| Plan Review Stops For Permit 05100328 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2006-04-10 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-04-10 |
Time |
14:25 |
Rev Time |
3.33 |
| Received By |
jwitmer |
Date |
2006-04-06 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2006-04-10 00:00:00 | BUILDING PROVISO:R317.1 TWO-FAMILY | | | DWELLINGS. | | | DWELLING UNITS IN TWO-FAMILY DWELLINGS | | | SHALL BE SEPARATED FROM EACH OTHER BY | | | WALL AND/OR FLOOR ASSEMBLIES HAVING NOT | | | LESS THAN 1-HOUR FIRE-RESISTANCE RATING | | | WHEN TESTED IN ACCORDANCE WITH ASTM E | | | 119. FIRE-RESISTANCE-RATED FLOOR-CEILING | | | AND WALL ASSEMBLIES SHALL EXTEND TO AND | | | BE TIGHT AGAINST THE EXTERIOR WALL, AND | | | WALL ASSEMBLIES SHALL EXTEND TO THE | | | UNDERSIDE OF THE ROOF SHEATHING. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-02-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-02-07 |
Time |
13:36 |
Rev Time |
1.10 |
| Received By |
jwitmer |
Date |
2006-02-07 |
Time |
13:35 |
Sent To |
|
|
| Notes |
| 2006-02-07 00:00:00 | PERMIT: 05100328 | | | ADD: 1513 FLORIDA AVENUE | | | CONT: CAPITAL BUILDERS OF S. FL INC. | | | TEL: (561)762-2436 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) COMMENT# 3 FROM THE PREVIOUS RVIEW | | | DELS WITH THE ENERGY CALCS, NOT SIGNED | | | WHO THEY WERE PREPARED BY NOR BY THE | | | OWNER OR AGENT. | | | | | | 3) COMMENT # 6 FROM THE PREVIOUS REVIEW | | | DEALS WITH IDENTIFY GLAZING IN | | | HAZARDOUS AREAS, R 308.4 ? WINDOW AT 2ND | | | FLOOR BATHROOM IN FRONT OF TUB, SAFETY | | | GLASS REQUIRED. | | | | | | 4) PLANS INDICATE GLAZING REPLACED UNDER | | | | | | PERMIT# 05081102. THIS MISC PERMIT WAS | | | DENIED WITH A PRE-INSPECT SUBMIT: | | | FL BLD CODE 1609.1.4: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) WINDOWS | | | B) GLAZED DOORS | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 5) COMMENT # 8 FROM THE PREVIOUS REVIEW | | | R311.2.2 UNDER STAIR PROTECTION. | | | ENCLOSED ACCESSIBLE SPACE UNDER STAIRS | | | SHALL HAVE WALLS, UNDER STAIR SURFACE & | | | ANY SOFFITS PROTECTED ON THE ENCLOSED | | | WITH 1/2" GYPSUM BOARD. | | | | | | 6) COMMENT# 12 FROM THE PREVIOUS REVIEW | | | BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-12-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2005-12-15 |
Time |
07:24 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2005-12-15 |
Time |
07:13 |
Sent To |
|
|
| Notes |
| 2005-12-15 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05100328 | | | ADD: 1513 FLORIDA AVENUE | | | CONT: CAPITAL BUILDERS OF S. FL INC. | | | TEL: (561)762-2436 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | | | 2) 110.2* W. P. B. ADMINISTRATIVE CODE, | | | INFORMATION THAT IS REQUIREDON PLANS FOR | | | RECORD KEEPING & FOR CERTIFICATE OF | | | OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH | | | THE PERMIT WAS ISSUED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | | WITH THE PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | | IN CHAPTER 6, TABLE 601. | | | D) THE DESIGN OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | | IS REQUIRED. | | | F) ANY SPECIAL STIPULATIONS & CONDITIONS | | | OF THE BUILDING PERMIT. | | | | | | 3) FL BLD CODE CHAP 13 ENERGY EFFICENCY | | | PROVIDE ENERGY CALS/ W MANUAL "J" | | | USED THE WRONG FORM, FORM IS FOR THE | | | 2001 CODE. | | | | | | 4)PLANS ARE TO BE DESIGNED UNDER: | | | 2004 FL RESIDENTIAL CODE | | | 2004 EXISTING BUILING CODE | | | 2004 FL BUILDING CODE | | | 5) EXISTING BUILDING301.1 THE WORK | | | PREFORMED ON AN EXISTING BUILDING SHALL | | | BE UNDER THIS CHAPTERPROVIDE TO WHAT | | | LEVEL, 1,2 OR 3 THE PLAN WAS DESIGNED TO | | | INDICATE ON THE PLAN AND SHOW | | | COMPLIANCE. | | | | | | 5) PROVIDE THE MINIMUM LIVE LOADS FOR | | | NEW FLOOR LOADS TABLE R301.5, DEFLECTION | | | OF STRUCTURAL MEMBERS, TABLE R301.7. | | | | | | 6) IDENTIFY GLAZING IN HAZARDOUS AREAS | | | SEE R308.4. | | | | | | 7) IDENTIFY THE EMERGENCY ESCAPE AND | | | RESCUE OPENINGS FOR SLEEPING ROOMS, | | | PROVIDE THE WINDOW TYPE AND SIZE,THE | | | OPEN SQ FT VENT AREA.(R310.1) | | | | | | 8) R311.2.2 UNDER STAIR PROTECTION. | | | ENCLOSED ACCESSIBLE SPACE UNDER STAIRS | | | SHALL HAVE WALLS, UNDER STAIR SURFACE& | | | ANY SOFFITS PROTECTED ON THE ENCLOSED | | | SIDEWITH 1/2" GGYPSUM BOARD. | | | | | | 9) FIRST FLOOR ENTRY R311.4.3 THE | | | LANDING AT AN EXTERIOR DOOR SHALL NOT BE | | | MORE THAN 73/4" BELOW THE TOP OF THE | | | THRESHOLD. | | | | | | 10) PLANS MISSING SMOKE ALARMS IN | | | CERTAIN BEDROOMS, R313.1. | | | | | | 11) R313.1.1 WHEN INTERIOR ALTERATIONS, | | | REPAIRS OR ADDITIONS REQUIRING A PERMIT | | | OCCUR, OR WHEN ONE OR MORE SLEEPING | | | ROOMS ARE ADDED OR CREATED IN EXISTING | | | DWELLINGS THE INDIVIDUAL DWELLING UNITS | | | SHALL BE PROVIDED WITH SMOKE ALARMS | | | LOCATED AS REQUIED FOR NEW DWELLING, THE | | | SMOKE ALARMS SHALL BE INTERCONNECTED AND | | | HARD WIRED. | | | | | | 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-04-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-04-05 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-04-05 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2006-04-05 00:00:00 | ******** PLANS REDLINED ********* | | | | | | 1) NOTE: PLEASE SEE A "J" BOX IS BEING | | | SHOWN IN STAIR CASE EGRESS AREA, PLEASE | | | SEE A LT FIXTURE WILL BE REQUIED, NO | | | EXCEPTIONS. 210.70, LS101 7.8 | | | | | | 2) NOTE: PLEASE SEE FAN/LT "J" BOX IS | | | BEING SHOWN IN BEDRMS, HOWEVER EITHER A | | | SWITCHED RECEPT IS TO BE ADDED OT THE | | | FAN/LT WILL BE REQUIRED, NOT JUST A | | | "J-BOX". 210.70,LS101 7.8 | | | | | | 3) NOTE: PLEASE SEE SWITCHES AR 2ND FLR | | | FOR STAIR LIGHTING WILL BE REQUIRED TO | | | BE LOCATED IN CLOSE PROXIMITY TO THE | | | EGRESS OF STAIRS IN THE AREA AT THE TOP | | | OF STAIRS. | | | | | | ** PLEASE KNOW, ALL OF THE ABOVE ITEMS | | | WERE REDLINED ON PLANS AND DO NOT NEED | | | TO BE CORRECTED AT THIS TIME. IF PLANS | | | COME BACK FOR ANY OTHER COMMENTS, THESE | | | CAN BE REVISED OR THEY WILL BE REQUIRED | | | TO BE REVISED AND SUBMITTED BEFORE ROUGH | | | ELECTRICAL INSPECTION SHOWING LT | | | FIXTURES OF SOME SORT. | | | THIS WAS ON PREVIOUS REVIEW AND THE ONLY | | | ITEM WHICH WAS DELETED IN MEETING WAS | | | NOT TO PORVIDE BATTERY BACK UP AND THE | | | 10 FT CANDLES. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-01-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-01-30 |
Time |
07:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-01-30 |
Time |
07:10 |
Sent To |
|
|
| Notes |
| 2006-01-30 00:00:00 | ************** UNSAT 2ND REVIEW ******* | | | | | | | | | ** PLEASE SEE MANY NOTESFROM PREVIOUS | | | REVIEW WHICH STILL NEED TO BE ADDRESSED. | | | PLEASE ALSO SEE NEW NOTES DUE TO CHANGES | | | IN PLANS. | | | | | | | | | 1) NOTE: NOTE # 1 OK. | | | | | | 2) NOTE: NOTE #2 OK. | | | | | | 3)NOTE: NOTE #3 NO, PLEASE SEE LOCATIONS | | | REDLINED ON PLANS. | | | | | | ** PLEASE SEE 210.52D, WHICH | | | REQUIRES THE GFI RECEPTS WITHIN 3' OF | | | SINK'S EGDE. PLEASE SEE MISSING ON | | | REDLINED PLANS.PLEASE ALSO SEE THESE MAY | | | NOT PLACED AS TOCROSS OVER SINK TO GET | | | TO RECEPT. | | | PLEASE EITHER ADD ONE OR MOVE EXISTING | | | SHOWN. | | | PLEASE ALSO INDICATE ALL AS GFI. 210.8A1 | | | | | | 4)NOTE: NOTE #4 NO, PLEASE SEE MANY SD'S | | | WERE ADDED, HOWEVER, PLEASE SEE SD | | | MISSING AT THE TOP OF STATIRWAY AND ON | | | LOWER LEVEL. | | | | | | **SMOKE DETECTORS ARE REQUIRED INSIDE | | | AND OUTSIDE ALL SLEEPING ROOMS. | | | ON EACH LEVEL OF A MULTI-LEVEL DWELLING | | | UNIT. | | | IN CLOSE PROXIMITY OF STAIRWAYS LEADING | | | TO FLOORS ABOVE AND IN THE VICINITY OF | | | BEDROOMS. | | | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE | | | A MIN OF 3' FROM BATHROOM DOORS AND | | | KITCHENS. | | | ABOVE PER: NFPA-72 11.5.1.1 | | | | | | 5) NOTE: NOTE #5 NO, PLEASE SEE MANY | | | MISSING. | | | | | | ** PLEASE SHOW OUTLET SPACING PER | | | 210.52. 2',6`,12` RULE. | | | PLEASE SEE REDLINED PLANS FOR MANY | | | MISSING. | | | | | | 6 ) NOTE: NOTE #6 NO. | | | | | | ** PLEASE SEE MISSING RECEPTS FOR | | | FRONT AND/OR REAR OF DWELLING. | | | 210.52E | | | | | | 7)NOTE: NOTE #7 OK, HOWEVER PLEASE SEE | | | DISC'S NOW SHOWN FOR CU'S DO NOT MEET | | | 110.26 | | | | | | 8 )NOTE: NOTE #8 NO. | | | | | | ** PLEASE SEE RECEPTS SERVING | | | KITCHEN COUNTERSPACE TO MEET 210.52C- | | | SEC'S 1,2,3,4 AND 5 | | | PLEASE SEE MANY MISSING, PLEASE ALSO SEE | | | WHAT APPEARS TO BE ISLAND SHOWS A | | | J-BOX?? | | | | | | 9)NOTE: NOTE #9 NO,PLEASE SEE THE | | | FOLLOWING COMMENTS FOR LIGHTING | | | REQUIRED. | | | | | | ** PLEASE SEE J-BOXES ARE SHOWN IN | | | MANY ROOMS, HOWEVER, PLEASE INDICATE IF | | | THESE ARE GOING TO BE "FAN" J-BOXES. | | | | | | 10)NOTE: NOTE #10 NO, PLEASE SEE ROOMS | | | AND AREAS ARE SHOWN WITH J-BOXES , | | | HOWEVER LT FIXTURES OF SOME SORT WILL BE | | | REQUIRED. PLEASE SEE LS 101 7.8.1.3 | | | WHICH REQUIRES A MIN OF 10FT CANDLES | | | DURING NORMAL POWER AND PLEASE SEE | | | 7.9.1.3 WHICH REQUIRES AN EM FIXTURE TO | | | PROVIDE A MIN OF 1FT CANDLE OF LT TO THE | | | PUBLIC RIGHT OF WAY. | | | | | | ** PLEASE SEE MISSING EGRESS LIGHTING AT | | | FIRST FLR APT PLANS, APPEARS TO BE SHOWN | | | ON 2ND FLR? | | | PLEASE ALSO SEE EGRESS CONTROL REQUIRED | | | ON MULTI-LEVELS/LANDING. | | | 210.70 | | | | | | 11)NOTE: NOTE #11 OK. | | | | | | 12)NOTE: NOTE #12 OK. | | | | | | 13)NOTE: NOTE # 13 OK. | | | | | | 14)NOTE: NOTE #14 OK. | | | | | | 15)NOTE: NOTE #15 OK/ NO, PLEASE SEE | | | THESE WERE ADDED , HOWEVER PLEASE SEE | | | EQUIPMENT GROUNDING CONDUCTORS ARE NOW | | | SHOWN BEFORE THE FIRST MEANS OF | | | DISCONNECT. PLEASE SEE THESE ARE ONLY | | | INSTALLED AFTER THE FIRST MEANS OF | | | DISCONNECT.250.6 | | | | | | ** PLEASE INCLUDE ALL EQUIPMENT | | | GROUNDING CONDUCTORS WHERE REQUIRED. | | | 250.110,250.122, 250.24 | | | | | | 16)NOTE: NOTE #16 NO, PLEASE SEE A SIZE | | | WAS ADDED FOR GUTTER, HOWEVER PLEASE SEE | | | THIS AS BEING SHOWN 8"X 8" AND BY 4"?? | | | | | | **PLEASE INDICATE THE MIN SIZE OF | | | GUTTER PER 366 | | | | | | 17)NOTE: NOTE #17 OK, HOWEVER PLEASE SEE | | | AN ADDITIONAL GRND ROD WILL BE REQUIRED. | | | | | | | | | **PLEASE SEE 250.66 FOR MIN SIZE | | | OF THE GROUNDING ELECTRODE CONDUCTOR. | | | | | | 18)NOTE:NOTE #18 OK. | | | | | | NEW NOTES: | | | | | | 1)NOTE: PLEASE SEE WATER HEATER ON FIRST | | | FLR IS BEING SHOWN WITH A RECEPT FOR THE | | | CONNECTION. PLEASE SEE422.31 WHICH | | | REQUIRES A DISCONNECT. | | | | | | 2)NOTE: PLEASE SEE DRYER DOES NOT | | | INDICATE ANY RECEPT? | | | 215.5 | | | | | | 3)NOTE: PLEASE SEE COPY OF FS | | | 553.80(2)(B) WITH RESPECT TO DESIGN | | | PROFESSIONALS AND PLANS WITH REPEAT CODE | | | COMMENTS 3 OR MORE TIMES. | | | PLEASE SEE THIS IS ONLY ATTACHED THIS | | | TIME AS A NOTICE. | | | | | | | | | *** PLEASE SEE MOST OF THE ABOVE ITEMS | | | ARE REDLINED ON ONE OF THE SETS OF PLANS | | | FOR NOTES ABOVE. | | | | | | **PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | ** PLEASE BE SURE TO REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW | | | REVISED SHEETS INTO COMPLETE SETS FOR | | | REVIEW AND STAMPING. | | | PLEASE SUBMIT ONE COPY OF OLD/VOIDED | | | PLANS FOR REFERENCE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-10-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-10-18 |
Time |
11:12 |
Rev Time |
2.00 |
| Received By |
dpalmer |
Date |
2005-10-18 |
Time |
10:51 |
Sent To |
P |
|
| Notes |
| 2005-10-18 00:00:00 | ************ UNSAT ************* | | | | | | 1) NOTE: PLEASE SHOW ALL RECEPTS SERVING | | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | | -ED PER 210.8A-6 | | | | | | 2) NOTE: PLEASE LIST ALL THE REQ'D | | | DEDICATED BATH(S) CIRCUIT(S) ON PANEL | | | SCHEDULE. PER 210.52D, 210.11C3 | | | MUST BE 20A AND #12. | | | | | | 3)NOTE: PLEASE SEE 210.52D, WHICH | | | REQUIRE STHE GFI RECEPT PLEASE SEE | | | MISSING ON REDLINED PLANS.PLEASE ALSO | | | SEE THESE MAY NOT PLACED AS TOCROSS | | | OVER SINK TO GET TO RECEPT. | | | PLEASE EITHER ADD ONE OR MOVE EXISTING | | | SHOWN. | | | PLEASE ALSO INDICATE ALL AS GFI. 210.8A1 | | | | | | 4)NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ON EACH LEVEL OF A MULTI-LEVEL DWELLING | | | UNIT. | | | IN CLOSE PROXIMITY OF STAIRWAYS LEADING | | | TO FLOORS ABOVE AND IN THE VICINITY OF | | | BEDROOMS. | | | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE | | | A MIN OF 3' FROM BATHROOM DOORS AND | | | KITCHENS. | | | ABOVE PER: NFPA-72 11.5.1.1 | | | | | | 5) NOTE: PLEASE SHOW OUTLET SPACING PER | | | 210.52. 2',6`,12` RULE. | | | PLEASE SEE REDLINED PLANS FOR MANY | | | MISSING. | | | | | | 6 ) NOTE: PLEASE SEE MISSING RECEPTS FOR | | | FRONT AND/OR REAR OF DWELLING. | | | 210.52E | | | | | | 7)NOTE: PLEASE SEE PLANS ARE MISSING THE | | | LOCATION OF CU'S ALONG WITH MISSING | | | DISC;S PER 440.11 AND GFI'S PER | | | 210.8,210.63 | | | | | | 8 )NOTE: PLEASE SEE RECEPTS SERVING | | | KITCHEN COUNTERSPACE TO MEET 210.52C- | | | SEC'S 1,2,3,4 AND 5 | | | PLEASE SEE MANY MISSING, PLEASE ALSO SEE | | | WHAT APPEARS TO BE ISLAND SHOWS A | | | J-BOX?? | | | | | | 9)NOTE: PLEASE SEE J-BOXES ARE SHOWN IN | | | MANY ROOMS, HOWEVER, PLEASE INDICATE IF | | | THESE ARE GOING TO BE "FAN" J-BOXES. | | | | | | 10)NOTE: PLEASE SEE MISSING EGRESS | | | LIGHTING AT FIRST FLR APT PLANS, APPEARS | | | TO BE SHOWN ON 2ND FLR? | | | PLEASE ALSO SEE EGRESS CONTROL REQUIRED | | | ON MULTI-LEVELS/LANDING. | | | 210.70 | | | | | | 11)NOTE: PLEASE LIST ALL THE REQUIRED | | | ARC FAULT CIRCUITS ON PANEL SCHEDULE. | | | PLEASE SEE 2002 NEC 210.12, WHICH | | | REQUIRES ARC FAULT FOR ALL OUTLETS IN | | | BEDRMS. | | | | | | 12)NOTE: PLEASE SIZE SERVICE ENT | | | CONDUCTORS FOR SERVICE AND LOAD | | | PROVIDED.240.4 SEC'S ARE NOT LARGE | | | ENOUGH. | | | | | | 13)NOTE: PLEASE SEE PANELS ARE BEING | | | SHOWN AS 150A WITH 158 LOAD, AND BEING | | | FED FROM A 125A DISC????? | | | PLEASE CORRELATE ALL TO MIN REQUIRED BY | | | CODE. | | | PLEASE ALSO SEE #4'S SHOWN FROM GUTTER | | | TO MAINS. THESE ARE ONLY REATED FOR | | | 85A'S?? | | | 240.4,310.16, 215.5, 90.7 ETC. | | | | | | 14)NOTE: PLEASE INDICATE WHAT APPEARS TO | | | BE ADDITIONAL DISCONNECT SON RISER | | | DIAGRAM?? THESE ITEMS ARE NOT LABELED. | | | | | | 15)NOTE: PLEASE INCLUDE ALL EQUIPMENT | | | GROUNDING CONDUCTORS WHERE REQUIRED. | | | 250.110,250.122, 250.24 | | | | | | 16)NOTE: PLEASE INDICATE THE MIN SIZE OF | | | GUTTER PER 366 | | | | | | 17)NOTE: PLEASE SEE 250.66 FOR MIN SIZE | | | OF THE GROUNDING ELECTRODE CONDUCTOR. | | | | | | 18)NOTE: PLEASE SHOW ALL SERVICE | | | EQUIPMENT ON PLANS. | | | | | | 215.5 | | | | | | **PLEASE SEE ANY POSSIBLE COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | ** PLEASE BE SURE TO REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW | | | REVISED SHEETS INTO COMPLETE SETS FOR | | | REVIEW AND STAMPING. | | | PLEASE SUBMIT ONE COPY OF OLD/VOIDED | | | PLANS FOR REFERENCE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
N |
Date |
2005-12-14 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-12-14 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-12-14 |
Time |
15:58 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-09-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-23 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-23 |
Time |
16:38 |
Sent To |
M |
|
| Notes |
| 2006-09-23 00:00:00 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-09-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-08 |
Time |
14:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-08 |
Time |
14:36 |
Sent To |
M |
|
| Notes |
