Plan Review Details - Permit 05100279
Plan Review Stops For Permit 05100279
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-08-07 Cont ID  
Sent By alange Date 2006-08-07 Time 09:09 Rev Time 0.00
Received By alange Date 2006-08-07 Time 09:09 Sent To  
Notes
2006-08-07 00:00:00ROOFING REVISION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-03-14 Cont ID  
Sent By alange Date 2006-03-14 Time 11:24 Rev Time 1.50
Received By alange Date 2006-03-13 Time 16:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-01-27 Cont ID  
Sent By alange Date 2006-01-27 Time 11:08 Rev Time 1.00
Received By alange Date 2006-01-27 Time 11:04 Sent To  
Notes
2006-01-27 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.TWO COPIES OF PRODUCT APPROVALS
 REQUIRED FOR THE FOLLOWING;LINTELS AND
 MULLIONS.
  
 3.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.BASED ON SBCCI BUILDING VALUATION
 DATA THE PERMIT VALUE HAS BEEN REVISED
 AS FOLLOWS, ADDITIONAL PERMIT FEES ARE
 DUE.
 498SQ. FT. X $76.96 = $38,326 SEE
 ATTACHED INVOICE.
  
 5.PLANS SUBMITTED FOR REVIEW AFTER
 OCTOBER 1, 2005 SHALL BE DESIGNED TO THE
 2004 FBC.
  
 6.SUBMIT TWO COPIES OF ENERGY CALCS.
 TO THE 2004 FBC
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-13 Cont ID  
Sent By alange Date 2005-12-13 Time 07:45 Rev Time 1.66
Received By alange Date 2005-12-13 Time 07:37 Sent To  
Notes
2005-12-13 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.TWO COPIES OF PRODUCT APPROVALS
 REQUIRED FOR THE FOLLOWING;STRAPS AND
 TIE-DOWNS, LINTELS AND MULLIONS.
  
 3.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.BASED ON SBCCI BUILDING VALUATION
 DATA THE PERMIT VALUE HAS BEEN REVISED
 AS FOLLOWS, ADDITIONAL PERMIT FEES ARE
 DUE.
 498SQ. FT. X $76.96 = $38,326 SEE
 ATTACHED INVOICE.
  
 5.PLANS SUBMITTED FOR REVIEW AFTER
 OCTOBER 1, 2005 SHALL BE DESIGNED TO THE
 2004 FBC.
  
 6.SUBMIT TWO COPIES OF ENERGY CALCS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-12-14 Cont ID  
Sent By btrobaug Date 2005-11-14 Time 06:33 Rev Time 0.50
Received By btrobaug Date 2005-11-14 Time 14:08 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-02 Cont ID  
Sent By adarroug Date 2006-08-02 Time 10:11 Rev Time 0.00
Received By adarroug Date 2006-08-02 Time 10:11 Sent To B
Notes
2006-08-02 00:00:00TO "ALANGE" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-03-02 Cont ID  
Sent By adarroug Date 2006-03-02 Time 10:18 Rev Time 0.00
Received By adarroug Date 2006-03-02 Time 10:18 Sent To B
Notes
2006-03-02 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-27 Cont ID  
Sent By adarroug Date 2006-01-27 Time 08:58 Rev Time 0.00
Received By adarroug Date 2006-01-27 Time 08:58 Sent To B
Notes
2006-01-27 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-01-05 Cont ID  
Sent By adarroug Date 2006-01-05 Time 10:20 Rev Time 0.00
Received By adarroug Date 2006-01-05 Time 10:20 Sent To Z
Notes
2006-01-05 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-10 Cont ID  
Sent By adarroug Date 2005-11-10 Time 10:41 Rev Time 0.00
Received By adarroug Date 2005-11-10 Time 10:41 Sent To E
Notes
2005-11-10 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-13 Cont ID  
Sent By alange Date 2005-12-13 Time 07:45 Rev Time 0.00
Received By alange Date 2005-10-11 Time 13:43 Sent To  
Notes
2005-10-11 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-12-06 Cont ID  
Sent By tgordon Date 2005-12-06 Time 14:58 Rev Time 0.20
Received By tgordon Date 2005-12-06 Time 14:58 Sent To B
Notes
2005-12-06 00:00:00NO MECH.PLANS OR MECH. CONTRACTOR
 SUBMITTED AT THIS TIME.

Review Stop P PLUMBING
Rev No 1 Status P Date 2005-12-06 Cont ID  
Sent By jleech Date 2005-12-06 Time 13:34 Rev Time 0.25
Received By jleech Date 2005-12-06 Time 13:34 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-01-26 Cont ID  
Sent By mmclean Date 2006-01-26 Time 18:35 Rev Time 0.00
Received By mmclean Date 2006-01-26 Time 18:35 Sent To I
Notes
2006-01-26 00:00:00NOTE: THE PROPOSED ADDITON IS WITHIN THE
 SETBACK OF THE EXISTING STRUCTURE.MEET
 THE SIDE SETBACKS.
 NOTE: THE OLD KITCHEN TO BE REMOVED AND
 RELOCATED IN THE PROPOSED ADDITON. ONE
 KITCHEN ALLOWED IN SF7.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-10-31 Cont ID  
Sent By sgraham Date 2005-10-31 Time 15:16 Rev Time 0.00
Received By sgraham Date 2005-10-31 Time 15:16 Sent To  
Notes
2005-10-31 00:00:00NEED TO SHOW OLD FLOOR PLAN AND NEW
 FLOOR PLAN. MUST SHOW DEMOLITION