Plan Review Details - Permit 05100339
Plan Review Stops For Permit 05100339
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-04-05 Cont ID  
Sent By alange Date 2006-04-05 Time 13:10 Rev Time 0.50
Received By alange Date 2006-04-05 Time 13:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-11-22 Cont ID  
Sent By alange Date 2005-11-22 Time 16:34 Rev Time 0.50
Received By alange Date 2005-11-22 Time 16:34 Sent To  
Notes
2005-11-22 00:00:00DENIED
  
 1. SUBMIT SPECS FOR GAS BBQ.IF IT IS
 TO BE INSTALLED UNDER A COVERED AREA
 SUBMIT SPECS FOR AN APPROVED EXHAUST
 HOOD.
  
 2.SUBMIT TWO COPIES OF ALL DOCUMENTS
 INCLUDING OWNERS MANUAL.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-04-13 Cont ID  
Sent By btrobaug Date 2006-04-13 Time 07:06 Rev Time 0.75
Received By btrobaug Date 2006-04-13 Time 06:31 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-03-29 Cont ID  
Sent By btrobaug Date 2006-03-29 Time 18:16 Rev Time 0.50
Received By btrobaug Date 2006-03-29 Time 17:33 Sent To B
Notes
2006-03-29 00:00:00 
 THE MANUAL TRANSFER SWITCH'S THIRD POLE
 DISCONNECTING THE NEUTRAL WOULD APPEAR
 TO ALSO DISCONNECT THE GROUNDING
 ELECTRODE CONDUCTOR SYSTEM. UNLESS THE
 GENERATOR NEUTRAL IS CONNECTED TO THE
 GEC IN THE OPTIONAL MODE , IT WOULD BE
 NECESSARY TO ESTABLISH A GROUNDING
 SYSTEM AT THE GENERATOR, COMPLYING WITH
 ALL PROVISIONS OF ARTICLE 250.52 AND
 250.66.
 IT WOULD BE BETTER APPLICATION TO
 INSTALL A 2POLE DISCONNECTING THE
 UNGROUNDED CONDUCTORS AND LEAVE THE
 GROUNDED CONDUCTOR SOLIDLY CONNECTED TO
 THE GEC.
  
 PLEASE SUBMIT DOCUMENTS INDICATING A 2
 POLE SWITCH OR INDICATING COMPLIANCE
 WITH 250.52 FOR A SEPERATELY DERIVED
 SYSTEM.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-11-16 Cont ID  
Sent By btrobaug Date 2005-11-16 Time 11:13 Rev Time 0.50
Received By btrobaug Date 2005-11-16 Time 07:22 Sent To M
Notes
2005-11-16 00:00:00 
 PLEASE SUBMIT GENERATOR MANUFACTURER
 SPECIFICATIONS FOR REVIEW. NOTE THAT
 2(TWO) COPIES ARE NEEDED AS WITH ALL
 DOCUMENTS SUBMITTED FOR REVIEW, PER
 104.2.1,FBC.
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT A CALCULATION FOR THE
 INTENDED LOAD OF THE GENERATOR TO BE
 TRANSFERRED TO THE 30 CKT PANEL SHOWN ON
 THE PLAN. SEE GEN SPEC'S FOR MAX AND
 USEABLE OUTPUT (PROBABLY 80%).
 THE 38.2KW TOTAL HOUSE LOAD SOBMITTED IS
 TOO LARGE FOR A 20KW GENERATOR.
  
 2} PLEASE LOCATE THE SERVICE AND
 GENERATOR ON THE SITE PLAN SO THAT
 COMPLIANCE WITH ARTICLE 225 CAN BE
 DETERMINED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  
  

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status N Date 2005-11-21 Cont ID  
Sent By jleech Date 2005-11-21 Time 18:23 Rev Time  
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-07-17 Cont ID  
Sent By mperson Date 2006-07-17 Time 14:53 Rev Time 0.45
Received By mperson Date 2006-07-17 Time 14:53 Sent To PC
Notes
2006-07-17 00:00:00REVISION: CHANGE GAS SYSTEM PRESSURE TO
 2LB SYSTEM WITH REGULATORS. REFERENCE:
 GAS PERMIT #05100341

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2005-11-21 Cont ID  
Sent By jleech Date 2005-11-21 Time 18:22 Rev Time 0.50
Received By jleech Date 2005-11-21 Time 18:22 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-11 Cont ID  
Sent By adarroug Date 2006-07-11 Time 12:12 Rev Time 0.00
Received By adarroug Date 2006-07-11 Time 12:12 Sent To P
Notes
2006-07-11 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-29 Cont ID  
Sent By adarroug Date 2006-03-29 Time 11:52 Rev Time 0.00
Received By adarroug Date 2006-03-29 Time 11:52 Sent To E
Notes
2006-03-29 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-10 Cont ID  
Sent By adarroug Date 2005-11-10 Time 15:49 Rev Time 0.00
Received By adarroug Date 2005-11-10 Time 15:49 Sent To E
Notes
2005-11-10 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-12 Cont ID  
Sent By adarroug Date 2005-10-12 Time 13:44 Rev Time 0.00
Received By adarroug Date 2005-10-12 Time 13:44 Sent To Z
Notes
2005-10-12 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-11-21 Cont ID  
Sent By tgordon Date 2005-11-21 Time 11:39 Rev Time 0.15
Received By tgordon Date 2005-11-21 Time 11:39 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-11-21 Cont ID  
Sent By jleech Date 2005-11-21 Time 18:06 Rev Time 0.00
Received By jleech Date 2005-11-21 Time 18:06 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-10-31 Cont ID  
Sent By sgraham Date 2005-10-31 Time 14:52 Rev Time 0.00
Received By sgraham Date 2005-10-31 Time 14:51 Sent To  
Notes
***NONE***