| Plan Review Stops For Permit 05100065 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2006-04-25 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-04-25 |
Time |
10:34 |
Rev Time |
1.00 |
| Received By |
alange |
Date |
2006-04-25 |
Time |
10:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2006-03-22 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-03-22 |
Time |
12:04 |
Rev Time |
0.75 |
| Received By |
alange |
Date |
2006-03-22 |
Time |
12:04 |
Sent To |
|
|
| Notes |
| 2006-03-22 00:00:00 | DENIED | | | | | | | | | 3.SUBMIT TWO COPIES OF PRODUCT | | | APPROVALS FOR THE FOLLOWING; ROOFING. | | | | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | NEW COMMENT: | | | SEE ELECTRICAL COMMENT #1 REGARDING | | | WHITE-OUT AND PENCIL ON PLANS. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-02-16 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-02-16 |
Time |
08:23 |
Rev Time |
1.50 |
| Received By |
alange |
Date |
2006-02-16 |
Time |
08:23 |
Sent To |
|
|
| Notes |
| 2006-02-16 00:00:00 | DENIED | | | | | | | | | 3.SUBMIT TWO COPIES OF PRODUCT | | | APPROVALS FOR THE FOLLOWING; ROOFING. | | | | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | NEW COMMENT: | | | SEE ELECTRICAL COMMENT #1 REGARDING | | | WHITE-OUT AND PENCIL ON PLANS. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-12-05 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-12-05 |
Time |
07:45 |
Rev Time |
2.75 |
| Received By |
alange |
Date |
2005-12-05 |
Time |
07:35 |
Sent To |
|
|
| Notes |
| 2005-12-05 00:00:00 | DENIED | | | | | | 1.ALL PLANS SUBMITTED AFTER OCTOBER 1, | | | 2005 SHALL BE DESIGNED TO TH 2004 FBC. | | | | | | 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 2.SHOW COMPLIANCE WITH SMOKE DETECTORS | | | ACCORDING TO FBC R-313.1 | | | | | | 3.SUBMIT TWO COPIES OF PRODUCT | | | APPROVALS FOR THE FOLLOWING; ROOFING, | | | STRAPS AND TIE-DOWNS. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 4.SHOW GARAGE SEPERATION COMPLYING | | | WITH R-309.2 | | | | | | 5. SHOW SEPERATION BETWEEN GARAGE AND | | | SLEEPING ROOM COMPLYING WITH R-309.1. | | | DOOR NOT PERMITTED BETWEEN A GARAGE AND | | | A SLEEPING ROOM. | | | | | | 6.SHOW A STAIR DETAIL PER R-311.5 | | | | | | 7.SHOW DWELLING SEPERATION BETWEEN | | | UNITS PER R-317.1 | | | | | | 8.SHOW FIRE BLOCKING COMPLYING WITH | | | R-602.4 AND R-602.8 | | | | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | ART LANGE | | | BUILDING PLANS EXAMINER | | | 805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2006-04-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-04-24 |
Time |
19:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-04-24 |
Time |
19:07 |
Sent To |
B |
|
| Notes |
| 2006-04-24 00:00:00 | ELECTRICAL PLANS STAMPED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2006-03-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-03-08 |
Time |
13:32 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-03-08 |
Time |
13:32 |
Sent To |
B |
|
| Notes |
| 2006-03-08 00:00:00 | ****** UNSAT 3RD REVIEW ******* | | | | | | **PLEASE SEE NOTES FROM PREVIOUS HAVE | | | BEEN ADDRESSED, HOWEVER PLEASE SEE NEW | | | NOTES DUE TO ITEMS ON PLANS. | | | | | | 1)NOTE: PLEASE SEE PLANS NOW CONTAIN | | | "WHITE-OUT" AND PENCILED ITEMS ON PLANS. | | | PLEASE SEE SOME PLANS SHOW DOOR AND SOME | | | DETAILS REMOVE DOOR?? | | | PLEASE SEE NOW DOOR IS OR IS NOT | | | REMOVED, ARE LIGHT SWITCHES STILL BEING | | | INSTALLED AT LOCATION SHOWN? | | | PLANS CAN NOT CONTAIN "WHITE-OUT" AND | | | PENCIL. | | | FS 471.025 | | | | | | 2)NOTE: PLEASE SEE NOW KITCHEN DINING | | | AREA SHOWS CIRCUITING SHARED WITH | | | LIVING/FAMILY RM. | | | PLEASE SEE210.52B1, KITCHEN/DINING AREA | | | MUST HAVE A 20A , #12 CIRCUIT, MAY BE | | | ONE OF THE SMALL APPLIANCE CIRCUITS. | | | SHOWN AS 15A #14. | | | | | | 3)NOTE: PLEASE SEE NEW TITLE BLOCKS ARE | | | NOW MISSING THE REQUIRED PRINTED LICENSE | | | # OF THE ENGINEER. | | | THIS IS REQUIRED TO BE PRINTED IN THE | | | TITLE BLOCK PER FAC 61G15-23.002 | | | | | | ** PLEASE SEE ONCE COPY OF ELECTRICAL | | | PLANS WERE STAMPED IN ERROR AND HAS | | | SINCE BEEN VOIDED AND NEEDS TO BE | | | REPLACED. | | | | | | PLEASE SUBMIT THE ABOVE CORRECTIONS FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-02-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-02-03 |
Time |
23:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-02-03 |
Time |
22:06 |
Sent To |
Z |
|
| Notes |
| 2006-02-03 00:00:00 | ******** UNSAT 2ND REVIEW ********* | | | | | | ** PLEASE KNOW, DUE TO CHANGES IN PLANS, | | | PLEASE SEE COMMENTS BELOW. | | | | | | | | | 1)NOTE: PLEASE CORRELATE SERVICE AS | | | PLANS INDICATE A MCB INSIDE GARAGE, YET | | | RISER SHOWS THIS AS MLO? | | | PLEASE ALSO SEE MISSING MAIN DISCONNECT. | | | PLEASE SEE PLANS DO NOT SHOW NEW SERVICE | | | AS SHOWN ON RISER. | | | 215.5 | | | | | | 2)NOTE: PLEASE SEE RISER SEEMS TO | | | INDICATE THE 22,000 AIC RATING FOR THE | | | MLO PANEL?? | | | PLEASE KNOW, IF THIS IS INDEED THE CASE, | | | ALL BRANCH BRKRS IN THIS MLO PANEL WOULD | | | BE REQUIRED TO HAVE 22,000 RATED BRKRS. | | | THIS MUST BE A MISPRINT. PLEASE SPECIFY | | | AIC RATING OF MAIN. | | | 110.9,215.5 | | | | | | 3)NOTE: PLEASE SEE SD'S WILL BE REQUIRED | | | INSIDE AND OUTSIDE "OFFICE" AS THIS IS | | | AN ADAPTABLE SLEEPING RM. | | | NFPA-72 11.5.1.1 | | | | | | 4)NOTE: PLEASE SEE OCP FOR RANGE SAHLL | | | NOT EXCEED THAT RATING OF THE RANGE | | | RECEPT. (50A'S) PLEASE SEE 210.21B3 | | | | | | 5)NOTE: PLEASE SEE CLOSET LT SHALL MEET | | | 410.8, AS SHELVING IS NOT INDICCATE | | | PLEASE SEE ASSUMED 18" ON EITHER SIDE | | | AND MIN TYPE OF FIXTURE SHALL BE | | | INDICATED. | | | | | | 6)NOTE: PLEASE SEE MISSING RECEPTS FOR | | | 2' OF WALL SPACE. 210.52 | | | REDLINED. | | | | | | 7)NOTE: PLEASE SEE NOTES AS MANY ITEMS | | | AS LISTED , CENTRAL VAC, SPKR WIRING ETC | | | ARE NOT SHOWN ON PLANS. IF THESE ITEMS | | | ARE GOING TO BE INSTALLED UNDER THIS | | | PERMIT , PLEASE SHOW. IF NOT, PLEASE | | | REMOVE FROM NOTES. | | | | | | 8)NOTE: PLEASE SEE NOTES, AS NOTE | | | MENTIONS NO MORE THAN 6 RECEPTS | | | PERMITTED ON A CIRCUIT, HOWEVER SOME | | | CIRCUITS ON PLANS INDICATE MORE THAN 6. | | | PLEASE ADJUST PLANS, CIRCUITING , OR | | | NOTE. | | | 215.5 | | | | | | 9)NOTE: PLEASE KNOW, HOUSE/APT SEEMS TO | | | BE A REMODEL, HOWEVER RISER SHOWS THE | | | FOOTER STEEL TO BE PART OF THE GROUNDING | | | ELECTRODE SYSTEM?? | | | ** PLEASE KNOW, EXISTING FOOTER ARE NOT | | | REQUIRED TO HAVE THE FOOTER STEEL AS | | | PART IF THE GROUNDING ELECTRODE SYSTEM. | | | PLEASE ALSO KNOW, MANY OLDER BLDGS DO NO | | | CONTAIN FOOTER STEEL. | | | PLEASE ADJUST THIS ON RISER AS THIS | | | WOULD BE MORE DETRIMENTAL TO THE | | | STRUCTURE/FOOTERS. | | | PLEASE INDICATE TWO GRND RODS.250.56 | | | | | | 10)NOTE: PLEASE SEE NOTES FROM PREVIOUS | | | REVIEW WHICH REQUESTED THE MANUFACTURES | | | CUT SHEETS FOR THE "INSTANT"ON DEMAND" | | | WATER HEATERS. NEED TO VERIFY OCP, KW | | | RATING, AND LISTING FROM A NRTL. | | | | | | ** PLEASE SEE ANY OTHER COMMENTS FROM | | | OTHER TRADES WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | ** PLEASE REMOVE ANY OLD/VOIDED SHEETS | | | AND ONLY INSERT NEW REVISED SHEETS INTO | | | TWO COMPLETE SETS FOR REVIEW AND | | | STAMPING. PLEASE ONLY SUBMIT ONE COPY OF | | | OLD/VOIDED SHEETS FOR REFERENCE. | | | | | | ** PLEASE SEE MANY OF THE ABOVE ITEMS | | | ARE REDLINED ON ONE OF THE SETS. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-11-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-11-09 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-11-09 |
Time |
15:03 |
Sent To |
P |
|
| Notes |
| 2005-11-09 00:00:00 | ********* UNSAT ************** | | | | | | | | | **** PLEASE SEE ZONING REVIEW COMMENTS | | | AS THIS WILL GREATLY AFFECT ELECTRICAL | | | PLANS AND OTHER PLANS AS WELL. | | | | | | | | | 1)NOTE: PLEASE SEE SF-14 DESIGNATION | | | ONLY PERMITS ONE METER FOR GARAGE APT | | | AND AND 230.2 ONLY PERMITS ONE SERVICE. | | | PLEASE SEE TWO RISER DIAGRAMS ARE SHOWN/ | | | PLEASE ALSO CLARIFY MAIN HOUSE SERVICE | | | AND THIS BEING PART OF GARAGE APT | | | SERVICE. WILL THIS BE A 2-GANG METER AND | | | ONE FEEDING GARAGE APT? | | | PLEASE KNOW, DUE TO CHANGES IN SERVICE, | | | THERE MAY BE COMMENTS AS PERMANANT | | | SERVICE IS NOT SHOWN AT THIS TIME. | | | | | | 2)NOTE: ELECTRICAL PLANS ARE TO SHOW ALL | | | A/C EQUIPMENT AND DISCONNECTS PER 440.11 | | | | | | 3)NOTE: PLEASE SEE MISSING RECEPTS PER | | | 210.52 | | | | | | 3)NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ON EACH LEVEL OF A MULTI-LEVEL DWELLING | | | UNIT. | | | IN CLOSE PROXIMITY OF STAIRWAYS LEADING | | | TO FLOORS ABOVE AND IN THE VICINITY OF | | | BEDROOMS. | | | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE | | | A MIN OF 3' FROM BATHROOM DOORS AND | | | KITCHENS. | | | ABOVE PER:FBC 905.2, NFPA-72 11.5.1.1 | | | | | | 4)NOTE: PLEASE INDICATE ALL OUTSIDE, | | | GARAGE RECEPTS AS GFI. 210.8A | | | | | | 5)NOTE: PLEASE SEE MISSING GFI FOR CU, | | | 210.63 | | | | | | 6)NOTE: PLEASE SHOW LOCATIONS OF ALL | | | ELECTRICAL EQUIPMENT, NO VERIFICATION | | | CAN BE DONE AT THIS TIME FOR CODE | | | COMPLIANCE OF 230.70,230.72, 230.2 ETC. | | | | | | 7)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR FROM MAIN TO PANEL. | | | 250.24,250.110,250.122 ETC. | | | | | | 8)NOTE: PLEASE VERIFY THE KW LOAD FOR | | | THE "ON DEMAND" HWH. | | | PLEASE SUBMIT SPECS ON UNIT. 4.5 KW UNIT | | | DO NOT SEEM LIKE A COMMON SIZE. | | | | | | 9)NOTE: PLEASE SEE MISSING REQUIRED | | | DEDICATED BATH CIRCUIT(S). 20A, #12. | | | 210.11C3 | | | | | | 10)NOTE: PLEASE SEE MISSING INFORMATION | | | REQUIRED ON TITLE BLOCK PER FAC | | | 61G15-23.002 | | | | | | 11)NOTE: PLEASE SEE PLANS INDICATE WHAT | | | APPEARS TO BE STACKABLE WASHER/DRYER | | | YET, PANEL SCHEDULE SHOWS TWO SEPARATE | | | UNITS? | | | | | | 12)NOTE: PLEASE LIST THE REQUIRED ARC | | | FAULT PROTECTED CIRCUITS PER 2002 NEC | | | 210.12 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW AND IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | 2005-10-09 00:00:00 | SENT TO ZONING FOR CONVERSION OF FIRST | | | FLR. | | | PLANS TO RETURN TO ELECTRICAL FOR REVIEW | | | AFTER ZONING REVIEW. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2006-04-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-20 |
Time |
15:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-04-20 |
Time |
15:27 |
Sent To |
E |
|
| Notes |
| 2006-04-20 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2006-03-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-03-04 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-03-04 |
Time |
14:29 |
Sent To |
E |
|
| Notes |
| 2006-03-04 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-02-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-02-13 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-02-13 |
Time |
08:23 |
Sent To |
P |
|
| Notes |
| 2006-02-13 00:00:00 | TO "P" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-01-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-01-28 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-01-28 |
Time |
16:47 |
Sent To |
E |
|
| Notes |
| 2006-01-28 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-10-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-10-21 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-10-21 |
Time |
14:03 |
Sent To |
E |
|
| Notes |
| 2005-10-21 00:00:00 | TO "DPALMER" DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-12-05 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-12-05 |
Time |
07:49 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2005-10-04 |
Time |
09:07 |
Sent To |
|
|
| Notes |
| 2005-10-04 00:00:00 | TO "E" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2005-12-02 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2005-12-02 |
Time |
08:03 |
Rev Time |
0.15 |
| Received By |
tgordon |
Date |
2005-12-02 |
Time |
08:03 |
Sent To |
B |
|
| Notes |
| 2005-12-02 00:00:00 | NO MECH. PLANS OR MECH. CONTRACTOR | | | SUBMITTED AT THIS TIME. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2006-02-15 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-02-15 |
Time |
07:32 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2006-02-15 |
Time |
07:32 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-11-30 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-11-30 |
Time |
12:25 |
Rev Time |
0.75 |
| Received By |
jleech |
Date |
2005-11-30 |
Time |
12:25 |
Sent To |
M |
|
| Notes |
| 2005-11-30 00:00:00 | DENIED; | | | 1.NO WATER HEATERS SHOWN. WATER WATER | | | REQUIRED UNDER MINIMUM PLUMBING | | | FACILITIES. | | | 2.W/M FACILITIES ARE REQUIRED IN EACH | | | APT. OR IN A COMMON AREA FOR USE BY BOTH | | | APTS. | | | 3.SEE ZONING COMMENTS ABOUT KITCHEN | | | SINKS. | | | 4.SANITARY RISER DIAGRAM. | | | RISER FOR W/M TO BE 3" 2004 CODE | | | SEC.406.3. | | | RISER DIAGRAM, SHR. NOT VENTED AND | | | | | | | | | KITCHEN SINK MUST DISCHARGE DOWN | | | STREAM OF THE BATHROOM GROUP. | | | | | | SEC. 909.1 | | | 5.PLUMBING NOTES. 2004 PLUMBING CODE TO | | | BE USED. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2006-02-10 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-02-10 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-02-10 |
Time |
10:43 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2005-10-18 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2005-10-18 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2005-10-18 |
Time |
13:49 |
Sent To |
I |
|
| Notes |
| 2005-10-18 00:00:00 | DENIED,- ZONED SF14 | | | 1. NOT ALLOWED TO HAVE A SECOND KITCHEN | | | IN THE GARAGE APARTMENT. | | | 2. NOT ALLOWED TO HAVE TWO METERS. | | | | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|