Plan Review Details - Permit 05100240
Plan Review Stops For Permit 05100240
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-15 Cont ID  
Sent By adarroug Date 2005-11-15 Time 14:01 Rev Time 0.00
Received By adarroug Date 2005-11-15 Time 14:01 Sent To M
Notes
2005-11-15 00:00:00TO "TGORDON" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-07 Cont ID  
Sent By adarroug Date 2005-10-07 Time 08:39 Rev Time 0.00
Received By adarroug Date 2005-10-07 Time 08:39 Sent To M
Notes
2005-10-07 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-11-17 Cont ID  
Sent By tgordon Date 2005-11-17 Time 08:46 Rev Time 0.25
Received By tgordon Date 2005-11-17 Time 08:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-10-13 Cont ID  
Sent By tgordon Date 2005-10-13 Time 14:16 Rev Time 0.30
Received By tgordon Date 2005-10-13 Time 14:16 Sent To  
Notes
2005-10-13 00:00:00*** DENIED ***
  
 1) DRAIN LINES NOT SHOWING ON PLANS. PER
 FBC/R M1411.3 .
 2) PLANS ARE CALLING FOR A 34,000 BTU
 A/C SYSTEM AND MANUAL 'J' IS CALLING FOR
 21,641 BTU'S OF COOLING THE TWO MUST
 COINCIED.
 3) PLEASE SHOW ON PLANS WHERE DOORS AND
 OPENINGS IN WALLS ARE.
 4) PLANS NOT SHOWING LOCATION OF
 CONDENSER UNIT.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.