Plan Review Details - Permit 05100089
| Plan Review Stops For Permit 05100089 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2006-08-17 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-08-17 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2006-08-17 |
Time |
09:31 |
Sent To |
|
|
| Notes |
| 2006-08-17 00:00:00 | NEW ADDRESS HAS BEEN ISSUED FOR THIS | | | LOCATION AS 1552 PALM BEACH LAKES | | | BLVD,ATTACH PERMIT |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2006-03-02 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-03-02 |
Time |
09:24 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2006-05-23 |
Time |
10:08 |
Sent To |
PC |
|
| Notes |
| 2006-03-02 00:00:00 | NEED REPLAT ,PRIVATE STREET TO BE NAMED | | | BEFORE ISSUING AN ADDRESS. | | | | | | NAME SCHMITZ ENTERED IN ERROR 3-04-06 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
14 |
Status |
P |
Date |
2007-10-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-10-30 |
Time |
07:11 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2007-10-29 |
Time |
16:44 |
Sent To |
|
|
| Notes |
| 2007-10-30 07:11:49 | TRUSS SHOP DRAWINGS OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
13 |
Status |
P |
Date |
2007-10-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-10-23 |
Time |
11:50 |
Rev Time |
1.22 |
| Received By |
jwitmer |
Date |
2007-10-23 |
Time |
11:50 |
Sent To |
|
|
| Notes |
| 2007-10-23 11:57:35 | YKK AP | | | YHS-50 FS STOREFRONT SYSSTEM NOA 06-1026.08 | | | 35H(MS)STOREFRONT DOOR W/ TRANSOM |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
12 |
Status |
F |
Date |
2007-10-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-10-23 |
Time |
11:44 |
Rev Time |
0.33 |
| Received By |
jwitmer |
Date |
2007-10-23 |
Time |
11:44 |
Sent To |
PC |
|
| Notes |
| 2007-10-23 11:47:54 | BUILDING PLAN REVIEW | | | PERMIT: 05100089 | | | ADD: 1552 PALM BEACH LAKES | | | CONT: KUEBLER BUILDERS | | | TEL: (419)467-6624 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2ND REVIEW-TRUSS SHOP DRAWINGREVIEW | | | ACTION: DENIED | | | | | | 1) PLEASE REVIEW 61G 15-23.002(1) & (2) ENGINEERS | | | SIGNINGAND SEALING PLANS, REPORTS ,ETC THE SIGNATURE IS | | | TO BE AN ORIGINAL, NOT COPIES THAT A ENBOSSED SEAL IS | | | PLACED ON EACH SHEET.PLEASE REVIEW REQUIREMENTS FOR A | | | COVER SHEET OR INDEX SHEET THAT MAY BE TO YOUR | | | BENEFIT.ENGINEERING TRUSS SHEETS HAVE BEEN RETAINED FOR | | | THE POSSIBLE REVIEW BY THE BOARD OF ENGINEERS. PLEASE | | | TAKE NOTE OF FLORIDA STATE STATUTE 471.025 WHEN PLANS | | | AND REPORTS ARE TO BE SIGNED AND SEALED. | | | | | | PLEASE SEE ATTACHMENT 553.80(2)(B). | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | | | | | | | | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
11 |
Status |
F |
Date |
2007-10-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-10-12 |
Time |
14:47 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2007-10-12 |
Time |
14:47 |
Sent To |
B |
|
| Notes |
| 2007-10-12 15:39:19 | BUILDING PLAN REVIEW | | | PERMIT: 05100089 | | | ADD: 1552 PALM BEACH LAKES | | | CONT: KUEBLER BUILDERS | | | TEL: (419)467-6624 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | TRUSS SHOP DRAWINGREVIEW | | | ACTION: DENIED | | | | | | 1) PLEASE REVIEW 61G 15-23.002(1) & (2) ENGINEERS | | | SIGNINGAND SEALING PLANS, REPORTS ,ETC THE SIGNATURE IS | | | TO BE AN ORIGINAL NOT COPIES THAT A ENBOSSED SEAL IS | | | PLACED ON EACH SHEET.PLEASE REVIEW REQUIREMENTS FOR A | | | COVER SHEET OR INDEX SHEET THAT MAY BE TO YOUR | | | BENEFIT. | | | | | | | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | | | | | | | | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
10 |
Status |
P |
Date |
2007-09-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-09-25 |
Time |
11:29 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2007-09-25 |
Time |
11:29 |
Sent To |
PC |
|
| Notes |
| 2007-09-25 11:30:52 | SUBMITTAL SPLICE HOOK BARS - LETTER MARK JOHNSON PE |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
P |
Date |
2007-09-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-09-14 |
Time |
14:36 |
Rev Time |
0.78 |
| Received By |
jwitmer |
Date |
2007-09-14 |
Time |
14:36 |
Sent To |
PC |
|
| Notes |
| 2007-09-14 14:47:08 | SUBMITTALS: | | | 1)LETTER SPLICE REPAIR FOR # 8 REINFORCEMENT IN THE | | | FRONT MASONRY WALL | | | 2) BEAM TO COLUMN REPAIR SK 8/29/07 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
F |
Date |
2007-09-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-09-04 |
Time |
11:33 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2007-09-04 |
Time |
11:33 |
Sent To |
|
|
| Notes |
| 2007-09-04 12:19:49 | PERMIT: 05100089 | | | ADD: 1552 PALM BEACH LAKES | | | CONT: KUEBLER BUILDERS | | | TEL: (419)467-6624 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | WINDOW & DOOR SHOP DRAWING REVIEW: | | | | | | ACTION: DENIED | | | REVISION: | | | YKK AP | | | | | | YES 45 FS STOREFRONT SYSTEM | | | 03-0801.04 MISSLE IMPACT RATING: NONE | | | | | | 1) THIS REVISION INDICATES THE USE OF A STOREFRONT | | | SYSTEM WITH NO LARGE MISSILE WILL REQUIRESTORM | | | SHUTTERS | | | | | | THE FOLLOWING IS TAKEN FROM THE BUILDING OFFICIALS | | | IMPLEMENTATION STANDARDS FOR HIGH WIND-BORNE DEBRIS | | | IMPACT PROTECTIONSTANDARD. | | | 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE | | | DEBRIS IMPACT PROTECTION | | | QUESTION# 13 RECOGNIZING SUCH CONCERNS AS ABSENTEE | | | OWNERS, OR CASES WHERE LONGER TIME & EFFORT IS | | | NECESSARY TO SECURE SHUTTERS ON LARGE OR MULTI-STORY | | | BUILDINGS, WHAT MEASURES ARE BEING RECOMMENDED OR | | | IMPLEMENTED TO ENSURE THAT COMPLETE INSTALLATION OR | | | SECURING IS DONE SUFFICIENTLY IN ADVANCE OF THE | | | HURRICANE? | | | | | | IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE | | | GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE, | | | SECTION 104.6 OF THE FLORIDA BUILDING CODE,BUILDING, | | | CHAPTER 1, | | | ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY | | | OF WEST PALM BEACH, PROVDES THE ABILITY FOR THE | | | BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR | | | ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION | | | OF EXISTING BUILDINGS. | | | | | | IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR | | | MULTI-STORY BUILDINGS, OR MULTIPLE BUILDINGS ON THE | | | SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST BE | | | SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS FOR | | | REVIEW BY THE CONSTRUCTION SRVICES DEPARTMENT. ANY SUCH | | | PLAN SHALL INCLUDE, AT A MINMUM, ON SITE LOCATION OF | | | THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE | | | SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH | | | COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND | | | THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS. | | | PROTECTION OF OPENINGS SHALL BE ACCOMPLISHEDWITHIN | | | TWELVE (12) HOURS OR LESS OF THE | | | OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES | | | OF A HURRICANE WATCH. | | | | | | PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD) | | | ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE | | | MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO | | | REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN | | | QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE, | | | DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED | | | UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE | | | MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE | | | BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO | | | SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE. | | | | | | IF STORM SHUTTERS ARE APPROVED FOR THIS PROJECT THE | | | FOLLOWING WOULD BE REQUIRED. | | | PRODUCT APPROVAL REPORT WITH THE FOLLOWING | | | INFORMATION. | | | PROVIDE STORM PANEL INFORMATION WITH INSTALLATION | | | SCHEDULE AND KEY PLAN WITH | | | SPECIFIC ANCHORS AND MOUNTING TO BE USED | | | FOR ALL NON-IMPACT GLAZING. | | | FBC 1606.1.4.FL BLD CODE 2001 SECTION 103.6, | | | 1606.1.4, 1707.4 & 3401.7.2.4. | | | PROCEDURES: 1(B) A COMPLETE INSTALLATION | | | SCHEDULE SUMMARIZING & IDENTIFYING | | | OPENING SIZES, STORY HEIGHTS, UNIT MARK | | | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM | | | BAR REINFORCING REQUIREMENTS, WALL PRES- | | | SURE ZONES, SLAT TYPES, ETC., SHALL BE | | | SUBMITTED AT TIME OF PERMIT APPLICATION | | | TO FACILITATE PLAN REVIEW AND PERMIT | | | ISSUANCE. | | | | | | | | | 2) WRONG ASCE7-98, SHOULD READ ASCE 7-02 | | | | | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | | REQUIREMENT, THE SPECIFIC | | | REQUIREMENT SHALL BE APPLICABLE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | | | | | | | | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2007-09-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-09-04 |
Time |
10:23 |
Rev Time |
1.55 |
| Received By |
jwitmer |
Date |
2007-09-04 |
Time |
10:23 |
Sent To |
PC |
|
| Notes |
| 2007-09-04 10:29:07 | BUILDING PLAN REVIEW | | | PERMIT: 05100089 | | | ADD: 1552 PALM BEACH LAKES | | | CONT: KUEBLER BUILDERS | | | TEL: (419)467-6624 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | WINDOW & DOOR SHOP DRAWING REVIEW: | | | | | | ACTION: DENIED: | | | REVISION: | | | YKK AP YHS 50 STOREFRONT IMPACT | | | YKK AP 35H(MS) STOREFRONT DOOR/ TRANSOM | | | | | | 1) 2) SHOP DRAWINGS,WINDOW NOTES 12 SHEET 1 OF 5. | | | NOTE 12 INDICATES MEETS THE DESIGN OF THE SOUTH | | | FLORIDA BUILDING CODE PLEASE CORRECT | | | AND SECOND THE WRONG ASCE 7 IS QOUTED USE THE CURRENT | | | STANDARD STATED IN CHAPTER 35 OF THE | | | 2004 FBC. | | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | | REQUIREMENT, THE SPECIFIC | | | REQUIREMENT SHALL BE APPLICABLE. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | | | | | | | | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2007-08-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-08-14 |
Time |
13:41 |
Rev Time |
1.33 |
| Received By |
jwitmer |
Date |
2007-08-14 |
Time |
13:41 |
Sent To |
PC |
|
| Notes |
| 2007-08-14 13:48:02 | STEEL SHOP DRAWINGS STRUCTURAL STEEL AND TRUSS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2007-04-24 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2007-04-24 |
Time |
18:08 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2007-04-24 |
Time |
18:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-03-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-03-08 |
Time |
12:19 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2007-03-08 |
Time |
12:05 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2006-10-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-10-02 |
Time |
17:27 |
Rev Time |
4.44 |
| Received By |
jwitmer |
Date |
2006-10-02 |
Time |
17:27 |
Sent To |
|
|
| Notes |
| 2006-10-02 00:00:00 | | | | BUILDING PLAN REVIEW | | | PERMIT: 05100089 | | | ADD: 1540 P B LAKES BLVD | | | CONT: "PLAN REVIEW" | | | RETAIL PROPERTY INVESTORS, | | | | | | LLC | | | TEL: (301)479-3248 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 3RD REVIEW | | | ACTION: DENIED | | | DO NOT IGNORE!!!! | | | ***VERY IMPORTANT NOTE*** | | | 1) WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & "REMOVE & | | | REPLACE" ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A | | | DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | THE DESIGN TEAM SHALL REMOVE ALL OF | | | THE PREVIOUS SHEETS THAT HAVE BEEN REVISED!!!!!!!! | | | | | | 2) COMPLIED. | | | | | | 3) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS | | | NOT ACTUALLY COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | | | 4) COMPLIED. | | | | | | 5) COMPLIED. | | | | | | 6) COMPLIED. | | | | | | 7) WILL REMAIN A NOTE, WILL BE ISSUED AS | | | A PROVISO: 109.3.10.* IMPACT OF | | | CONSTRUCTION. | | | | | | 8) WILL REMAIN A NOTE, WILL BE ISSUED AS | | | A PROVISO:109.3.10.1* HURRICANE | | | PROTECTION. | | | | | | 9) COMPLIED. | | | | | | 10) COMPLIED. | | | | | | 11) COMPLIED | | | | | | 12) COMPLIED | | | | | | 13) COMPLIED | | | | | | 14) COMPLIED | | | | | | 15) COMPLIED | | | | | | 16) COMPLIED | | | | | | 17) COMPLIED | | | | | | 18) COMPLIED | | | | | | 19) COMPLIED | | | | | | 20) COMPLIED | | | | | | 21) COMPLIED | | | | | | 22)BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-05-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-05-23 |
Time |
10:25 |
Rev Time |
3.33 |
| Received By |
jwitmer |
Date |
2006-05-23 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2006-05-23 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05100089 | | | ADD: 1540 P B LAKES BLVD | | | CONT: "PLAN REVIEW" | | | RETAIL PROPERTY INVESTORS, | | | | | | LLC | | | TEL: (301)479-3248 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2NDREVIEW | | | ACTION: DENIED | | | | | | 1) WHEN RESUBMITTING PLANS PLEASE | | | INDICATE THE REVISION & "REMOVE & | | | REPLACE" ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A | | | DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) @ND REQUEST, SUBMIT SURVEY WITH THE | | | PROPOSED BUILDING LAYOUT. PLANS | | | SUBMITTED ARE CIVIL PLANS NOT A SURVEY. | | | | | | 3) 2ND REQUEST, FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT BEFORE A | | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OF | | | COMMENCEMENT IS NOT ACTUALLY COMMENCED | | | WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | | | 4) SHEET C-3 NOW INDICATES (4) | | | HANDICAPPED SPACES:11-4.6.2 LOCATION. | | | ACCESSIBLE PARKING SPACES SERVING A | | | PARTICULAR BUILDING SHALL BE LOCATED ON | | | THE SHORTEST SAFELY ACCESSIBLE ROUTE OF | | | TRAVEL FROM ADJACENT PARKING TO AN | | | ACCESSIBLE ENTRANCE. | | | | | | 5) COMPLIED. | | | | | | 6) COMPLIED. | | | | | | 7)WILL REMAIN A NOTE , WILL BE ISSUED | | | WITH THIS AS A PROVISO: | | | 109.3.10* IMPACT OF CONSTRUCTION. ALL | | | CONSTRUCTION ACTIVITY REGULATED BY THIS | | | CODE SHALL BE PERMORMED IN A MANNER SO | | | AS NOT TO ADVERSLY IMPACT THE CONDITION | | | OF ADJACENT PROPERTY, UNLESS SUCH | | | ACTIVITY IS PERMITTED TO AFFECT SAID | | | PROPERTY PURSUANT TO A CONSENT BY THE | | | APPLICABLE PROPERTY OWNER, UNDER TERMS & | | | CONDITIONS AGREEABLE TO THE APPLICABLE | | | PROPERTY OWNER.THIS INCLUDES BUT IS NOT | | | LIMITED TO THE CONTROL OF DUST, NOISE, | | | WATER OR DRAINAGE RUN-OFF, DEBRIS, AND | | | THE STORAGE OF CONSTRUCTION MATERIALS. | | | NEW CONSTRUCTION ACTIVITY SHALL NOT | | | ADVERSELY IMPACT HISTORICSURFACE WATER | | | DRAINAGE FLOWS SERVING ADJACENT | | | PROPERTIES, & MAY REQUIRE SPECIAL | | | DRAINAGE DESIGNCOMPLYING WITH | | | ENGINEERING STANDARDS TO PRESERVE THE | | | POSITIVE PATTERNS OF THE AFFECTED | | | SITES.ACCORDINGLY, DEVELOPERS, | | | CONTRACTORS, AND OWNERS OF ALL NEW | | | RESIDENTIAL DEVELOPMENET, INCLUDING | | | ADDITIONS, POOLS, PATIOS, DRIVEWAYS, | | | DECKS, OR SIMILAR ITEMS, ON EXISTING | | | PROPERTIES RESULTING IN A DECREASE IN | | | EXCESS OF 800SQ FT OF PERMEABLE LAND | | | AREA ON ANY PARCELL SHALL AS A PERMIT | | | CONDITION, PROVIDE A PROFESSIONALY | | | PREPARED DRAINAGE PLAN CLEARLY | | | INDICATING COMPLIANCE WITH THIS | | | PARAGRAPH. UPON COMPLETION OF THE | | | IMPROVEMENT, A CERTIFICATE FROM A | | | LICENSED ENGINEER SHALL BE SUBMITTED TO | | | THE INSPECTOR IN ORDER TO RECEIVE | | | APPROVAL OF THE FINAL INSPECTION. | | | | | | 8) WILL REMAIN A NOTE, WILL BE ISSUED AS | | | A PROVISO: | | | 109.3.10.1 HURICANE PROTECTION. | | | IT SHALL BE UNLAWFUL FOR ANY PERSON TO | | | ALLOW CONSTRUCTION RELATED MATERIALS | | | EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR | | | OTHERWISE UNSECURED AT A CONSTRUCTION | | | SITE FROM 24 HRS. AFTER A HURRICANE | | | WATCH HAS BEEN ISSUED UNTIL THE | | | HURRICANE WATCH OR WARNING HAS BEEN | | | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, | | | EQUIPMENT AND DEBRIS SHALL BE EITHER | | | REMOVED FROM THE CONSTRUCTION SITE OR | | | SECURED IN SUCH A MANNER AS TO MINIMIZE | | | THE DANGER OF SUCH CONSTRUCTION | | | MATERIALS, EQUIPMENT AND DEBRIS CAUSING | | | DAMAGE TO PERSONS OR PROPERTY FROM | | | HIGHWINDS. | | | ANY PERSONS WHO FAILS TO COMPLY TO | | | REMOVE OR SECURE THE CONSTRUCTION | | | MATERIALS EQUIPMENT AND DEBRIS WITHIN | | | 24 HRS AFTER A HURRICANE WATCH HAS BEEN | | | ISSUED SHALL BE SUBJECT TO A FINE NOT TO | | | EXCEED $500.00. | | | IN ADDITION TO THE ABOVE, A LICENSED | | | CONTRACTOR WHO VIOLATES THIS SECTION | | | SHALL BE SUBJECT TO DISCIPLINE PURSUANT | | | TO SECTION 113 OF THIS CHAPTER. | | | | | | 9A-F) COMPLIED. | | | | | | 10) COMPLIED. | | | | | | 11) PRODUCT APPROVALS | | | A) METAL EXT DOORS- COMPLIED | | | B) GLAZED DOORS- COMPLIED | | | C) WINDOWS- COMPLIED | | | D) MULLIONS_ COMPLIED | | | E) EFIS- COMPLIED | | | F) AWNINGSUNDER SEPERATE PERMIT. | | | G) ROOFING ASSEMBLIES: | | | ROOF INSULATION- COMPLIED | | | UNDERLAYMENT- COMPLIED | | | MODIFIED- COMPLIED | | | H)MONIER TILE- CONTRACTOR TO | | | HIGHLIGHT WHICH FASTENER TYPE ( | | | (FT-LBS) | | | | | | 12) COMPLIED- AWNINGS UNDER SEPERATE | | | PERMIT. | | | | | | 13) COMPLIED. | | | | | | 14) COMPLIED. | | | | | | 15) COMPLIED. | | | | | | 16A) ENERGY FORMS- THIS IS STILL A PLAN | | | REVIEW WHEN TURNED TO PERMIT RAISED SEAL | | | IS REQUIRED. | | | PLANS, SPECIFICATIONS,REPORTS OR | | | OTHER DOCUMENTS PREPARED BY THE DESIGN | | | PROFESSIONAL AND BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | | TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | | | | 16B) WILL BE THE WRONG FORM, WILL NEED | | | TO BE FORM 400A-2004 FOR PERMIT. | | | | | | 17) THE ENERGY FORM WHEN TURNED INTO | | | PERMIT WILL REQUIRE:NOTE PLANS | | | SUBMITTED AFTER 01-01-06 FOR PERMIT | | | APPLICATION SHALL HAVE THE WORD | | | "LICENSE" RATHER THAN CERTIFICATE ON THE | | | EMBOSSED SEAL. RULE 61G15-23.001(1) | | | | | | 18) SHEET S1.0 STILL REFRENENCES THE | | | WRONG ASCE, 2004 CODE / ASCE 7-02. | | | | | | 19) COMPLIED. | | | | | | 20) @ND REQUEST, THE SOILS REPORTS | | | SUBMITTED IN THE PROJECT MANUAL ARE | | | COPIES. | | | PLANS, SPECIFICATIONS,REPORTS OR | | | OTHER DOCUMENTS PREPARED BY THE DESIGN | | | PROFESSIONAL AND BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | | TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | | | | FL BLD CODE 1802.2.1 QUESTIONABLE | | | SOILS, WHERE THE BEARING CAPACITY IS | | | NOT DEFINETLY KNOWN OR IS IN QUESTION. | | | WHERE THE BEARING CAPACITY OF THE SOIL | | | IS NOT DEFINITLY KNOWN OR IS IN QUESTION | | | THE BUILDING OFFICIAL MAY REQUIRE EXPLOR | | | ATIONS, TEST OR OTHER ADEQUATE PROOF AS | | | TO THE PERMISSIBLE SAFE BEARING | | | CAPACITY. REQUIRED TEST AND RECOMMENDA- | | | TIONS SUBMITTED TO VERIFY BEARING CAPA- | | | CITY SHALL BE CERTIFIED BY A GEOTECH- | | | NICALREPORT FROM A DESIGN PROFESSIONAL | | | PROPERLY LICENSED IN THE STATE OF | | | FLORIDA. | | | | | | 21) COMPLIED | | | | | | 22) 2ND REQUEST.BEFORE A PERMIT TO | | | CONSTRUCT, MAY BE ISSUED, IMPACT FEES | | | MUST BE PAID TO PALM BEACH COUNTY. THE | | | ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-03-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-03-01 |
Time |
13:08 |
Rev Time |
5.55 |
| Received By |
jwitmer |
Date |
2006-03-01 |
Time |
13:07 |
Sent To |
|
|
| Notes |
| 2006-03-01 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05100089 | | | ADD: 1540 P B LAKES BLVD | | | CONT: "PLAN REVIEW" | | | RETAIL PROPERTY INVESTORS, | | | | | | LLC | | | TEL: (301)479-3248 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | 1) SEE ADDRESSING CONTACT LILI URSA AT | | | (561)822-1239 FOR APPROVED ADDRESS AND | | | SUBMIT REPLAT. | | | | | | 2) SUBMIT SURVEY WITH PROPOSED BUILDING | | | ON SURVEY. | | | | | | 3) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | NOTE RECORDED NOC IF WORK HAS NOT | | | STARTED WITHIN 90 DAYS OF RECORDING, NOC | | | BECOMES NULL AND VOID REQUIRING | | | RE-RECODING. FL S S 713.13(2) | | | | | | 4)SHEET C-3 INDICATES ONLY 2 HANDICAPPED | | | SPOTS WHILE 3 ARE REQUIRED.11-4.1.2(5) | | | PARKING SPACES: | | | (A)IF PARKING SPACES ARE PROVIDED FOR | | | SELF-PARKING BY EMPLOYEES OR VISITORS, | | | OR BOTH, THEN ACCESSIBLE SPACES | | | COMPLYING WITH SECTION 11-4.6 SHALL BE | | | PROVIDED IN EACH SUCH PARKING AREA. SUCH | | | SPACES SHALL BE DESIGNED AND MARKED FOR | | | EXCLUSIVE USE OF THOSE INDIVIDUALS WHO | | | HAVE A SEVERE PHYSICAL DISABILITY AND | | | HAVE PERMANENT OR TEMPORARY MOBILITY | | | PROBLEMS THAT SUBSTANTIALLY IMPAIR THEIR | | | ABILITY TO AMBULATE AND WHO HAVE BEEN | | | ISSUED EITHER A DISABLED PARKING PERMIT | | | UNDER SECTION 316.1958 OR 320.0848, | | | FLORIDA STATUTES, OR A LICENSE PLATE | | | UNDER SECTION 320.084, 320.0842, | | | 320.0843, OR 320.0845, FLORIDA STATUTES. | | | THE NUMBER OF ACCESSIBLE PARKING SPACES | | | SHALL COMPLY WITH THE TABLE BELOW AND | | | THE FOLLOWING: | | | | | | TOTAL PARKING IN LOT | | | REQUIRED MINIMUM NUMBER OF ACCESSIBLE | | | SPACES | | | 1 TO 251 | | | 26 TO 502 | | | 51 TO 753 | | | | | | 5)SHEET C-3 SHOW COMPLICANCE WITH | | | 11-4.1.2(1) | | | AT LEAST ONE ACCESSIBLE ROUTE COMPLYING | | | WITH SECTION 11-4.3 SHALL BE PROVIDED | | | WITHIN THE BOUNDARY OF THE SITE FROM | | | PUBLIC TRANSPORTATION STOPS, ACCESSIBLE | | | PARKING SPACES, PASSENGER LOADING ZONES | | | IF PROVIDED, AND PUBLIC STREETS OR | | | SIDEWALKS, TO AN ACCESSIBLE BUILDING | | | ENTRANCE. | | | | | | 6) SHEET AA INDICATES THE WRONG CODE, | | | OCT 1, 2006 PLANS SUBMITTED ON THIS DATE | | | AND AFTER WILL BE REVIEWED UNDER THE | | | 2004 FL BUILDING CODE. NOTE, IF PLANS | | | SUBMITTED BEFORE THIS DATE UNDER PLAN | | | REVIEW AND NO PERMIT APPLICATION WAS | | | APPLIED FOR BEFORE OCT 1, 2006, THE | | | PROJECT WILL NEED TO BE RE-REVIEWED | | | UNDER THE 2004 FBC. | | | | | | 7) 109.3.10* IMPACT OF CONSTRUCTION. ALL | | | CONSTRUCTION ACTIVITY REGULATED BY THIS | | | CODE SHALL BE PERMORMED IN A MANNER SO | | | AS NOT TO ADVERSLY IMPACT THE CONDITION | | | OF ADJACENT PROPERTY, UNLESS SUCH | | | ACTIVITY IS PERMITTED TO AFFECT SAID | | | PROPERTY PURSUANT TO A CONSENT BY THE | | | APPLICABLE PROPERTY OWNER, UNDER TERMS & | | | CONDITIONS AGREEABLE TO THE APPLICABLE | | | PROPERTY OWNER.THIS INCLUDES BUT IS NOT | | | LIMITED TO THE CONTROL OF DUST, NOISE, | | | WATER OR DRAINAGE RUN-OFF, DEBRIS, AND | | | THE STORAGE OF CONSTRUCTION MATERIALS. | | | NEW CONSTRUCTION ACTIVITY SHALL NOT | | | ADVERSELY IMPACT HISTORICSURFACE WATER | | | DRAINAGE FLOWS SERVING ADJACENT | | | PROPERTIES, & MAY REQUIRE SPECIAL | | | DRAINAGE DESIGNCOMPLYING WITH | | | ENGINEERING STANDARDS TO PRESERVE THE | | | POSITIVE PATTERNS OF THE AFFECTED | | | SITES.ACCORDINGLY, DEVELOPERS, | | | CONTRACTORS, AND OWNERS OF ALL NEW | | | RESIDENTIAL DEVELOPMENET, INCLUDING | | | ADDITIONS, POOLS, PATIOS, DRIVEWAYS, | | | DECKS, OR SIMILAR ITEMS, ON EXISTING | | | PROPERTIES RESULTING IN A DECREASE IN | | | EXCESS OF 800SQ FT OF PERMEABLE LAND | | | AREA ON ANY PARCELL SHALL AS A PERMIT | | | CONDITION, PROVIDE A PROFESSIONALY | | | PREPARED DRAINAGE PLAN CLEARLY | | | INDICATING COMPLIANCE WITH THIS | | | PARAGRAPH. UPON COMPLETION OF THE | | | IMPROVEMENT, A CERTIFICATE FROM A | | | LICENSED ENGINEER SHALL BE SUBMITTED TO | | | THE INSPECTOR IN ORDER TO RECEIVE | | | APPROVAL OF THE FINAL INSPECTION. | | | | | | 8) 109.3.10.1 HURICANE PROTECTION. | | | IT SHALL BE UNLAWFUL FOR ANY PERSON TO | | | ALLOW CONSTRUCTION RELATED MATERIALS | | | EQUIPMENET AND DEBRIS TO REMAIN LOOSE OR | | | OTHERWISE UNSECURED AT A CONSTRUCTION | | | SITE FROM 24 HRS. AFTER A HURRICANE | | | WATCH HAS BEEN ISSUED UNTIL THE | | | HURRICANE WATCH OR WARNING HAS BEEN | | | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, | | | EQUIPMENT AND DEBRIS SHALL BE EITHER | | | REMOVED FROM THE CONSTRUCTION SITE OR | | | SECURED IN SUCH A MANNER AS TO MINIMIZE | | | THE DANGER OF SUCH CONSTRUCTION | | | MATERIALS, EQUIPMENT AND DEBRIS CAUSING | | | DAMAGE TO PERSONS OR PROPERTY FROM | | | HIGHWINDS. | | | ANY PERSONS WHO FAILS TO COMPLY TO | | | REMOVE OR SECURE THE CONSTRUCTION | | | MATERIALS EQUIPMENT AND DEBRIS WITHIN | | | 24 HRS AFTER A HURRICANE WATCH HAS BEEN | | | ISSUED SHALL BE SUBJECT TO A FINE NOT TO | | | EXCEED $500.00. | | | IN ADDITION TO THE ABOVE, A LICENSED | | | CONTRACTOR WHO VIOLATES THIS SECTION | | | SHALL BE SUBJECT TO DISCIPLINE PURSUANT | | | TO SECTION 113 OF THIS CHAPTER. | | | | | | 9) 110.2* W. P. B. ADMINISTRATIVE CODE, | | | INFORMATION THAT IS REQUIRED FOR RECORD | | | KEEPING & FOR CERTIFICATE OF OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH | | | THE PERMIT WAS ISSUED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | | WITH THE PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | | IN CHAPTER 6, TABLE 601. | | | D) THE DESIGN OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | | IS REQUIRED. | | | F) ANY SPECIAL STIPULATIONS & CONDITIONS | | | OF THE BUILDING PERMIT. | | | | | | 10) 1609.1.4 PROTECTION OF OPENINGS. | | | IN WIND-BORNE DEBRIS REGIONS, EXTERIOR | | | GLAZING THAT RECEIVES POSITIVE PRESSURE | | | IN THE LOWER 60 FEET (18.3 M) IN | | | BUILDINGS SHALL BE ASSUMED TO BE | | | OPENINGS AND THE BALANCE OF GLAZED | | | OPENINGS IN THE REST OF THE BUILDING | | | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH | | | GLAZING THAT RECEIVES POSITIVE PRESSURE | | | IS IMPACT RESISTANT OR PROTECTED WITH AN | | | IMPACT RESISTANT COVERING MEETING THE | | | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND | | | ASTM E 1996, OR MIAMI-DADE TAS 201, 202 | | | AND 203 REFERENCED THEREIN AS FOLLOWS: | | | 1.GLAZED OPENINGS LOCATED WITHIN 30 | | | FEET (9.1 M) OF GRADE SHALL MEET THE | | | REQUIREMENTS OF THE LARGE MISSILE TEST. | | | 2.GLAZED OPENINGS LOCATED MORE THAN | | | 30 FEET (9.1 M) ABOVE GRADE SHALL MEET | | | THE PROVISIONS OF THE SMALL MISSILE | | | TEST. | | | | | | 11) FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) METAL EXTERIOR DOORS | | | B) GLAZED DOORS | | | C) WINDOWS | | | D) MULLIONS | | | E) EFIS SYSTEMS AND COMPONENTS | | | F) AWNINGS | | | G) ROOFING ASSEMBLIES | | | FLAT ROOF MEMBRANE | | | INSULATION | | | UNDERLAYMENT | | | TILE | | | | | | 12) FABRIC AWNINGS: | | | 3105.4.1 | | | DESIGN OF THE FRAMING MEMBERS SHALL NOT | | | BE BASED ON REMOVAL OR REPOSITIONING OF | | | PARTS, OR THE WHOLE, DURING PERIODS OF | | | 75 MPH WIND VELOCITY. | | | | | | 3105.4.2 | | | DESIGN OF THE STRUCTURAL FRAMING MEMBERS | | | SHALL BE BASED ON RATIONAL ANALYSIS, | | | USING THE APPLICABLE WIND LOADS OF | | | CHAPTER 16 AS SHOWN BELOW: | | | | | | 3105.4.2.1 | | | THE WIND DESIGN LOADS FOR ANY FABRIC OR | | | MEMBRANE-COVERED STRUCTURE DESIGNED WITH | | | A QUICK REMOVAL OR BREAKAWAY MEMBRANE OR | | | FABRIC AT WIND VELOCITIES OF 75 MPH, | | | SHALL BE BASED ON THE FOLLOWING | | | CRITERIA: | | | 1.MINIMUM WIND VELOCITY OF 3-SECOND | | | WIND GUST 90 MPH | | | 2.IMPORTANCE FACTOR BASED ON LOW | | | HAZARD TO HUMAN LIFE OF 0.77. | | | 3.EXPOSURE CATEGORY B FOR OR C AS | | | DEFINED IN CHAPTER 16 . | | | | | | 3105.4.2.2 | | | THE WIND DESIGN LOADS FOR ANY FABRIC OR | | | MEMBRANE COVERED STRUCTURE DESIGNED WITH | | | A PERMANENT OR NONREMOVABLE FABRIC OR | | | MEMBRANE, SHALL BE BASED ON THE | | | FOLLOWING CRITERIA: | | | 1.MINIMUM WIND VELOCITY AS REQUIRED | | | IN CHAPTER 16 . | | | 2.IMPORTANCE FACTOR BASED ON LOW | | | HAZARD TO HUMAN LIFE OF 0.77. | | | 3.EXPOSURE CATEGORY B OR C AS | | | DEFINED IN CHAPTER 16 . | | | | | | 3105.4.2 | | | THE FABRIC PORTIONS OF AWNINGS FABRIC | | | COVERED FRAMES SHALL BE SECURELY LACED, | | | TIED OR OTHERWISE FASTENED TO THE FRAME; | | | NO RAFTER OR FRONT BAR WILL BE PERMITTED | | | IN POCKETS; AND IN NO CASE SHALL A | | | ROLLING CURTAIN BE CAUSED TO OPERATE | | | OVER A CANOPY FRAME. | | | | | | 3105.4.3 | | | THE HORIZONTAL PROJECTION OF | | | CANTILEVERED PORTIONS SHALL NOT BE | | | GREATER THAN TWO TIMES THE HEIGHT, | | | EXCEPT WHERE THE BUILDING CONSTRUCTION | | | DOES NOT PERMIT A PROPER INSTALLATION; | | | IN WHICH CASE, VARIANCE MAY BE PERMITTED | | | BY THE BUILDING OFFICIAL, BASED ON | | | SPECIAL DESIGN AND CONSTRUCTION. | | | | | | 13) CONCENTRATED LOADS PROVIDE | | | INFORMATION ON THE CONCENTRATED LOADS OF | | | THE AIR HANDLERS ON THE ROOF ABOVE THE | | | BAR JOIST.1607.4 CONCENTRATED LOADS . | | | FLOORS AND OTHER SIMILAR SURFACES SHALL | | | BE DESIGNED TO SUPPORT THE UNIFORMLY | | | DISTRIBUTED LIVE LOADS PRESCRIBED IN | | | SECTION 1607.3 OR THE CONCENTRATED LOAD, | | | IN POUNDS (KILONEWTONS), GIVEN IN TABLE | | | 1607.1 , WHICHEVER PRODUCES THE GREATER | | | LOAD EFFECTS. UNLESS OTHERWISE | | | SPECIFIED, THE INDICATED CONCENTRATION | | | SHALL BE ASSUMED TO BE UNIFORMLY | | | DISTRIBUTED OVER AN AREA 2.5 FEET BY 2.5 | | | FEET [6.25 FT 2 (0.58 M 2 )] AND SHALL | | | BE LOCATED SO AS TO PRODUCE THE MAXIMUM | | | LOAD EFFECTS IN THE STRUCTURAL MEMBERS. | | | | | | 14) PROVIDE INFORMATION ON ATTACHMENT OF | | | THE ROOF TOP AIR HANDLERS TO THE ROOF | | | DECK. ADDITIONAL INFORMATION. | | | | | | 15) NOTE PROVIDE THE EFIS PRODUCT | | | APPROVAL REPORT, ALSO PROVIDE | | | INFORMATION ON EFIS FOR HORIZONTAL | | | APPLICATION. | | | | | | 16) ENGINEER TO SIGN AND SEAL PLANS SO | | | SEAL IS VISIBLE. | | | PLANS, SPECIFICATIONS,REPORTS OR | | | OTHER DOCUMENTS PREPARED BY THE DESIGN | | | PROFESSIONAL AND BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | | TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | | | | 17) SEAL IS UNREADABLE STAMPED OVER THE | | | ENGINEERS HEADER. NOTE PLANS SUBMITTED | | | AFTER 01-01-06 FOR PERMIT APPLICATION | | | SHALL HAVE THE WORD "LICENSE" RATHER | | | THAN CERTIFICATE ON THE EMBOSSED SEAL. | | | RULE 61G15-23.001(1) | | | | | | 18) SHEET S.01 REVISE PLANS TO THE 2004 | | | FBC. | | | | | | 19) SHEET S.30 DETAIL 1 INDICATES USE OF | | | PLYWOOD SHEETHING, SEE TABLE 601 | | | FOOTNOTE (2). | | | IN TYPE I AND II CONSTRUCTION, | | | FIRE-RETARDANT-TREATED WOOD SHALL BE | | | ALLOWED IN BUILDINGS INCLUDING GIRDERS | | | AND TRUSSES AS PART OF THE ROOF | | | CONSTRUCTION WHEN THE BUILDING IS: | | | I. TWO STORIES OR LESS IN HEIGHT; | | | II. TYPE II CONSTRUCTION OVER TWO | | | STORIES; OR | | | III. TYPE I CONSTRUCTION OVER TWO | | | STORIES AND THE VERTICAL DISTANCE FROM | | | THE UPPER FLOOR TO THE ROOF IS 20 FEET | | | OR MORE. | | | | | | 20) SUBMIT GEOTECH REPORT: | | | 1802.2.1 QUESTIONABLE SOIL. | | | WHERE THE SAFE-SUSTAINING POWER OF THE | | | SOIL IS IN DOUBT, OR WHERE A | | | LOAD-BEARING VALUE SUPERIOR TO THAT | | | SPECIFIED IN THIS CODE IS CLAIMED, THE | | | BUILDING OFFICIAL SHALL REQUIRE THAT THE | | | NECESSARY INVESTIGATION BE MADE. SUCH | | | INVESTIGATION SHALL COMPLY WITH THE | | | PROVISIONS OF SECTIONS 1802.4 THROUGH | | | 1802.6 . | | | | | | 21) SHEET S.20 BAASE PLATE MISSING SIZE | | | OF WELD COLUMN TO BASE PLATE. | | | | | | 22) BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | 1609.1.4 PROTECTION OF OPENINGS. | | | IN WIND-BORNE DEBRIS REGIONS, EXTERIOR | | | GLAZING THAT RECEIVES POSITIVE PRESSURE | | | IN THE LOWER 60 FEET (18.3 M) IN | | | BUILDINGS SHALL BE ASSUMED TO BE | | | OPENINGS AND THE BALANCE OF GLAZED | | | OPENINGS IN THE REST OF THE BUILDING | | | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH | | | GLAZING THAT RECEIVES POSITIVE PRESSURE | | | IS IMPACT RESISTANT OR PROTECTED WITH AN | | | IMPACT RESISTANT COVERING MEETING THE | | | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND | | | ASTM E 1996, OR MIAMI-DADE TAS 201, 202 | | | AND 203 REFERENCED THEREIN AS FOLLOWS: | | | 1.GLAZED OPENINGS LOCATED WITHIN 30 | | | FEET (9.1 M) OF GRADE SHALL MEET THE | | | REQUIREMENTS OF THE LARGE MISSILE TEST. | | | 2.GLAZED OPENINGS LOCATED MORE THAN | | | 30 FEET (9.1 M) ABOVE GRADE SHALL MEET | | | THE PROVISIONS OF THE SMALL MISSILE | | | TEST. | | | ) 106.3.3* PRODUCT APPROVALS- 2004 | | | THOSE PRODUCTS THAT ARE RGULATED BY DCA | | | RULE 9B-72 SHALL BE REVIEWED AND | | | APPROVED IN WRITTING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2007-04-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-04-10 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-04-10 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2007-04-10 15:58:14 | ELEC OK,STAMPED ELEC. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2007-02-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-02-04 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-02-04 |
Time |
13:22 |
Sent To |
|
|
| Notes |
| 2007-02-04 14:51:40 | *** UNSAT 4TH REVIEW *** | | | | | | ** PLEASE SEE THIS IS THE FIRST REVIEW UNDER PERMIT | | | APPLICATION. THIS IS THE 4TH REVIEW FOR THE PROJECT. | | | | | | ** PLEASE SEE SOME OF THE NOTES ARE THE SAME FROM | | | PREVIOUS REVIEW. PLEASE ALSO SEE NEW COMMENTS DUE TO | | | CHANGES MADE TO PLANS, CHANGES IN CODE AND PLANS | | | SUBMITTED. | | | | | | | | | 1) NOTE: PLEASE SEE THAT THE PLANS WERE ONLY NOW | | | SUBMITTED FOR PERMIT APPLICATION ON JANUARY 16, 2007 | | | WHICH PLACES THE ENTIRE PROJECT UNDER THE NEW CODES | | | WHICH WERE ADOPTED BY THE STATE OF FLORIDA ON DECEMBER | | | 8TH, 2006. THIS INFORMATION WAS DIRECTLY CONVEYED TO | | | THE DESIGN TEAM AND ON PREVIOUS REVIEW NOTES THAT THE | | | PLANS WERE ONLY SUBMITTED UNDER *PLAN REVIEW* AND WERE | | | NOT SUBMITTED UNDER PERMIT APPLICATION. ONLY IF | | | SUBMITTED UNDER PERMIT APPLICATION BEFORE THE DECEMBER | | | 8TH, 2006 DATE WOULD THIS PROJECT FALL UNDER THE | | | PREVIOUS CODES? | | | THIS INFORMATION WAS ALSO GIVEN TO THE CONTRACTOR | | | BEFORE THE PLANS WERE SUBMITTED THAT THE NEW CODES WENT | | | INTO AFFECT AND THE CONTRACTOR MENTIONED HE WAS ASSURED | | | BY THE DESIGN TEAM THAT THE PLANS HAD BEEN CHANGED, | | | HOWEVER THE PLANS HAVE NOT CHANGED AND THE CODES ARE | | | STILL UNDER THE OLD CODES. | | | PLEASE SEE THAT PLANS SHALL NOW BE DESIGNED UNDER 2006 | | | REVISIONS TO THE 2004 FBC, AND THE 2005 NEC. | | | (NFPA-70). | | | | | | 2) NOTE: PLEASE SEE HAND DRAWN CHANGES TO THE | | | ELECTRICAL PLANS WERE DONE AND SOME ARE SIGNED BY OTHER | | | THAN THE ENGINEER OF RECORD OF THOSE SHEETS. THE | | | SIGNATURE AS ON THE ARCHITECTURAL PLANS IS THAT ON THE | | | ELECTRICAL PLANS. | | | PLEASE ALSO SEE OTHER ITEMS WHICH WERE HAND DRAWN ON | | | PLANS WITH OUT ANY INFORMATION WHICH IS NOT PERMITTED. | | | PLEASE RE-PRINT ALL SHEETS FOR CODE CORRECTIONS, AND | | | OTHER ITEMS HAND DRAWN ON PLANS AND HAVE PLANS | | | RE-SIGNED, DATED AND SEALED BY THE DESIGNER(S) OF | | | RECORD WHICH ARE RESPONSIBLE FOR THEIR SHEETS ONLY. | | | FS 471.025, FAC 61G15-23.002 | | | FBC 106.1, 106.3.5.1.2 | | | ** PLEASE KNOW THAT ONE SET OF PLANS ARE NOW BEING | | | RETAINED BY THIS OFFICE. | | | | | | 3) NOTE: PLEASE SEE ONLY ONE SET OF UPDATED ENERGY | | | CALCULATIONS WERE SUBMITTED AND THE DATES ON THOSE WERE | | | 12/11/06. PLEASE SEE THAT IN ANY CASE THEY DO NOT | | | CORRELATE WITH THE PLANS FOR LIGHTING ALLOWANCES. | | | PLEASE SEE THE 2006 REVISIONS TO THE 2004 FBC CHAPTER | | | HAVE HAD REVISIONS. | | | PLEASE SEE 13-415.1.AB.1 AND 13-415.2 FOR PERFORMANCE | | | CALCULATIONS WHICH NEED TO CORRELATE WITH THE ENERGY | | | CALCULATIONS AND PLANS FOR MAXIMUM LIGHTING | | | ALLOWANCES. | | | | | | 4) NOTE: PLEASE SEE COMPLIANCE WITH CHAPTER 13 HAS NOT | | | YET BEEN ACCOMPLISHED. PLEASE SEE THAT THE CODE HAS | | | CHANGED, HOWEVER ITEMS FROM PREVIOUS REVIEW HAVE NOT | | | YET BEEN COMPLETELY ADDRESSED. | | | PLEASE SEE ALL ENTRANCES INTO SPACE SHALL CONTAIN AN | | | OVER RIDE DEVICE OF SOME KIND. (FRONT DOOR?) WHICH DOES | | | NOT CONTAIN EITHER OC TYPE DEVICE TO OVER-RIDE THE | | | TIMED SCHEDULING OR AN OVER RIDE TYPE SWITCHING | | | DEVICE. | | | PLEASE SEE THE SWITCHES ON SW BANK *A* AND *B* DO NOT | | | INDICATE ANY MAXIMUM TIMES FOR OVER RIDE, ONLY THE SW | | | *C* INDICATES THE MAXIMUM OF 4HRS ON OVER RIDE. | | | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. | | | (PLEASE BE SURE TO SEE NEW 2006 REVISIONS TO THE 2004 | | | FBC). | | | | | | 5) NOTE: PLEASE SEE THE PHOTO-METRICS SUBMITTED NOW | | | CONTAIN A SIGNATURE AND LICENSE NUMBER FOR THE | | | ARCHITECT, HOWEVER NOT COMPLETE TITLE BLOCK IS ON | | | PLANS/SHEETS AND THEY ARE NOT SEALED WITH THE REQUIRED | | | RAISED SEAL. | | | FAC 61G1-16.004, FS 481.221 | | | | | | | | | ** ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2006-09-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-09-24 |
Time |
12:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-09-24 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2006-09-24 00:00:00 | ********** UNSAT 3RD REVIEW ********** | | | | | | **PLEASE KNOW PLANS ARE BEING SUBMITTED | | | FOR "PLAN REVIEW " FOR THE 3RD TIME. | | | | | | ** PLEASE SEE SOME COMMENTS FROM THE | | | PREVIOUS REVIEW HAVE NOT BEEN ADDRESSED | | | ANDNEW COMMENTS. | | | | | | | | | 1)NOTE: NO, COMPLETE COMPLIANCE WITH THE | | | FBC CHAPTER 13 IS NOT YET ACHIEVED. | | | PELASE SEE THAT ALL LIGHTING SHALL BE | | | AUTOMATICALLY SHUT OFF FOR INTERIOR. NL | | | CIRCUIT(S) ARE OK. ). | | | PLEASE SEE OVER -RIDES SHALL LOCATED IN | | | THE LOCATION OF INGRESS AND EGRES INTO | | | SPACES/AREAS AND THE OCCUPANT MUST BE | | | ABLE TO SEE ALL LIGHTING IN WHICH IS | | | BEING OVER-RIDEN. PLEASE SEE THAT ALL | | | OVER TIMES SHALL BE STATED ON PLANS FOR | | | THE DEVICES BEING CHOSEN. IF A TIMER | | | TYOE OFR OR, THEN 4HRS MAX, IF OCCUPANT | | | SENSOR TYOE THEN 30 MINS MAX. | | | PLEASE SEE ALSO ALL SEPARATE SPACES WITH | | | NFLR TO CEILING HEIGHT PARTITIONS. | | | PLEASE SEE MANY AREAS WHICH DO NOT | | | CONTAIN THESE OVER RIDES. | | | PLEASE SEE NO LIGHTING DENSITES ARE | | | SUBMITTED OR INDICATED. PLEASE SEE FORM | | | "A" SHOWS "MANUAL" MEANS FOR ALL | | | SHUTOFF, WHICH IS NOT THE CASE. | | | PLEASE SEE PERFORMANCE CALCULATIONS | | | WHICH LIMITS THE WATTAGE USEAGE. | | | PLEASE SEE FBC 2004 CHAPTER 13, | | | 13-415.1.ABC.1.1, .1.2 AND .1.3. | | | 13-415.1.AB.1 WHICH MENTIONS 415.2, THEN | | | SEE 13-415.2, 13-415.2.ABC.1, WHICH | | | GIVES TABLES 415.2.C.1, 415.2.B.1 | | | ** PLEASE KNOW, AS THIS INFORMATION HAS | | | NOT YET BEEN SUBMITTED, THIS CANE NOT BE | | | REVIEWED. | | | | | | ** PREVIOUS REVIEW NOTE REVIEW #2** | | | NOTE #1 NO, PLEASE SEE THAT THE | | | PREVIOUS REVIEW NOTE WAS ALSO FOR | | | COMPLIANCE OF THE FBC 2004. | | | PLEASE SEE REPSONSE MENTIONS, THE PLANS | | | INDICATED 2002 NEC. | | | PLEASE SEE FBC 2004, CHAPTER 13 | | | 413.1ABC.1 FOR VOLTAGE DROP CALCS | | | REQUIED FOR WORST CASE. | | | PLEASE SEE 13-413.1.ABC.2.2 | | | PLEASE SEE 13-415.1.ABC.1.1 , .2 AND .3 | | | PLEASE SEE A TIME CLOCK SYSTEM IS BEING | | | PROPOSED WITH SWITCHES LOCATED AT THE | | | ACCESSIBLE LOCATION, HOWEVER PLEASE | | | PROVIDE INFORMATION ON THESE SWITCHES. | | | THEY CAN OVER-RIDE NO LONGER THAN 4HRS. | | | PLEASE SEE SEPARATE SPACES AND CONTROLS | | | REQUIRED. | | | ** PLEASE SEE ENERGY CALCS SHEETS ARE | | | "RUBBER-STAMPED" WITHE THE ENGINEERS | | | SEAL WHICH IS NOT PERMITTED UNDER FS | | | 471.025. PLEASE ALSO SEE THE WORDING | | | "CERTIFICATE" IS NO LONGER PERMITTED IN | | | SAID SEALS. PLEASE SEE FAC 61G15-23.001, | | | IN A RULING PASSED IN FEB 04, IN WHICH | | | THE WORDING "CERTIFICATE" IN SEAL HAD TO | | | BE CHANGED TO "LICENSE". THE EXTENSION | | | GRANTED WAS TO DEC 31ST,2005. THESE TYOE | | | SEALS ARE NO LONGER PERMITTED. | | | | | | **PREVIOUS NOTE REVIEW #1 ** | | | PLEASE SEE THAT AS OF OCT 1ST, | | | 2005 THE STATE OF FLORIDA HAS NOW | | | ADOPTED THE 2004 FBC. PLEASE ADJUST ALL | | | LOCATIONS AND DESIGNS ON PLANS. | | | THIS IS REQUIRED FOR ALL TRADES AND FOR | | | ALL TRADES WHETHER OR NOT COMMENTS ARE | | | MADE BY OTHER REVIEWER(S). | | | PLEASE KNOW, WE ARE CURRENTLY UNDER THE | | | 2002 NEC WHICH DOES NEED TO BE CHANGED | | | ON PLANS. | | | | | | 2)NOTE: NO, PLEASE SEE ELECTRICAL SHEETS | | | HAVE NOW HAD THE TITLE BLOCKS REVISED TO | | | NOW INCLUDE AN ENGINEERING FIRM. PLEASE | | | SEE THESE TITLE BLOCKS FOR ELECTRICAL | | | SHEETS ARE REQUIRED TO CONTAIN THE | | | PRINTED NAME AND PRINTED LICENSE NUMBER | | | OF THE ENGINEER OF RECORD. FAC | | | 61G15-23.002. | | | ** THE RESPONSE LETTER WAS REVIEWED | | | WHERE HERSCHMAN DOES NOT BELIEVE THE | | | ARCHITECTUARAL FIRM IS REQUIRED TO | | | CONTAIN AND CA FOR THE ENGINEERING | | | BUSINESS. | | | PLEASE KNOW, WHEN THE VALUE AND SCOPE | | | RELEVANT TO PROJECT ISINCIDENTAL TO | | | THE MAJORITY OF SCOPE AND THE ARCHITECT | | | IS QUALIFIED TO DO SCOPE AND SIGNS AND | | | SEAL PLANS WHICH DOES NOT REQUIRE AN | | | ENGINEER, THIS WOULD BE OK, HOWEVER THIS | | | WAS CONFIRMED WITH THE STATE OF | | | FLORIDA'S FLORIDA BOARD OF PROFESSIONAL | | | ENGINEER'S AS THE PLANS ARE SIGNED, | | | DATED AND SEALED BY AN ENGINEER. IF THE | | | ENGINEER WORKS FOR HERSCHMAN AND IS | | | PROVIDING ENGINEERING SERVICES, THEN A | | | CERTIFICATE OF AUTHORIZATION NUMBER IS | | | REQUIRED FOR THE FIRM. PLEASE OBTAIN IN | | | WRITING FROM THE STATE BOARD AND STATE'S | | | LEGAL COUNSEL TO THE BOARD WHERE THIS IS | | | NOT REQUIRED ON THIS PROJECT AS THIS IS | | | IN DIRECT CONFLICT WITH THE DIRECTION | | | GIVEN TO THIS OFFICE BY THE BOARD AND | | | LEAGAL COUNSEL. | | | WE HAVE ONTACTED THE STATE'S LEGAL | | | COUNSEL MORE THAN ONCE FOR THIS. | | | ONCE ALL REVIEWS ARE COMPLETE, THE PLANS | | | WILL BE RETAINED ANDTURNED OVER TO THE | | | STATE FLORIDA BOARD OF PROFESSIONAL | | | ENGINEERS FOR REVIEW OF THIS AND CODE | | | COMPLIANT COMMENTS AS PLANS HAVE BEEN | | | SUBMITTED THREE TIMES WITH MANY COMMENTS | | | FOR CODE COMPLIANCE NOT ADDRESSED. | | | | | | ** PREVIOUS REVIEW COMMENTS REVIEW #2** | | | NOTE #2 NO, PLEASE SEE THAT SAME | | | COMMENT STANDS AS TITLE BLOCKS DO NOT | | | CONTAIN THE REQUIRED CA # FOR NEW | | | SHEETS. A CA# IS NOW SHOWN ONLY ON | | | ARCHITECTURALS WHICH IS VALID FOR THE | | | ARCH BUSINESS. PLEASE SEE NOTES BELOW, | | | FOR ENGINEERING SERVICES PROVIDED. WE | | | HAVE CONFIRMED THIS WITH THE STATE BOARD | | | OF ENGINEERS. ONE ROLL OF PLANS ARE | | | BEING RETAINED AT THE REQUEST OF THE | | | FLORIDA BOARD OF PROFESSIONAL ENGINEERS. | | | PLEASE ADDRESS THIS COMMENT FOR ALL | | | TRADES AND FOR ALL SHEETS WHETHER OR NOT | | | THIS COMMENT IS MADE BY ANY OTHER | | | TRADES. | | | | | | ** PREVIOUS NOTE **PLEASE COMPLETE ALL | | | TITLE BLOCK INFORMATION FOR MEP PLANS. | | | PLEASE SEE FLORIDA ADMINISTRATIVE CODE | | | WHICH REQUIRES, THE CERTIFICATE OF | | | AUTHORIZATION # ON TITLE BLOCK ALONG | | | WITH ALL OTHER INFORMATION AS SET FORTH | | | IN FAC 61G15-23.002, AS REQUIRED UNDER | | | FS 471.023. | | | PLEASE SEE IF FIRM LISTED ON TITLE | | | BLOCK, (HERSCHMAN) IS ALSO PRACTICING | | | UNDER ENGINEERING, THEN A CA # FOR | | | ENGINEERING BUS WOULD ALSO BE REQUIRED. | | | PLEASE CALL TO GO OVER THIS IF THERE ARE | | | ANY QUESTIONS. | | | | | | 3)NOTE: NOTE #3 OK. | | | | | | 4)NOTE: NOTE #4, OK. | | | | | | 5)NOTE: OK | | | | | | 6)NOTE: NOTE #6 OK. | | | | | | 7)NOTE: OK, HOWEVER PLEASE SEE THAT ALL | | | SETS MUST BE SIGNED, DATED AND SEALED. | | | PLEASE SEE SHEETS WHICH ARE ONLY | | | PHOTO-COPIES. WHICH IS NOT PERMITTED. | | | FAC 61G15-23.002, FS 471.025 | | | | | | ** NEW NOTES** | | | | | | 1) NOTE:NO, PLEASE SEE THESE CONTAIN A | | | TITLE BLOCK FROM HERSCHMAN AND ARE | | | REQUIRED TO BE SIGNED, DATED SEALED. FS | | | 481.221. | | | PLEASE KNOW IF THESE DOCUMNETS WERE NTO | | | BE HERSCHMAN, THEN PLEASE REMOVE TITLE | | | BLOCKS AND THE PERSON/PERSONS WHO ARE | | | RESPONSIBLE FOR SAID PLANS SHALL CLEARLY | | | INDICATE ALL THEIR INFORMATIONA AND SIGN | | | PLANS. ETC | | | FBC 106.1, FS 481, 471, FAC 61G1-16.004, | | | 61G15-23.002 ETC. | | | | | | ** PREVIOUS REVIEW NOTE REVIEW #2 | | | PLEASE SEE PHOTO-METRICS WHICH | | | WERE SUBMITTED IN INDIVIDUAL SHEETS IN | | | PACKAGE. PLEASE BE SURE THESE SHEETS ARE | | | SIGNED, DATED AND SEALED AND INSERTED | | | INTO SETS. | | | | | | 2) NOTE: THIS NOTE WILL STAND FOR NEW | | | PLANS. | | | | | | ** PREVIOUS REVIEW NOTE REVIEW #2** | | | PLEASE SEE PREVIOUS NOTES FROM | | | MORE THAN ONE TRADE WHICH REQUESTED ALL | | | OLD/VOIDED SHEETS TO BE REMOVED FROM | | | SETS AND ONLY INSERT NEW SHEETS INTO TWO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | ONLY ONE COPY OF THE OLD/VOIDED SHOULD | | | BE SUBMITTED SEPARATELY FOR REFERENCE. | | | | | | ** NEW NOTES 3RD REVIEW ** | | | | | | 1) NOTE: PLEASE SEE THAT AN ADDRESS OF | | | 1552 PALM BEACH LAKES BLVD HAS BEEN | | | ASSIGNED TO THIS BUILDING AND PROJECT. | | | PLEASE BE SURE THAT ALL SHEETS AND ALL | | | TITLE BLOCKS CONTAIN THE CORRECT | | | ADDRESS. PLEASE SEE SOME PAPERWORK | | | SUBMITTED BACK CONTAINS "1540". | | | FAC 61G1-16.004, 61G15-23.002 | | | | | | ** IMPORTANT ** | | | PLEASW KNOW, MANY COMMENTS ABOVE ARE | | | REQUIRED FOR ALL TRADES AND FOR ALL | | | SHEETS WHETHER OR NOT COMMENTS ARE MADE | | | BY OTHER REVIEWER(S). | | | | | | | | | | | | ** PLEASE SEE ANY OTHER COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | 2006-09-22 00:00:00 | IN ELEC FOR REVIEW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-05-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-05-18 |
Time |
08:36 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-05-17 |
Time |
21:04 |
Sent To |
|
|
| Notes |
| 2006-05-18 00:00:00 | ********** UNSAT 2ND REVIEW ********** | | | | | | **PLEASE KNOW PLANS HAVE ONLY BEEN | | | SUBMITTED FOR "PLAN REVIEW " FOR THE 2ND | | | TIME AND HAVE NOT BEEN SUBMITTED FOR | | | PERMIT. | | | | | | ** PLEASE SEE SOME COMMENTS FROM THE | | | PREVIOUS REVIEW HAVE NOT BEEN ADDRESSED | | | ANDNEW COMMENT. | | | | | | | | | 1)NOTE: NOTE #1 NO, PLEASE SEE THAT THE | | | PREVIOUS REVIEW NOTE WAS ALSO FOR | | | COMPLIANCE OF THE FBC 2004. | | | PLEASE SEE REPSONSE MENTIONS, THE PLANS | | | INDICATED 2002 NEC. | | | PLEASE SEE FBC 2004, CHAPTER 13 | | | 413.1ABC.1 FOR VOLTAGE DROP CALCS | | | REQUIED FOR WORST CASE. | | | PLEASE SEE 13-413.1.ABC.2.2 | | | PLEASE SEE 13-415.1.ABC.1.1 , .2 AND .3 | | | PLEASE SEE A TIME CLOCK SYSTEM IS BEING | | | PROPOSED WITH SWITCHES LOCATED AT THE | | | ACCESSIBLE LOCATION, HOWEVER PLEASE | | | PROVIDE INFORMATION ON THESE SWITCHES. | | | THEY CAN OVER-RIDE NO LONGER THAN 4HRS. | | | PLEASE SEE SEPARATE SPACES AND CONTROLS | | | REQUIRED. | | | ** PLEASE SEE ENERGY CALCS SHEETS ARE | | | "RUBBER-STAMPED" WITHE THE ENGINEERS | | | SEAL WHICH IS NOT PERMITTED UNDER FS | | | 471.025. PLEASE ALSO SEE THE WORDING | | | "CERTIFICATE" IS NO LONGER PERMITTED IN | | | SAID SEALS. PLEASE SEE FAC 61G15-23.001, | | | IN A RULING PASSED IN FEB 04, IN WHICH | | | THE WORDING "CERTIFICATE" IN SEAL HAD TO | | | BE CHANGED TO "LICENSE". THE EXTENSION | | | GRANTED WAS TO DEC 31ST,2005. THESE TYOE | | | SEALS ARE NO LONGER PERMITTED. | | | | | | | | | **PREVIOUS NOTE** | | | PLEASE SEE THAT AS OF OCT 1ST, | | | 2005 THE STATE OF FLORIDA HAS NOW | | | ADOPTED THE 2004 FBC. PLEASE ADJUST ALL | | | LOCATIONS AND DESIGNS ON PLANS. | | | THIS IS REQUIRED FOR ALL TRADES AND FOR | | | ALL TRADES WHETHER OR NOT COMMENTS ARE | | | MADE BY OTHER REVIEWER(S). | | | PLEASE KNOW, WE ARE CURRENTLY UNDER THE | | | 2002 NEC WHICH DOES NEED TO BE CHANGED | | | ON PLANS. | | | | | | 2)NOTE: NOTE #2 NO, PLEASE SEE THAT SAME | | | COMMENT STANDS AS TITLE BLOCKS DO NOT | | | CONTAIN THE REQUIRED CA # FOR NEW | | | SHEETS. A CA# IS NOW SHOWN ONLY ON | | | ARCHITECTURALS WHICH IS VALID FOR THE | | | ARCH BUSINESS. PLEASE SEE NOTES BELOW, | | | FOR ENGINEERING SERVICES PROVIDED. WE | | | HAVE CONFIRMED THIS WITH THE STATE BOARD | | | OF ENGINEERS. ONE ROLL OF PLANS ARE | | | BEING RETAINED AT THE REQUEST OF THE | | | FLORIDA BOARD OF PROFESSIONAL ENGINEERS. | | | PLEASE ADDRESS THIS COMMENT FOR ALL | | | TRADES AND FOR ALL SHEETS WHETHER OR NOT | | | THIS COMMENT IS MADE BY ANY OTHER | | | TRADES. | | | | | | | | | ** PREVIOUS NOTE **PLEASE COMPLETE ALL | | | TITLE BLOCK INFORMATION FOR MEP PLANS. | | | PLEASE SEE FLORIDA ADMINISTRATIVE CODE | | | WHICH REQUIRES, THE CERTIFICATE OF | | | AUTHORIZATION # ON TITLE BLOCK ALONG | | | WITH ALL OTHER INFORMATION AS SET FORTH | | | IN FAC 61G15-23.002, AS REQUIRED UNDER | | | FS 471.023. | | | PLEASE SEE IF FIRM LISTED ON TITLE | | | BLOCK, (HERSCHMAN) IS ALSO PRACTICING | | | UNDER ENGINEERING, THEN A CA # FOR | | | ENGINEERING BUS WOULD ALSO BE REQUIRED. | | | PLEASE CALL TO GO OVER THIS IF THERE ARE | | | ANY QUESTIONS. | | | | | | 3)NOTE: NOTE #3 OK. | | | | | | | | | | | | 4)NOTE: NOTE #4, PLEASE SEE LOCATION IS | | | NOW SHOWN MEETING CLEARENCE REQUIREMENTS | | | SEPARATING THIS FROM STORAGE AREA, | | | HOWEVER PLEASE SEE NOW IF MAINS ARE | | | NEEDED TO BE ACCESSED BY FIRE DEPT | | | PERSONNEL IT WOULD APPEAR ONCE INTO THE | | | REAR DOOR OF THE BLDG THEY WOULD HAVE TO | | | OBTAIN ACCESS BY ANOTHER DOOR( STORAGE) | | | WHICH MAY OR MAY NOT BE LOCKED, THEN | | | TRAVEL THROUGH A "STORAGE ROOM" TO | | | ANOTHER FENCED IN ENCLOSURE WHICH WILL | | | ALSO MOST LIKELY BE LOCKED. PLEASE KNOW, | | | THIS LOCATION DOES NOT SEEM TO BE | | | READILY ACCESSIBLE FOR MEANS OF SHUTTING | | | DOWN ELECTRICAL. 230.70,110.26 100,90.4. | | | THIS HAS BEEN CONFIRMED WITH THE FIRE | | | MARSHAL'S OFFICE AND SUCH LOCATION WOULD | | | NOT BE ACCEPTABLE. PLEASE ADJUST ROOM/ | | | ELECTRICAL MAINS ACCESSIBILITY. | | | THIS WAS DISCUSSED AS THIS AREA COULD BE | | | CLOSED IN BY PARITIIONS, HOWEVER THIS | | | ACCESS SHOULD BE MADE CLOSER TO THE | | | BUILDING REAR ACCESS/ ENTRANCE DOOR. | | | | | | | | | ** PREVIOUS NOTE ** | | | PLEASE VERIFY LOCATION FOR | | | SERVICE EQUIPMENT. PLEASE SEE | | | 408.7,240.24,110.26 | | | IT APPEARS TO SHOW EQUIPMENT IN A | | | "STORAGE ROOM" WHICH WOULD NOT BE | | | PERMITTED. | | | A PARTIONED AREA AROUND THIS EQUIPMENT | | | MEETING WIDTH AND HEIGHT REQUIREMENT AS | | | LISTED IN 110.26, WOULD BE PERMITTED TO | | | MAINTAIN CLEARENCES, AND KEEP OCP AWAY | | | FROM COMBUSTIBLES AND EASILY IGNITIBLE | | | MATERIALS. | | | | | | 5)NOTE: OK | | | | | | 6)NOTE: NOTE #6 NO, THIS COULD NOT BE | | | LOCATED ON PLANS?? PLEASE SEE NEW NOTE | | | FOR PHOTO-METRICS. | | | | | | ** PREVIOUS NOTE ** | | | PLEASE PROVIDE WIND LOAD | | | CALCUALTIONS FOR SITE LIGHTING POLES , | | | INCLUDING FIXTURE ATTACHED TO POLES. | | | PLEASE KNOW THESE CALCUALTIONS ARE DUE | | | IF PERMITTING WITH MAIN BUILDING. | | | PLEASE ALSO KNOW, ALL CALCS TO MEET THE | | | MIN FBC 140 MPH. | | | | | | 7)NOTE: OK | | | | | | ** NEW NOTES** | | | | | | 1) NOTE: PLEASE SEE PHOTO-METRICS WHICH | | | WERE SUBMITTED IN INDIVIDUAL SHEETS IN | | | PACKAGE. PLEASE BE SURE THESE SHEETS ARE | | | SIGNED, DATED AND SEALED AND INSERTED | | | INTO SETS. | | | | | | 2) NOTE: PLEASE SEE PREVIOUS NOTES FROM | | | MORE THAN ONE TRADE WHICH REQUESTED ALL | | | OLD/VOIDED SHEETS TO BE REMOVED FROM | | | SETS AND ONLY INSERT NEW SHEETS INTO TWO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | ONLY ONE COPY OF THE OLD/VOIDED SHOULD | | | BE SUBMITTED SEPARATELY FOR REFERENCE. | | | | | | | | | | | | ** PLEASE SEE ANY OTHER COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS | | | FROM SETS AND ONLYINSERT NEW REVISED | | | SHEETS INTO COMPLETE SETS FOR REVIEW AND | | | STAMPING. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW ALONG WITH PERMIT APPLICATION. IF | | | THERE ARE ANY QUESTIONS, PLEASE DO NOT | | | HESITATE IN CONTACTING THIS OFFICE. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | | | 2006-05-17 00:00:00 | IN ELEC FOR REVIEW | | | PLANS WILL GO TO A "F" STATUS, REVIEW | | | COMPLETED. NOTES TO FOLLOW ON 5/18 | | | NOTES ON 5/18 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-12-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-12-24 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-12-24 |
Time |
15:12 |
Sent To |
|
|
| Notes |
| 2005-12-24 00:00:00 | ********** UNSAT ********** | | | | | | PLEASE SEE PLANS HAVE ONLY BEEN | | | SUBMITTED FOR "PLAN REVIEW " ONLY AND | | | HAVE NOT BEEN SUBMITTED FOR PERMIT. | | | | | | | | | 1)NOTE: PLEASE SEE THAT AS OF OCT 1ST, | | | 2005 THE STATE OF FLORIDA HAS NOW | | | ADOPTED THE 2004 FBC. PLEASE ADJUST ALL | | | LOCATIONS AND DESIGNS ON PLANS. | | | THIS IS REQUIRED FOR ALL TRADES AND FOR | | | ALL TRADES WHETHER OR NOT COMMENTS ARE | | | MADE BY OTHER REVIEWER(S). | | | PLEASE KNOW, WE ARE CURRENTLY UNDER THE | | | 2002 NEC WHICH DOES NEED TO BE CHANGED | | | ON PLANS. | | | | | | 2)NOTE:PLEASE COMPLETE ALL TITLE BLOCK | | | INFORMATION FOR MEP PLANS. | | | PLEASE SEE FLORIDA ADMINISTRATIVE CODE | | | WHICH REQUIRES, THE CERTIFICATE OF | | | AUTHORIZATION # ON TITLE BLOCK ALONG | | | WITH ALL OTHER INFORMATION AS SET FORTH | | | IN FAC 61G15-23.002, AS REQUIRED UNDER | | | FS 471.023. | | | PLEASE SEE IF FIRM LISTED ON TITLE | | | BLOCK, (HERSCHMAN) IS ALSO PRACTICING | | | UNDER ENGINEERING, THEN A CA # FOR | | | ENGINEERING BUS WOULD ALSO BE REQUIRED. | | | PLEASE CALL TO GO OVER THIS IF THERE ARE | | | ANY QUESTIONS. | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING INSTALL- | | | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE | | | RATED FOR THE AVAILABLE FAULT CURRENT. | | | PER 110.9/215.5 | | | PLEASE KNOW, IT IS KNOWN THAT THE AIC | | | RATINGS ARE INDICATED FOR THE PANELS A | | | AND B. JUST NEED MAIN DISCAND TWO 80 A | | | MCB DISCONNECTS. | | | | | | 4)NOTE: PLEASE VERIFY LOCATION FOR | | | SERVICE EQUIPMENT. PLEASE SEE | | | 408.7,240.24,110.26 | | | IT APPEARS TO SHOW EQUIPMENT IN A | | | "STORAGE ROOM" WHICH WOULD NOT BE | | | PERMITTED. | | | A PARTIONED AREA AROUND THIS EQUIPMENT | | | MEETING WIDTH AND HEIGHT REQUIREMENT AS | | | LISTED IN 110.26, WOULD BE PERMITTED TO | | | MAINTAIN CLEARENCES, AND KEEP OCP AWAY | | | FROM COMBUSTIBLES AND EASILY IGNITIBLE | | | MATERIALS. | | | | | | 5)NOTE: PLEASE SEE COLOR CODING FOR | | | 277/480 SHALL BE BROWN , PURPLE, YELLOW, | | | AS 277/480 DOES NOT CONTAIN A "HIGH-LEG" | | | AS LISTED IN WHICH THE NEC DOES REQUIRE | | | "ORANGE". | | | ELECTRICAL SYSTEM FOR THIS PROJECT DOES | | | NOT APPEAR TO SHOW ANY 277/480V SYSTEMS, | | | THEREFORE THE GENERAL NOT ON E-5 CAN BE | | | REMOVED. | | | | | | 6)NOTE: PLEASE PROVIDE WIND LOAD | | | CALCUALTIONS FOR SITE LIGHTING POLES , | | | INCLUDING FIXTURE ATTACHED TO POLES. | | | PLEASE KNOW THESE CALCUALTIONS ARE DUE | | | IF PERMITTING WITH MAIN BUILDING. | | | PLEASE ALSO KNOW, ALL CALCS TO MEET THE | | | MIN FBC 140 MPH. | | | | | | 7)NOTE: PLEASE ALSO INCLUDE THE FOOTER | | | STEEL IN THE MAIN GROUNDING ELECTRODE | | | SYSTEM. | | | 250.50. | | | | | | ** PLEASE SEE ANY OTHER COMMENTS FROM | | | OTHER REVIEWER(S) WHICH MAY AFFECT | | | ELECTRICAL PLANS. | | | | | | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS | | | FROM SETS AND ONLYINSERT NEW REVISED | | | SHEETS INTO COMPLETE SETS FOR REVIEW AND | | | STAMPING. | | | | | | ** PLEASE KNOW, THIS WAS FOR PLAN REVIEW | | | ONLY. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW ALONG WITH PERMIT APPLICATION. IF | | | THERE ARE ANY QUESTIONS, PLEASE DO NOT | | | HESITATE IN CONTACTING THIS OFFICE. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
N |
Date |
2007-04-23 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2007-04-23 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2007-04-23 |
Time |
16:40 |
Sent To |
|
|
| Notes |
| 2007-04-23 16:52:18 | CIVILS COVERED UNDER #07030572LM |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2005-10-20 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2005-10-20 |
Time |
08:24 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2005-10-20 |
Time |
08:24 |
Sent To |
|
|
| Notes |
| 2005-10-20 00:00:00 | PASSED WITH PROVISOS: | | | | | | 1. POLLUTION PREVENTION PLAN; SILT | | | FENCE, INLET PROTECTION, ECT. MUST BE | | | INSTALLED IN THE FIELD PRIOR TO ANY | | | CONSTRUCTION ACTIVITIES. | | | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2007-04-11 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-04-11 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-04-11 |
Time |
16:11 |
Sent To |
|
|
| Notes |
| 2007-04-11 16:50:17 | *****APPROVED***** | | | | | | | | | PLAN SHEETS A-5, F-1, AND E-3 WERE STAMPED, INITIALED, | | | AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2007-03-07 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-03-07 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-03-07 |
Time |
14:27 |
Sent To |
|
|
| Notes |
| 2007-03-07 15:05:43 | *****UNSAT***** | | | | | | | | | ALL COMMENTS FROM PREVIOUS FIRE PLAN REVIEWS HAVE BEEN | | | ADDRESSED, HOWEVER, THE UPDATED PLANS SHALL BE | | | PRESENTED WITH NO INK, PENCIL, OR ANY OTHER HAND DRAWN | | | MARKINGS. | | | | | | | | | | | | CAPT MICHEAL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2006-06-08 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-06-08 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-06-08 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2006-06-08 00:00:00 | ***DENIED*** | | | | | | 1) COMMENT #1&2- PLEASE ADD MINIMUM | | | INTERIOR FINISH CLASSIFICATION NOTE TO | | | THE PLANS THAT IS PERTINENT TO THIS | | | PROJECT. | | | | | | 2) COMMENT #3- RESPONSE INDICATES THAT | | | SHEET A-5 WAS REVISED TO REFLECT THIS | | | REQUIREMENT. NO REVISION WAS FOUND. | | | PLEASE ILLUSTRATE ADDRESS REQUIREMENT ON | | | ELEVATIONS. | | | | | | 3) LIFE SAFETY SHALL COMPLY WITH NFPA | | | 101, 2003 EDITION. | | | | | | 4) 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | | REQUIRED AND SHALL BE MOUNTED NOT TO | | | EXCEED 75'TRAVEL DISTANCE. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-11-16 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2005-11-16 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2005-11-16 |
Time |
16:06 |
Sent To |
|
|
| Notes |
| 2005-11-16 00:00:00 | PROVISO: | | | | | | 1) INTERIOR WALL AND CEILING FINISH | | | MATERIAL COMPLYING WITH SECTION 10.2 | | | SHALL BE CLASS A OR CLASS B IN EXITS AND | | | IN EXIT ACCESS CORRIDORS. | | | | | | 2) INTERIOR WALL AND CEILING FINISHES | | | SHALL BE CLASS A, CLASS B, OR CLASS C IN | | | ALL OTHER AREAS. | | | | | | 3) ADDRESS IS REQUIRED WITH THE NUMBERS | | | MINIMUM 6" HIGH ON CONTRASTING | | | BACKGROUND. | | | | | | 4) CONSTRUCTION AND CONSTRUCTION DEBRIS | | | ARE TO COMPLY WITH NFPA 241. | | | | | | | | | NATE MCCRAY, ASSISTANT FIRE MARSHAL | | | 561-804-4754 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2007-10-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-18 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-18 |
Time |
12:49 |
Sent To |
B |
|
| Notes |
| 2007-10-18 12:50:15 | TO "JWITMER" DESK/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2007-10-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-12 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-12 |
Time |
08:20 |
Sent To |
B |
|
| Notes |
| 2007-10-12 08:21:08 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2007-09-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-19 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-19 |
Time |
11:00 |
Sent To |
B |
|
| Notes |
| 2007-09-19 11:01:10 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2007-09-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-09-10 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-09-10 |
Time |
09:46 |
Sent To |
B |
|
| Notes |
| 2007-09-10 09:47:13 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2007-08-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-30 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-30 |
Time |
14:45 |
Sent To |
B |
|
| Notes |
| 2007-08-30 14:45:39 | TO "JWITMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-08-08 |
|
|
Cont ID |
|
| Sent By |
mmiller |
Date |
2007-08-08 |
Time |
18:24 |
Rev Time |
0.00 |
| Received By |
mmiller |
Date |
2007-08-08 |
Time |
18:23 |
Sent To |
B |
|
| Notes |
| 2007-08-08 18:24:03 | SENT TO JIM WITMER'S DESK MMILLER |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-04-02 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2007-04-02 |
Time |
18:28 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2007-04-02 |
Time |
18:28 |
Sent To |
|
|
| Notes |
| 2007-04-09 08:30:53 | TO "COMM" BD#26/PLANS ON RACK/2 SETS OF PLANS AND | | | PAPERWORK | | 2007-04-02 18:28:24 | WAITING FOR COMM BOARD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-01-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-01-19 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-01-19 |
Time |
15:00 |
Sent To |
|
|
| Notes |
| 2007-01-30 11:03:41 | TO "COMM" BD#49/PLANS ON RACK--2 SMALL ROLLS, AND | | | PAPERWORK | | 2007-01-19 15:01:04 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-09-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-18 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-18 |
Time |
09:10 |
Sent To |
|
|
| Notes |
| 2006-09-20 00:00:00 | TO "COMM" BD#40 | | 2006-09-18 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-04-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-21 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-04-21 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2006-05-16 00:00:00 | TO "COMM" BD#59 | | 2006-04-21 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-03-22 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2006-03-04 |
Time |
16:00 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2005-10-04 |
Time |
13:45 |
Sent To |
|
|
| Notes |
| 2005-10-18 00:00:00 | TO "COMM" BD#62 | | 2005-10-04 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2007-03-02 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-03-02 |
Time |
08:33 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-03-01 |
Time |
15:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2006-10-16 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2006-10-16 |
Time |
17:48 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2006-10-16 |
Time |
17:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2006-06-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-06-14 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-06-14 |
Time |
16:40 |
Sent To |
|
|
| Notes |
| 2006-06-14 00:00:00 | DENIED: 2ND PLAN CHECK ONLY | | | | | | PLEASE NOTE, TITLE BLOCK INDICATED ON | | | THE MECHANICAL PLANS SHALL HAVE THE | | | CERTIFICATE OF AUTHORIZATION NUMBER FOR | | | THE FIRM INDICATED ON THE TITLE BLOCK. | | | THIS IS A REQUIREMENT OF THE FLORIDA | | | ADMINSTRATIVE CODE 61G15-23.002 & FS | | | 471.023.PLEASE INDICATE CERTIFICATE OF | | | AUTHORIZATION NUMBER ON THE PLANS. | | | | | | PLANS ARE OTHERWISE CODE COMPLIANT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-12-05 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2005-12-05 |
Time |
19:29 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2005-12-05 |
Time |
18:07 |
Sent To |
|
|
| Notes |
| 2005-12-05 00:00:00 | ------------------DENIED---------------- | | | NOTE: ALL CODE SECTIONS CITED REFER TO | | | THE FLORIDA BUILDING CODE, MECHANICAL | | | 2004 EDITION. | | | | | | 1) PAGE MP1.0: PLAN SHOWS 900 CFM OF | | | SUPPLY INTO BACK ROOM.THIS REQUIRES A | | | MIN. OF 450 SQ. IN. TOTAL AREA OF | | | TRANSFER GRILLS TO ACHIEVE BALANCED | | | RETURN PER 601.4.PLAN SHOWS (2) 18X10 | | | TGS WITH TOTAL 360 SQ IN. | | | | | | 2) PAGE MP1.0: PLAN INDICATES MANUAL | | | VOLUME DAMPERS IN 18" ROUND AND 24" | | | ROUND DOUBLE-WALL LINED DUCTS.IS THERE | | | AN APPROVED PRODUCT FOR THIS APPLICATION | | | OR WILL THE DAMPERS BE RELOACTED? | | | | | | 3) PAGE MP3.0 MECHANICAL SPECIFICATIONS: | | | DUCT SMOKE DETECTORS SHALL BE CONNECTED | | | TO THE BUILDING FIRE ALARM SYSTEM, IF | | | APPLICABLE, OR SHALL ACTIVATE AN | | | AUDIBLE/VISIBLE NOTIFICATION DEVICE | | | (HORN/STROBE) IN AN APPROVED LOCATION | | | PER 606.4.1. | | | | | | 4) PLEASE INDICATE LOCATION OF | | | CONDENSATE DISPOSAL TO ENSURE COMPLIANCE | | | WITH FBC,M 307.2.1. | | | | | | 5) AUXILIARY DRAIN PROTECTION IS | | | REQUIRED FOR ROOFTOP PACKAGE UNITS PER | | | 307.2.3.THIS MAY BE ACHIEVED VIA A | | | WATER-LEVEL DETECTION DEVICE IN THE | | | UNIT'S PRIMARY DRAIN PAN TO SHUT-DOWN | | | THE UNIT PRIOR TO OVERFLOW INTO THE | | | SPACE BELOW. | | | | | | 6) WHEN EQUIPMENT REQUIRING ACCESS IS | | | INSTALLED ON A ROOF AT A HEIGHT | | | EXCEEDING 16', ACCES SHALL BE PROVIDED | | | BY PERMANENT APPROVED MEANS IN | | | ACCORDANCE WITH 306.5 | | | | | | PLEASE CALL RON REGUEIRO AT 561.805.6734 | | | OR PATTY KRAUS AT 561.805.6719 IF YOU | | | HAVE ANY QUESTIONS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2007-02-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-02-24 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-02-24 |
Time |
10:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2006-09-28 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-09-28 |
Time |
14:20 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-09-28 |
Time |
14:20 |
Sent To |
|
|
| Notes |
| 2006-09-28 00:00:00 | PAUL SCHMITZ | | | [email protected] | | | FBC 2004 PLUMBING CODE PLAN REVIEW | | | FBC2004 FUEL GAS CODEPLAN REVIEW | | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPT.1, ADMINISTRATION, 2004 EDITION | | | | | | DENIED | | | FROM PREVIOUS COMMENTS | | | | | | SHT A-4 ROOF PLAN: | | | RESPONSE DATED 6-18-06 | | | SHOWS A SCUPPER AS WELL AS THE PRIMARY | | | ROOF DRAIN IN ONE OPENING, NEXT TO THAT | | | IS THE SECONDARY ROOF DRAIN. | | | PLEASE CLARIFI,THEY ARE SEPERATE DRAINS. | | | PROVIDE THE LOCATION OF THE CALCULATIONS | | | FOR THE ROOF DRAINS AND THE SECONDARY | | | DRAINS, COMPONET SIZES. | | | PROVIDE AN ELEVATION DETAIL OF THE ROOF | | | DRAIN AND THE SCUPPER DRAIN. | | | SHT A-5 DETAIL "C" SHOWS ONE DRAIN THRU | | | THE PARAPET WALL. | | | END OF COMMENTS QUESTIONS 561-805-6692 | | | | | | 1) PREVIOUS NOTE #3 SHT A-4 | | | NOT ADDRESSED. | | | SEPERATE SECONDARY DRAINAGE, FROM | | | PRIMARY DRAINAGE SYSTEM REQUIRED. | | | SECTION 1107 | | | SECONDARY (EMERGENCY) ROOF DRAINS | | | 1107.1 SECONDARY DRAINAGE REQUIRED. | | | SECONDARY (EMERGENCY) ROOF DRAINS OR | | | SCUPPERS SHALL BE PROVIDED WHERE THE | | | ROOF PERIMETER CONSTRUCTION EXTENDS | | | ABOVE THE ROOF IN SUCH A MANNER THAT | | | WATER WILL BE ENTRAPPED IF THE PRIMARY | | | DRAINS ALLOW BUILDUP FOR ANY REASON. | | | 1107.2 SEPARATE SYSTEMS REQUIRED. | | | SECONDARY ROOF DRAIN SYSTEMS SHALL HAVE | | | THE END POINT OF DISCHARGE SEPARATE FROM | | | THE PRIMARY SYSTEM. DISCHARGE SHALL BE | | | ABOVE GRADE, IN A LOCATION WHICH WOULD | | | NORMALLY BE OBSERVED BY THE BUILDING | | | OCCUPANTS OR MAINTENANCE PERSONNEL. | | | 1107.3 SIZING OF SECONDARY DRAINS. | | | SECONDARY (EMERGENCY) ROOF DRAIN SYSTEMS | | | SHALL BE SIZED IN ACCORDANCE WITH | | | SECTION 1106 BASED ON THE RAINFALL RATE | | | FOR WHICH THE PRIMARY SYSTEM IS SIZED IN | | | TABLES 1106.2, 1106.3 AND 1106.6. | | | SCUPPERS SHALL BE SIZED TO PREVENT THE | | | DEPTH OF PONDING WATER FROM EXCEEDING | | | THAT FOR WHICH THE ROOF WAS DESIGNED AS | | | DETERMINED BY SECTION 1101.7. SCUPPERS | | | SHALL NOT HAVE AN OPENING DIMENSION OF | | | LESS THAN 4 INCHES (102 MM). THE FLOW | | | THROUGH THE PRIMARY SYSTEM SHALL NOT BE | | | CONSIDERED WHEN SIZING THE SECONDARY | | | ROOF DRAIN SYSTEM. | | | | | | END OF COMMENTS QUESTIONS 561-805-6692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-06-18 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-06-18 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-06-18 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2006-06-18 00:00:00 | PAUL SCHMITZ | | | [email protected] | | | FBC 2004 PLUMBING CODE PLAN REVIEW | | | FBC2004 FUEL GAS CODEPLAN REVIEW | | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPT.1, ADMINISTRATION, 2004 EDITION | | | | | | DENIED | | | 1) PREVIOUS NOTE #3 SHT A-4 | | | NOT ADDRESSED. | | | SEPERATE SECONDARY DRAINAGE, FROM | | | PRIMARY DRAINAGE SYSTEM REQUIRED. | | | SECTION 1107 | | | SECONDARY (EMERGENCY) ROOF DRAINS | | | 1107.1 SECONDARY DRAINAGE REQUIRED. | | | SECONDARY (EMERGENCY) ROOF DRAINS OR | | | SCUPPERS SHALL BE PROVIDED WHERE THE | | | ROOF PERIMETER CONSTRUCTION EXTENDS | | | ABOVE THE ROOF IN SUCH A MANNER THAT | | | WATER WILL BE ENTRAPPED IF THE PRIMARY | | | DRAINS ALLOW BUILDUP FOR ANY REASON. | | | 1107.2 SEPARATE SYSTEMS REQUIRED. | | | SECONDARY ROOF DRAIN SYSTEMS SHALL HAVE | | | THE END POINT OF DISCHARGE SEPARATE FROM | | | THE PRIMARY SYSTEM. DISCHARGE SHALL BE | | | ABOVE GRADE, IN A LOCATION WHICH WOULD | | | NORMALLY BE OBSERVED BY THE BUILDING | | | OCCUPANTS OR MAINTENANCE PERSONNEL. | | | 1107.3 SIZING OF SECONDARY DRAINS. | | | SECONDARY (EMERGENCY) ROOF DRAIN SYSTEMS | | | SHALL BE SIZED IN ACCORDANCE WITH | | | SECTION 1106 BASED ON THE RAINFALL RATE | | | FOR WHICH THE PRIMARY SYSTEM IS SIZED IN | | | TABLES 1106.2, 1106.3 AND 1106.6. | | | SCUPPERS SHALL BE SIZED TO PREVENT THE | | | DEPTH OF PONDING WATER FROM EXCEEDING | | | THAT FOR WHICH THE ROOF WAS DESIGNED AS | | | DETERMINED BY SECTION 1101.7. SCUPPERS | | | SHALL NOT HAVE AN OPENING DIMENSION OF | | | LESS THAN 4 INCHES (102 MM). THE FLOW | | | THROUGH THE PRIMARY SYSTEM SHALL NOT BE | | | CONSIDERED WHEN SIZING THE SECONDARY | | | ROOF DRAIN SYSTEM. | | | | | | END OF COMMENTS QUESTIONS 561-805-6692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-03-04 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-03-04 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-03-04 |
Time |
08:52 |
Sent To |
|
|
| Notes |
| 2006-03-04 00:00:00 | PAUL SCHMITZ | | | [email protected] | | | FBC 2004 PLUMBING CODE PLAN REVIEW | | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | | REVIEW | | | | | | DENIED | | | 1)PLANS TO BE DESIGNED PER FBC-2004 | | | 106.3.5.1 MINIMUM PLAN REVIEW CRITERIA | | | FOR BILDINGS | | | 2) SHT LA1, INCLUDE IRRIGATIONS PLANS. | | | | | | 3) SHT A-4 ROOF PLAN | | | SECONDARY (EMERGENCY) ROOF DRAINS | | | 1107.1 SECONDARY DRAINAGE REQUIRED. | | | SECONDARY (EMERGENCY) ROOF DRAINS OR | | | SCUPPERS SHALL BE PROVIDED WHERE THE | | | ROOF PERIMETER CONSTRUCTION EXTENDS | | | ABOVE THE ROOF IN SUCH A MANNER THAT | | | WATER WILL BE ENTRAPPED IF THE PRIMARY | | | DRAINS ALLOW BUILDUP FOR ANY REASON. | | | | | | END OF COMMENTS, QUESTIONS 561-805-6692 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2007-04-10 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2007-04-10 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2007-04-10 |
Time |
12:05 |
Sent To |
|
|
| Notes |
| 2007-04-10 12:07:07 | ***PASSED WITH PROVISOS*** | | | | | | 1) AWNINGS SHALL BE PERMITTED AND INSTALLED PRIOR TO | | | THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY. | | | | | | 2) STUCCO COLOR SHALL MATCH THE ADJACENT RETAIL | | | BUILDINGS. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER, | | | AT (561) 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2007-02-11 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2007-02-11 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2007-02-11 |
Time |
13:29 |
Sent To |
|
|
| Notes |
| 2007-02-11 13:29:56 | ***PASSED WITH PROVISOS*** | | | | | | 1) AWNINGS SHALL BE PERMITTED AND INSTALLED PRIOR TO | | | THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY. | | | | | | 2) STUCCO COLOR SHALL MATCH THE ADJACENT RETAIL | | | BUILDINGS. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER, | | | AT (561) 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2006-07-02 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2006-07-02 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2006-07-02 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2006-07-02 00:00:00 | 7/2/2006 ***PASSED WITH PROVISOS*** | | | | | | 1) AWNINGS SHALL BE PERMITTED AND | | | INSTALLED PRIOR TO THE ISSUANCE OF A | | | CERTIFICATE OF OCCUPANCY. | | | | | | 2) YELLOW STUCCO SHALL MATCH THE | | | ADJACENT RETAIL BUILDINGS. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, | | | SENIOR PLANNER, AT (561) 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-01-18 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2006-01-18 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2006-01-18 |
Time |
11:17 |
Sent To |
|
|
| Notes |
| 2006-01-18 00:00:00 | 1/18/06 ***FAILED*** | | | | | | 1) A MINIMUM OF 5 ADDITIONAL FEET OF | | | CLEAR SIDEWALK WIDTH SHALL BE PROVIDED | | | IN WHEN 2 FOOT VEHICLE OVERHANG IS | | | LOCATED OVER THE SIDEWALK.PLANS | | | INDICATE 4 FEET MINIMUM IN FRONT OF THE | | | MAIN ENTRANCE. | | | | | | 2) SITE PLAN INDICATES AN 8,985 SQ. FT. | | | BUILDING WHILE THE DATA TABLE INDICATES | | | 10,080 SQ. FT.PLEASE CLARIFY. | | | | | | 3) THE PARKING STALL DETAIL SHALL BE | | | MODIFIED TO PROVIDE DOUBLE-STRIPING, AS | | | REQUIRED BY SECTION 94-485 OF THE ZONING | | | AND LAND DEVELOPMENT REGULATIONS.ONLY | | | 18 FOOT OVERALL STALL DEPTH IS REQUIRED, | | | INCLUDING 2 FEET OF VEHICLE OVERHANG, | | | PLANS INDICATE 20 FEET.ONLY A 4 INCH | | | STRIPE IS REQUIRED. | | | | | | 4) THE LANDSCAPE CALCULATION SUMMARY | | | SHALL BE MODIFIED TO REFLECT THE PROPER | | | OPEN SPACE REQUIREMENTS (40% OF THE LOT | | | AREA). | | | | | | 5) A NOTE SHALL BE ADDED TO THE | | | LANDSCAPE PLANS THAT A TREE | | | REMOVAL/RELOCATION LICENSE SHALL BE | | | OBTAINED FROM THE CITY OF WEST PALM | | | BEACH PRIOR TO THE REMOVAL AND/OR | | | RELOCATION OF ANY EXISTING TREES. | | | | | | 6) ADD AND/OR MODIFY THE PLANTING | | | DETAILS TO REFLECT THE ATTACHED | | | INFORMATION. | | | | | | 7) INFORMATION SHALL BE PROVIDED | | | REGARDING THE PHOTOGRAPHIC IMAGES TO BE | | | PLACED IN THE WINDOWS.SIGNAGE IN | | | WINDOWS IS LIMITED TO SPECIAL SALES, | | | EVENTS, ETC. AND IS REGULATED BY SECTION | | | 94-408(D)(5) OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS.CLEAR GLAZING, | | | VISIBLE TO THE INSIDE, SHALL BE PROVIDED | | | WHEN AT ALL POSSIBLE, ESPECIALLY ON THE | | | NORTH SIDE FACING PALM BEACH LAKES | | | BOULEVARD.CONSIDER FLIPPING THE FLOOR | | | PLAN/DISPLAY LAYOUT TO PROVIDE MORE OPEN | | | WALL SPACE WITH NO SHELVING AND CLEAR | | | GLAZING ALONG THE NORTH WALL. | | | | | | 8) IT IS STRONGLY RECOMMENDED THAT SOME | | | GLAZING BE ADDED TO THE SOUTH ELEVATION, | | | SIMILAR TO THAT SHOWN ON THE NORTH. | | | | | | 9) AWNINGS SHALL BE PROVIDED ON THE | | | SOUTH ELEVATION. | | | | | | 10) SIGNAGE SHALL BE PERMITTED | | | SEPARATELY. | | | | | | 11) THE "FLAG" ON THE NORTH SIGN SHALL | | | BE ADJUSTED TO THE APPROPRIATE LOCATION. | | | | | | 12) THE "WHEEL" SHALL NOT BE PERMITTED | | | AS SIGNAGE...AS DISCUSSED PREVIOUSLY, IT | | | SHALL ONLY BE PERMITTED IF IT IS A | | | PERMANENT ELEMENT OF THE BUILDING. | | | | | | 13) A PHOTOMETRIC PLAN SHALL BE | | | PROVIDED.LEVELS SHALL BE INDICATED AT | | | THE BOUNDARY OF THE COMMERCIAL PLANNED | | | DEVELOPEMNT (CPD) ALONG THE CANAL AND | | | SHALL NOT EXCEED 1.0 FOOTCANDLES. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, | | | PLANNER AT (561) 822-1435. | | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy