| Plan Review Stops For Permit 05100085 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2005-12-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-12-20 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-12-20 |
Time |
10:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2005-11-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-11-29 |
Time |
07:35 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-11-29 |
Time |
07:35 |
Sent To |
|
|
| Notes |
| 2005-11-29 00:00:00 | DENIED | | | | | | 1) THE ORIGINAL WET SIGNATURE OF THE | | | TRUSS ENGINEER IS REQUIRED ON THE TRUSS | | | LAYOUT AND TRUSS DRAWINGS. SEE F.A.C. | | | 61G1-16.003 | | | | | | 2) THE TRUSS LAYOUT IS REQUIRED TO BE | | | REVIEWED AND APPROVED BY THE DESIGNER OF | | | RECORD FOR THE STRUCTURE. | | | | | | 3) THE PRODUCT APPROVALS REQUIRED BY | | | RULE 9B-72 ARE REQUIRED TO BE REVIEWED | | | AND APPROVED BY THE DESIGNER OF RECORD | | | FOR THE STRUCTURE BY SECTION 106.3.3 OF | | | THE CITY AMENDMENTS TO THE 2004 FBC. | | | | | | 4) SUBMIT AN INSTALLATION SCHEDULE FOR | | | THE STORM PANELS. SPECIFY THE ANCHORS | | | THAT WILL BE USED, THE ANCHOR SPACING, | | | THE MOUNT TYPE (SECTION # FROM PRODUCT | | | APPROVAL) AND EDGE DISTANCE. THE PLANS | | | SPECIFY TAPCONS WITH AN EDGE DISTANCE OF | | | 3". THE PRODUCT APPROVAL SPECIFIES | | | 3-1/2" EDGE DISTANCE. THE INFORMATION ON | | | THE PLANS MUST CORRESPOND WITH THE | | | INSTALLATION SELECTED FROM THE PRODUCT | | | APPROVAL. | | | | | | 5) THE NOAS SUBMITTED FOR THE SH | | | WINDOWS, WINDOW MULLIONS AND GAF | | | SHINGLES HAVE BEEN UPDATED FOR THE 2004 | | | FBC ON THE STATE WEBSITE. SUBMIT THE | | | NOAS THAT ARE LISTED ON THE WEBSITE FOR | | | THE PRODUCT. SEE WWW.FLORIDABUILDING.ORG | | | | | | 6) THE INSTALLATION INSTRUCTIONS THAT | | | WERE SUBMITTED FOR THE THERMA-TRU DOORS | | | ARE MIAMI-DADE NOAS AND THE EVALUATION | | | ENTITY SUBMITTED FOR STATE APPROVAL WAS | | | NAMI. SUBMIT THE CORRESPONDING REPORTS. | | | SEE FL 5262 AND THE CORRESPONDING PDF | | | FILES. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-10-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-10-19 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-10-19 |
Time |
10:46 |
Sent To |
|
|
| Notes |
| 2005-10-19 00:00:00 | DENIED | | | | | | 1) DUE TO THE CHANGE IN BUILDING CODES | | | FROM THE 2001 FBC TO THE 2004 FBC | | | RESIDENTIAL CODE ON OCTOBER 1, 2005, | | | PERMITS CAN NO LONGER BE ISSUED UNDER | | | THE MASTER (#04050070) THAT WAS APPROVED | | | UNDER THE 2001 FBC. | | | | | | 2) IF YOU WISH TO RE-MASTER THIS PROJECT | | | SUBMIT (2) COMPLETE SETS OF PLANS, | | | PRODUCT APPROVALS, SITE PLANS, TRUSS | | | DRAWINGS AND ENERGY CALCULATIONS FOR | | | REVIEW. SOIL REPORTS, SURVEYS ENERGY | | | CALCS. AND IMPACT FEES WILL BE REQUIRED | | | TO BE SUBMITTED WITH EACH PERMIT APPLIED | | | FOR UNDER THE MASTER. | | | | | | NOTE: ALL INFORMATION ON THE PLANS WILL | | | BE REQUIRED TO REFLECT THE 2004 FBC | | | RESIDENTIAL CODE. REVISE ALL DESIGN | | | INFORMATION AND CODE REFERENCES TO THE | | | CURRENT CODE. ALL PRODUCT APPROVALS NEED | | | TO BE UPDATED TO THE 2004 EDITION OF | | | THOSE LISTED ON THE STATE WEBSITE | | | (WWW.FLORIDABUILDING.ORG). | | | - THE TRUSS DRAWINGS MUST INCLUDE ALL | | | THE INFORMATION REQUIRED BY FBC | | | R802.10.1. | | | - SUBMIT A SITE DRAINAGE PLAN COMPLYING | | | WITH THE REQUIREMENTS OF FBC R401.3. | | | - THE ENERGY CALCULATIONS MUST BE DONE | | | USING THE 2004 FORMS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2005-11-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-11-17 |
Time |
08:04 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2005-11-17 |
Time |
07:53 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-10-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-10-19 |
Time |
12:14 |
Rev Time |
|
| Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2005-10-19 00:00:00 | *** UNSAT *** | | | | | | | | | NO ELECTRICAL PLANS SUBMITTED FOR | | | REVIEW. | | | NEW PLANS NEEDED FOR CHANGE IN FBC. | | | PLEASE KNOW, PLANS WOULD STILL BE UNDER | | | THE 2002 NEC AND SHOULD NOT CHANGE ANY | | | ELECTRICAL FROM PREVIOUS MASTER. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
N |
Date |
2005-11-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-11-15 |
Time |
17:23 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-11-15 |
Time |
17:23 |
Sent To |
E |
|
| Notes |
| 2005-11-15 00:00:00 | TO "DPALMER" DESK/REESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-10-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-10-17 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-10-17 |
Time |
16:56 |
Sent To |
B |
|
| Notes |
| 2005-10-17 00:00:00 | TO "RMCDOUGAL" DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-11-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-11-09 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-10-04 |
Time |
13:13 |
Sent To |
|
|
| Notes |
| 2005-10-13 00:00:00 | ROUTED TO ANGELLA JONES-VANN | | | | | 2005-10-04 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2005-11-18 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2005-11-18 |
Time |
08:24 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2005-11-18 |
Time |
08:24 |
Sent To |
P |
|
| Notes |
| 2005-11-18 00:00:00 | *** NOTE*** | | | FOR FUTURE MECHANICAL PLANS PLEASE SHOW | | | ON PLAN. | | | 1) A/C EQUIP. MANUFACTURE'S NAME. | | | 2) AIR HANDLER MODEL NUMBER. | | | 3) HEATER K.W. . | | | 4) CONDENSER MODEL NUMBER. | | | 5) A/C SYSTEMS SEER. | | | 6) A/C SYSTEMS SENSIBLE COOLING BTU'S, | | | LATENT COOLING BTU'S, & TOTAL COOLING | | | BTU'S. | | | 7) COPPER LINE SIZES. | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2005-10-19 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2005-10-19 |
Time |
14:06 |
Rev Time |
0.15 |
| Received By |
tgordon |
Date |
2005-10-19 |
Time |
14:06 |
Sent To |
B |
|
| Notes |
| 2005-10-19 00:00:00 | 1) MECH. PLANS NEED THE A/C | | | EQUIPMENT MANUFACTURE'S NAME, MODEL | | | NUMBER, SEER, AND COPPER LINE SIZES. | | | 2) NEW ENERGY CAL'S. FORM 600-2004 AND | | | MANUAL 'J' WILL BE NEEDED. | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2005-11-18 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2005-11-18 |
Time |
09:57 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2005-11-18 |
Time |
09:57 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2005-10-17 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2005-10-17 |
Time |
09:59 |
Rev Time |
|
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|