 1) EACH SHEET OF THE DRAWINGS ARE TO BE
 SIGNED, DATED AND SEALED IN ACCORDANCE
 WITH FS REQUIREMENTS.
  
 2) LIFE SAFETY TO COMPLY WITH NFPA-101,
 AND NFPA-1, 2003 EDITIONS.
  
 3) PLEASE INDICATE THE INTERIOR FINISH
 CLASSIFICATION OF WALLS AND CEILING IN
 TERMS OF CLASS A, B OR C.
  
 4) IN ACCORDANCE WITH LOCAL
 REQUIREMENTS, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM, NOT
 SUPERVISORY SIGNAL WHEN ACTIVATED.
  
 5) IN ADDITION TO THE FIRE SPRINKLER
 SYSTEM, SEPARATE SHOP DRAWINGS AND
 PERMITS ARE REQUIRED FOR FIRE ALARM
 REMODEL.
  
 6) PLEASE NOTE THE LOCATIONS OF REQUIRED
 2A-10B,C RATED FIRE EXTINGUISHERS, THAT
 SHALL NOT EXCEED 75' TRAVEL DISTANCE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-11-07 Cont ID  
Sent By adarroug Date 2006-11-07 Time 15:46 Rev Time 0.00
Received By adarroug Date 2006-11-07 Time 15:46 Sent To E
Notes
2006-11-07 15:47:02TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-09-18 Cont ID  
Sent By adarroug Date 2006-09-18 Time 11:37 Rev Time 0.00
Received By adarroug Date 2006-09-18 Time 11:37 Sent To E
Notes
2006-09-18 00:00:00TO "DPALMER' DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-09-18 Cont ID  
Sent By adarroug Date 2006-09-18 Time 11:20 Rev Time 0.00
Received By adarroug Date 2006-09-18 Time 11:20 Sent To P
Notes
2006-09-18 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-09-12 Cont ID  
Sent By adarroug Date 2006-09-12 Time 08:46 Rev Time 0.00
Received By adarroug Date 2006-09-12 Time 08:46 Sent To B
Notes
2006-09-12 00:00:00TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-07 Cont ID  
Sent By adarroug Date 2006-08-07 Time 16:18 Rev Time 0.00
Received By adarroug Date 2006-08-07 Time 16:18 Sent To  
Notes
2006-08-07 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-07-14 Cont ID  
Sent By adarroug Date 2006-07-14 Time 14:19 Rev Time 0.00
Received By adarroug Date 2006-07-14 Time 14:19 Sent To  
Notes
2006-07-27 00:00:00TO "COMM' BD#31
2006-07-14 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-03 Cont ID  
Sent By adarroug Date 2006-05-03 Time 08:14 Rev Time 0.00
Received By adarroug Date 2006-05-03 Time 08:14 Sent To  
Notes
2006-06-02 00:00:00TO "COMM" BD#60
2006-05-03 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-01-26 Cont ID  
Sent By adarroug Date 2006-01-26 Time 16:06 Rev Time 0.00
Received By adarroug Date 2006-01-26 Time 16:06 Sent To  
Notes
2006-02-22 00:00:00TO "COMM" BD#31
2006-01-26 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-28 Cont ID  
Sent By adarroug Date 2005-12-28 Time 16:36 Rev Time 0.00
Received By adarroug Date 2005-12-28 Time 16:36 Sent To  
Notes
2005-12-28 00:00:00TO "BOB"#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-06 Cont ID  
Sent By pkrauss Date 2005-11-22 Time 13:41 Rev Time 0.00
Received By pkrauss Date 2005-10-18 Time 09:59 Sent To  
Notes
2005-11-14 00:00:00TO "BOB"#2
2005-10-18 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2006-08-16 Cont ID  
Sent By pkrauss Date 2006-08-16 Time 14:15 Rev Time 0.00
Received By pkrauss Date 2006-08-16 Time 14:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2006-08-11 Cont ID  
Sent By pkrauss Date 2006-08-11 Time 14:55 Rev Time 0.00
Received By pkrauss Date 2006-08-11 Time 14:48 Sent To  
Notes
2006-08-11 00:00:00CALLED ENGINEER (BOB FORMICA),
 ARCHITECTURAL PLANS WERE REVISED TO
 WHICH NOW THE MECHANICAL PLANS ARE NO
 LONGER CODE COMPLIANT.DUCTS
 PENETRATING FIRE RATED WALLS OR
 PARTITIONS SHALL BE PROTECTED BY FIRE
 DAMPERS 2004 FMC 607.5.3.
  
 FLEX DUCTS ARE NOT PERMITTED TO
 PENETRATE RATED WALLS OR PARTITIONS PER
 2004 FMC 607.7
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2006-08-04 Cont ID  
Sent By tgordon Date 2006-08-04 Time 11:09 Rev Time 0.15
Received By tgordon Date 2006-08-04 Time 11:09 Sent To  
Notes
2006-08-04 00:00:00*** DENIED ***
 1) SEE LAST MECHANICAL REVIEW (COPY).
 MECHANICAL PLANS NOT REVIEWED AT THIS
 TIME.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2006-06-21 Cont ID  
Sent By pkrauss Date 2006-06-21 Time 12:38 Rev Time 0.00
Received By pkrauss Date 2006-06-21 Time 12:37 Sent To  
Notes
2006-06-21 00:00:00DENIED:
  
 THE ENERGY CALCULATIONS SUBMITTED ARE
 COPIES.PLEASE SUBMIT ORIGIANL
 SIGNATURE, DATE ON THE EMBOSSED DEALED
 AS REQUIRED PER FS 471.025 & FAC
 61G15-23.002.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-02-27 Cont ID  
Sent By pkrauss Date 2006-02-27 Time 07:55 Rev Time 0.00
Received By pkrauss Date 2006-02-27 Time 07:55 Sent To  
Notes
2006-02-27 00:00:00DENIED:
 2ND REQUEST
 COMMENT #2 BY TOM GORDON (1-3-06), WAS
 NOT ADDRESSED; PLEASE PROVIDE ENERGY
 CALCULATIONS PER 2004 FBC CHAPTER 13
 SUB-CHAPTER 4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-01-03 Cont ID  
Sent By tgordon Date 2006-01-03 Time 16:43 Rev Time 0.30
Received By tgordon Date 2006-01-03 Time 16:43 Sent To  
Notes
2006-01-03 00:00:00*** DENIED ***
 1) ARCTITECTUAL LICENSE NUMBER MISSING
 FROM TITLE BLOCK. SEE ELECT. NOTE #2.
  
 2) ENERGY CAL'S NEEDED FOR PROPER
 MECHANICAL REVIEW.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-11-21 Cont ID  
Sent By rregueir Date 2005-11-21 Time 17:33 Rev Time 1.50
Received By rregueir Date 2005-11-21 Time 16:18 Sent To PC
Notes
2005-11-21 00:00:00----------------PROVISO-----------------
  
 1.NO ROOF PLAN PROVIDED. ENSURE THAT
 THERE
 ARE NO PLUMBING VENTS OR EXHAUST OUTLETS
 WITHIN 10 FEET OF RTU OUTSIDE AIR
 INTAKES.
  
 2.MECHANICAL PLAN SHOWS EF 2 (SEE FAN
 SCHEDULE) IN GANG BATHROOMS AND EF 1 IN
 CLOSET.ELECTRICAL PLAN CALLS FOR THE
 REVERSE.EF 2 IS THE CORRECT FAN FOR
 THE GANG BATHROOMS.
  
 ANY QUESTIONS PLEASE CALL RONALD J
 REGUEIRO AT 561-805-6734 OR
 [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2006-10-14 Cont ID  
Sent By jleech Date 2006-10-14 Time 06:32 Rev Time 0.00
Received By jleech Date 2006-10-14 Time 06:32 Sent To  
Notes
2006-10-14 06:35:04REVISION;
 CHANGED WATER HEATERAND DRYWELL LOCATIONS.

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-06-22 Cont ID  
Sent By jleech Date 2006-06-22 Time 15:19 Rev Time 0.00
Received By jleech Date 2006-06-22 Time 15:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-03-16 Cont ID  
Sent By jleech Date 2006-03-16 Time 10:53 Rev Time 1.00
Received By jleech Date 2006-03-16 Time 10:53 Sent To  
Notes
2006-03-16 00:00:00DENIED;
 1. PLEASE SEE MISSING LICENSE
 INFORMATION REQUIRED FOR ARCHITECTUAL
 FIRM ON TITAL BLOCK.
 2.PAGE A-942 ELEVATION M-15 DOES NOT
 COMPLY WITH FBC-2004 CHAPTER 11 SEC'S
 11-4.23.3 KNEE CLEARANCE AND 11-4.24.7,
 PLEASE SHOW FAUCET HANDLES OR ADD NOTE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-01-03 Cont ID  
Sent By jleech Date 2006-01-03 Time 12:13 Rev Time 1.00
Received By jleech Date 2006-01-03 Time 12:13 Sent To  
Notes
2006-01-03 00:00:00DENIED;
 BREAK SINK DETAIL DOES NOT MEET FBC-2004
 CHAPTER 11 HANDICAP CODE. SEC. 11-4.24.1
 THRU 11-4.24.7. KICK PLAT AND DOORS
 CANNOT BE INSTALLED AS SHOWN AND MEET
 SEC.11-4.24.3 (KNEE CLEARANCE) FOR A
 FORWARD APPROACH.
 PLEASE SHOW DETAIL OF HANDICAP DRINKING
 FOUNTAIN. SEE FIGURE 27.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-11-17 Cont ID  
Sent By   Date 2005-11-17 Time   Rev Time 0.00
Received By pschmitz Date 2005-11-17 Time 14:05 Sent To  
Notes
2005-11-17 00:00:00PAUL SCHMITZ
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 DENIED
 1)SHT P1.01 A/C CONDENSATE DISPOSAL:
 OPTIONS RTU TO ROOF DRAINS.
 IF BELOW ROOF TERMINATE TO STORM
 OUTSIDE OF BUILDING,
 PLANTER OR DRY WELL.
 2)SHT P2.01 DETAIL WATER HEATER:
 SEC 607.3 PROVIDE INFORMATION FOR
 THERMAL EXPASNSION CONTROL.
 3)SHT P2.01 WATER RISER:
 EXPLAIN ABBREVIATION WATTS BRVT.
 SHOW ON PLUMBING LEGEND.
 4) SEC 403 MINIMUM REQUIRED NUMBER OF
 PLUMBING FIXTURES.
 PLUMBING FIXTURES SHALL BE PROVIDEDFOR
 THE TYPE OF OCCUPANCY AND THE MINIMUM
 NUMBER SHOWN IN TABLE 403.1
 SEC 410 DRINKING FOUNTAINS.1-PER 100
 END OF COMMENTS QUESTIONS 561-805-6692

Review Stop Z ZONING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-03-14 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***