Plan Review Details - Permit 05100175
Plan Review Stops For Permit 05100175
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-22 Cont ID  
Sent By adarroug Date 2005-10-22 Time 12:06 Rev Time 0.00
Received By adarroug Date 2005-10-22 Time 12:06 Sent To M
Notes
2005-10-22 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-06 Cont ID  
Sent By adarroug Date 2005-10-06 Time 12:23 Rev Time 0.00
Received By adarroug Date 2005-10-06 Time 12:23 Sent To M
Notes
2005-10-06 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-11-10 Cont ID  
Sent By tgordon Date 2005-11-10 Time 14:48 Rev Time 0.30
Received By tgordon Date 2005-11-10 Time 14:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-10-12 Cont ID  
Sent By tgordon Date 2005-10-12 Time 10:38 Rev Time 0.30
Received By tgordon Date 2005-10-12 Time 10:38 Sent To  
Notes
2005-10-12 00:00:00*** DENIED ***
 1) PLANS NEED JOB LOCATION AND
 CONTRACTOR INFORMATION ON THEM.
 2) NEED ENERGY CAL'S. FORM 600 OR MANUAL
 'J' PER 2004 FBC CH.13 .
 4) NO RETURN AIR GRILL TO A.H.U.
 SHOWING.
 5) RETURN AIR REQUIRED IN EACH BEDROOM
 PER 2004 FBC/R M1602.4 .
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.