Plan Review Details - Permit 05100065
Plan Review Stops For Permit 05100065
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-04-25 Cont ID  
Sent By alange Date 2006-04-25 Time 10:34 Rev Time 1.00
Received By alange Date 2006-04-25 Time 10:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-03-22 Cont ID  
Sent By alange Date 2006-03-22 Time 12:04 Rev Time 0.75
Received By alange Date 2006-03-22 Time 12:04 Sent To  
Notes
2006-03-22 00:00:00DENIED
  
  
 3.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR THE FOLLOWING; ROOFING.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 NEW COMMENT:
 SEE ELECTRICAL COMMENT #1 REGARDING
 WHITE-OUT AND PENCIL ON PLANS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-02-16 Cont ID  
Sent By alange Date 2006-02-16 Time 08:23 Rev Time 1.50
Received By alange Date 2006-02-16 Time 08:23 Sent To  
Notes
2006-02-16 00:00:00DENIED
  
  
 3.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR THE FOLLOWING; ROOFING.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 NEW COMMENT:
 SEE ELECTRICAL COMMENT #1 REGARDING
 WHITE-OUT AND PENCIL ON PLANS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-05 Cont ID  
Sent By alange Date 2005-12-05 Time 07:45 Rev Time 2.75
Received By alange Date 2005-12-05 Time 07:35 Sent To  
Notes
2005-12-05 00:00:00DENIED
  
 1.ALL PLANS SUBMITTED AFTER OCTOBER 1,
 2005 SHALL BE DESIGNED TO TH 2004 FBC.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2.SHOW COMPLIANCE WITH SMOKE DETECTORS
 ACCORDING TO FBC R-313.1
  
 3.SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR THE FOLLOWING; ROOFING,
 STRAPS AND TIE-DOWNS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4.SHOW GARAGE SEPERATION COMPLYING
 WITH R-309.2
  
 5. SHOW SEPERATION BETWEEN GARAGE AND
 SLEEPING ROOM COMPLYING WITH R-309.1.
 DOOR NOT PERMITTED BETWEEN A GARAGE AND
 A SLEEPING ROOM.
  
 6.SHOW A STAIR DETAIL PER R-311.5
  
 7.SHOW DWELLING SEPERATION BETWEEN
 UNITS PER R-317.1
  
 8.SHOW FIRE BLOCKING COMPLYING WITH
 R-602.4 AND R-602.8
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-04-24 Cont ID  
Sent By dpalmer Date 2006-04-24 Time 19:07 Rev Time 0.00
Received By dpalmer Date 2006-04-24 Time 19:07 Sent To B
Notes
2006-04-24 00:00:00ELECTRICAL PLANS STAMPED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-03-08 Cont ID  
Sent By dpalmer Date 2006-03-08 Time 13:32 Rev Time 0.00
Received By dpalmer Date 2006-03-08 Time 13:32 Sent To B
Notes
2006-03-08 00:00:00****** UNSAT 3RD REVIEW *******
  
 **PLEASE SEE NOTES FROM PREVIOUS HAVE
 BEEN ADDRESSED, HOWEVER PLEASE SEE NEW
 NOTES DUE TO ITEMS ON PLANS.
  
 1)NOTE: PLEASE SEE PLANS NOW CONTAIN
 "WHITE-OUT" AND PENCILED ITEMS ON PLANS.
 PLEASE SEE SOME PLANS SHOW DOOR AND SOME
 DETAILS REMOVE DOOR??
 PLEASE SEE NOW DOOR IS OR IS NOT
 REMOVED, ARE LIGHT SWITCHES STILL BEING
 INSTALLED AT LOCATION SHOWN?
 PLANS CAN NOT CONTAIN "WHITE-OUT" AND
 PENCIL.
 FS 471.025
  
 2)NOTE: PLEASE SEE NOW KITCHEN DINING
 AREA SHOWS CIRCUITING SHARED WITH
 LIVING/FAMILY RM.
 PLEASE SEE210.52B1, KITCHEN/DINING AREA
 MUST HAVE A 20A , #12 CIRCUIT, MAY BE
 ONE OF THE SMALL APPLIANCE CIRCUITS.
 SHOWN AS 15A #14.
  
 3)NOTE: PLEASE SEE NEW TITLE BLOCKS ARE
 NOW MISSING THE REQUIRED PRINTED LICENSE
 # OF THE ENGINEER.
 THIS IS REQUIRED TO BE PRINTED IN THE
 TITLE BLOCK PER FAC 61G15-23.002
  
 ** PLEASE SEE ONCE COPY OF ELECTRICAL
 PLANS WERE STAMPED IN ERROR AND HAS
 SINCE BEEN VOIDED AND NEEDS TO BE
 REPLACED.
  
 PLEASE SUBMIT THE ABOVE CORRECTIONS FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-02-03 Cont ID  
Sent By dpalmer Date 2006-02-03 Time 23:07 Rev Time 0.00
Received By dpalmer Date 2006-02-03 Time 22:06 Sent To Z
Notes
2006-02-03 00:00:00******** UNSAT 2ND REVIEW *********
  
 ** PLEASE KNOW, DUE TO CHANGES IN PLANS,
 PLEASE SEE COMMENTS BELOW.
  
  
 1)NOTE: PLEASE CORRELATE SERVICE AS
 PLANS INDICATE A MCB INSIDE GARAGE, YET
 RISER SHOWS THIS AS MLO?
 PLEASE ALSO SEE MISSING MAIN DISCONNECT.
 PLEASE SEE PLANS DO NOT SHOW NEW SERVICE
 AS SHOWN ON RISER.
 215.5
  
 2)NOTE: PLEASE SEE RISER SEEMS TO
 INDICATE THE 22,000 AIC RATING FOR THE
 MLO PANEL??
 PLEASE KNOW, IF THIS IS INDEED THE CASE,
 ALL BRANCH BRKRS IN THIS MLO PANEL WOULD
 BE REQUIRED TO HAVE 22,000 RATED BRKRS.
 THIS MUST BE A MISPRINT. PLEASE SPECIFY
 AIC RATING OF MAIN.
 110.9,215.5
  
 3)NOTE: PLEASE SEE SD'S WILL BE REQUIRED
 INSIDE AND OUTSIDE "OFFICE" AS THIS IS
 AN ADAPTABLE SLEEPING RM.
 NFPA-72 11.5.1.1
  
 4)NOTE: PLEASE SEE OCP FOR RANGE SAHLL
 NOT EXCEED THAT RATING OF THE RANGE
 RECEPT. (50A'S) PLEASE SEE 210.21B3
  
 5)NOTE: PLEASE SEE CLOSET LT SHALL MEET
 410.8, AS SHELVING IS NOT INDICCATE
 PLEASE SEE ASSUMED 18" ON EITHER SIDE
 AND MIN TYPE OF FIXTURE SHALL BE
 INDICATED.
  
 6)NOTE: PLEASE SEE MISSING RECEPTS FOR
 2' OF WALL SPACE. 210.52
 REDLINED.
  
 7)NOTE: PLEASE SEE NOTES AS MANY ITEMS
 AS LISTED , CENTRAL VAC, SPKR WIRING ETC
 ARE NOT SHOWN ON PLANS. IF THESE ITEMS
 ARE GOING TO BE INSTALLED UNDER THIS
 PERMIT , PLEASE SHOW. IF NOT, PLEASE
 REMOVE FROM NOTES.
  
