Plan Review Details - Permit 05100469
Plan Review Stops For Permit 05100469
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-01-18 Cont ID  
Sent By alange Date 2006-01-18 Time 16:26 Rev Time 0.75
Received By alange Date 2006-01-11 Time 14:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-14 Cont ID  
Sent By adarroug Date 2005-12-19 Time 10:53 Rev Time 0.50
Received By alange Date 2005-12-14 Time 09:32 Sent To  
Notes
2005-12-14 00:00:00DENIED
  
 1.PLANS SUBMITTED AFTER OCTOBER 1,
 2005 SHALL BE DESIGNED TO THE 2004 FBC
 AND THE 2004 EXISTING BUILDING CODE.
  
 2.PERMIT VALUATION IS TOO LOW.ADJUST
 PERMIT VALUE TO REFLECT ALL MATERIALS
 AND LABOR OR I WILL ADJUST IT ACCORDING
 TO MARSHALL AND SWIFT ESTIMATING GUIDE.
  
 3.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR EXTERIOR DOORS AND
 WINDOWS.ALL PRODUCT APPROVALS
 SUBMITTED SHALL HAVE THE FOLLOWING STATE
 PRODUCT APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-07-18 Cont ID  
Sent By btrobaug Date 2006-07-18 Time 06:40 Rev Time 0.50
Received By btrobaug Date 2006-07-18 Time 06:36 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-11-10 Cont ID  
Sent By btrobaug Date 2005-11-10 Time 16:38 Rev Time 0.50
Received By btrobaug Date 2005-11-10 Time 16:17 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-10 Cont ID  
Sent By adarroug Date 2006-07-10 Time 15:04 Rev Time 0.00
Received By adarroug Date 2006-07-10 Time 15:04 Sent To E
Notes
2006-07-10 00:00:00TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-05 Cont ID  
Sent By adarroug Date 2006-01-05 Time 08:14 Rev Time 0.00
Received By adarroug Date 2006-01-05 Time 08:14 Sent To B
Notes
2006-01-05 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-14 Cont ID  
Sent By adarroug Date 2005-10-14 Time 16:45 Rev Time 0.00
Received By adarroug Date 2005-10-14 Time 16:45 Sent To E
Notes
2005-10-14 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-12-06 Cont ID  
Sent By tgordon Date 2005-12-06 Time 15:28 Rev Time 0.15
Received By tgordon Date 2005-12-06 Time 15:28 Sent To B
Notes
2005-12-06 00:00:00NO MECH. PLANS OR MECH. CONTRACTOR
 SUBMITTED AT THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-01-13 Cont ID  
Sent By jleech Date 2006-01-13 Time 07:41 Rev Time 0.25
Received By jleech Date 2006-01-13 Time 07:41 Sent To B
Notes
2006-01-13 00:00:00RE-STAMP

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-12-06 Cont ID  
Sent By jleech Date 2005-12-06 Time 14:15 Rev Time 0.33
Received By jleech Date 2005-12-06 Time 14:15 Sent To M
Notes
2005-12-06 00:00:00PROVISO;
 SHOWER TRAP TO BE 2" OR 2 SEALED LETTERS
 FROM ENGIEER REFURING TO LOW FLOW SHOWER
 HEAD.