| 2005-11-08 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05100515 |
| | ADD: 501 S FLAGLER DR |
| | CONT: "PLAN REVIEW" |
| | TEL: (781)727-8632 |
| | FL BLD CODE= 2004FLORIDA BUILDING CODE * |
| | WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1A)PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 1B) MISSING UNIT OR SUITE ON THE PERMIT |
| | APP,& PLANS. |
| | |
| | 2A)SHEET A1.0 CODE INFORMATION INDICATES |
| | THAT THE PLANS WERE DESIGNED TO THE |
| | 2001 FL BLDG CODE, CORRECT TO 2004. |
| | UNDER 2004 FL BLDG CODE EXISTING BLDGS, |
| | INDICATE TO WHAT LEVEL OF ALTERATIONS |
| | THE DESIGN TEAM HAS DESIGNED TOO.SEE |
| | SECTIONS 303, 304 & 305. |
| | |
| | 2B) ACCESSIBILITY REQUIREMENTS INDICATE |
| | COMPLIANCE WITH THE FEDERAL ADA, FLORIDA |
| | |
| | ACCESSIBILITY CODE IS MORE STRINGENT AND |
| | |
| | RECONIZED YOUR DESIGN PERAMETERS SHOULD |
| | BE THE 2004 FLORIDA CODE CHAPTER 11, |
| | ACCESSIBILITY. |
| | |
| | 2C) SCOPE OF WORK SEE 2004 TABLE 503 FOR |
| | THE TYPE OF BUILDING. |
| | |
| | |
| | 3) A2.0 INDICATES 2 CLOSET DOORS THAT DO |
| | NOT MEET THE REQUIREMENTS OF 1005.2 DOOR |
| | |
| | ENCROACHMENT. |
| | |
| | 4A)PLANS DO NOT INDICATE TYPE OF ROOMS |
| | OR DOORS, PLANS MARKED IN RED WHERE THE |
| | REQUIRED 18" ON THE PULL SIDE OF DOOR. |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | 4B)11-4.1.6(2) DUTY TO PROVIDE AN |
| | ACCESSIBLE PATH OF TRAVEL TO ALTERED |
| | AREAS SHALL BE DEEMED DISPROPORTIONATE |
| | TO THE OVERALL ALTERATION WHEN THE COST |
| | EXCEEDS 20 % OF THE COST OF THE ALTERA- |
| | TION TO THE PRIMARY FUNCTION AREA. |
| | (A)(I) AN ACCESSIBLE ENTRANCE |
| | (II) AN ACCESSIBLE ROUTE |
| | (III) AT LEAST ONE ACCESSIBLE REST- |
| | ROOM FOR EACH SEX OR A SINGLE |
| | UNISEX RESTROOM |
| | (IIII) ACCESSIBLE TELEPHONE |
| | (IV) ELEMENTS SUCH AS PARKING, STOR- |
| | AGE OR ALARMS. |
| | |
| | 5) PLANS DO NOT INDICATE IF THE NEW |
| | WALLS ARE TO BE GLAZED DOORS, THE SIDE- |
| | LIGHTS WILL REQIURE SAFETY GLAZING SEE |
| | 2406.3 HAZARDOUS LOCATION. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |