Plan Review Details - Permit 05100121
Plan Review Stops For Permit 05100121
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2005-12-22 Cont ID  
Sent By btrobaug Date 2005-12-22 Time 08:23 Rev Time 1.00
Received By btrobaug Date 2005-12-22 Time 07:12 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-10-06 Cont ID  
Sent By btrobaug Date 2005-10-06 Time 09:03 Rev Time 0.50
Received By btrobaug Date 2005-10-06 Time 07:28 Sent To PC
Notes
2005-10-06 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
  
 1} PLANDS MUST BEAR THE PRINTED AND
 SIGNED NAME OF THE DESIGNER, SEE 104.2.1
 FBC.
  
 2} SUBMIT A RISER DIAGRAM INDICATING THE
 GROUNDING ELECTRODE SYSTEM AND SIZE OF
 THAT CONDUCTOR. 250.50 & 250.66.
  
 3} THE CONDUCTORS APPEAR TO BE PASSING
 THROUGH THE BUILDING FROM THE METER.
 ARTICLE 230.70 REQUIRES A DISCONNECTING
 MEANS FOR THE UNGROUNDED CONDUCTORS.
 SHOW COMPLIANCE WITH A DISCONNECT AT THE
 NEW METER LOCATION ON THE RISER DIAGRAM.
 INDICATE THE AMPERAGE RATING OF SAME.
  
 4} THE 1/0 SERVICE CONDUCTORS ARE TOO
 SMALL FOR THE 200 AMP PANEL THEY ARE
 SERVING. SEE 310.15(B)(6).,SHOW THE OCP
 AT THE FIRST MEANS OF DISCONNECT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-16 Cont ID  
Sent By adarroug Date 2005-12-16 Time 10:15 Rev Time 0.00
Received By adarroug Date 2005-12-16 Time 10:15 Sent To E
Notes
2005-12-16 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-05 Cont ID  
Sent By adarroug Date 2005-10-05 Time 09:40 Rev Time 0.00
Received By adarroug Date 2005-10-05 Time 09:40 Sent To E
Notes
2005-10-05 00:00:00TO "E" BOX