Plan Review Details - Permit 05100174
Plan Review Stops For Permit 05100174
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-22 Cont ID  
Sent By adarroug Date 2005-10-22 Time 12:07 Rev Time 0.00
Received By adarroug Date 2005-10-22 Time 12:07 Sent To M
Notes
2005-10-22 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-06 Cont ID  
Sent By adarroug Date 2005-10-06 Time 12:24 Rev Time 0.00
Received By adarroug Date 2005-10-06 Time 12:24 Sent To M
Notes
2005-10-06 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-11-10 Cont ID  
Sent By tgordon Date 2005-11-10 Time 15:40 Rev Time 0.30
Received By tgordon Date 2005-11-10 Time 15:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-10-12 Cont ID  
Sent By tgordon Date 2005-10-12 Time 12:11 Rev Time 0.30
Received By tgordon Date 2005-10-12 Time 12:11 Sent To  
Notes
2005-10-12 00:00:00*** DENIED ***
 1) PLANS DO NOT COINCIDE WITH ENERGY
 CALCULATIONS ON FILE. ENERGY CAL'S. ARE
 CALLING FOR 3 A/C SYSTEMS TOTALING 10
 1/2 TONS, PLANS ARE CALLING FOR 4 A/C
 SYSTEMS TOTALING 13 1/2 TONS.
 2) RETURN AIR DUCTS ARE NEEDED IN THE
 DINING ROOM & LIBRARY. PER 2001 FBC/M
 601.4 .
 3) RETURN AIR DUCT IN MASTER BEDROOM
 NEEDS TO BE 16" . PER 2001 FBC/M 601.4 .
 4) POOL HOUSE NEEDS DUCT SIZES FOR
 RETURN AND SOME SUPPLY AIR DUCTS.
 5) CONDENSATE DRAIN LINES NOT SHOWING.
 PER 2001 FBC/M 307.2 .
 6) BATHROOM EXHAUST FANS NOT SHOWING.
 PER 2001 FBC/M 402.3.1 .
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.