Plan Review Details - Permit 05091697
Plan Review Stops For Permit 05091697
Review Stop G GAS REVIEW
Rev No 1 Status F Date 2005-10-18 Cont ID  
Sent By jleech Date 2005-10-18 Time 14:13 Rev Time 0.50
Received By jleech Date 2005-10-18 Time 14:13 Sent To  
Notes
2005-10-18 00:00:00DENIED;
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. TYPE OF GAS, (LP OR NATURAL)
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 5. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 6.HOW IS PIPE TO BE INSTALLED, UNDER
 GROUND, OR STAPED TO DECK.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-03 Cont ID  
Sent By adarroug Date 2005-10-03 Time 08:28 Rev Time 0.00
Received By adarroug Date 2005-10-03 Time 08:28 Sent To G
Notes
2005-10-03 00:00:00TO "G" BOX