| 2005-12-01 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1-PROVIDE FLORIDA PRODUCT APPROVAL OR |
| | APPLY FOR LOCAL PRODUCT APPROVAL FOR |
| | SHUTTERS (COMPLYING WITH 2004 FBC) AS |
| | REQUIRED BY RULE 9B-72 OF DCA.GO TO |
| | WWW.FLORIDABUILDING.ORG FOR INFORMATION |
| | AND REQUIREMENTS FOR PRODUCT APPROVALS. |
| | ***NOTE: DADE COUNTY NOA ALONE IS NOT |
| | AUTOMATICALLY AN STATEWIDE FLORIDA |
| | PRODUCT APPROVAL. IF MANUFACTURER HASN'T |
| | APPLIED FOR FLORIDA PRODUCT APPROVAL, |
| | THEN, MANUFACTURER MAY APPLY FOR LOCAL |
| | PRODUCT APPROVAL BY USING THE DADE |
| | COUNTY NOA AND COMPLETING THE LOCAL |
| | PRODUCT APPROVAL FORM DOWNLOADED FROM |
| | WWW.FLORIDABUILDING.ORG. |
| | |
| | 2- A) PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE (SEE ATTACHED SAMPLE) AS REQ'D |
| | BY CITY IMPLEMENTATION STANDARD FOR |
| | HURRICANE MISSILE IMPACT PROTECTION AND |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC/2004 |
| | |
| | B) CLEARLY MARK IN DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS AND ANCHOR TYPE AND |
| | SPACING TO BE USED ACCORDING TO THE |
| | DESIGN PRESSURES, SHUTTER SPAN, EDGE |
| | DISTANCE, CONNECTION TYPE AND STRUCTURE |
| | TO BE ATTACHED TO (CONCRETE, CONCRETE |
| | BLOCK, WOOD). SEC. 106.1.2 OF CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 3- NOTICE OF COMMENCEMENT: EXPIRED AFTER |
| | 90 DAYS OF RECORDING IF WORK IS NOT |
| | STARTED. FL. STATUTES SEC. 713.13(2). |
| | |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |