Plan Review Details - Permit 05100118
Plan Review Stops For Permit 05100118
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-03-15 Cont ID  
Sent By jgomez Date 2006-03-15 Time 15:44 Rev Time 0.40
Received By jgomez Date 2006-03-15 Time 15:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date 2006-03-07 Cont ID  
Sent By jgomez Date 2006-03-07 Time 17:42 Rev Time 0.00
Received By jgomez Date 2006-03-10 Time 16:15 Sent To B
Notes
2006-03-10 00:00:00BUILDING REVIEW COMMENTS TO PROCESS
 LOCAL PRODUCT APPROVAL APPLICATION:
 1- APPLICATION FOR LOCAL PRODUCT
 APPROVAL NEEDS TWO COPIES OF LOCAL
 PRODUCT APPROVAL FORM WITH APPLICANTS
 ORIGINAL SIGNATURE AND DATE.
  
 2- APPLICATION TO ADDRESS SPECIFIC DADE
 COUNTY NOA NUMBER THAT WAS SUBMITTED TO
 OBTAIN LOCAL PRODUCT APPROVAL. PROVIDE
 THIS INFORMATION ON ITEM #1 OF
 APPLICATION. EG: ACCORDION SHUTTERS PER
 DADE COUNTY NOA #05-0815.17.
 ALSO, PROVIDE NOA NUMBER ON ITEM #8,
 WHICH COVERS ALL REQUIRED INFORMATION.
  
 3- ITEM #6: A) SPECIFY TITLE OF
 APPLICANT'S TECHNICAL REPRESENTATIVE.
  
 B) FLORIDA PROFESSIONAL REGISTRATION
 NUMBER REFERS TO ENGINEERS OR ARCHITECTS
 ONLY, NOT GENERAL CONTRACTOR. REVISE AS
 REQUIRED.
  
  
 4- ITEM #7: THIRD PARTY QUALITY
 ASSURANCE ENTITY IS DONE BYDADE COUNTY
 BUILDING CODE COMPLIANCE OFFICE (SEE
 DADE COUNTY NOA), NOT THORNTON-TOMASETTI
 GROUP. QUALITY ASSURANCE ENTITY MUST BE
 APPROVED BY THE FLORIDA BUILDING
 COMMISSION. REVISE ALL INFORMATION AS
 REQUIRED.
  
  
 ***NOTE:
 PROVIDE ALL THIS INFORMATION TO PROCESS
 LOCAL PRODUCT APPROVAL APPLICATION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-01 Cont ID  
Sent By jgomez Date 2005-12-01 Time 10:53 Rev Time 0.50
Received By jgomez Date 2005-12-01 Time 10:53 Sent To PC
Notes
2005-12-01 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED FLORIDA PRODUCT APPROVAL OR
 APPLY FOR LOCAL PRODUCT APPROVAL FOR
 SHUTTERS AS REQUIRED BY RULE 9B-72 OF
 DCA (COMPLYING WITH FBC 2004). GO TO
 WWW.FLORIDABUILDING.ORG FOR PRODUCT
 APPROVAL INFORMATION.
 ***NOTE: DADE COUNTY NOA ALONE IS NOT
 AUTOMATICALLY AN STATEWIDE FLORIDA
 PRODUCT APPROVAL. IF MANUFACTURER HASN'T
 APPLIED FOR FLORIDA PRODUCT APPROVAL,
 THEN, MANUFACTURER MAY APPLY FOR LOCAL
 PRODUCT APPROVAL USING THE DADE COUNTY
 NOA AND COMPLETING THE LOCAL PRODUCT
 APPROVAL FORM DOWNLOADED FROM WEBSITE
 WWW.FLORIDABUILDING.ORG.
  
 2- ACCORDING TO NOA NO 02-1216.12 SHEET
 1 OF 1 OF DWG 02-561 GENERAL NOTE 2(A)
 THE MAX. SHUTTER SPAN IS 8'-0". PROPOSED
 SHUTTER IS 9'-0", THEREFORE, IT CAN'T BE
 USED.
  
 3- PROVIDE COMPLETE INSTALLATION
 SCHEDULE (SEE ATTACHED SAMPLE) AS REQ'D
 BY CITY IMPLEMENTATION STANDARD FOR
 HURRICANE MISSILE IMPACT PROTECTION AND
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
  
 4- NOTICE OF COMMENCEMENT IS EXPIRED
 AFTER 90 DAYS OF RECORDING IF WORK IS
 NOT STARTED. SEC. 713.13(2) OF FLORIDA
 STATUTES. NEED RE-RECORDED NOTICE OF
 COMMENCEMENT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-04 Cont ID  
Sent By adarroug Date 2006-03-04 Time 14:52 Rev Time 0.00
Received By adarroug Date 2006-03-04 Time 14:52 Sent To  
Notes
2006-03-04 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-05 Cont ID  
Sent By adarroug Date 2005-10-05 Time 18:27 Rev Time 0.00
Received By adarroug Date 2005-10-05 Time 18:27 Sent To B
Notes
2005-10-05 00:00:00TO "MISC" BOX#1