 8)NOTE: PLEASE SEE NOTES, AS NOTE
 MENTIONS NO MORE THAN 6 RECEPTS
 PERMITTED ON A CIRCUIT, HOWEVER SOME
 CIRCUITS ON PLANS INDICATE MORE THAN 6.
 PLEASE ADJUST PLANS, CIRCUITING , OR
 NOTE.
 215.5
  
 9)NOTE: PLEASE KNOW, HOUSE/APT SEEMS TO
 BE A REMODEL, HOWEVER RISER SHOWS THE
 FOOTER STEEL TO BE PART OF THE GROUNDING
 ELECTRODE SYSTEM??
 ** PLEASE KNOW, EXISTING FOOTER ARE NOT
 REQUIRED TO HAVE THE FOOTER STEEL AS
 PART IF THE GROUNDING ELECTRODE SYSTEM.
 PLEASE ALSO KNOW, MANY OLDER BLDGS DO NO
 CONTAIN FOOTER STEEL.
 PLEASE ADJUST THIS ON RISER AS THIS
 WOULD BE MORE DETRIMENTAL TO THE
 STRUCTURE/FOOTERS.
 PLEASE INDICATE TWO GRND RODS.250.56
  
 10)NOTE: PLEASE SEE NOTES FROM PREVIOUS
 REVIEW WHICH REQUESTED THE MANUFACTURES
 CUT SHEETS FOR THE "INSTANT"ON DEMAND"
 WATER HEATERS. NEED TO VERIFY OCP, KW
 RATING, AND LISTING FROM A NRTL.
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE REMOVE ANY OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 TWO COMPLETE SETS FOR REVIEW AND
 STAMPING. PLEASE ONLY SUBMIT ONE COPY OF
 OLD/VOIDED SHEETS FOR REFERENCE.
  
 ** PLEASE SEE MANY OF THE ABOVE ITEMS
 ARE REDLINED ON ONE OF THE SETS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-11-09 Cont ID  
Sent By dpalmer Date 2005-11-09 Time 15:03 Rev Time 0.00
Received By dpalmer Date 2005-11-09 Time 15:03 Sent To P
Notes
2005-11-09 00:00:00********* UNSAT **************
  
  
 **** PLEASE SEE ZONING REVIEW COMMENTS
 AS THIS WILL GREATLY AFFECT ELECTRICAL
 PLANS AND OTHER PLANS AS WELL.
  
  
 1)NOTE: PLEASE SEE SF-14 DESIGNATION
 ONLY PERMITS ONE METER FOR GARAGE APT
 AND AND 230.2 ONLY PERMITS ONE SERVICE.
 PLEASE SEE TWO RISER DIAGRAMS ARE SHOWN/
 PLEASE ALSO CLARIFY MAIN HOUSE SERVICE
 AND THIS BEING PART OF GARAGE APT
 SERVICE. WILL THIS BE A 2-GANG METER AND
 ONE FEEDING GARAGE APT?
 PLEASE KNOW, DUE TO CHANGES IN SERVICE,
 THERE MAY BE COMMENTS AS PERMANANT
 SERVICE IS NOT SHOWN AT THIS TIME.
  
 2)NOTE: ELECTRICAL PLANS ARE TO SHOW ALL
 A/C EQUIPMENT AND DISCONNECTS PER 440.11
  
 3)NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52
  
 3)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 11.5.1.1
  
 4)NOTE: PLEASE INDICATE ALL OUTSIDE,
 GARAGE RECEPTS AS GFI. 210.8A
  
 5)NOTE: PLEASE SEE MISSING GFI FOR CU,
 210.63
  
 6)NOTE: PLEASE SHOW LOCATIONS OF ALL
 ELECTRICAL EQUIPMENT, NO VERIFICATION
 CAN BE DONE AT THIS TIME FOR CODE
 COMPLIANCE OF 230.70,230.72, 230.2 ETC.
  
 7)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO PANEL.
 250.24,250.110,250.122 ETC.
  
 8)NOTE: PLEASE VERIFY THE KW LOAD FOR
 THE "ON DEMAND" HWH.
 PLEASE SUBMIT SPECS ON UNIT. 4.5 KW UNIT
 DO NOT SEEM LIKE A COMMON SIZE.
  
 9)NOTE: PLEASE SEE MISSING REQUIRED
 DEDICATED BATH CIRCUIT(S). 20A, #12.
 210.11C3
  
 10)NOTE: PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCK PER FAC
 61G15-23.002
  
 11)NOTE: PLEASE SEE PLANS INDICATE WHAT
 APPEARS TO BE STACKABLE WASHER/DRYER
 YET, PANEL SCHEDULE SHOWS TWO SEPARATE
 UNITS?
  
 12)NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS PER 2002 NEC
 210.12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW AND IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-10-09 00:00:00SENT TO ZONING FOR CONVERSION OF FIRST
 FLR.
 PLANS TO RETURN TO ELECTRICAL FOR REVIEW
 AFTER ZONING REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-04-20 Cont ID  
Sent By adarroug Date 2006-04-20 Time 15:27 Rev Time 0.00
Received By adarroug Date 2006-04-20 Time 15:27 Sent To E
Notes
2006-04-20 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-03-04 Cont ID  
Sent By adarroug Date 2006-03-04 Time 14:29 Rev Time 0.00
Received By adarroug Date 2006-03-04 Time 14:29 Sent To E
Notes
2006-03-04 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-13 Cont ID  
Sent By adarroug Date 2006-02-13 Time 08:23 Rev Time 0.00
Received By adarroug Date 2006-02-13 Time 08:23 Sent To P
Notes
2006-02-13 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-01-28 Cont ID  
Sent By adarroug Date 2006-01-28 Time 16:47 Rev Time 0.00
Received By adarroug Date 2006-01-28 Time 16:47 Sent To E
Notes
2006-01-28 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-10-21 Cont ID  
Sent By adarroug Date 2005-10-21 Time 14:03 Rev Time 0.00
Received By adarroug Date 2005-10-21 Time 14:03 Sent To E
Notes
2005-10-21 00:00:00TO "DPALMER" DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-05 Cont ID  
Sent By alange Date 2005-12-05 Time 07:49 Rev Time 0.00
Received By alange Date 2005-10-04 Time 09:07 Sent To  
Notes
2005-10-04 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-12-02 Cont ID  
Sent By tgordon Date 2005-12-02 Time 08:03 Rev Time 0.15
Received By tgordon Date 2005-12-02 Time 08:03 Sent To B
Notes
2005-12-02 00:00:00NO MECH. PLANS OR MECH. CONTRACTOR
 SUBMITTED AT THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-02-15 Cont ID  
Sent By jleech Date 2006-02-15 Time 07:32 Rev Time 0.00
Received By jleech Date 2006-02-15 Time 07:32 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-11-30 Cont ID  
Sent By jleech Date 2005-11-30 Time 12:25 Rev Time 0.75
Received By jleech Date 2005-11-30 Time 12:25 Sent To M
Notes
2005-11-30 00:00:00DENIED;
 1.NO WATER HEATERS SHOWN. WATER WATER
 REQUIRED UNDER MINIMUM PLUMBING
 FACILITIES.
 2.W/M FACILITIES ARE REQUIRED IN EACH
 APT. OR IN A COMMON AREA FOR USE BY BOTH
 APTS.
 3.SEE ZONING COMMENTS ABOUT KITCHEN
 SINKS.
 4.SANITARY RISER DIAGRAM.
 RISER FOR W/M TO BE 3" 2004 CODE
 SEC.406.3.
 RISER DIAGRAM, SHR. NOT VENTED AND
  
  
 KITCHEN SINK MUST DISCHARGE DOWN
 STREAM OF THE BATHROOM GROUP.
  
 SEC. 909.1
 5.PLUMBING NOTES. 2004 PLUMBING CODE TO
 BE USED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2006-02-10 Cont ID  
Sent By mmclean Date 2006-02-10 Time 10:43 Rev Time 0.00
Received By mmclean Date 2006-02-10 Time 10:43 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2005-10-18 Cont ID  
Sent By mmclean Date 2005-10-18 Time 13:49 Rev Time 0.00
Received By mmclean Date 2005-10-18 Time 13:49 Sent To I
Notes
2005-10-18 00:00:00DENIED,- ZONED SF14
 1. NOT ALLOWED TO HAVE A SECOND KITCHEN
 IN THE GARAGE APARTMENT.
 2. NOT ALLOWED TO HAVE TWO METERS.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved