Plan Review Details - Permit 05100207
Plan Review Stops For Permit 05100207
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-09-05 Cont ID  
Sent By alange Date 2006-09-05 Time 14:29 Rev Time 0.66
Received By alange Date 2006-09-05 Time 14:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-08-15 Cont ID  
Sent By alange Date 2006-08-15 Time 10:58 Rev Time 0.66
Received By alange Date 2006-08-15 Time 10:58 Sent To  
Notes
2006-08-15 00:00:00REVISION DENIED
  
 1.SUBMIT THE FOLLOWING STATE PRODUCT
 APPROVAL FOR ODL AND THERMA-TRU PRODUCTS
 WITH THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 2.ADJUST PERMIT VALUE TO REFLECT THE
 ADDITIONAL WORK BEING COMPLETED.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-01-11 Cont ID  
Sent By alange Date 2006-01-11 Time 15:30 Rev Time 1.66
Received By alange Date 2006-01-11 Time 15:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-02 Cont ID  
Sent By alange Date 2005-12-02 Time 08:34 Rev Time 2.00
Received By alange Date 2005-12-02 Time 07:43 Sent To  
Notes
2005-12-02 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3. TWO COPIES OF PRODUCT APPROVALS
 REQUIRED.PRODUCT APPROVALS MISSING FOR
 LINTELS, STRAPS AND TIE-DOWNS AND IMPACT
 PROTECTION.
  
 4.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5.PLEASE SIGN OWNER AGENT ON ENERGY
 CALCS.
  
 6.ALL PLANS SUBMITTED AFTER OCTOBER 1,
 2005 SHALL BE DESIGNED TO THE 2004 FBC
  
 7.A DESIGN PROFESSIONAL MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION
 PURSUANT TO SECTIONS 303,304 AND 305 OF
 THE 2004 EXISTING BUILDING CODE 301.5.
 SHOW HOW BUILDING WILL BE DESINGED TO
 THIS SECTION.
  
 8. R613.6.2 MASONRY, CONCRETE OR OTHER
 STRUCTURAL SUBSTRATE.
 WHERE THE WOOD SHIM OR BUCK THICKNESS IS
 LESS THAN 1? INCHES (38 MM), WINDOW AND
 DOOR ASSEMBLIES SHALL BE ANCHORED
 THROUGH THE MAIN FRAME OR BY JAMB CLIP
 OR SUBFRAME SYSTEM, IN ACCORDANCE WITH
 THE MANUFACTURERS PUBLISHED INSTALLATION
 INSTRUCTIONS. ANCHORS SHALL BE SECURELY
 FASTENED DIRECTLY INTO THE MASONRY,
 CONCRETE OR OTHER STRUCTURAL SUBSTRATE
 MATERIAL. UNLESS OTHERWISE TESTED, BUCKS
 SHALL EXTEND BEYOND THE INTERIOR FACE OF
 THE WINDOW OR DOOR FRAME SUCH THAT FULL
 SUPPORT OF THE FRAME IS PROVIDED.
  
 9.CLEARLY SHOW EXISTING AREAS AND
 AREAS OF NEW WORK.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-01-09 Cont ID  
Sent By btrobaug Date 2006-01-09 Time 12:01 Rev Time 0.50
Received By btrobaug Date 2006-01-09 Time 11:37 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-11-09 Cont ID  
Sent By btrobaug Date 2005-11-09 Time 10:05 Rev Time 0.75
Received By btrobaug Date 2005-11-09 Time 07:50 Sent To M
Notes
2005-11-09 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1}PLEASE SUBMIT AIC RATINGS FOR ALL
 NEW SERVICE EQUIPMENT BEING INSTALLED.
 MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9.
  
 2} INCLDE BUILDING STEEL IN THE
 GROUNDING ELECTRODE SYSTEM. SEE 250.50.
  
 3} INCLUDE THE BATH CIRCUIT ON THE PANEL
 SCHEDULE PER 210.11(C)(3).
  
 4} THE MASTER BATH REQUIRES A RECEPTACLE
 FOR THE SECOND SINK. SEE 210.52(D).
  
 5} THE BATH RECEPTACLES MUST BE GFI
 PROTECTED PER 210.8(A)(1).
  
 6} THE GARAGE IS REQUIRED TO HAVE A
 RECEPTACLE PER 210.52(G). ALSO GFI PER
 210.8(A)(2).
  
 7} THE KITCHEN COUNTERTOP RECEPTACLES
 MUST BE GFI PER 210.8(A)(6), ALSO SPACED
 PER 210.52(C)(1).
  
 8} A RECEPTACLE NEEDS TO BE ADDED AT THE
 DOORWAY OF THE MASTER BEDROOM PER
 210.52(A)(2), ALSO IN THE LIVING ROOM
 PER 210.52(A)(1).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-25 Cont ID  
Sent By adarroug Date 2006-08-25 Time 15:17 Rev Time 0.00
Received By adarroug Date 2006-08-25 Time 15:17 Sent To M
Notes
2006-08-25 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-08 Cont ID  
Sent By adarroug Date 2006-08-08 Time 16:54 Rev Time 0.00
Received By adarroug Date 2006-08-08 Time 16:54 Sent To M
Notes
2006-08-08 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-01-09 Cont ID  
Sent By adarroug Date 2006-01-09 Time 09:28 Rev Time 0.00
Received By adarroug Date 2006-01-09 Time 09:28 Sent To E
Notes
2006-01-09 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2005-12-20 Cont ID  
Sent By adarroug Date 2005-12-20 Time 10:03 Rev Time 0.00
Received By adarroug Date 2005-12-20 Time 10:03 Sent To Z
Notes
2005-12-20 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-21 Cont ID  
Sent By adarroug Date 2005-10-21 Time 14:09 Rev Time 0.00
Received By adarroug Date 2005-10-21 Time 14:09 Sent To E
Notes
2005-10-21 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-02 Cont ID  
Sent By alange Date 2005-12-02 Time 08:34 Rev Time 0.00
Received By alange Date 2005-10-06 Time 13:59 Sent To  
Notes
2005-10-06 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-08-31 Cont ID  
Sent By tgordon Date 2006-08-31 Time 09:25 Rev Time 0.25
Received By tgordon Date 2006-08-31 Time 09:25 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-08-10 Cont ID  
Sent By tgordon Date 2006-08-10 Time 15:31 Rev Time 0.30
Received By tgordon Date 2006-08-10 Time 15:31 Sent To B
Notes
2006-08-10 00:00:00MECHANICAL REVISION
 *** DENIED ***
 1) RETURN AIR TRANSFER DUCT TO MASTER
 SUITE NEEDS TO BE 12" PER 2004 FBC/R
 M1602.4 .
  
 2) ARCHITECT'S LICENSE NUMBER MUST
 APPEAR IN TITLE BLOCK, PER FAC
 61G1-16.003 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-05-08 Cont ID  
Sent By tgordon Date 2006-05-08 Time 15:19 Rev Time 0.20
Received By tgordon Date 2006-05-08 Time 15:19 Sent To  
Notes
2006-05-08 00:00:00*** PROVISO ***
 1) CLOTHES DRYER EXHAUST VENT MUST
 TERMINATN A MIN. OF 4 FEET FROM A/C
 CONDENSER UNIT , PER 2004 FBC/M 401.5.2.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-11-09 Cont ID  
Sent By tgordon Date 2005-11-09 Time 11:50 Rev Time 0.15
Received By tgordon Date 2005-11-09 Time 11:50 Sent To P
Notes
2005-11-09 00:00:00NO MECH. PLANS OR MECH. CONTRACTOR
 SUBMITTED AT THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-01-11 Cont ID  
Sent By jleech Date 2006-01-11 Time 13:57 Rev Time 0.33
Received By jleech Date 2006-01-11 Time 13:57 Sent To B1
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-11-29 Cont ID  
Sent By jleech Date 2005-11-29 Time 15:54 Rev Time 0.50
Received By jleech Date 2005-11-29 Time 15:44 Sent To B
Notes
2005-11-29 00:00:00DENIED;
 1.KITCHEN SINK IS NOT VENTED.
 2.KITCHEN SINK SHALL NOT DISCHARGE THRU
 THE WET VENTED BATHROOM GROUP. FBC-2004
 PLUMBING SEC. 909.1
 3.SHOW ALL PLUMBING WORK TO BE DONE ON
 RISER DIAGRAM. W/M AND AND RELOCATION OF
 BATHROOM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2006-01-07 Cont ID  
Sent By mmclean Date 2006-01-07 Time 08:44 Rev Time 0.00
Received By mmclean Date 2006-01-07 Time 08:44 Sent To I
Notes
2006-01-07 00:00:00REVISION TO PLANS.

Review Stop Z ZONING
Rev No 1 Status P Date 2005-10-20 Cont ID  
Sent By mmclean Date 2005-10-20 Time 15:00 Rev Time 0.00
Received By mmclean Date 2005-10-20 Time 15:00 Sent To B
Notes
2005-10-20 00:00:00PROPOSED ADDITION MEETS THE SIDE
 SETBACK, PLANS SHOWS 6FT.
  
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/DECK.