| 2006-09-08 00:00:00 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-08-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-17 |
Time |
18:35 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-17 |
Time |
18:35 |
Sent To |
M |
|
| Notes |
| 2006-08-17 00:00:00 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-03-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-03-10 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-03-10 |
Time |
15:21 |
Sent To |
|
|
| Notes |
| 2006-04-05 00:00:00 | TO "COMM" BD#49 | | 2006-03-10 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-12-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-12-27 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-12-27 |
Time |
15:58 |
Sent To |
|
|
| Notes |
| 2006-01-26 00:00:00 | TO "COMM" BD#61 | | 2005-12-27 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-12-19 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-12-19 |
Time |
17:32 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-10-17 |
Time |
15:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
F |
Date |
2006-10-02 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-10-02 |
Time |
13:36 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-10-02 |
Time |
13:36 |
Sent To |
|
|
| Notes |
| 2006-10-02 00:00:00 | ** MECHANICAL REVISION TO PAGE M-1 ** | | | *** DENIED *** | | | 1) SEE 12X12 RETURN AIR TRANSFER GRILLS | | | GO TO WATER HEATER CLOSET, NOT AIR | | | HANDLER CLOSET, PLEASE CORRECT. | | | | | | 2) PLEASE PROVIDE RETURN AIR FOR THE | | | LIVING ROOM AND KITCHEN. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2006-09-12 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-09-12 |
Time |
14:06 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2006-09-12 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2006-09-12 00:00:00 | MECH/REV. TO PAGE M-1. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2006-08-18 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2006-08-18 |
Time |
08:19 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2006-08-18 |
Time |
08:19 |
Sent To |
|
|
| Notes |
| 2006-08-18 00:00:00 | MECHANICAL REVISION | | | *** DENIED *** | | | 1) MECHANICAL PLANS ON FILE WERE DONE BY | | | A ENGINEER (THOMAS TWOMEY) AND SEALED SO | | | ONLY HE CAN MAKE REVISIONS TO THEM. | | | | | | 2) CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY. PER 2004 FBC 106.1.1 | | | . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2006-04-12 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-04-12 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-04-12 |
Time |
11:39 |
Sent To |
|
|
| Notes |
| 2006-04-12 00:00:00 | PLANS APPROVED BY HAROLD MOSER ON | | | 1/25/06 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2006-01-25 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2006-01-25 |
Time |
17:57 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2006-01-25 |
Time |
17:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-11-30 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2005-11-30 |
Time |
16:37 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2005-11-30 |
Time |
16:37 |
Sent To |
FIRE |
|
| Notes |
| 2005-11-30 00:00:00 | *** DENIED *** | | | 1) 1ST. FLOOR SUPPLY AIR DUCT TO BOLTH | | | BATHROOMS ARE NOT SIZED. | | | 2) 1ST. FLOOR SUPPLY AIR DUCT TO KITCHEN | | | NOT SIZED. | | | 3) 1ST. FLOOR NO RETURN AIR IN LIVING | | | AREA. | | | 4) 2ND. FLOOR MASTER BATHROOM SUPPLY AIR | | | DUCT AND GRILL NOT SIZED AND ON CFM'S.. | | | 5) 2ND. FLOOR NO RETURN AIR TO MAIN | | | LIVING AREA. | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2006-04-11 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-04-11 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-04-11 |
Time |
09:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-02-04 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-02-04 |
Time |
13:00 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-02-04 |
Time |
14:05 |
Sent To |
|
|
| Notes |
| 2006-02-04 00:00:00 | PLUMBING PLAN REVIEW EXAMINER | | | PAUL SCHMITZ 561-805-6692 | | | [email protected] | | | FBC PLUMBING 2001 | | | \DENIED 2ND TIME | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | PREVIOUS PLAN REVIEW NOTES BY JOHN LEECH | | | DATED 11-30-05 NOT ADDRESSED. | | | DENIED; | | | 1.SHOW WATER RISER DIAGRAM, SIZE ALL | | | PIPES. | | | 2.IF BOTH APTS. ON SAME WATER SERVICE A | | | BACKFLOW PROVENTOR IS REQUIRED, IF NOT | | | 2ND FLOOR APT. NEEDS A WATER HEATER. | | | 3.SHOW DIAMETER OF WATER HEATER AND THE | | | OPENING. MUST BE ABLE TO REMOVE W/H FOR | | | REPLACEMENT. | | | 4.SANITARY RISER DIAGRAM NOT TO CODE. | | | (MARKED IN RED) | | | A.WET VENT SIZE SEE TABLE 909.3 | | | B.W/M MUST BE DOWN STREAM OF BATH- | | | ROOM GROUP SEC.909.1 | | | C. CLEANOUT ON W/M STACK TO BE | | | 48" AFF. | | | 5.IS W/M IN COMMAN AREA FOR 2ND FLOOR | | | USES? SEE TABLE 403.1(7) | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 | | | ADDITIONAL COMMENTS | | | 1) PERMIT APPLICATION.DISCRIPTION OF | | | WORK, AND PLANS SUBMITTED APTS #1,2 | | | SHOULD INCLUDE BUILDING #1 ON THE | | | APPLICATION. | | | 2)ENERGY CALCULATIONS SUBMITTED ARE FOR | | | SIX UNITS,THREE BUILDINGS. PLEASE | | | CLARIFY.OR REMOVE FROM SUBMITTED PLANS. | | | 3)VOIDED SHT.M-2, WAS REMOVED FROM RED | | | LINED PACKAGE. THIS IS REFERENCED IN | | | NOTE (4) PREVIOUS COMMENTS. | | | END OF COMMENTS, QUESTIONS 561-805-6692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-11-30 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-11-30 |
Time |
11:46 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2005-11-30 |
Time |
11:46 |
Sent To |
M |
|
| Notes |
| 2005-11-30 00:00:00 | DENIED; | | | 1.SHOW WATER RISER DIAGRAM, SIZE ALL | | | PIPES. | | | 2.IF BOTH APTS. ON SAME WATER SERVICE A | | | BACKFLOW PROVENTOR IS REQUIRED, IF NOT | | | 2ND FLOOR APT. NEEDS A WATER HEATER. | | | 3.SHOW DIAMETER OF WATER HEATER AND THE | | | OPENING. MUST BE ABLE TO REMOVE W/H FOR | | | REPLACEMENT. | | | 4.SANITARY RISER DIAGRAM NOT TO CODE. | | | (MARKED IN RED) | | | A.WET VENT SIZE SEE TABLE 909.3 | | | B.W/M MUST BE DOWN STREAM OF BATH- | | | ROOM GROUP SEC.909.1 | | | C. CLEANOUT ON W/M STACK TO BE | | | 48" AFF. | | | 5.IS W/M IN COMMAN AREA FOR 2ND FLOOR | | | USES? SEE TABLE 403.1(7) | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|