| 2005-11-30 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- RESIDENTIAL CONTRACTOR SERVICES ARE |
| | LIMITED TO DO WORK IN ONE-FAMILY, |
| | TWO-FAMILY OR THREEE-FAMILY RESIDENCES |
| | WHICH ARE NOT MORE THAN TWO STORIES |
| | HIGH. THIS IS A HIGHRISE BUILDING, |
| | THEREFORE CONTRACTOR CANN'T DO THIS |
| | WORK. NEED CONTRACTOR WITH LICENSE TO |
| | PERFORM THIS TYPE OF WORK. |
| | |
| | 2- NEED RECORDED NOTICE OF COMMENCEMENT. |
| | SEC. 713.13 FLORIDA STATUTES. |
| | |
| | 3- THIS IS A HIGHRISE BUILDING. NEED TO |
| | PROVIDE ENGINEERING CALCULATIONS FOR |
| | THE DESIGN PRESSURES OF THE OPENINGS TO |
| | VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES SPECIFIED ON SHUTTERS PRODUCT |
| | APPROVAL. SEC. 1609.1.1 FBC 2004 AND |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 |
| | |
| | 4- PROVIDE FLORIDA PRODUCT APPROVAL OR |
| | APPLY FOR LOCAL PRODUCT APPROVAL AS |
| | REQUIRED BY RULE 9B-72 OF DCA FOR THE |
| | ACCORDION SHUTTERS. SEE DCA WEBSITE |
| | WWW.FLORIDABUILDING.ORG FOR ADDITIONAL |
| | PRODUCT APPROVAL INFORMATION AND |
| | REQUIREMENTS. |
| | ***NOTE: DADE COUNTY NOA ALONE IS NOT |
| | AUTOMATICALLY AN STATEWIDE FLORIDA |
| | PRODUCT APPROVAL. IF MANUFACTURER DIDN'T |
| | APPLY FOR 2004 PRODUCT APPROVAL, THEN, |
| | MANUFACTURER MAY APPLY FOR LOCAL PRODUCT |
| | APPROVAL USING THE DADE COUNTY NOA AND |
| | COMPLETING LOCAL PRODUCT APPROVAL FORM |
| | DOWNLOADED FROM WWW.FLORIDABUILDING.ORG. |
| | |
| | 5- PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE AND KEY PLAN TO FACILITATE PLAN |
| | REVIEW AND INSPECTION AS REQUIRED BY |
| | CITY IMPLEMENTATION STANDARD FOR |
| | HURRICANE MISSILE IMPACT PROTECTION. SEE |
| | ATTACHED INSTALLATION SCHEDULE SAMPLE. |
| | |
| | 6- SHEET 8 OF 9 OF ACCORDION SHUTTERS: |
| | CHART AT BOTTOM LEFT SIDE OF PAGE WAS |
| | CIRCLED WITH 9" ANCHOR SPACING. CHECK |
| | NOTE #1 FOR MAX. PANEL SPAN AND REVISE |
| | AS REQUIRED. |
| | |
| | 7- ACCORDING TO THE KEY PLAN ALL |
| | OPENINGS IN THIS APARTMENT, INCLUDING |
| | ENTRY DOOR ARE GOING TO HAVE SHUTTERS. |
| | CLARIFY HOW IS EMERGENCY EGRESS ACHIEVED |
| | TO COMPLY WITH SEC. 1008.1.3.6 FBC 2004. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |