Plan Review Details - Permit 05100256
Plan Review Stops For Permit 05100256
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2005-12-30 Cont ID  
Sent By alange Date 2005-12-30 Time 08:02 Rev Time 0.33
Received By alange Date 2005-12-30 Time 08:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-15 Cont ID  
Sent By alange Date 2005-12-15 Time 08:47 Rev Time 0.50
Received By alange Date 2005-12-15 Time 08:47 Sent To  
Notes
2005-12-15 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2. SUBMIT A SLAB DETAIL SHOWING METHOD
 OF REINFORCEMENT AND SHOW METHOD OF
 ATTACHMENT FROM GENERATOR TO SLAB.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-01-11 Cont ID  
Sent By btrobaug Date 2006-01-11 Time 11:58 Rev Time 1.00
Received By btrobaug Date 2006-01-11 Time 11:52 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2005-12-22 Cont ID  
Sent By btrobaug Date 2005-12-22 Time 14:18 Rev Time 0.50
Received By btrobaug Date 2005-12-22 Time 14:10 Sent To B
Notes
2005-12-22 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE TRANSFER SWITCH MUST BE SERVICE
 RATED AND CONTAIN A MAIN PER 225.36.
 PLEASE SUBMIT MANUFACTURERS
 SPECIFICATIONS FOR SAME.
  
 2} SHOW THE LOCATION OF ALL EQUIPMENT ON
 THE SITE PLAN SO THAT COMPLIANCE WITH
 ARTILES 225.31 THROUGH 225.37 CAN BE
 DETERMINED.
  
 3} THE PERSON RESPONSIBLE FOR THE
 PLANS MUST PRINT NAME AND SIGN SAME.
 104.2.1 FBC.
  
 4} THE LOAD MUST NOT EXCEED THE RATING
 OF THE GENERATOR, SEE 702.5. THE LOAD
 CALC IS 120 AMPS AND THE MAX OUTPUT IS
 104 AMPS. PLEASE CHOOSE LOADS TO BE USED
 AND ISOLATE SAME AS GENERATOR LOAD ONLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-11-28 Cont ID  
Sent By btrobaug Date 2005-11-28 Time 17:41 Rev Time 0.33
Received By btrobaug Date 2005-11-28 Time 17:29 Sent To M
Notes
2005-11-22 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE TRANSFER SWITCH MUST BE SERVICE
 RATED AND CONTAIN A MAIN PER 225.36.
 PLEASE SUBMIT MANUFACTURERS
 SPECIFICATIONS FOR SAME.
  
 2} SHOW THE LOCATION OF ALL EQUIPMENT ON
 THE SITE PLAN SO THAT COMPLIANCE WITH
 ARTILES 225.31 THROUGH 225.37 CAN BE
 DETERMINED.
  
 3} THE PERSON RESPONSIBLE FOR THE
 PLANS MUST PRINT NAME AND SIGN SAME.
 104.2.1 FBC.
  
 4} THE LOAD MUST NOT EXCEED THE RATING
 OF THE GENERATOR, SEE 702.5. THE LOAD
 CALC IS 120 AMPS AND THE MAX OUTPUT IS
 104 AMPS. PLEASE CHOOSE LOADS TO BE USED
 AND ISOLATE SAME AS GENERATOR LOAD ONLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2005-12-06 Cont ID  
Sent By jleech Date 2005-12-06 Time 14:58 Rev Time 0.25
Received By jleech Date 2005-12-06 Time 14:58 Sent To B
Notes
2005-12-06 00:00:00GAS PERMIT APPLIED FOR #05111078

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-16 Cont ID  
Sent By adarroug Date 2005-12-16 Time 16:27 Rev Time 0.00
Received By adarroug Date 2005-12-16 Time 16:27 Sent To E
Notes
2005-12-16 00:00:00TO "BTROBAUG"DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-09 Cont ID  
Sent By adarroug Date 2005-11-09 Time 15:07 Rev Time 0.00
Received By adarroug Date 2005-11-09 Time 15:07 Sent To E
Notes
2005-11-09 00:00:00TO "GEN-RES" BOX "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-07 Cont ID  
Sent By adarroug Date 2005-10-07 Time 08:20 Rev Time 0.00
Received By adarroug Date 2005-10-07 Time 08:20 Sent To Z
Notes
2005-10-07 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-11-29 Cont ID  
Sent By tgordon Date 2005-11-29 Time 08:55 Rev Time 0.15
Received By tgordon Date 2005-11-29 Time 08:55 Sent To P
Notes
2005-11-29 00:00:00*** PROVISO ***
 1) GENERATOR EXHUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS
 (WINDOWS, DOORS, ROOF & EAVE VENTS), AND
 TEN FEET AWAY FROM ADJECENT BUILDING
 OPENS.
 2) DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS MUST BE ON JOB SITE.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2005-12-06 Cont ID  
Sent By jleech Date 2005-12-06 Time 14:57 Rev Time  
Received By jleech Date   Time   Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2005-10-31 Cont ID  
Sent By mmclean Date 2005-10-31 Time 13:15 Rev Time 0.00
Received By mmclean Date 2005-10-31 Time 13:15 Sent To I
Notes
2005-10-31 00:00:00GENERATOR CAN ONLY ENCROACH 4FT INTO A
 SETBACK.