Plan Review Details - Permit 05100073
Plan Review Stops For Permit 05100073
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-05-25 Cont ID  
Sent By lmartine Date 2007-05-25 Time 13:49 Rev Time 0.00
Received By lmartine Date 2007-05-25 Time 13:49 Sent To  
Notes
2007-05-25 13:50:52STRUCTURAL REVISION FOR BEAMS AND COLUMNSOKLM

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-07-06 Cont ID  
Sent By alange Date 2006-07-06 Time 16:42 Rev Time 2.75
Received By alange Date 2006-07-06 Time 16:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-09 Cont ID  
Sent By alange Date 2006-05-09 Time 08:17 Rev Time 2.00
Received By alange Date 2006-05-09 Time 08:17 Sent To  
Notes
2006-05-09 00:00:00DENIED
  
 3.ENGINEERS SEAL ON SOILS REPORT IS
 NOT VALID.ENGINEERS SEALS USED AFTER
 JANUARY 1, 2006 SHALL SHOW "LICENSED"
 NOT "CERTIFICATE". 61G1-16.001
  
 5.PRODUCT APPROVALS;
 A.PRODUCT APPROVALS REQUIRED FOR STRAPS
 AND TIE-DOWNS.
 B. CHECK STATE PRODUCT APPROVALS FOR
 MULLIONS AND PGT EXTERIOR DOOR
 SUBMITTED.STATE PRODUCT APPROVAL PAGES
 ARE NOT THE CORRECT PAGES. WHEN
 SEARCHING FOR STATE PRODUCT APPROVAL YOU
 NEED TO GO ONE STEP FURTHER AND SELECT
 THE PAGE SHOWING THE CATAGORY USED TO
 COINSIDE WITH THE NOA SUBMITTED.
 C.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 ART LANGE
 BUILDING PLAN EXAMINER
 805-6672
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-21 Cont ID  
Sent By alange Date 2005-12-21 Time 12:13 Rev Time 3.50
Received By alange Date 2005-12-21 Time 07:34 Sent To  
Notes
2005-12-21 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.SITE IS IN AN AREA OF QUESTIONABLE
 SOILS.SUBMIT TWO ORIGONALS SOILS
 REPORT WITH FOUNDATION RECOMMENDATIONS.
  
 4.ALL PLANS SUBMITTED AFTER OCTOBER 1,
 2004 SHALL BE DESIGNED TO THE 2004 FBC.
  
 5.PRODUCT APPROVALS;
 A.PRODUCT APPROVALS REQUIRED FOR
 OVERHEAD DOOR, LINTELS, FIXED WINDOW AND
 STRAPS AND TIE-DOWNS.
 B. STATE PRODUCT APPROVAL PAGES ARE NOT
 THE CORRECT PAGES. WHEN SEARCHING FOR
 STATE PRODUCT APPROVAL YOU NEED TO GO
 ONE STEP FURTHER AND SELECT THE PAGE
 SHOWING THE CATAGORY USED TO COINSIDE
 WITH THE NOA SUBMITTED.
 C.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6.FIRST FLOOR WINDOW AND DOOR SCHEDULE
 DOES NOT SHOW TYPE OF WINDOW USED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLAN EXAMINER
 805-6672
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-03-26 Cont ID  
Sent By dpalmer Date 2007-03-26 Time 12:13 Rev Time 0.00
Received By dpalmer Date 2007-03-26 Time 10:52 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-03-21 Cont ID  
Sent By dpalmer Date 2007-03-21 Time 18:14 Rev Time 0.00
Received By dpalmer Date 2007-03-21 Time 13:04 Sent To PC
Notes
2007-03-21 18:15:28 
 ** UNSAT **
  
 1) NOTE:PLEASE CORRELATE RISER AND PANELS. PLEASE SEE
 RISER SHOWS 3-3/0'S FOR THE FEEDERS TO THE JANDY PANEL,
 WHEN THE SCHEDULE FOR THE JANDY PANEL AND THE JANDY
 PANEL ITSELF SHOWS 3-#3'S.
 PLEASE KNOW IF THIS IS INDEED 3/0'S THEN THE CONDUIT
 SIZE OF 1 1/4 INCH IS TOO SMALL PER CHAPTER 9 TABLES
 FOR CONDUIT FILL.
 PLEASE ADJUST.
 408.4, 204.4, 310.16. FBC 106.1.2
  
 2) NOTE: PLEASE SEE NEW SCHEDULE FOR THE 400A MAIN
 PANEL. PLEASE CLARIFY THE NUMBER OF CIRCUITS AND THIS
 EQUIPMENT BEING SHOWN WITH MORE THAN 6 CIRCUITS AND
 SPACES. PLEASE SEE 230.71 AS NO MORE THAN 6 SPACES IS
 PERMITTED OR THIS EQUIPMENT MUST CONTAIN A MCB. (SHOWN
 AS MLO).
  
 3) NOTE: PLEASE SEE BOTH PANELS A AND B ARE BEING SHOWN
 ON PANEL AS 42 CIRCUIT PANELS, HOWEVER ONLY PANEL *A*
 IS SHOWN WITH 42 CIRCUITS, PANEL *B* SHOWS ONLY 40?
 PLEASE CORRELATE.
 FBC 106.1.2
  
 4) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16 AS
 ONE OR MORE OF THE CIRCUITS AS CONSIDERED IN 210.52B
 ARE REQUIRED TO BE ON ONE OR MORE OF THE SMALL
 APPLIANCE CIRCUITS. PLEASE SEE THAT EACH CIRCUIT OVER
 SHALL BE SHOWN AND FIGURED AT 1500VA EACH. PLEASE SEE
 PANEL *A* SEEMS TO SHOW A MINIMUM OF FOUR OF THESE
 CIRCUITS, YET LOAD CALCULATIONS ONLY SHOW THREE
 CIRCUITS AND LOADS FOR ONLY TWO?
 PLEASE VERIFY HOW MANY OF THESE CIRCUITS ARE ACTUALLY
 INSTALLED AND ADJUST ACCORDINGLY.
 FBC 106.3.5.4
  
 5) NOTE: PLEASE SEE THE LOAD SHOWN FOR THE
 REFRIGERATOR/FREEZER IN LOAD CALCULATIONS IS SHOWN AT
 1800VA WHICH EXCEEDS THAT OF THE 15AMP CIRCUIT
 PROVIDED.
 PLEASE VERIFY ACTUAL LOAD AND ADJUST ACCORDINGLY.
 PLEASE KNOW IF THE LOAD IS NOT AS HIGH AS SHOWN, THE
 CIRCUIT WOULD NOT NEED TO BE ADJUSTED. IF LOAD IS
 INDEED THIS HIGH, PLEASE CHANGE TO A 20AMP CIRCUIT.
 240.4, 310.16 ETC.
  
 6) NOTE: PLEASE CORRELATE THE LAUNDRY CIRCUIT FROM THE
 LOAD CALCULATIONS AND THE PANEL SCHEDULE. PLEASE SEE
 THE LOAD CALCULATIONS SHOW 1-POLE 30AMP CIRCUIT, YET
 PANEL A SHOWS 1-POLE 20AMP CIRCUIT??
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE THE BATHROOM DEDICATED GFI CIRCUITS
 ARE NOTED ON PLANS AS 20AMP AND ARE ON PANEL SCHEDULES
 AS 20AMP, HOWEVER PLEASE SEE THE LOAD CALCULATIONS
 SCHEDULE WHICH SHOWS THESE AS 15AMPS CIRCUITS. THIS
 SEEMS TO BE A MISPRINT.
 210.11C3, 210.52D.
 FBC 106.1.2
  
 8) NOTE: PLEASE SEE THE LOAD CALCULATIONS WHICH
 INDICATE A TOTAL OF 8-GEN LTS AND RECEPTS CIRCUITS WITH
 A LOAD OF 13,923, WHICH PLACES A LOAD OF 14.503 AMPS ON
 EACH OF THESE 15AMP RATED CIRCUITS.
 PLEASE GO OVER LOADS BEING SHOWN ON THESE 15AMPS
 CIRCUIT AND ADJUST.
 FBC 106.3.5.4
  
 ** PLEASE CALL TO GO OVER ANY OF THE COMMENTS IF NEED
 BE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-03-02 Cont ID  
Sent By dpalmer Date 2007-03-02 Time 07:24 Rev Time 0.00
Received By dpalmer Date 2007-03-01 Time 17:56 Sent To PC
Notes
2007-03-02 07:41:07*** UNSAT ***
  
  
  
 ** PLEASE SEE RISER HAS CHANGED FROM PREVIOUS PLANS AND
 PLEASE SEE ITEMS WHICH WERE REDLINED FROM PREVIOUS
 PLANS FROM 4/28/06 WHICH WERE NOT ADJUSTED AS MENTIONED
 ON PLANS TO BE DONE BEFORE ROUGH.
  
 1) NOTE: PLEASE SEE SERVICE HAS NOW COMPLETELY CHANGED
 TO INCLUDE SERVICE AT 400AMPS HOWEVER GROUNDING
 ELECTRODE CONDUCTOR WAS NOT INCREASED PER 250.66,
 310.15B6. (1/0)
  
 2) NOTE: PLEASE PLANS STILL INDICATE A MAIN DISCONNECT
 OUTSIDE WHERE RISER DOES NOT INCLUDE THIS.
 PLEASE CORRELATE RISER AND PLANS.
 PLEASE SEE LOAD CALCULATIONS ALSO CALL FOR A 300AMP
 SERVICE AS SHOWN ON PREVIOUS PLANS HOWEVER PLANS NOW
 SHOW 400AMP SERVICE.
 PLEASE SEE THAT THE RISER NOW SHOWS PANEL *B* AS
 200AMPS WITH WHAT APPEARS TO BE 2-100AMP BREAKERS SHOWN
 ON RISER?? IT IS UNCLEAR WHAT THIS IS?
 PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS OR FEEDERS
 DEPENDING IF THERE IS A MAIN OUTSIDE ARE NOT RATED FOR
 THE NEW 200AMP RATED MAIN.
 PLEASE CORRELATE SEVERAL ITEMS ON PLANS AND RISER.
 PLEASE SEE 310.15B6, 310.16, 240.4, 230.70 ETC FOR THE
 MINIMUM REQUIRED FOR SERVICE, MAINS ETC.
  
 3) NOTE: PLEASE VERIFY IF THERE IS NO MAINS OUTSIDE
 THAT THE CONDUITS FROM METER TO PANELS ARE IN THE SLAB
 AS REQUIRED PER 230.70, 230.71
  
 4) NOTE: PLEASE SEE NEW RECEPTACLE ADDED TO COUNTER
 SPACE IN KITCHEN SHALL BE GFI/GFI PROTECTED PER
 210.8A6.(PLEASE SHOW).
  
 5) NOTE: PLEASE KNOW THAT A MEETING WAS HELD AT THE
 SOUTHERN SECTION MEETING IN OCT 06 WHERE WE WERE
 DIRECTLY INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE
 DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT
 ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER
 THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS
 SA/SMOKE ALARMS.
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. BY
 THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE*.
 PLEASE SEE NFPA-72 11.5.1.1, 11.8.3
  
 6) NOTE: PLEASE KNOW THAT COMPLETE PANEL SCHEDULES
 SHOWING ALL ROOMS AND AREAS IN WHICH CIRCUITS FEED WILL
 BE REQUIRED FOR EACH PANEL. PLEASE SEE TEXT WHICH IS
 TAKEN FROM COMMENTARY IN THE CODE WHICH STATES THE USE
 OF *GEN LT* ETC IS NOT ACCEPTABLE.
  
 *CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* PLEASE
 INCLUDE THESE IN TWO SEPARATE PANEL SCHEDULE(S) AND
 DEPENDING ON RISER BASED ON NOTES ABOVE IT BEING
 UNCLEAR WHAT THE TWO 100AMP BREAKERS ARE?
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 7) NOTE: PLEASE SEE THE NOTES ON THE LOWER PART OF LOAD
 CALCULATIONS WHICH STILL MENTIONS OUTSIDE WP LIGHTING
 TO BE ON BATH CIRCUIT(S) WHICH IS NOT PERMITTED. THIS
 WAS REDLINED ALSO ON PREVIOUS PLANS.
 210.52D, 210.11C3
  
 * PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-04-28 Cont ID  
Sent By dpalmer Date 2006-04-28 Time 15:07 Rev Time 0.00
Received By dpalmer Date 2006-04-28 Time 14:53 Sent To M
Notes
2006-04-28 00:00:00REDLINED ITEMS ON PLANS.
  
  
  
 1) PLEASE SEE PLANS INDICATE A
 DISCONNECT OUTSIDE WITH METER, HOWEVER
 RISER SHOWS SLAB FEED TO MCB PANELS IN
 GARAGE. ** WORK PER RISER NOTED **
  
 2) NOTE: PLEASE SEE NOTE MENTIONS FOR WP
 LT FIXTURES TO BE CIRCUITED TO BATH
 CIRCUIT? BATH CIRCUIT MAY NOT FEED
 OUTDOOR LTS.* REDLINED**
  
 3) MISSING LT FIXTURE IN EGRES HALL
 UPSTAIRS. ** REDLINED **
  
  
 PLEASE REVISE THE ABOVE ALONG WIHT ANY
 OTHER REVISIONS BEFORE ROUGH. IF NO
 OTHER REVISIONS ARE MADE, THEN "REDLINED
 PLANS" DO NOT NEED TO BE REVISED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-10-19 Cont ID  
Sent By dpalmer Date 2005-10-19 Time 09:19 Rev Time 2.00
Received By dpalmer Date 2005-10-18 Time 13:25 Sent To M
Notes
2005-10-19 00:00:00*********** UNSAT ***********
  
  
 1) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
  
 2)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANEL SCHEDULES SUBMITTED.
 PLEASE SEE RISER SHOWS WHAT APPEARS TO
 BE A DISCONNECT LOCATED AT THE GROUNDING
 ELECTRODE CONDUCTOR??
 PLEASE SEE A FEEDER/CONDUIT SEEMS TO
 EXIT PANEL "A" AT TOP , BUT DOES NOT
 SHOW OR INDICATE WHERE THIS GOES??
 PLEASE SEE THE SAME IS HOWN FOR PANEL
 "B".
 PLEASE SEE SEC'S DO NOT MEET MIN FOR
 CODE COMPLIANCE PER 310.15B6, 240.4.
  
  
 3)NOTE: PLEASE SEE 250.66 FOR MIN GEC,
 SHOWN AS #4.
  
 4)NOTE: PLEASE SEE NOTE MENTIONS ALL
 RECEPTS WITHIN 15' OF POOL TO BE GFI??
 PLEASE SEE 680.22 ETC, A MIN OF 20'
 PLEASE ALSO SEE 680.22 FOR MIN DISTANCE
 AND PROTECTION REQUIRED FOR ALL FIXTURES
 WITH POOL AREA. PLEASE SEE LTS AS SHOWN
 ON PLANS FOR SCONCE LOCATIONS AND FUTURE
 POOL SHOWN.
  
 5)NOTE: PLEASE CORRELATE NOTES ON PLANS
 IN FOUR LOCATIONS FOR THE REQUIRED ARC
 FAULT PROTECTION.
 PLEASE SEE NOTE #6 MENTIONS THAT SD'S
 "SHALL NOT" HAVE ARC FAULT PROTECTION??
 PLEASE SEE OTHER NOTES MENTIONS ONLY
 RECEPTS AND OTHE NOTES MENTIONS ARC
 FAULT REQUIRED???
  
 ** PLEASE LIST ON THE PANEL SCHEDULE ALL
 THE MIN REQUIRED ARC FAULT PROTECTED
 CIRCUITS. PLEASE KNOW, UNDER THE 2002
 NEC 210.12 ALL OUTLETSIN BEDRMS ARE
 REQUIRED TO HAVE ARC FAULT PROTECTION.
 THIS IS LTS, FANS, SD'S AND RECEPTS.
  
 6)NOTE: PLEASE 210.52 FOR RECEPTS
 MISSING ON PLANS. PLEASE SEE MANY OF
 THESE HAVE BEEN REDLINED AT LOCATIONS
 MENTIONED.
  
 7)NOTE: PLEASE SEE MISSING RECEPTS ALONG
 KITCHEN COUNTERSPACE REQUIRED PER
 210.52C1
  
 8)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI
 PROTECTED.,210.8A6
  
 9)NOTE: PLEASE SEE MISSING REQUIRED
 EGRESS LT FIXTURES SHOWN AS "J" -BOXES
 ON PLANS. PLEASE SEE 210.70, LS 101 7.8
  
 10)NOTE: PLEASE SEE MISSING FRONT GFI
 RECEPT PER 210.52E, 210.8A
  
 11)NOTE: PLEASE SEE MISSING SD REQUIRED
 LEADING TO THE FLR ABOVE PER NFAP-72
 11.5.1.1
  
 PLEASE BE SURE TO ANY POSSIBLE COMMETNS
 FROM OTHER REVIEWERS WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS FOR
 REVIEW AND STAMPING.
 ON ECOPY OF ANY OLD/VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 NOTE,
  
  

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-05-02 Cont ID  
Sent By adarroug Date 2007-05-02 Time 11:42 Rev Time 0.00
Received By adarroug Date 2007-05-02 Time 11:42 Sent To B
Notes
2007-05-02 11:42:46TO "LMARTINEZ" DESK/2 REV'S

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-03-20 Cont ID  
Sent By adarroug Date 2007-03-20 Time 10:06 Rev Time 0.00
Received By adarroug Date 2007-03-20 Time 10:06 Sent To E
Notes
2007-03-20 10:07:15TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-02-22 Cont ID  
Sent By adarroug Date 2007-02-22 Time 17:20 Rev Time 0.00
Received By adarroug Date 2007-02-22 Time 17:20 Sent To E
Notes
2007-02-22 17:21:33TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-06-23 Cont ID  
Sent By adarroug Date 2006-06-23 Time 15:29 Rev Time 0.00
Received By adarroug Date 2006-06-23 Time 15:29 Sent To B
Notes
2006-06-23 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-04-27 Cont ID  
Sent By adarroug Date 2006-04-27 Time 10:24 Rev Time 0.00
Received By adarroug Date 2006-04-27 Time 10:24 Sent To E
Notes
2006-04-27 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-13 Cont ID  
Sent By adarroug Date 2006-04-13 Time 16:45 Rev Time 0.00
Received By adarroug Date 2006-04-13 Time 16:45 Sent To Z
Notes
2006-04-13 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-18 Cont ID  
Sent By adarroug Date 2005-10-18 Time 09:49 Rev Time 0.00
Received By adarroug Date 2005-10-18 Time 09:49 Sent To E
Notes
2005-10-18 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-21 Cont ID  
Sent By alange Date 2005-12-21 Time 12:14 Rev Time 0.00
Received By alange Date 2005-10-04 Time 08:51 Sent To  
Notes
2005-10-04 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-05-01 Cont ID  
Sent By tgordon Date 2006-05-01 Time 10:28 Rev Time 0.20
Received By tgordon Date 2006-05-01 Time 10:28 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-11-14 Cont ID  
Sent By tgordon Date 2005-11-14 Time 08:22 Rev Time 0.30
Received By tgordon Date 2005-11-14 Time 08:22 Sent To P
Notes
2005-11-14 00:00:00*** DENIED ***
 1) NEED DETAILED MANUFACTURE'S
 SPECIFICATION'S ON FIREPLACE.
 2) NEED DETAILED MANUFACTURE'S
 SPECIFICATION'S ON DOWN DRAFT RANGE.
 3) NEED NOTICE OF COMMENCEMENT.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-05-05 Cont ID  
Sent By jleech Date 2006-05-05 Time 09:25 Rev Time 0.00
Received By jleech Date 2006-05-05 Time 09:25 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-11-22 Cont ID  
Sent By jleech Date 2005-11-22 Time 16:54 Rev Time 1.00
Received By jleech Date 2005-11-22 Time 16:54 Sent To B
Notes
2005-11-22 00:00:00DENIED;
 1. VENT REQUIRED ON KITCHEN SINK AND W/W
 DISCHARGE HOSE MUST BE INSTALLED BEFORE
 THE KITCHEN SINK TRAP.
 2.W/M DRAIN TO BE 3"DRAIN, SEE FBC-2004
 PLUMBING SECTION 406.3. INSTALL CLEANOUT
 FOR W/M AT 48" AFF.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2006-04-26 Cont ID  
Sent By mmclean Date 2006-04-26 Time 07:09 Rev Time 0.00
Received By mmclean Date 2006-04-26 Time 07:09 Sent To I
Notes
2006-04-26 00:00:00NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/SPA/DECK/SCREEN ENCLOSURE.
  
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 FENCE/WALL/GATE WITH EASEMENT APPROVAL
 FROM THE CITY OF WEST PALM UTILITY DEPT
 AND FPL, FLORIDA PUBLIC UTILITIES,
 ADELPHIA, BELLSOUTH FOR HE 5FT UTILITY
 EASEMENT IN THE REAR OF PROPERTY.
  
 NOTE: CANNOT BUILD ANYTHING WITHIN THE
 5FT UTILITY EASEMENT.

Review Stop Z ZONING
Rev No 1 Status F Date 2005-10-17 Cont ID  
Sent By mmclean Date 2005-10-17 Time 16:24 Rev Time 0.00
Received By mmclean Date 2005-10-17 Time 16:24 Sent To I
Notes
2005-10-17 00:00:00DENIED,
 1. THE PROPOSED STRUCTURE IS OVER THE
 HEIGHT REQUIREMENT OF 33FT (30FT PLUS
 10% FOR CHIMNEY, TOTAL OF 33FT).
  
 ****************************************
 ****************************************
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 FENCE/WALL/COLUMNS WITH EASEMENT
 APPROVAL FROM THE CITY OF WEST PALM
 BEACH UTILITIES DEPT.
  
 NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/SPA/SCREEN ENCLOSURE/DECK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
  