| 2005-11-29 00:00:00 | DENIED |
| | |
| | 1) THE ORIGINAL WET SIGNATURE OF THE |
| | TRUSS ENGINEER IS REQUIRED ON THE TRUSS |
| | LAYOUT AND TRUSS DRAWINGS. SEE F.A.C. |
| | 61G1-16.003 |
| | |
| | 2) THE TRUSS LAYOUT IS REQUIRED TO BE |
| | REVIEWED AND APPROVED BY THE DESIGNER OF |
| | RECORD FOR THE STRUCTURE. |
| | |
| | 3) THE PRODUCT APPROVALS REQUIRED BY |
| | RULE 9B-72 ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED BY THE DESIGNER OF RECORD |
| | FOR THE STRUCTURE BY SECTION 106.3.3 OF |
| | THE CITY AMENDMENTS TO THE 2004 FBC. |
| | |
| | 4) SUBMIT AN INSTALLATION SCHEDULE FOR |
| | THE STORM PANELS. SPECIFY THE ANCHORS |
| | THAT WILL BE USED, THE ANCHOR SPACING, |
| | THE MOUNT TYPE (SECTION # FROM PRODUCT |
| | APPROVAL) AND EDGE DISTANCE. THE PLANS |
| | SPECIFY TAPCONS WITH AN EDGE DISTANCE OF |
| | 3". THE PRODUCT APPROVAL SPECIFIES |
| | 3-1/2" EDGE DISTANCE. THE INFORMATION ON |
| | THE PLANS MUST CORRESPOND WITH THE |
| | INSTALLATION SELECTED FROM THE PRODUCT |
| | APPROVAL. |
| | |
| | 5) THE NOAS SUBMITTED FOR THE SH |
| | WINDOWS, WINDOW MULLIONS AND GAF |
| | SHINGLES HAVE BEEN UPDATED FOR THE 2004 |
| | FBC ON THE STATE WEBSITE. SUBMIT THE |
| | NOAS THAT ARE LISTED ON THE WEBSITE FOR |
| | THE PRODUCT. SEE WWW.FLORIDABUILDING.ORG |
| | |
| | 6) THE INSTALLATION INSTRUCTIONS THAT |
| | WERE SUBMITTED FOR THE THERMA-TRU DOORS |
| | ARE MIAMI-DADE NOAS AND THE EVALUATION |
| | ENTITY SUBMITTED FOR STATE APPROVAL WAS |
| | NAMI. SUBMIT THE CORRESPONDING REPORTS. |
| | SEE FL 5262 AND THE CORRESPONDING PDF |
| | FILES. |
| | |