Plan Review Details - Permit 05100515
Plan Review Stops For Permit 05100515
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-12-14 Cont ID  
Sent By jwitmer Date 2005-12-14 Time 08:04 Rev Time 0.56
Received By jwitmer Date 2005-12-14 Time 06:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-08 Cont ID  
Sent By jwitmer Date 2005-11-08 Time 13:05 Rev Time 1.55
Received By jwitmer Date 2005-11-08 Time 13:05 Sent To  
Notes
2005-11-08 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05100515
 ADD: 501 S FLAGLER DR
 CONT: "PLAN REVIEW"
 TEL: (781)727-8632
 FL BLD CODE= 2004FLORIDA BUILDING CODE *
 WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A)PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 1B) MISSING UNIT OR SUITE ON THE PERMIT
 APP,& PLANS.
  
 2A)SHEET A1.0 CODE INFORMATION INDICATES
 THAT THE PLANS WERE DESIGNED TO THE
 2001 FL BLDG CODE, CORRECT TO 2004.
 UNDER 2004 FL BLDG CODE EXISTING BLDGS,
 INDICATE TO WHAT LEVEL OF ALTERATIONS
 THE DESIGN TEAM HAS DESIGNED TOO.SEE
 SECTIONS 303, 304 & 305.
  
 2B) ACCESSIBILITY REQUIREMENTS INDICATE
 COMPLIANCE WITH THE FEDERAL ADA, FLORIDA
  
 ACCESSIBILITY CODE IS MORE STRINGENT AND
  
 RECONIZED YOUR DESIGN PERAMETERS SHOULD
 BE THE 2004 FLORIDA CODE CHAPTER 11,
 ACCESSIBILITY.
  
 2C) SCOPE OF WORK SEE 2004 TABLE 503 FOR
 THE TYPE OF BUILDING.
  
  
 3) A2.0 INDICATES 2 CLOSET DOORS THAT DO
 NOT MEET THE REQUIREMENTS OF 1005.2 DOOR
  
 ENCROACHMENT.
  
 4A)PLANS DO NOT INDICATE TYPE OF ROOMS
 OR DOORS, PLANS MARKED IN RED WHERE THE
 REQUIRED 18" ON THE PULL SIDE OF DOOR.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 4B)11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
 5) PLANS DO NOT INDICATE IF THE NEW
 WALLS ARE TO BE GLAZED DOORS, THE SIDE-
 LIGHTS WILL REQIURE SAFETY GLAZING SEE
 2406.3 HAZARDOUS LOCATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-10-21 Cont ID  
Sent By dpalmer Date 2005-10-21 Time 09:57 Rev Time 0.30
Received By dpalmer Date 2005-10-20 Time 17:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-11-09 Cont ID  
Sent By mwennerg Date 2005-11-09 Time 10:06 Rev Time 0.00
Received By jwitmer Date 2005-12-14 Time 06:54 Sent To  
Notes
2005-11-09 00:00:00******PLAN REVIEW ONLY******

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-06 Cont ID  
Sent By adarroug Date 2005-12-06 Time 12:29 Rev Time 0.00
Received By adarroug Date 2005-12-06 Time 12:29 Sent To  
Notes
2005-12-06 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-14 Cont ID  
Sent By adarroug Date 2005-10-14 Time 18:03 Rev Time 0.00
Received By adarroug Date 2005-10-14 Time 18:03 Sent To  
Notes
2005-10-14 00:00:00TO "BOB"#2

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-10-18 Cont ID  
Sent By hmoser Date 2005-10-18 Time 10:28 Rev Time 0.00
Received By hmoser Date 2005-10-18 Time 10:13 Sent To  
Notes
2005-10-18 00:00:0010/18/05 NO MECHANICAL PLANS HM.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-10-15 Cont ID  
Sent By jleech Date 2005-10-15 Time 07:58 Rev Time 0.33
Received By jleech Date 2005-10-15 Time 07:58 Sent To  
Notes
***NONE***