| 2006-06-11 00:00:00 | IN ELEC |
| | ************ UNSAT 2ND REVIEW********* |
| | |
| | |
| | ** IT IS KNOWN THAT PLANS ARE UNDER THE |
| | 2001 FBC, AS THE ELECTRICLA REVIEW WAS |
| | DONE UNDER THE 2001FBC AND OTHER ADOPTED |
| | CODES UNDER THE 2001 FBC. |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM |
| | PREVIOUS REVIEW STILL NEED TO BE |
| | ADDRESSED AND SOME NEW COMMENTS FOR |
| | ITEMS ON PLANS. |
| | |
| | ************************************ |
| | IMPORTANT |
| | PLEASE SEE BUILDING REVIEW COMMENTS AND |
| | PLEASE KNOW, IT WAS CONFIRMED BY THE |
| | ASST BUILDING OFFICAL THAT THIS JOB WILL |
| | REQUIRE A MIN OF A RESIDENT INPSECTOR. |
| | IN THIS CASE THREE SETS OF ALL PLANS |
| | UNDER EACH PERMIT WILL BE REQUIRED ONCE |
| | ALL IS READY TO BE ISSUED. IF THERE ARE |
| | NAY QUESTIONS, PLEASE CONTACT MR. ROBERT |
| | BROWN ASST BUILDING OFFICAL/LICENSE AND |
| | PEMRITS MANAGER. |
| | *********************************** |
| | |
| | ** PLEASE SEE NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW AND NEW |
| | NOTE(S) ARE ADDED BELOW. |
| | |
| | DIXIE MEWS / AQUA TERRACE |
| | |
| | 1)NOTE: NOTE#1 NO, PLEASE SEE NOTE ALL |
| | SHEET COMPLY. PLEASE SEE CIVILS WHICH |
| | CONTAIN A RAISED SEAL OVER A |
| | PHOTO-COPIED SIGNATURE BY THE ENGINEER. |
| | PLEASE SEE THIS IS NOT PERMITTED AND |
| | SHALL BE SIGNED WITH AN ORIGINAL |
| | SIGNATURE AND DATE. PLANS MAY BE |
| | RETAINED. |
| | PLEASE SEE LANDSCAPE PLANS WHICH ARE |
| | SIGNED WITH WHAT APPEARS TO BE A CRAYON? |
| | PLEASE BE SURE THIS IS SIGNED IN INK. |
| | PLEASE SEE MEP PLANS APPEAR TO BE SIGNED |
| | WITH WHAT APPEARS TO BE "INITIALS"? |
| | PLEASE SEE FS 471.025 WHICH REQUIRES A |
| | SIGNATURE. THIS SHOULD BE THE DESIGNER'S |
| | LEGAL SIGNATURE. IF THIS IS INDEED THE |
| | "LEGAL SIGNATURE" OF ENGINEER, PLEASE |
| | PROVIDE A SIGNED, DATED, SEALED LETTER |
| | FOR ATTESTING TO THIS AS THE LEGAL |
| | SIGNATURE. THIS LETTER MUST ALSO BE |
| | NOTORIZED PER FS 117.05 |
| | THIS LTR WILL THEN BE PLACED IN OUR |
| | SIGNATURE FILE FOR ANY FUTURE REFERENCE. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE PROVIDE SIGNED, DATED AND |
| | SEALED PLANS BY ARCHITECT AND |
| | ENGINEER(S) OF RECORD. FS 481.221 AND |
| | 471.025. |
| | PLEASE SEE PLANS CONTAIN SOME SORT OF |
| | "CORPORATE SEAL' WHICH IS NOT |
| | ACCEPTABLE. |
| | PLEASE KNOW THIS IS REQUIRED OF ALL |
| | SHEETS AND FOR ALL TRADE REVIEWS WHETHER |
| | OR NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | |
| | 2)NOTE: NOTE #2 NO, PLEASE SEE MISSING |
| | FIRM LICENSE NUMBER IN THE TITLE BLOCKS |
| | FOR THE ARCHITECTURAL FIRM, LANDSCAPE |
| | ARCH FIRM. PLEASE ALSO SEE THE "A" |
| | SHEETS SHALL ALSO INDICATE THE |
| | ARCHITECT'S PRINTED NAME. PLEASE SEE |
| | THIS WAS REQUESTED BY MORE THAN ONE |
| | REVIEWER ON PREVIOUS REVIEW AND THE |
| | RESPONSE LTR MENTIONS "FIRM NAME ADDED". |
| | PLEASE SEE THIS COMMENT WAS FOR ALL |
| | REQUIRED INFORMATION. |
| | PLEASE KNOW, THIS INFORMATION IS |
| | REQUIRED ON ALL TITLE BLOCKS, ALL SHEETS |
| | AND FOR ALL TRADES. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE COMPLETE AND INCLUDE ALL |
| | INFORMATION ON SAID TITLE BLOCKS FOR |
| | ARCHITECTUAL AND ENGINEERING FIRMS. |
| | PLEASE SEE FLORIDA ADMINISTRATIVE CODES |
| | 61G1-16.004 (ARCH) AND 61G15-23.002 |
| | (ENG). |
| | PLEASE KNOW THIS IS REQUIRED FOR ALL |
| | SHEETS AND FOR ALL TRADES. |
| | |
| | 3)NOTE: OK |
| | |
| | 4)NOTE: NOTE #4 OK, DOORS REMOVED TO |
| | MEET 110.26, PLEASE SEE BUILDING REVIEW |
| | FOR ANY QUESTION FOR EGRESS. |
| | PLEASE KNOW, OTHERWISE THIS COMMENT WAS |
| | ADDRESSED. |
| | |
| | **PREVIOUS NOTE ** |
| | PLEASE VERIFY CLEARENCES FOR |
| | ELECTRICAL SERVICE PER 110.26, |
| | APPEARS TO SHOW DOORS WHICH WILL SLIDE |
| | OPEN ON EACH SIDE, HOWEVER THIS WILL |
| | ALWAYS CREATE A COMMON POINT IN THE |
| | CENTER WHICH WOULD NOT MEET CODE. |
| | PLEASE PROVIDE AN ELEVATION AS HEIGHT |
| | AND WIDTH IS TO BE VERIFIED. |
| | PLEASE ALSO VERIFY IT APPEARS THIS |
| | ROOM/AREA IS ALSO THE GRESS FROM COMMON |
| | STAIR TOWER AND LOBBY AREA? |
| | PLEASE SEE BLDG REVIEW COMMENTS FOR FIRE |
| | SEPARATION AS STAIRS EXIT INTO THIS AREA |
| | AND NO DOORS ARE SHOWN WHICH MAY ALLOW |
| | EXITING BACK INTO COMMON LOBBY AREA |
| | PLEASE SEE THIS IS SHOWING SWITCHING FOR |
| | LTS? |
| | PLEASE ALSO SEE NEXT COMMENT WITH |
| | RESPECT TO THE CIRCUIT SHOWN. |
| | |
| | 5)NOTE: NOTE #5 NO, PLEASE SEE THAT THE |
| | DEDICATED CIRCUITS PER 620.23,620.24 |
| | SHALL NOT FEED ANY OTHER ITEMS. PLEASE |
| | SEE THE RECEPT IN ELEV RM, CAN NOT BE ON |
| | THE SAME CIRCUIT WITH PIT RECEPT. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE HOUSE CIRCUIT SHOWN |
| | FOR ELEVATOR MACHINE ROOM IS ALSO SHOWN |
| | FEEDING OTHER AREAS. PLEASE SEE 620.23 |
| | WHICH REQUIRES THE BRANCH CIRCUIT FOR |
| | LTS AND RECEPTS TO BE DEDICATED. |
| | PLEASE ADJUST. |
| | |
| | 6)NOTE: NOTE #6 NO, PLEASE SEE SOME |
| | MENTION OF FC'S ARE NOTED ON PLANS, |
| | HOWEVER COMPLETE PHOTO-METRICS ARE |
| | NEEDED. |
| | PLEASE SUBMIT. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE PROVIDE PHOTOMETRICS FOR |
| | COMMON AREAS FOR EGRESS LIGHTING. PLEASE |
| | SEE THIS WOULD INCLUDE LOBBY AREAS, |
| | STAIR TOWERS, SHOW ALL FT CANDLES TO THE |
| | EXIT/PUBLIC RIGHT OF WAY. |
| | PLEASE SEE 2003 NFPA-101 7.8 AND 7.9 |
| | WHICH REQUIRES 10 FT CANDLES UNDER |
| | NORMAL POWERE AND A MIN OF 1FT CANDLE |
| | UNDER EM POWER. |
| | PLEASE ALSO SEE FURTHER COMMENTS WIHT |
| | RESPECT TO FIXTURES. |
| | |
| | 7)NOTE: OK |
| | |
| | 8)NOTE: OK. |
| | |
| | 9)NOTE: NOTE #9 OK, HOWEVER SEE NEW |
| | NOTES FOR ADDED CONDUCTORS. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE SHOW THE CONDUCTORS FROM |
| | HOUSE GUTTER TO EACH DISCONNECT. |
| | 215.5 |
| | |
| | 10)NOTE: NOTE #10, THIS HAS NOT YET BEEN |
| | CONFIRMED. PLEASE SEE PLANS AND |
| | PAPERWORK NOW MENTION BUILDING SHALL |
| | CONTAIN NEW "CONDO UNITS" AS SINGLE |
| | FANILY RESIDENCES. |
| | PLEASE SEE THE SD'S IN THE RES CONDO |
| | UNITS MAY BE REQUIRED TO BE 120V WIRED |
| | INLINE AND WITH ARC FAULT PROTECTION PER |
| | 210.12B |
| | CONTACT TO THE FIRE MARSHAL'S OFFICE AND |
| | CHIEF CARSILLO WILL BE MADE. |
| | IT SEEMS IF THESE ARE NOW SFR CONDO'S, |
| | TRIPPING OF THE SD'S IN EACH UNIT UPON |
| | SOME COOKING PRACTICES ETC WOULD CREATE |
| | TRIPPING OF THE ENTIRE BUILDINGS FIRE |
| | ALARM SYSTEM?? |
| | |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE VERIFY WITH THE FIRE |
| | MARSHAL'S OFFICE IF INDEED THE UNIT SD'S |
| | WILL BE TIED INTO BASE BLDG PROTECTION |
| | SYSTEM. |
| | PLEASE KNOW, IF THESE ARE 120V WIRED |
| | INLINE IN UNITS, THEN CIRCUITING WILL BE |
| | REQUIRED ALONG WITH ARC FAULT |
| | PROTECTION. |
| | 215.5,210.12 |
| | THIS WOULD ALSO BE AFFECTED BY THE |
| | "TOWNHOUSE" DECLARATION. |
| | |
| | 11)NOTE: OK. |
| | |
| | 12)NOTE: OK. |
| | |
| | 13)NOTE: OK. |
| | |
| | 15)NOTE: OK. |
| | |
| | 16)NOTE: OK. |
| | |
| | 17)NOTE: NOTE #17 NO, ALMOST ALL WERE |
| | DONE HOWEVER PLEASE SEE WALL SPACE 2' OR |
| | MORE EVEN BEHIND DOORS WILL BE REQUIRED |
| | TO HAVE A RECEPT. PLEASE SEE TWO |
| | REDLINED IN PH UNITS. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE 210.52 FOR RECEPTS |
| | MISSING FOR 2' OR MORE OF WALL SPACE. |
| | PLEASE SEE MOST IF THESE LOCATIONS ARE |
| | REDLINED ON PLANS. (SEE MOSTLY 3RD FLR. |
| | |
| | 18)NOTE: OK. |
| | |
| | 19)NOTE: OK, HOWEVER SEE NEW NOTES FOR |
| | DINGIN CIRCUITS ADDED. |
| | |
| | 20)NOTE: OK. |
| | |
| | 21)NOTE: OK. |
| | |
| | 22)NOTE: OK. |
| | |
| | 23)NOTE: OK. |
| | |
| | 24)NOTE: OK. |
| | |
| | 25)NOTE: NOTE #25 NO, COULD NOT FIND? |
| | RESPONSE MENTIONS THIS WAS ADDED? |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE PLACE NOTE ON PLANS FOR |
| | ALL SD'S TO BE INSTALLED PER 2002 |
| | NFPA-72 11.8.3.5 |
| | |
| | 26)NOTE: NOTE #26 NO, AND NO RESPONSE |
| | WAS GIVEN FOR THE NOTE. |
| | THIS SHOULD BE ADDED TO NOTES ON E-10 |
| | |
| | **PREIVOUS NOTE ** |
| | PLEASE MAKE NOTE FOR ALL MIN |
| | FAIR HOUSING ACT REQUIREMENTS FOR DEVICE |
| | HEIGHTS. |
| | 24 CFR 100.205 |
| | |
| | *********** NEW NOTES *********** |
| | |
| | 27) NOTE: PLEASE SEE DINING RM CIRCUITS |
| | AND THE LIKE SHALL BE SHOWN WITH THE MIN |
| | VA FIGURED FOR THE CIRCUIT AT 1.5VA. |
| | PLEASE SEE 210.52B1,210.11C1, 220.16 |
| | |
| | 28) NOTE: PLEASE SEE THE FOLLOWING CODES |
| | SHALL BE PRINTED ON ELECTRICAL PLANS. |
| | NFPA-101 2003,NFPA-72 2002, NFPA-70 |
| | 2002. |
| | |
| | 29) NOTE: PLEASE SEE RISER IS NOW |
| | SHOWING "EQUIPMENT GROUNDING CONDUCTORS" |
| | FOR SEC'S FROM GUTTER TO MAINS FOR |
| | HOUSE. |
| | PLEASE SEE 250.6,250.24B , THESE ARE |
| | ONLY INSTALLED AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | |
| | 30) NOTE: PLEASE SEE WHAT APPEARS TO BE |
| | A MISPRINT FOR THE RISER NOTE #5, |
| | MENTIONS "MLB" , SHOULD THIS BE "MCB"? |
| | |
| | 31) NOTE: PLEASE SEE CIRCUITS FOR GEN |
| | LTS AND RECEPTS SHALL BE SPECIFIC TO |
| | ROOMS AND AREAS IN WHICH THESE CIRCUITS |
| | ARE FEEDING. IE: MASTER BEDRM RECEPTS. |
| | BATH #2 LTS, KITCHEN LTS ETC. |
| | 408.4 |
| | |
| | 32) NOTE: PLEASE KNOW, AS PLANS WERE |
| | INDEED SUBMITTED FOR PERMIT, PLEASE SEE |
| | COPY OF FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS THREE OR MORE TIMES. |
| | THIS IS ONLY A NOTICE GIVEN AT THIS |
| | TIME. |
| | |
| | *** IMPORTANT** |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE BE SURE |
| | TO SUBMIT ONE COPY OF THE OLD PLANS FOR |
| | REFERENCE. |
| | |
| | ** PLEASE SEE ONE SET OF PLANS HAS MUCH |
| | OF THE ABOVE REDLINED FOR AREAS OF |
| | COMMENTS. THIS MAY HELP IN AREAS AS |
| | NOTED. (RECEPTS ETC) |
| | |
| | ** PLEASE KNOW, A RESPONSE LETTER WITH |
| | RESPECT TO COMMENTS AND WHAT ACTIONS |
| | WERE TAKEN WOULD GREATLY HELP IN |
| | EXPEDITING THE PLAN REVIEW PROCESS. |
| | PLEASE KEEP IN MIND TO CLOUD/TRIANGLE |
| | ANY REVISED LOCATIONS ON PLANS. |
| | |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES |
| | WHICH MAY HAVE AN AFFECT ON ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |