| 2005-11-07 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05100475 |
| | ADD: 325 CLEMATIS ST. SUITE A |
| | CONT: DENNIS PETERSON |
| | TEL: (561)622-8290 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) FL BLD CODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | THE SYMBOLS FOR NEW WALLS IS NOT USED |
| | ON SHEET A04 OR A05. IT IS DIFFICULT TO |
| | TELL WHAT WILL BE EXISTING AND WHAT IS |
| | NEW? |
| | |
| | 2) THE DOOR TO THE REAR STAIRWWELL |
| | APPEARS TO ALSO HAVE BEEN MOVED WITHOUT |
| | SYMBOLS INDICATING SUCH. SEE A01 VS A05. |
| | IN ITHER CASE THE DEFINITION OF EXIT: |
| | EXIT. THAT PORTION OF THE MEANS OF |
| | EGRESS WHICH IS SEPARATED FROM ALL |
| | OTHER SPACES OF A BUILDING OR STRUCTURE |
| | BY CONSTRUCTION AND OPENING |
| | PROTECTIVES, AS REQUIRED FOR EXITS, TO |
| | PROVIDE A PROTECTED WAY OF TRAVEL |
| | TO THE EXIT DISCHARGE. EXITS INCLUDE |
| | EXTERIOR EXIT DOORS, SEPARATED EXIT |
| | STAIRS, EXIT PASSAGEWAYS AND HORIZONTAL |
| | EXITS. |
| | THE BREAK ROOM SHOULD NOT HAVE A DOOR |
| | DIRECTLY INTO THE EXIT. NOR SHOULD THE |
| | MENS RESTROOM HAVE A DOOR DIRECTLY IN |
| | THE EXIT.ALSO SEE 1006.1.1. |
| | |
| | 3) THE CORRIDOR TO THE BREAK ROOM IS TO |
| | NARROW, A MINIMUM OF 36" SHALL BE |
| | REQUIRED, SEE TABLE 1004 FOOTNOTE 10. |
| | |
| | 4) THE PLANS DO NOT INDICATE WORK IN THE |
| | COMMON AREAS BUT TO CORRECT THE DOORWAYS |
| | INTO THE STAIRWELL THIS ENVOKES THE |
| | 11-4.1.6 ACCESSIBLE BUILDINGS |
| | ALTERATIONS,EGRESS IN THE COMMON AREAS |
| | UNDER ALTERATIONS. INDICATE WHERE THE |
| | REQUIRED (2) AREA OF RESCUE ASSISTANCE |
| | SHALL BE PROVIDE 11-4.1.3(9). SEE |
| | 11-4.3.11 FOR LOCATION & CONSTRUCTION. |
| | |
| | 5)FL BLDCODE 104.2.1.2 |
| | ADDITIONAL INFORMATION REQUIRED, |
| | PLANAS DO NOT PROVIDE AN ELEVATION OF |
| | THE BREAKROOM SINK SEE: |
| | 11-4.24.2 HEIGHT. SINKS SHALL BE MOUNTED |
| | WITH THE COUNTER OR RIM NO HIGHER THAN |
| | 34 IN. (865 MM) ABOVE THE FINISH FLOOR. |
| | |
| | 11-4.24.3 KNEE CLEARANCE. KNEE |
| | CLEARANCE THAT IS AT LEAST 27 IN. (685 |
| | MM) HIGH, 30 IN. (760 MM) WIDE, AND 19 |
| | IN (485 MM) DEEP SHALL BE |
| | PROVIDED UNDERNEATH SINKS. |
| | |
| | 11-4.24.4 DEPTH. EACH SINK SHALL BE A |
| | MAXIMUM OF 6-1/2 IN (165 MM) |
| | DEEP. |
| | |
| | 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR |
| | FLOOR SPACE AT LEAST 30 IN. BY 48 |
| | IN. (760 MM BY 1220 MM) COMPLYING WITH |
| | 11-4.2.4 SHALL BE PROVIDED IN |
| | FRONT OF A SINK TO ALLOW FORWARD |
| | APPROACH.THE CLEAR FLOOR SPACE SHALL |
| | BE ON AN ACCESSIBLE ROUTE AND SHALL |
| | EXTEND A MAXIMUM OF 19 IN. (485 MM) |
| | UNDERNEATH THE SINK (SEE FIGURE |
| | 11-32). |
| | |
| | 11-4.24.6 EXPOSED PIPES AND SURFACES. |
| | HOT WATER AND DRAIN PIPES EXPOSED |
| | UNDER SINKS SHALL BE INSULATED OR |
| | OTHERWISE CONFIGURED SO AS TO PROTECT |
| | AGAINST CONTACT.THERE SHALL BE NO |
| | SHARP OR ABRASIVE SURFACES UNDER |
| | SINKS. |
| | |
| | 11-4.24.7 FAUCETS. FAUCETS SHALL |
| | COMPLY WITH ?11-4.27.4.LEVER- |
| | OPERATED, PUSH-TYPE, TOUCH-TYPE, OR |
| | ELECTRONICALLY CONTROLLED MECHANISMS |
| | ARE ACCEPTABLE DESIGNS. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |