Plan Review Details - Permit 05091687
Plan Review Stops For Permit 05091687
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2007-12-05 Cont ID  
Sent By lursu Date 2007-09-24 Time 09:50 Rev Time 0.00
Received By lursu Date 2007-09-24 Time 08:26 Sent To  
Notes
2007-09-24 09:50:37NEW SITE ADDRESS HAS BEEN ASSIGNED TO BUILDING 3 AS 331
 COURTNEY LAKES CIR , WEST PALM BEACH, FL 33401.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]
  

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-03-01 Cont ID  
Sent By lursu Date 2006-03-01 Time 15:20 Rev Time 0.00
Received By lursu Date 2006-03-01 Time 15:19 Sent To  
Notes
2006-03-01 00:00:00SITE PLAN NEEDED TO ISSUE AN ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-10-16 Cont ID  
Sent By jjohnsto Date 2007-10-16 Time 13:30 Rev Time 8.00
Received By jjohnsto Date 2007-10-16 Time 13:28 Sent To  
Notes
2007-10-16 13:30:07CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713FAX:
 561-805-6731
  
 JAMES JOHNSTON, PERMIT NO 05091687
 BUILDING PLAN EXAMINERII PROJECT
 NAME COURTNEY LAKES, BLDG. 3
 E-MAIL:JJOHNSTON @WPB.ORG ADDRESS
 331 COURTNEY LAKES CIRCLE
  DATE OCTOBER 15, 2007
  
 BUILDINGPLANREVIEW
 FLORIDA BUILDING CODE 2001
  
  
 FOR YOUR INFORMATION?.
 THE PLANS SUBMITTED ARE DRAWN FOR THIS PROJECT?S
 BUILDINGS TO BE CONSTRUCTED IN PHASES.PLEASE SEE THE
 2001 CODE RELATED SECTION 104.5.1.104.5.1.1,
 104.5.1.2 -NOTED HEREIN -REFERCENING,?WORK NOT
 COMMENCED WITHIN 6 MONTHS AFTER DATE OF PERMIT ISSUANCE
 THE PERMIT SHALL BE REVOKED AND A NEW PERMIT SHALL BE
 ISSUED.? THE NEW PERMIT SHALL BE ISSUED UNDER THE2004
 BUIDING CODENOT THE 2001, REQUIRING EXISTING PLANS TO
 BE REDRAWN IN COMPLIANCE WITH THIS CODE.
  
  
 104.5 CONDITIONS OF THE PERMIT
 104.5.1 PERMIT INTENT. A PERMIT ISSUED SHALL BE
 CONSTRUED TO BE A LICENSE TO PROCEED WITH THE WORK AND
 NOT AS AUTHORITY TO VIOLATE, CANCEL, ALTER, OR SET
 ASIDE ANY OF THE PROVISIONS OF THE TECHNICAL CODES, NOR
 SHALL ISSUANCE OF A PERMIT PREVENT THE BUILDING
 OFFICIAL FROM THEREAFTER REQUIRING A CORRECTION OF
 ERRORS IN PLANS, CONSTRUCTION, OR VIOLATIONS OF THIS
 CODE. EVERY PERMIT ISSUED SHALL BECOME INVALID UNLESS
 THE WORK AUTHORIZED BY SUCH PERMIT IS COMMENCED WITHIN
 6 MONTHS AFTER ITS ISSUANCE, OR IF THE WORK AUTHORIZED
 BY SUCH PERMIT IS SUSPENDED OR ABANDONED FOR A PERIOD
 OF 6 MONTHS AFTER THE TIME THE WORK IS COMMENCED.
  
  
 104.5.1.1 IF WORK HAS COMMENCED AND THE PERMIT IS
 REVOKED, BECOMES NULL AND VOID, OR EXPIRES BECAUSE OF
 LACK OF PROGRESS OR ABANDONMENT, A NEW PERMIT COVERING
 THE PROPOSED CONSTRUCTION SHALL BE OBTAINED BEFORE
 PROCEEDING WITH THE WORK.
  
  
  
 104.5.1.2 IF A NEW PERMIT IS NOT OBTAINED WITHIN 180
 DAYS FROM THE DATE THE INITIAL PERMIT BECAME NULL AND
 VOID, THE BUILDING OFFICIAL IS AUTHORIZED TO REQUIRE
 THAT ANY WORK WHICH HAS BEEN COMMENCED OR COMPLETED BE
 REMOVED FROM THE BUILDING SITE. ALTERNATELY, A NEW
 PERMIT MAY BE ISSUED ON APPLICATION, PROVIDING THE WORK
 IN PLACE AND REQUIRED TO COMPLETE THE STRUCTURE MEETS
 ALL APPLICABLE REGULATIONS IN EFFECT AT THE TIME THE
 INITIAL PERMIT BECAME NULL AND VOID AND ANY REGULATIONS
 WHICH MAY HAVE BECOME EFFECTIVE BETWEEN THE DATE OF
 EXPIRATION AND THE DATE OF ISSUANCE OF THE NEW PERMIT.
  
  
  
  
  
  
  
  
 A 1804.2.2SOIL TEST REPORT
 THE REPORT SUBMITTED IN 2003 REFERENCES A CONCLUSION OF
 BEARING CAPACITY
 FOR A SINGLE STORY STRUCTURE. WHERE THE BEARING
 CAPACITY OF THE SOIL IS
 NOT DEFINITELY KNOWN OR IS IN QUESTION, THE BUILDING
 OFFICIAL MAY REQUIRE
 LOAD TESTS OR OTHER ADEQUATE PROOF AS TO THE
 PERMISSIBLE SAFE BEARING
 CAPACITY AT THAT PARTICULAR LOCATION.TO DETERMINE THE
 SAFE BEARING
 CAPACITY OF SOIL, IT SHALL BE TESTED AT SUCH LOCATIONS
 AND LEVELS AS
 CONDITIONS WARRANT, BY LOADING AN AREA NOT LESS THAN 4
 SQ FT (0.37 M{2})
 TO NOT LESS THAN TWICE THE MAXIMUM BEARING CAPACITY
 DESIRED FOR USE.SUCH
 DOUBLE LOAD SHALL BE SUSTAINED BY THE SOIL FOR A PERIOD
 OF NOT LESS THAN
 48 HOURS WITH NO ADDITIONAL SETTLEMENT TAKING PLACE, IN
 ORDER THAT SUCH
 DESIRED BEARING CAPACITY MAY BE USED.SUBSOIL
 CONDITIONS SHALL BE
 EXAMINED AT THE EXPENSE OF THE OWNER, WHEN DEEMED
 NECESSARY BY THE
 BUILDING OFFICIAL.
 COMMENTPLEASE FURNISH A SOIL TEST REPORT APPLICABLE
 FOR THE THREE BUILDINGS ?FIVE STORIES EACH TO BE
 CONSTRUCTED WITH THE RECOMMENDATIONS FOR PROPER GROUND
 PREPARATION TO ACHIEVE THE DESIRED BEARING CAPACITY
 FOR EACH BUILDING.
 TWO COPIES OF THIS REPORT SHALL BE INCLUDED FOR EACH
 SEPARATE BUILDING PROJECT.THE REPORT IS TO ENCOMPASS
 THE THREE BUILDINGS, TWO COPIES FOR EACH BUILDING
  
 A-1 FBC105.11SOIL TREATMENT
 COMMENTIDENTIFY THE CHEMICAL SOIL TREATMENT TO BE
 USED IN THE SLAB NOTES SHEET APS3.21
  
  
  
 B PRODUCT APPROVALS
 COMMENTTHE FLORIDA PRODUCT APPROVAL COVER SHEET
 SHALL INCLUDE THE APPROVAL INFORMATION FOR THE PRODUCT
 SELECTED.SEE ATTACHED SAMPLE INCLUDED.
 THE DESIGNER OF RECORD SHALL REVIEW EACH APPROVAL?S
 SPECIFICATION PACKETAND ACKNOWLEDGE SAME ON THE
 APPROVAL COVER SHEETBY NAME DATE AND STATEMENT OF
 ACCEPTANCE
  
  
 B-1 WINDOWS / DOORS PRODUCT APPROVALS
 WPB ADMINISTRATIVE CODE 106.3 REGULATED BY DCA RULE
 9B-72FLORIDA PRODUCT APPROVAL
 SUBMIT TWO COPIES OF EACH APPROVAL WITH FLORIDA PRODUCT
 APPROVAL COVER SHEET THE ARCHITECT?S / ENGINEER?S
 SIGNATURE AS APPLICABLE, STATING ?TO THE BEST OF THEIR
 KNOWLEDGE THE PRODUCT APPROVAL COMPLIES WITH THE PLANS
 AND SPECIFICATIONS.SEE:WEB SITE
 WWW.FLORIDABUILDING.COM
 NOTE: SEE DIVISION FACTOR TO BE USED IN DESIGN PRESSURE
 BY LEGACYFPA
 COMMENT-FOR YOUR INFORMATION
  
  
 B-2 SUBMIT PRODUCT APPROVALS WITH FLORIDA PRODUCT
 APPROVAL COVER
 PAGE FOR THE FOLLOWING
 OPERABLE WINDOWS
 FIXED GLASS
 MULLION TUBES
 PANEL WALLS
 STORE FRONT GLAZING SYSTEM
 ALUMINUM OUT -SWING DOORS
 HOLLOW METAL DOORS
 TRUSS ANCHORS
 ROOFINGCOMPONENTS
 SHUTTERS
 SKYLIGHTS
 OVERHEAD GARAGE DOOR
 COMMENT-PLEASE COMPLY
  
 B-3 3RD REQUEST ?
 COMMENT-FURNISH THE FOLLOWING PRODUCT REPORTS
 TRACO OPERABLE WINDOWSNON IMPACT 0? TO 30?,LARGE
 MISSLE 30? TO 60?
 TRACO FIXED WINDOWS
 MULLIONS
 EXTERIOR HOLLOW METAL DOORS
 EXTERIOR GLAZED DOORS
 EXTERIOR LOUVER DOORS
 EXTERIOR RAILINGS, ENGINEERING REQUIRED
 LOUVERS,NO REPORT SUBMITTED
 ROOF ASSEMBLIES, DENSE DECK, ATTACHMENTS, INSULATION,
 UNDERLAYMENT,ROOF TILE,ROOF SYSTEM
 IDENTIFY EACH COMPONENT TO BE USED
 RATIONAL ANALYSIS FOR ZONE 2 AND THREE
 EFIS WALL SYSTEM (IF USED)
 5/8? AQUA ROCK SHEATHING
 ROLL UP DOOR
 WOOD BASE STRUCTURAL PANELSFBC 2315.1.11
  
  
 B-4 PROVIDE DESIGN LOADS ON ALL WINDOW , DOOR,
 COMPONENTS ON SCHEDULE
 2405.3.2.1 THE DESIGN LOADS SHALL BE COMBINED
 AS FOLLOWS:
  
 1. NEGATIVE WIND LOAD - DEAD LOAD
 2. POSITIVE WIND LOAD + DEAD LOAD
 3. DEAD LOAD + 1/2 POSITIVE WIND LOAD
 WIND LOADS SHALL BE DETERMINED FROM 1606. THE DEAD LOAD
 FOR THE GLASS IN LB/SQ FT SHALL BE TAKEN AS THE TOTAL
 THICKNESS OF THE GLASS PANES AND PLIES IN INCHES X 13.
 THIS APPLIES FOR GLASS 30 DEGREES OR LESS FROM
 HORIZONTAL. FOR OTHER SLOPES THE GLASS DEAD LOAD IS
 EQUAL TO THIS VALUE TIMES THE COSINE OF ITS SLOPE FROM
 HORIZONTAL.
  
  
 B-5 FBC2411.3.1.4 THE ARCHITECT OR PROFESSIONAL
 ENGINEER OF RECORD SHALL BE
  REQUIRED TO SPECIFY THE DESIGN WIND PRESSURE,
 DETERMINED IN ACCORDANCE
  WITH CHAPTER 16 (HIGH VELOCITY HURRICANE ZONES),
 FOR ALL GARAGE DOORS,
  SKYLIGHTS OPERATIVE WINDOWS AND FIXED GLAZING.
 THE DESIGN WIND PRESSURE
  FOR EACH COMPONENT OF THE EXTERIOR BUILDING
 SURFACE, SHALL BE
  INCORPORATED INTO THE BUILDING DESIGN DRAWING SO
 AS TO ALLOW THE
  RESPECTIVE MANUFACTURER TO SIZE THE PREFABRICATED
 ASSEMBLY FOR THE
  PROPER WIND PRESSURES.
  COMMENTPLEASE PROVIDE THIS INFORMATION ON THE
 ELEVATIONS
  
  
 C 105.13 THRESHOLD BUILDING
  105.13.2 THE SPECIAL INSPECTOR SHALL INSPECT THE
 SHORING AND RE-SHORING
  FOR CONFORMANCE TO THE SHORING AND RE-SHORING PLANS
 SUBMITTED TO THE
  ENFORCING AGENCY.A FEE SIMPLE TITLE OWNER OF A
 BUILDING WHICH DOES NOT
  MEET THE MINIMUM SIZE, HEIGHT, OCCUPANCY, OCCUPANCY
 CLASSIFICATION OR
  NUMBER-OF-STORIES CRITERIA WHICH WOULD RESULT IN
 CLASSIFICATION AS A
  THRESHOLD BUILDING UNDER ?553.71(7) FLORIDA
 STATUTES, MAY DESIGNATE
  SUCH BUILDING AS A THRESHOLD BUILDING, SUBJECT TO
 MORE THAN THE MINIMUM
  NUMBER OF INSPECTIONS REQUIRED BY THE FLORIDA
 BUILDING CODE, BUILDING.
  COMMENTPLEASE FURNISH A SHORING AND RE-SHORING PLAN
  
  
  
 D SITE PLAN AND ASSOCIATED COMPONENTS REQUIRED3RD
 REQUEST(NOT INCLUDED)
  
  COMMENTPLEASE FURNISH A SEPARATE SITE PLAN FOR
 BUILDING NO III. INCLUDE THIS SITE PLANWITHTHE
  ARCHITECTURAL DRAWINGS FOR THE FOLLOWING
  (A) PARKING SPACES LOCATED OUTSIDE AND UNDERNEATH THE
 BUILDING. CURBING, RAMPS, ACCESSIBLE ISLES FOR THE
 HANDICAP, SIGNAGE, SIDEWALKS, CURB CUTS, PEDESTRIAN
 CROSS WALKS (B) HANDICAP SPACES LOCATED OUTSIDE AND
 UNDERNEATH THE BUILDING PERIMETER. IDENTIFY ALL
  HANDICAP PARKING SPACES AS DEFINED BY THEAMERICANS
 WITH DISABILITIES FLORIDA BUILDING CODE CHAPTER 11
 PART BANSIA117-1 ANDFAIR HOUSING ACT GUIDELINES
  (C) IDENTIFY THE ACCESSIBLE ROUTE AS DEFINED BY
 THE AMERICANS WITH DISABILITIES- FLORIDA BUILDING
  CODE CHAPTER 11 AND FAIR HOUSING ACT GUIDELINES
  (D) IDENTIFY VAN ACCESSIBLE PARKING SPACES UNDER
 BUILDING AND EXTERIOR IN COMPLIANCE WITH
  THE AMERICANS WITH DISABILITIES FLORIDA BUILDING CODE
 CHAPTER 11ANDFAIR HOUSING ACT
  GUIDELINES, NOTE PARKING SPACES FOR VANS SHALL HAVE
 VERTICAL CLEARANCE OF 98?
  (E) ONE ACCESSIBLE ROUTE FAIR HOUSING, FROM THE
 BOUNDARY SITES PUBLIC TRANSPORTATION STOP TO AN
  ACCESSIBLE BUILDING ENTRANCE. CHAPTER 11, PART B ?
 ANSI A117.1,502.6
  
 E FBC411.2 AUTOMOBILE PARKING ARAGES
  COMMENTPLEASE VERIFY OPEN OR ENCLOSED WITH THE CODE
 SECTIONS PROVIDED HEREIN
  
  411.2.1 AUTOMOBILE PARKING GARAGES SHALL BE CLASSIFIED
 AS EITHER OPEN, AS DEFINED IN 411.3, OR ENCLOSED AND
 SHALL MEET THE APPROPRIATE CRITERIA OF 411.3 OR 411.4.
  
  FBC411.3ENCLOSED PARKING GARAGES
  
  FBC 411.4.1 ENCLOSED AUTOMOBILE PARKING GARAGES AND
 PORTIONS THEREOF WHICH DO NOT MEET THE DEFINITION OF
 OPEN PARKING GARAGES SHALL BE LIMITED TO THE ALLOWABLE
 HEIGHTS AND AREAS SPECIFIED IN TABLE 500 FOR GROUP S
 BUILDINGS.
  
  411.4.2 A MECHANICAL VENTILATION SYSTEM FOR THE
 REMOVAL OF THE PRODUCTS OF COMBUSTION SHALL BE
  PROVIDED IN ENCLOSED AUTOMOBILE PARKING GARAGES. THE
 MECHANICAL SYSTEM SHALL BE CAPABLE OF PROVIDING AT
 LEAST 6 AIR CHANGES PER HOUR FOR EACH LEVEL. UNDER
 NORMAL USE THE VENTILATION OF THE
  ENCLOSED AUTOMOBILE PARKING GARAGE SHALL COMPLY WITH
 THE VENTILATION REQUIREMENTS OF 411.5.
  411.2.2 THE CLEAR HEIGHT OF EACH FLOOR LEVEL IN
 VEHICLE AND PEDESTRIAN TRAFFIC AREAS SHALL NOT BE LESS
  THAN 7?
  
 FBC 411.3 OPEN PARKING GARAGES411.3.1
 OPEN AUTOMOBILE PARKING GARAGES WITH ROOF PARKING MAY
 BE CONSTRUCTED TO THE ALLOWABLE HEIGHTS AND AREAS
 SPECIFIED IN TABLE 411.3.1. TO BE CONSIDERED OPEN, THE
 GARAGE SHALL MEET THE REQUIREMENTS OF411.3.2,
 411.3.3 AND411.3.4.
  
 411.3.2 THE EXTERIOR AND INTERIOR WALLS OF THE GARAGE
 SHALL BE DESIGNED IN ACCORDANCE WITH ONE OF THE
 FOLLOWING:
  
  1. AT LEAST 50 PERCENT OF THE CLEAR HEIGHT BETWEEN
 FLOORS SHALL BE OPEN TO THE ATMOSPHERE FOR THE FULL
  LENGTH OF AT LEAST TWO EXTERIOR WALLS, EXCLUDING
 REQUIRED STAIR AND ELEVATOR WALLS AND STRUCTURAL
  COLUMNS. INTERIOR WALL LINES AND COLUMN LINES SHALL BE
 AT LEAST 20 PERCENT OPEN AND UNIFORMLY DISTRIBUTED,
 OR
  
  2. THE EXTERIOR WALLS OF THE STRUCTURE SHALL HAVE
 UNIFORMLY DISTRIBUTED OPENINGS ON TWO OR MORE SIDES
  TOTALING NO LESS THAN 40 PERCENT OF THE BUILDING
 PERIMETER. THE AREA OF SUCH OPENINGS IN THE EXTERIOR
  WALLS ON EACH LEVEL SHALL BE AT LEAST 20 PERCENT OF
 THE TOTAL PERIMETER WALL AREA OF EACH LEVEL. INTERIOR
 WALL LINES AND COLUMN LINES SHALL BE AT LEAST 20
 PERCENT OPEN AND UNIFORMLY DISTRIBUTED.
  
  411.3.3 THE DISTANCE FROM ANY POINT ON ANY FLOOR LEVEL
 TO AN OPEN EXTERIOR WALL FACING ON A STREET, OR TO
 OTHER PERMANENTLY MAINTAINED OPEN SPACE AT LEAST 20
 FT (6096 MM) WIDE EXTENDING FULL WIDTH TO A STREET,
 SHALL NOT EXCEED 200 FT (61 M).
  
  411.3.4 GARAGES WITHIN 10 FT (3048 MM) OF A COMMON
 PROPERTY OR BUILDING LINE SHALL BE PROVIDED WITH AN
 ENCLOSURE WALL ALONG THE LINE OF NOT LESS THAN 1-HOUR
 FIRE RESISTANCE WITHOUT OPENINGS THEREIN, EXCEPT DOOR
 OPENINGS MEETING THE REQUIREMENTS OF705.1.3 SHALL BE
 PERMITTED.
  
 F APA6.40, A6.41,A6.45
  COMMENTPLEASE IDENTIFY WINDOWS, DOORS, OVERHEAD
 DOORS ON THE BUILDING ELEVATIONS TO CORRESPOND WITH
 THE INFORMATION PROVIDED ONA9.03
  
 G TRASH CHUTE ACCESS DOORS
  COMMENT PLEASE IDENTIFY THE ACCESS CHUTE DOOR ON THE
 DOOR SCHEDULE WITH NOTE E SHEET A8.20
  
 H ARCHITECTURAL TRIM1404.1.1ABOVE 3 STORIES OR 40
 FT
  COMMENT-A7.02IDENTIFY THE FASTENING HARDWARE TO
 BE USED IN SECURING THE FOAM TRIM TO THE BUILDING
 EXTERIOR SURFACE
  
 I SHEET GN-A1.05,GN-A1.06
  COMMENTPLEASE PROVIDE LEGIBLE INFORMATION ON
 THESE SHEETS
  
 J 11-4.10 ELEVATORS
  11-4.10.9 FLOOR PLAN OF ELEVATOR CARS. THE FLOOR AREA
 OF ELEVATOR CARS SHALL PROVIDE SPACE FOR WHEELCHAIR
 USERS TO ENTER THE CAR, MANEUVER WITHIN REACH OF
 CONTROLS, AND EXIT FROM THE CAR. ACCEPTABLE DOOR
 OPENING AND INSIDE DIMENSIONS SHALL BE AS SHOWN IN
 FIGURE 11-22. THE CLEARANCE BETWEEN THE CAR PLATFORM
 SILL AND THE EDGE OF ANY HOIST WAY LANDING SHALL BE NO
 GREATER THAN 1-1/4 INCHES (32 MM).
  COMMENTPROVIDE A FLOOR PLAN OF THE ELEVATOR CAB
 UTILIZING THIS SECTION OF THE ADACHAPTER 11
  
 K THERE IS A DISCREPANCY IN BETWEEN THE STRUCTURAL AND
 ARCHITECTURAL DRAWINGS
  SHEETAP-S3.31ATHIS SHEET DETAILS THE ELEVATOR
 SHAFT WITH A TRASH CHUTE. THE ELEVATOR LANDINGIS
  RAISED 3?-6? OFF THE FINISHED FLOOR. THE ACCESSIBILITY
 PATH FROM THE ELEVATOR TO THE EXTERIOR IS BLOCKED
  BY A WALL. THERE IS AN ADDITIONAL WALL BLOCKING THE
 STAIR DRAWN ON THE PLAN. THE SPACE CONTAINING THE
  DUMPSTER HAS A FLOOR ELEVATION OF 3?6? LEADING TO THE
 EXTERIOR. THE REQUIRED DIMENSIONS FOR CONSTRUCTION ARE
 MISSING IN MANY AREAS.
  
  SHEET AP-A5.40THIS SHEET DETAILS THE ELEVATOR
 LANDING AT THE ELEVATION OFTHE FINISHED FLOOR BUT,
  HAS STAIRS DRAWN. THE MATCH LINE DOES NOT MATCH THE
 LOCATION DRAWN ON SHEETS3.31A
  COMMENTIF THISBUILDING IS BEING SUBMITTED FOR
 PERMITTING IN TWO PHASES, ALL INFORMATION MUST BE
  INCLUDED WITH A DESCRIPTION OF EACH PHASE. ALL EXIT
 ACCESS MUST BE CONSIDERED CHAPTER 11, ADA FAIR HOUSING
 ACT.LIFE SAFETY ISSUES MUST BE ADDRESSED.
  THIS PLAN SHOULDBE DRAWN BY THE ARCHITECT AND
 ENGINEER TO ADDRESS THE PROJECT BEING CONSTRUCTED IN
 TWO PHASES WITH ADEQUATE COMMUNICATION REFERENCING
 COMPLIANCE OF ALL APPLICABLE CODES
  
 L WHAT IS THE PURPOSE OF THE HATCHED AREA ON THE ?B?
 SECTION FLOOR PLANS BEGINNING WITH SHEET APS3.32A
 ????
  
 M A SECTION THRU THE BUILDING REFERENCING THE
 FOUNDATION, WALLS, BALCONIES, BEAMS, ROOF, PARAPET HAVE
 NOT BEEN INCLUDED.SEE SHEET AP.701 BLDG. 2 FOR
 INFORMATION REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-02-09 Cont ID  
Sent By jwitmer Date 2007-02-09 Time 15:05 Rev Time 9.99
Received By jwitmer Date 2007-02-09 Time 15:05 Sent To  
Notes
2007-02-09 15:10:07 
  
  
 PERMIT: 05091687 BLDG# 3
 ADD:XXX N CONGRESS
 74-43-43-20-00-000-3010
 CONT: E. A. LANDERS
 TEL: (305)823-3938
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 COURTNEY LAKES APARTMENTS, LLC
  
 ARCH: FORUM ARCHITECTURE & INTERIOR DESIGN
 (407)830-1400
 STRUC: ROBERT PLOWFIELD & ASSOC
 (407)657-6657
 2ND REVIEW
 ACTION: DENIED
  
 ***IMPORTANT***
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 NOTE NOC WILL BE NULL & VOID 90 DAYS
 AFTER RECORDING AT THE CLERK OF THE
 COURTS OFFICE IF WORK HAS NOT STARTED.
 FL S S 713.13(2).
  
 2) THIS COMMENT WAS PARTIALLY SATISFIED, FOR THE WHOLE
 OF THE PROJECT (3 BUILDINGS)
 THREE SIGNED & SEALED REPORTS WERE SUBMITTED TO THE
 CITY. THIS WILL SATISFY THE REQUIREMENT
 TO HAVE (1 ) REPORT WITH EACH PERMIT OR BUILDING. THE
 NEED STILL ARISES TO HAVE AT LEAST ONE SIGNED/ SEALED
 ORIGINAL FOR THE CONTRACTOR AS WELL AS THE THRESHOLD
 INSPECTOR.
 AN ADDITIONAL 2 ORIGINAL SOILS REPORTS SIGNED & SEALED
 SHALL BE REQUIRED.
 FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3-4) COMPLIED.
  
 5)BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPECTION PLAN
 PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE STRUCTURAL INSPECTION
 PLAN IS TO PROVIDE SPECIFIC INSPECTION PROCEDURES AND
 SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 7) WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 8) COMPLIED.
  
 9A) 2ND REQUEST, CONTACT LILI URSA FOR ADDRESSING
 REQUIREMENTS @ (561)822-1239
  
 9B) 2ND REQUEST, PLEASE PROVIDE A COPY OF THE NEW PLAT,
 LOT
 HAS BEEN SUBDIVIDED.
  
 9C) 2ND REQUEST, ON ALL (3) PERMIT APPLICATIONS CORRECT
 THE PROPERTY CONTROL NUMBER TO
 THE NEW LOT.
  
 9D) PROVIDE A SITE PLAN WITH LOCATION OF THE PROPOSED
 STRUCTURES WITH DIMENSIONS
 FOR TABLE 600 ISSUES.A2.01 HAS NO DIMENSIONS! RESPONSE
 COMMENTS ARETO SEE CIVIL PLANS ,NO CIVIL PLANS PROVIDED
 IN THIS SET OF PLANS.
  
 10A-K) COMPLIED.
  
 11) SHEET A1.05
  
 11A & B) COMPLIED.
  
 12)SITE PLAN A2.01
 NEW COMMENT THAT DEALS WITH THE OVER ALL PARKING SPACES
 AND THE REQUIRED NUMBER OF ACCESSIBLE SPACES. THE PLANS
 INDICATE A TOTAL OF 912 SPACES WHERE AS IT APPEARS TO
 BE 1008 PARKING SPACES IF THIS IS TRUE THE REQUIRED
 NUMBER OF ACCESSIBLE SPACES WOULD BE 21.
 CHAPTER 11 PART B- 4PARKING AND PASSENGER LOADING:
 ACCESSIBLE PARKING ON A ROUTE ACCESSIBLE TO WHEELCHAIRS
 FOR AT LEAST 2% OF THE COVERED DWELLING UNITS:
 ACCESSIBLE VISITOR PARKING SUFFICIENT TO PROVIDE ACCESS
 TO GRADE LEVEL ENTRANCES OF COVERED MULTIFAMILY
 DWELLINGS; AND ACCESSIBLE PARKING AT FACILITIES (E.G.,
 SWIMMING POOLS) THAT SERVE ACCESSIBLE BUILDINGS.
  
 12A) 2ND REQUEST, THERE ARE NO CIVIL PLANS INCORPORATED
 INTO THIS SET OF PLANS TO REVIEW FOR ACCESSIBILITY.
 ACCESSIBLE ROUTE: FAIR HOUSING AT LEAST ONE ACCESSIBLE
 ROUTE SHALL BE
 PROVIDED WITHIN THE BOUNDARY OF THE SITE FROM PUBLIC
 TRANSPORTATION STOPS,
 ACCESSIBLE PARKING SPACES, PASSENGER LOADING ZONES IF
 PROVIDED, AND PUBLIC
 STREETS OR SIDEWALKS, TO AN ACCESSIBLE BUILDING
 ENTRANCE.
  
 12B)2ND REQUEST, THERE ARE NO CIVIL PLANS INCORPORATED
 INTO THIS SET OF PLANS TO REVIEW FOR ACCESSIBILITY.
 THE SITE PLAN DOES NOT PROVIDE ANY INFORMATION AS TO
 CURB CUTS, PEDESTRIAN
 CROSS WALKS, ETC. RESPONSE IS THE CIVIL ENGINEER IS TO
 RESPOND? WHERE?
  
 12B)(1) PLEASE PROVIDE INFORMATION WHICH ACCESSIBLE
 PARKING SPACES WILL BE THE VAN ACCESSIBLE SPACES?
 CHAPTER 11 PART B ANSI A117-1 502.5 PARKING SPACESFOR
 VANS SHALL HAVE A VERTICAL CLEARANCE OF 98" MINIMUM AT
 THE SPACE AND ALONG THE VEHICULAR ROUTE THERETO.
  
 12B)(2) PLEASE PROVIDE SIGNAGE FOR ALL ACCESSIBLE
 PARKING SPACES . CHAPTER 11 PART B ANSI A117.1502.6.
  
 13) SHEET A5.40:
  
 13A-C) COMPLIED.
  
 13D) TRASH TERMINATION ROOM NO RATING, THE IS NO WALL
 TAG IDENTIFYING THE HOURLY WALL RATING OF THE WALL?
 TABLE 705.1.2.
  
 13E) FIRE PUMP ROOM NO RATING OF WALL, NFPA
 20:5.1.12.1.1REQUIRES A 2 HR WALL RATING, DOOR
 PROTECTIVE OF1 ? HR.
  
 13F-I) COMPLIED.
  
 14) COMPLIED.
  
 15) SHEET A5.41:
  
 15A) 2ND REQUEST, TRASH ROOM DETAIL 1& 2 OF A8.20 THE
 DETAIL IS MISSING THE ENCLOSURE TO THE BOTTOM OF THE
 CHUTE ENCLOSURE .705.2.4.2ALL OPENINGS INTO THE SHAFT
 ENCLOSURE,
 INCLUDING THOSE FROM ACCESS ROOMS AND TERMINATION
 ROOMS, SHALL BE PROTECTED IN ACCORDANCE WITH TABLE
 705.1.2.SUCH OPENING PROTECTIVE SHALL BE SELF-CLOSING
 OR AUTOMATIC-CLOSING UPON DETECTION OF SMOKE, EXCEPT
 THAT THE OPENING PROTECTIVE BETWEEN THE SHAFT AND THE
 TERMINATION ROOM MAY BE CLOSED BY A HEAT-ACTIVATED
 DEVICE.
 PLEASE PROVIDE INFORMATION ON THE TRASH CHUTE SHOP
 DRAWINGS, WALL THICKNESS OF CHUTE, THE
 SELF CLOSING DEVICES, LOCATION OF SPRINKLER HEADS IN
 THE CHUTE.
  
 15B) THE TRASH REFUSE ROOM DETAIL 4 / A8.20 INDICATES
 THE 2 HR RATING ON THE FRONT & BACK WALL NOT THE SIDE
 WALLS? NOR RATING OF THE ACCESS ROOM WALLS? TABLE
 705.1.2 & 705.2.4.3.
  
 15C) NEW COMMENT:SHEET A5.43 INDICATES AN ELEVATOR
 DETAIL 2 /A8.10 , THIS ELEVATOR MACHINE ROOM DOES NOT
 INDICATE WALL OR DOOR RATINGS?
  
 15D) NEW COMMENT: SHEET A5.44 ROOF ACCESS FROM
 STAIRWELL# 2 PLANS DO NOT IDENTIFY THIS DOORWAY NOR
 RATING.
  
 15E) NEW COMMENT: SHEET A5.44 STAIRWELL ACCESS TO ROOF.
 SEE 1008 SUCH STAIRWAY SHALL BE MARKED AT STREET AND
 FLOOR LEVELS WITH A SIGN INDICATING THAT IT CONTINUES
 TO THE ROOF.
  
 15F) NEW COMMENT: SHEET A7.01WALL SECTION# 2& A7.02
 WALL SECTION# 3, DETAIL# 12/ A7.10 INDICATES THE USE OF
 WHAT APPEARS TO BE EFIS WALL SYSTEMS, THERE IS A WALL
 IDENTITY TAG W1-14 , NO SUCH TAG ON SHEET A1.04?
  
 15G) NEW COMMENT: SHEET A7.02 KEY NOTE # 10 NOTES SEE
 STRUCTURAL DRAWINGS FOR ROOF TRUSS ANCHORAGE, NO
 TRUSSES NEAR THE NOTE, WHY IS THE BATT INSULATION ON
 THE FLOOR?
  
 15H) NEW COMMENT SHEET A7.02NOTE # 29 INDICATES THE USE
 OF FOAM BAND TRIM ON THE EXTERIOR OF THE BUILDING. SEE
 1404.1.1.ARCHITECTURAL TRIM ON BUILDINGS OF TYPE I,
 II AND IV
 CONSTRUCTION NOT MORE THAN THREE STORIES OR 40 FT
 (12.2 M) HIGH MAY BE OF
 TYPE VI CONSTRUCTION, AND MAY BE OF TYPE VI
 CONSTRUCTION ON ALL BUILDINGS
 OF TYPE III, V AND VI CONSTRUCTION.TRIM SHALL BE
 SECURED TO THE WALL
 WITH METAL OR OTHER APPROVED BRACKETS OR FASTENERS.
 WHEN ARCHITECTURAL
 TRIM IS LOCATED ALONG THE TOP OF EXTERIOR WALLS, IT
 SHALL BE COMPLETELY
 BACKED BY THE EXTERIOR WALL AND SHALL NOT EXTEND OVER
 THE TOP OF EXTERIOR
 WALLS.
  
 15I) NOTE# 39 DEALS WITH ROOF TILE RIDGE AND EDGE CAPS,
 IT APPEARS TO BE MISPLACED. PLEASE PROVIDE RIDGE AND
 HIP ATTACHMENT METHODS, IF NOT COVERED UNDER THE
 PRODUCT APPROVALS SEE ROOFING STANDARD FRSA/RTI
 07320..
  
  
 16) SHEET A7.10.
  
 16A) COMPLIED.
  
 16B) SEE 15E & 15F.
  
 16C) COMMENT# 15H . 2ND REQUEST,
 THIS SAME SECTION INDICATES USE OF
 FOAM TRIM ON THE EXTERIOR OF THE
 BUILDING ABOVE 40'.1404.1.1
 ARCHITECTURAL TRIM ON BUILDINGS OF TYPE
 I, II AND IV CONSTRUCTION NOT MORE THAN
 THREE STORIES OR 40 FT (12.2 M) HIGH MAY
 BE OFTYPE VI CONSTRUCTION, AND MAY BE
 OF TYPE VI CONSTRUCTION ON ALL BUILDINGS
 OF TYPE III, V AND VI CONSTRUCTION.
 TRIM SHALL BE SECURED TO THE WALL WITH
 METAL OR OTHER APPROVED BRACKETS OR
 FASTENERS.WHEN ARCHITECTURAL TRIM IS
 LOCATED ALONG THE TOP OF EXTERIOR WALLS,
 IT SHALL BE COMPLETELY BACKED BY THE
 EXTERIOR WALL AND SHALL NOT EXTEND OVER
 THE TOP OF EXTERIOR WALLS.
  
  
 17) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 18) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) OPERABLE WINDOWS
 FL 3485TRACO TR-6800 -OK
 FL 3044.3TRACO HS-HC 65 NON-IMPACT WINDOW
 REQUIRED 0-30'LARGE MISSILE, 30'-60'SMALL MISSILE -
 DENIED
 FL 3044.4TRACO HS-AW 55NON-IMPACT WINDOW
 REQUIRED 0-30'LARGE MISSILE, 30'-60'SMALL MISSILE -
 DENIED
 FL 3044.5TRACO HS-AW55 NON-IMPACT WINDOW
 REQUIRED 0-30'LARGE MISSILE, 30'-60'SMALL MISSILE -
 DENIED
  
 B) FIXED WINDOWS
 FL 3487TRACOTR-3800 - OK
 FL 632KAWNEER EXPIRED NOA NON-IMPACT
 REQUIRED 0-30'LARGE MISSILE, 30'-60'SMALL MISSILE -
 DENIED
  
 C) MULLIONS MAY OR MAY NOT BE INCLUDED IN THE PRODUCT
 APPROVALS
  
 D) EXTERIOR HOLLOW METAL DOORS
 FL3078 AMWELD DENIED LOW PRESSURES SINGLE &
 PAIRS
  
 E) EXTERIOR GLAZED DOORS
 FL 3038TRACO 03-0829.06 SMALL MISSILE ONLY, NO
 PRESSURE TEST - DENIED
 FL 3038.3TRACO 03-0422.04 TR-8910 SMALL
 MISSILE TEST NO PRESSURE TEST - DENIED
 FL 3038.4TRACO 03-0422.04 TR-8910 LARGE
 MISSILE HIGHLIGHT ANCHOR FASTENING SCHEDULE MAY COMPLY
 FL3477TRACO TR-8300SLIDING GLASS DOOR
 NON-IMPACTREQUIRES 0-30' LARGE MISSILE, 30'-60' SMALL
 MISSILE - DENIED
  
 F) EXTERIOR LOUVERED DOORS NO REPORT SUBMITTED
  
 G) EXTERIOR RAILINGS- WILL ONLY NEED ENGINEERING NOT A
 PRODUCT APPROVAL
  
 H) LOUVERS NO REPORT SUBMITTED.
  
 I) TRUSS ANCHORS NO REPORT SUBMITTED.
  
 J) ROOF ASSEMBLIES INCLUDING DENSE DECK, INSULATION,
 UNDERLAYMENT, ROOF TILE AND ATTACHMENT METHODS. FL 1559
 SINGLE PLY ROOF SYSTEMS- HIGHLIGHT WHICH SUB-SYSTEM TO
 BE USED.
 NOTE ZONES 2 & 3 MAY REQUIRE ENHANCED FASTENING
 PROVIDE RATIONAL ANALYSIS BY QUALIFIED PROFESSIONAL
  
 K) EFIS WALL SYSTEMS IF USED
  
 L)5/8" FIBER TOUGH AQUA ROCK SHEATHING
  
 M ) PRE-MANUFACTURED ROOF A/C STANDS- OK
  
 N) ROLL UP DOOR - NO REPORT SUBMITTED
  
 O) DENSE DECK- MAY BE INCORPORATED IN A PRODUCT
 APPROVAL
  
 P) ROOF TILE - NO REPORT SUBMITTED- CIRCLE OR HIGHLIGHT
 WHAT ANCHOR METHOD TO INSTALLROOF TILE
  
 19) IMPACT GLASS IS SPECIFIED, COMPLIED.
  
 20)IMPACT GLASS IS SPECIFIED, COMPLIED.
  
  
 21)IMPACT GLASS IS SPECIFIED, COMPLIED.
  
  
 22- 29) COMPLIED
  
 NOTE: CALCULATED VALUE: $ 10,848,462.00/144,666 SQ
 FT
  
 ADDITIONAL COMMENTS MAY APPEAR ON THE
 NEXT REVIEW NOT COVERED FROM THE FIRST
 REVIEW DUE TO THE COMMENT RESPONSE OR
 ADDITIONAL INFORMATION NOT PROVIDED
 UNDER THE FIRST REVIEW.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 COURTNEY LAKES BLD.# 3 REV. (2).DOC

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-06 Cont ID  
Sent By jwitmer Date 2006-02-06 Time 16:54 Rev Time 8.00
Received By jwitmer Date 2006-02-06 Time 16:53 Sent To  
Notes
2006-02-06 00:00:00PERMIT: 05091687 BLDG# 3
 ADD:XXX N CONGRESS
 74-43-43-20-00-000-3010
 CONT: E. A. LANDERS
 TEL: (305)823-3938
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 COURTNEY LAKES APARTMENTS, LLC
  
 ARCH: FORUM ARCHITECTURE & INTERIOR DESIGN
 (407)830-1400
 STRUC: ROBERT PLOWFIELD & ASSOC
 (407)657-6657
  
 1ST REVIEW
 ACTION: DENIED
  
 ***IMPORTANT***
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 NOTE NOC WILL BE NULL & VOID 90 DAYS
 AFTER RECORDING AT THE CLERK OF THE
 COURTS OFFICE IF WORK HAS NOT STARTED.
 FL S S 713.13(2).
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS/ W MANUAL "J"
  
 4) ARCHITECTURAL PAGES DO NOT HAVE A
 RAISED SEAL.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 5)BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 7) WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 8) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO
 BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CON- TAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 9A) CONTACT LILI URSA FOR ADDRESSING
 REQUIREMENTS @ (561)822-1239
  
 9B)PROVIDE A COPY OF THE NEW PLAT, LOT
 HAS BEEN SUBDIVIDED.
  
 9C) ON ALL (3) PERMIT APPLICATIONS
 CORRECT THE PROPERTY CONTROL NUMBER TO
 THE NEW LOT.
  
 9D) PROVIDE A SITE PLAN WITH LOCATION OF
  
 THE PROPOSED STRUCTURES WITH DIMENSIONS
 FOR TABLE 600 ISSUES.A2.01 HAS NO
 DIMENSIONS!
  
 10A) CORRECT PERMIT APPLICATIONS AS TO
 DESRIPTION OF WORK FOR THE THREE
 BUILDINGS, CURRENTLY THERE WILL BE 1350
 UNITS ON THIS PROJECT WHEN FINISHED, SEE DESCRIPTION OF
 PROJECT, EACH APPLICATION
 FOR BUILDINGS 1, 450 UNITS BUILDING 2
 450 UNITS & BUILDING 3, 450 UNITS
 TOTALING 1350. .
  
 10B) PLEASE PULL PLANS APART INTO 3 SETS
 OF PLANS SO ALL PAGES THAT DEAL WITH
 BUILDING # 1 ARE IN ONE SET ETC.
  
 10C) ADDITIONAL INFORMATION REQUIRED FOR
 RECORD KEEPING PURPOSES 106.1.2*:
 10C)A) FLOOD ZONE
 10C)B) FLOOD ELEVATION (IF A ZONE)
 10C)C) LOMAR (IF A ZONE)
 10C)D) NUMBER OF UNITS
 10C)E) NUMBER OF FLOORS
 10C)F) NUMBER OF BEDROOMS
 10C)G) NUMBER OF ROOMS
 10C)H) NUMBER OF BATHROOM
 10C)I) SQ FT LIVING SPACE(TOTAL)
 10C)J) SQ FT FOOT PRINT
 10C)K) SQ FT UNDER ROOF (TOTAL)
  
 10D) THE DESCRIPTION OF BUILDINGS AND
 PHASING ARE CONFUSING BECAUSE THE
 TERMINOLOGY, CURRENTLY THE CONTRACTOR
 HAS PERMIT APPLICATIONS IN FOR BUILDINGS
 1,2& 3 NOT 4 NOR 5 AS BUILDINGS ARE
 DEPICTED ON SHEET A1.02.
  
 10E) A1.04 INDICATES A PHASED PROJECT OF
 5 BUILDINGS SEPERATED BY 4 HR WALLS.
 THEN THERE IS ANOTHER NOTE INDICATING
 TEMPORARY I HR WALLS WITH 45 MIN RATED
 DOORS. THIS PLAN IS NOT CLEAR AS WHAT
 WORK WILL BE COMPLETED WHEN. A MEETING
 WITH ALL CONCERNED WOULD BE GREATLY
 APPRECIATED. CONCERNS ON HOW EGRESS WAYS
 ARE TO BE ADDRESSED. HOW ACTIVE FIRE
 ALARM, FIRE SPRINKLER WILL BE MAITAINED
 WITH THE NEW PHASES BEING BUILT. WORK
 AREA BEING ISSOLATED FROM THE GENERAL
 PUBLIC.A ACCESSIBLE PATH TO THE RIGHT OF
 WAY DURING CONSTRUCTION OF ALL PHASES.
  
 10F) THE PHASING PLAN INDICATED ON SHEET
 A1.04 INDICATES WORK ON BUILDING# 1 THEN
 JUMPING TO TWO OTHER BUILDINGS THEN BACK
 TO BUILDING# 1 JUMPING OVER AREAS TO BE
 PHASED IN LATER VERY IMPARTICAL AS TO
 HOW LIVE SYSTEMS ELECTRIC WATER AND FIRE SPRINKLERS ARE
 TO BE BUILT AND
 MAINTAINED.
  
 10G) THIS REVIEW WILL CONSTITUTE OF
 BUILDING# 1 OF 515,540 SQ FT. PLANS
 REFER TO THIS AS BEING BLDG 1,2 & 3.
  
 10H) A1.02 CODE COMPLIANCE FOR APARTMENT BUILDINGS
 PLANS INDICATE TYPE IV, UNPROTECTED ,
 SPRINKLERED
 MAXIMUMHEIGHT ALLOWED IS 55'
 PROPOSED HEIGHT69'-3"
 PLEASE CORRECT BUILDING TYPE!!!!!!
 503.2.2 ALLOWED THE DEDUCTION OF 1 STORY
 FOR THE PARKING GARAGE IF TYPE I OR TYPE
 II BUILDING.
  
 10I) THE OTHER ISSUE IS THE ALLOWABLE
 AREA FOR A TYPE IV , UNPROTECTED,
 SPREINKLERED BUILDING THE ALLOWABLE
 AREAIS ONLY 24,000 SQ FT / FL.
  
 10J) EVEN IF THE BUILDING WAS CONSIDERED
 A TYPE IV , 1 HR PROTECTED, SPRINKLERED
 BUILDING THE ALLOWABLE AREA INCREASE
 WILL BE 36,000/ FL BUT THE HEIGHT OF 65'
 STILL 4'-3" OF THE OVERALL HEIGH OF THE
 BUILDING, STILL REQUIRING THE 4 FOUR HR
 FIRE WALLS TO MAKE UP THE TOTAL AREA FOR
 THIS ONE BUILDING. THE OTHER ISSUE IS
 THE 4 HR FIRE WALLS DO NOT CONTINUE
 THROUGH THE GARAGE SEPERATING THEM INTO
 SEPERATE BUILDINGS. A 3HR FIRE RATED
 DOOR WOULD BE REQUIRED IN THE GARAGE
 LEVEL. PLEASE CORRECT.
  
 10K) DISCREPANCY A1.02 CONSTRUCTION TYPE
 IV UNPROTECTED VS A1.21 FIRE RATING
 IV I HR RATED.
  
 11) SHEET A1.05
  
 11A) PLEASE PROVIDE THE LISTING FOR
 RATED WALLS, U.L. OR OTHER
 RECOGNIZED LISTING AGENCY.
  
 11B) PLANS INDICATE USE OF RINKER BLOCK,
 PROVIDE FROM THE MANUCATURER THE
 EQIVALENT THICKNESS OF BLOCK,709.3.1.1
 THE FIRE RESISTANCE RATING OF WALLS AND
 PARTITIONS CONSTRUCTED OF CONCRETE
 MASONRY UNITS SHALL BE DETERMINED FROM
 TABLE 709.3.1.THE RATING SHALL BE
 BASED ON THE EQUIVALENT THICKNESS OF THE
 MASONRY AND TYPE OF AGGREGATE USED.
  
 12)SITE PLAN A2.01
  
 12A) ACCESSIBLE ROUTE: FAIR HOUSING AT
 LEAST ONE ACCESSIBLE ROUTE SHALL BE
 PROVIDED WITHIN THE BOUNDARY OF THE SITE
 FROM PUBLIC TRANSPORTATION STOPS,
 ACCESSIBLE PARKING SPACES, PASSENGER
 LOADING ZONES IF PROVIDED, AND PUBLIC
 STREETS OR SIDEWALKS, TO AN ACCESSIBLE
 BUILDING ENTRANCE.
  
 12B) SITE PLAN DOES NOT PROVIDE ANY
 INFORMATION AS TO CURB CUTS, PEDSTRIAN
 CROSS WALKS, ETC.
  
 13) SHEET A5.40:
  
 13A) ELEVATOR LOBBY DOOR # 5.003 SWINGS
 THE WRONG WAY AGAINST EGRESS.
 NO HR RATING!
  
 13B) STAIRWELL# 12,13&14EXIT DOOR NO
 LISTING, NO RATING!
  
 13C) STAIRWWELL 12 LEAD BACK INTO THE
 GARAGE NOT THE EXIT DISCHARGE.
  
 13D) TRASH REFUSE ROOM# 5NO RATING
  
 13E) FIRE PUMP ROOM NO RATING OF DOOR
  
 13F) PARKING GARAGE TO BE CONSIDERED AN
 ENCLOSED PARKING GARAGE PROVIDE
 COMPLIANCE WITH 6 AIRCHANGES PER
 HR.411.4.2.
  
 13G) MAILBOXES SEE DETAIL A5.56 DETAIL
 # 7, PROVIDE DIMENSIONS (ELE) TO COMPLY
 WITH SIDE REACH RANGES.
  
 13H) PLANS ARE NOT CLEAR IF STAIRWELL
 12 & 4 ARE IN PHASE "D" OR PHASE "E". IF
 LOCATED IN 2ND PHASE DEAD END
 CORRIDORS EXIST.
  
 13I) GARAGE 4 HR FIRE WALL, PROVIDE 3 HR
 FIRE RATED DOOR BETWEEN BUILDINGS,
 INDICATE HOW DOOR WILL ACTIVATE WITH THE
 SMOKE/ FIRE ALARM?
 705.1.3.1 WALL OPENINGS REQUIRED TO BE
 PROTECTED SHALL BE PROTECTED BY APPROVED
 LISTED AND LABELED FIRE DOORS, WINDOWS
 AND SHUTTERS AND THEIR ACCOMPANYING
 HARDWARE, INCLUDING ALL FRAMES, CLOSING
 DEVICES, ANCHORAGE AND SILLS, IN
 ACCORDANCE WITH THE REQUIREMENTS OF NFPA
 80, EXCEPT AS OTHERWISE SPECIFIED IN
 THIS CODE.
  
  
  
  
  
 14)BUILDING# 5 SHOWS PHASING AND IT
 APPEARS TO BE A SINGLE 4HR FIRE WALL
 SEPERATING THIS BUILDING INTO 2 SEPERATE BUILDINGS. THE
 STAIR TOWER WILL HAVE
 TO BE BUILTWITH A 4HR WALL, ROOF
 STRUCTURE INDEPENDENT OF THE OTHER
 BUILDINGS AND DIRECT ACCESS FROM EACH OF
 THE BUILDINGS EXIT ACCESS CORRIDORS,PLUS
 THE REQUIRED 3 HR OPENING PROTECTIVES.
 YOUR BUILDINGS DESIGN WAS BROUGHT TO THE
 BUILDING OFFICIAL FOR HIS INTERPRETATION
  
 PLANS INDICATE TYPE IV UNPROTECTED,
 FIRE SPRINKLERED TABLE 600 ALLOWS 24,000
 SQ FT PER FLOOR PLANS INDICATE 28,486
 PER FLOOR. AREA INCREASES IF TAKEN
 APPEARS TO MEET THE CODE FOR AREA, THERE
 SEEMS TO BE A PROBLEM WITH HEIGH
 PROPOSED 69' ALLOWED 55'.
  
  
 DEF:WALL, PARTY. A FIRE WALL ON AN
 INTERIOR LOT LINE, USED OR ADAPTED FOR
 JOINT SERVICE BETWEEN TWO BUILDINGS.
  
 SELF-CLOSING. AS APPLIED TO A FIRE DOOR
 OR OTHER OPENING, MEANS NORMALLY CLOSED
 AND EQUIPPED WITH AN APPROVED DEVICE
 WHICH WILL INSURE CLOSING AFTER HAVING
 BEEN OPENED FOR USE.
  
 705.1.3.1 WALL OPENINGS REQUIRED TO BE
 PROTECTED SHALL BE PROTECTED BY APPROVED
 LISTED AND LABELED FIRE DOORS, WINDOWS
 AND SHUTTERS AND THEIR ACCOMPANYING
 HARDWARE, INCLUDING ALL FRAMES, CLOSING
 DEVICES, ANCHORAGE AND SILLS, IN
 ACCORDANCE WITH THE REQUIREMENTS OF NFPA
 80, EXCEPT AS OTHERWISE SPECIFIED IN
 THIS CODE.
  
 705.1.5 OPENING PROTECTION IN STAIRWAY
 ENCLOSURES. OPENING PROTECTIVESIN
 STAIRWAY SHAFTS ARE LIMITED TO
 SELF-CLOSING OR SMOKE ACTUATED,
 AUTOMATIC-CLOSING FIRE DOOR
 ASSEMBLIES.IF SMOKE-ACTUATED CLOSURES
 CLOSE ONE DOOR, ALL DOORS SERVING THAT
 STAIRWAY SHALL CLOSE.
  
 THE OTHER ISSUE IS A UNITY OF TITLE
 WOULD BE REQUIRED EVEN FOR A SINGLE LOT
 AS TO NOT BE ABLE TO SELL OFF A PORTION
 OR BUILDING CREATING A CODE VIOLATION.
  
 15) SHEET A5.41:
  
 15A) TRASH ROOM DETAIL 1&2 OF A8.20 THE
 DETAIL IS MISSING THE ENCLOSURE TO THE
 BOTTOM OF THE CHUTE ENCLOSURE.705.2.4.2
 ALL OPENINGS INTO THE SHAFT ENCLOSURE,
 INCLUDING THOSE FROM ACCESS ROOMS AND
 TERMINATION ROOMS, SHALL BE PROTECTED IN ACCORDANCE
 WITH TABLE 705.1.2.SUCH
 OPENING PROTECTIVES SHALL BE
 SELF-CLOSING OR AUTOMATIC-CLOSING UPON
 DETECTION OF SMOKE, EXCEPT THAT THE
 OPENING PROTECTIVE BETWEEN THE SHAFT AND
 THE TERMINATION ROOM MAY BE CLOSED BY A HEAT-ACTIVATED
 DEVICE.
  
 15B) THE TERMINATION ROOM DOOR NO
 INFORMATION ON RATING?
  
 16) VARIOUS SHEETS ON BUILD# 5
 INDICATE A DETAIL SECTION# 23 SHEET
 A7.10.
  
 16A) THIS SECTION INDICATES METAL
 TRUSSES TO BE USED BUT NO INFORMATION
 AS TO THE ROOF DECKING MATERIAL TO BE
 USED? TYPE IV UNPROTECTED- NC
 TYPE IV 1HR- IHR PROTECTED
  
 16B) PROVIDE A DETAIL INDICATING ACCESS
 TO ATTIC AREA.
  
 16C) THIS SAME SECTION INDICATES USE OF
 FOAM TRIM ON THE EXTERIOR OF THE
 BUILDING ABOVE 40'.1404.1.1
 ARCHITECTURAL TRIM ON BUILDINGS OF TYPE
 I, II AND IV CONSTRUCTION NOT MORE THAN
 THREE STORIES OR 40 FT (12.2 M) HIGH MAY
 BE OFTYPE VI CONSTRUCTION, AND MAY BE
 OF TYPE VI CONSTRUCTION ON ALL BUILDINGS
 OF TYPE III, V AND VI CONSTRUCTION.
 TRIM SHALL BE SECURED TO THE WALL WITH
 METAL OR OTHER APPROVED BRACKETS OR
 FASTENERS.WHEN ARCHITECTURAL TRIM IS
 LOCATED ALONG THE TOP OF EXTERIOR WALLS,
 IT SHALL BE COMPLETELY BACKED BY THE
 EXTERIOR WALL AND SHALL NOT EXTEND OVER
 THE TOP OF EXTERIOR WALLS.
  
  
 17) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 18) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) OPARATABLE WINDOWS
 B) FIXED WINDOWS
 C) MULLION
 D) EXTERIOR DOORS SOLID
 E) EXTERIOR DOORS GLAZED
 F) EXTERIOR DOORS LOUVERED
 G) STORM SHUTTERS
 H) EXTERIOR RAILINGS
 I) LOUVERS
 J) TRUSS ANCHORS
 K) ROOFING ASSEMBLIES
 L) EFIS SYSTEMS
  
 19) AN INTERPRETATION FROM THE BUILDING
 OFFICIAL ON STORM SHUTTERS THAT ARE USED
 ON LARGE PROJECTS:
 QUESTION# 13) RECOGNIZING SUCH CONCERNS
 AS ABSENTEE OWNERS, OR CASES WHERE
 LONGER TIME AND EFFORT IS NECESSARY TO
 SECURE SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING
 RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING
 IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE EVENT?
  
 IN MATTERS FLORIDA BUILDING CODE, 2004
 EDITION, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT
 REQUIREMENTS FOR ENSURING STABILITY,
 STRENGTH, AND PROPER OPERATION OF
 EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF
 SHUTTERS ON LARGE OR MULTI-STORY
 BUILDING, OR MULTIPLE BUILDINGS ON THE
 SAME PROPERTY, PRE-STORM PREPARATION
 PLANS MUST BE SUBMITTED BY THE PROPERTY
 OWNERS OR MANAGING AGENTS FOR REVIEW BY
 THE CONSTRUCTION SERVICES DEPARTMENT.
 ANY SUCH PLAN SHALL INCLUDE, AT A
 MINIMUM, ON-SITE LOCATION OF SHUTTERS,
 PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS (SAID PARTIES MUST BE LOCATED
 WITHIN PALM BEACH COUNTY), TOTAL NUMBER
 OF OPENINGS TO BE PROTECTED AND TOTAL
 TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE
 ACCOMPLISHED WITHIN TWELVE (12) HOURS OR
 LESS OF THE OFFICIAL NOTIFICATION BY THE
 NATIONAL WEATHER SERVICE OF A HURRICANE
 WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND
 THIS STANDARD) ARE NOT INTENDED TO
 PROHIBIT THE USE OF ALTERNATIVE
 MATERIALS AND METHODS, AND ALLOW THE
 BUILDING OFFICIAL TO REVIEW AND APPROVE
 ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE
 RESISTANCE, DURABILITY AND SAFETY
 PRESCRIBED BY CODE. BASED UPON THIS CODE PROVISION,
 ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON
 A CASE-BY-CASE BASIS AND SHALL REQUIRE
 SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING
 THE ALTERNATE.
  
 QUESTION# 14) ARE REMOVABLE STORM PANELS APPROPRIATE
 FOR USE ON VERY LARGE, MID
 OR HIGH-RISE STRUCTURES?
  
 NO, EXCEPT ON THE GROUND FLOOR. ON
 COMMERCIAL AND MULTI-UNIT RESIDENTIAL
 STRUCTURES, ABOVE THE FIRST LEVEL,
 IMPACT RESISTANT GLAZING OR PERMANENTLY
 AFFIXED PROTECTIVE DEVICES SHALL BE
 INSTALLED. PERMANENTLY AFFIXED
 PROTECTIVE DEVICES SHALL REQUIRE THE
 WRITTEN APPROVAL OF THE BUILDING
 OFFICIAL.
  
 20) PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 21) FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 22) 3003.6.1 VENTS. HOISTWAYS OF ELEVA-
 TORS SERVING MORE THAN 3 FLOORS SHALL BE
 PROVIDED WITH MEANS OF VENTING SMOKE AND
 HOT GASES TO THE OUTER AIR IN CASE OF
 FIRE.
  
 23)3003.6.2 VENTS SHALL BE LOCATED BELOW
 THE FLOOR OR FLOORS AT THE TOP OF THE
 HOISTWAY, AND SHALL BE EITHER DIR- ECTLY
 TO THE OUTER AIR OR THROUGH NON-
 COMBUSTIBLE DUCTS TO THE OUTER AIR.
  
 24) 3003.6.3 THE AREA OF THE VENTS SHALL
 BE NOT LESS THAN 3 SQ FT FOR EACH
 ELEVATOR CAR, WHICHEVER IS GREATER.
  
 25)SHEET S4.00 INDICATES THE ROOF ZONES
 FOR A SIMPLE RECTANGLE. PROVIDE A
 DETAILED ZONE MAP AS IT RELATES TO THIS
 BUILDING INCLUDING PENTHOUSES WITH THE
 APPROPRIATE PRESSURES.
  
 26) A9.03 WINDOW BUCK DETAIL CORRECT:
 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 27) S3.51-S3.54
 1511.7 ROOF MOUNTED MECHANICAL UNITS
 SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
  
 28) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 29) ELECTRICAL SHEETS MISSING SMOKE
 ALARMS IN BEDROOMS.905.1.1A FIRE ALARM
 SYSTEM IN ACCORDANCE WITH NFPA 72SHALL
 BE INSTALLED.
  
 ADDITIONAL COMMENTS MAY APPEAR ON THE
 NEXT REVIEW NOT COVERED FROM THE FIRST
 REVIEW DUE TO THE COMMENT RESPONCEOR
 ADDITIONAL INFORMATION NOT PROVIDED
 UNDER THE FIRST REVIEW.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-09-20 Cont ID  
Sent By dpalmer Date 2007-09-20 Time 08:18 Rev Time 0.00
Received By dpalmer Date 2007-09-16 Time 13:06 Sent To  
Notes
2007-09-20 08:19:00 
 ** DENIED 3RD REVIEW**
  
 ** PLEASE SEE THERE ARE SOME ITEMS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE ALSO SEE
 THERE ARE SOME NEW COMMENTS BASED ON REVISED
 PLANS/PLANS AND DOCUMENTS NOW SUBMITTED.
 ** SOME ITEMS COULD HAVE BEEN REDLINED/PROVISO, HOWEVER
 MANY OF THESE ARE IN NEED OF ADDRESSING AT THIS TIME.
  
 1) NOTE:PLEASE SEE THE PLANS DO NOT INDICATE FIXTURE
 DESIGNATIONS FOR ALL LIGHTING. PLEASE SEE THERE ARE
 SEVERAL AREAS INCLUDING FIRST FLOOR AND OTHER FLOORS
 WHERE FIXTURES ARE STILL MISSING DESIGNATIONS. PLEASE
 SEE THE FIXTURE LEGEND COULD NOT BE COORDINATED WITH
 THESE AT THIS TIME.
 PLEASE SEE COMMON AREAS WHICH THE LEGEND ON ELECTRICAL
 PLANS COULD NOT BE FOUND.
 PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORT FOR
 EXTERIOR LIGHTING ALSO NEEDS TO CORRELATE WITH PLANS.
 THE LIGHTING, TYPES, NUMBER OF FIXTURES, ETC IS NOT
 STATED ON THE IDR AS ON PLANS.
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED AS THE
 INPUT DATA REPORT DOES NOT CORRELATE WITH ALL
 ELECTRICAL LIGHTING FOR INTERIOR LIGHTING WHICH IS ON
 PLANS. PLEASE SEE MISSING A SUBSTANTIAL AMOUNT OF
 LIGHTING ON THE INPUT DATA REPORT.
 13-415.0, 415.1.ABCD, 415.1.A, 415.2
  
 2) NOTE: PLEASE SEE ONLY ONE COPY OF THE ENERGY
 CALCULATIONS (1.22 VERSION) SUBMITTED ACTUALLY CONTAINS
 AN ORIGINAL SIGNATURE AND DATE. PLEASE SEE THAT TWO
 SETS CONTAIN A RAISED SEAL OVER A PHOTO-COPIED
 SIGNATURE AND THE THIRD DOES NOT CONTAIN A RAISED
 SEALED OR ORIGINAL SIGNATURE.
 **PLEASE KNOW THIS COMMENT HAS BEEN MADE TO THIS DESIGN
 PROFESSIONAL ON SEVERAL PROJECTS SUBMITTED TO THIS
 JURISDICTION. THIS COMMENT WILL ALSO BE UNDER BUILDINGS
 1 AND 3.
 PLEASE KNOW THIS OFFICE IS RETAINING ALL COPIES
 SUBMITTED FOR POSSIBLE SUBMISSION TO THE FLORIDA BOARD
 OF ENGINEERS.
 THIS IS A FLORIDA STATUTE AND IS ALSO STATED IN THE
 FLORIDA ADMINISTRATIVE CODE.FS 471.025, FAC
 61G15-23.002, FBC 103.1.
 ** WHEN PLANS WERE RE-SUBMITTED THIS REVIEWER NOTICED
 THE INCORRECT VERSION ON THE CALCULATIONS SUBMITTED AND
 NEW CALCULATIONS WITH THE CORRECT VERSION WAS SENT VIA
 FED-EX. PLEASE SEE THAT THE ONES DONE UNDER THE 2004
 FBC WERE ALSO NOT SIGNED, DATED AND SEALED CORRECTLY
 AND AS REQUIRED BY THE FLORIDA STATUTES. THIS SHOWS
 SAME NON-COMPLIANCE ON MULTIPLE SETS OF DOCUMENTS.
 ** PLEASE BE SURE TO GO OVER ALL AND CORRECT.
  
 3) NOTE: PLEASE SEE INFORMATION FOR SITE LIGHTING POLES
 DO NOT CONTAIN THE MINIMUM WIND LOAD INFORMATION.
 PLEASE KNOW IF THIS INFORMATION IS NOT COMPLETE UNDER
 BASE PLANS, THESE WILL BE REQUIRED TO BE UNDER SEPARATE
 PERMITS, PLANS AND FEES.
 PLEASE KNOW HOWEVER THE LIGHTING INFORMATION AS NOTED
 ABOVE IN NOTE #1 FOR THE ENERGY CALCULATIONS WILL STILL
 NEED TO BE CORRECTED.
 PLEASE IDENTIFY THE CIRCUITS AS SHOWN ON PLANS TO WHICH
 BUILDING HOUSE PANEL THEY TERMINATE. PLEASE SEE THIS IS
 DONE FOR THE SITE LIGHTING CIRCUITS FOR BUILDING #2 BUT
 NOT THE OTHERS.
  
 4) NOTE: PLEASE SEE THE SYMBOL LEGEND STILL INDICATES
 *SMOKE DETECTORS*. THIS COULD BE REDLINED IF AND WHEN
 ALL OTHER COMMENTS AS ADDRESSED. PLEASE KNOW IF THERE
 ARE ANY COMMENTS HOWEVER WHICH MAY AFFECT THE SAME
 SHEET(S), PLEASE CORRECT AT THIS TIME. E16.01 THIS
 COULD BE REDLINED ON THIS SHEET IF NOT OTHER CHANGES IS
 MADE.
  
 5) NOTE: PLEASE BE SURE TO CORRELATE ALL LAYOUTS FOR
 UNITS AS THE ELECTRICAL PLANS SEEM TO HAVE DIFFERENT
 LAYOUT(S) FOR SOME UNITS. PLEASE SEE C-3 FOR EXAMPLE ON
 16.03, 16.04.
 PLEASE CORRELATE THE TWO AS THESE LAYOUTS DO NOT MATCH
 AT THIS TIME.
 PLEASE SEE ANY CHANGES IN LIGHTING ETC. PLEASE ALSO BE
 SURE TO COORDINATE WITH THE A-SHEETS.
 FBC 104.1.2 (2001) ADMIN SECTION FOR ADDITIONAL
 INFORMATION AND COORDINATION OF PLANS.
  
 6) NOTE: PLEASE SEE DISHWASHER AND DISPOSAL WHICH IS
 BEING SHOWN WITH A J-BOX. ARE THESE ITEMS GOING TO BE
 HARDWIRED?
 PLEASE SEE 422.30, 422.31 FOR REQUIRED DISCONNECTING
 MEANS.
 ARE THESE NOT CORD AND PLUG TYPE APPLIANCES WHICH WOULD
 PLUG IN?
  
 7) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS AND PLEASE
 KNOW THERE ARE SEVERAL A-SHEETS ON THE REVIEWED SET
 WHICH WERE NOT SEALED WITH THE RAISED EMBOSSED SEAL AS
 REQUIRED UNDER FS 481.221, FAC 61G1-16.002
  
 8) NOTE: PLEASE SEE THE LIGHT FIXTURE OUTSIDE FIRE PUMP
 ROOM WILL BE REQUIRED TO BE BATTERY BACK UP. THIS IS
 SHOWN AS A *J* FIXTURE. AS NO FIXTURE LEGEND WAS
 SUBMITTED THIS CAN NOT BE VERIFIED AT THIS TIME.
 PLEASE ALSO SEE ARE OUT SIDE ELEVATOR EQUIPMENT AREA
 AND MAIN ELECTRICAL ROOM WILL ALSO REQUIRE AN EMERGENCY
 BATTERY BACK UP LIGHTING FIXTURE OF SOME KIND.
 NEC 700.12E, 700.16, LS-101 7.8, 7.9
  
 9) NOTE: PLEASE SEE RISER NOTE #10 WHICH MENTIONS
 CONDUCTORS BEING INSTALLED BY POWER COMPANY HOWEVER
 PLEASE KNOW THE POWER COMPANY (FPL) FLORIDA POWER AND
 LIGHT SHOULD BE CONSULTED.
 IT IS KNOWN TO THIS OFFICE THAT THESE CONDUCTORS AFTER
 THE METERING DEVICES ARE NOT INSTALLED BY THE POWER
 COMPANY AND IN FACT THERE ARE SEVERAL TIMES THE SERVICE
 ENTRANCE CONDUCTORS FROM THE TRANSFORMERS TO THE
 SERVICE METERS AND MAINS ARE ACTUALLY OWNER SUPPLIED.
 THIS WOULD PLACE ALL CONDUITS AND CONDUCTORS UNDER THE
 NEC FOR CODE COMPLIANCE.
 PLEASE ADJUST RISER FOR CONDUCTORS ETC.
 240.4, 310.16
 FBC 106.3.5.1.2
  
 10) NOTE: PLEASE CLARIFY THE FIRE PUMP AND INFORMATION
 AS REQUESTED ON THE PREVIOUS REVIEWS.
 PLEASE SEE NO INFORMATION WAS SUBMITTED WITH RESPECT TO
 THE MINIMUM FUEL REQUIREMENTS AND SIZE OF TANK. PLEASE
 SEE NO TIMES AT 100% RUNNING IS SHOWN.
 PLEASE SEE NFPA-20 9.6.2.2 AND SEE COMMENTS FROM FIRE
 MARSHAL.
 PLEASE SEE THE FUEL NOTE WHICH IS ON SHEET FP13.09 #3,
 DOES NOT CONTAIN THE TEXT FOR CODE.
 PLEASE SEE THE MINIMUM ON THE BASE BUILDING IS REQUIRED
 AT THIS TIME.
 PLEASE SEE THE PREVIOUS NOTES WHICH REQUESTED THIS SAME
 INFORMATION.
 PLEASE SEE THE FP SHEETS INDICATE A DIESEL FIRE PUMP,
 YET THE SUBMITTALS WHICH WERE SUBMITTED WITH PLANS
 INDICATE AN ELECTRICAL FIRE PUMP.
 PLEASE SUBMIT THE ACTUAL DOCUMENTATION AND CORRELATE
 WITH PLANS.
 110.3, 90.7, NFPA-70 695, NFPA-20 2003
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-18 16:30:272007-09-18 16:30:27
  
 REVIEW COMMENCED ON BLDG #3
2007-09-16 13:06:512007-09-16 13:06:51
  
 IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-31 Cont ID  
Sent By dpalmer Date 2006-12-31 Time 19:44 Rev Time 0.00
Received By dpalmer Date 2006-12-29 Time 18:16 Sent To  
Notes
2006-12-31 19:44:43**** UNSAT2ND REVIEW ********
  
 COURTNEY LAKES BUILDING #3
 N. CONGRESS.
  
 ** PLEASE SEE MANY OF THE SAME COMMENTS FROM THE
 PREVIOUS REVIEW STILL NEED TO BE ADDRESSED.
  
 ** PLEASE SEE AS THREE SEPARATE BUILDING PERMITS AND
 PLANS ARE NOW SEPARATED FOR EACH, PLEASE ALSO SEE NEW
 COMMENTS BASED ONE THE PLANS NOW SUBMITTED INTO EACH
 SET.
  
 ** PLEASE ALSO SEE THERE ARE SOME NEW NOTES BASED ON
 PLANS SUBMITTED.
  
 ** PLEASE SEE BELOW ARE SOME OF THE NOTES FROM THE
 PREVIOUS REVIEW ARE BEING NOTED IF ADDRESSED OR NOT BY
 A "NO, OK, NO/OK, N/A OR SEE NEW ".
 1) NO WILL HAVE FURTHER EXPLANATION IN AN ATTEMPT TO
 BETTER EXPLAIN COMMENT MADE.
 2) OK, WILL HAVE PREVIOUS NOTE REMOVED.
 3) NO/OK, MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL. THIS WILL ALSO BE FOLLOWED
 BY FURTHER EXPLANATION OF PREVIOUS NOTE.
 4) N/A, THIS MEANS THE COMMENT NO LONGER APPLIES TO
 THIS BUILDING AND PREVIOUS NOTE IS REMOVED.
  
 ** PLEASE SEE ALL NEW NOTES WILL BE NOTED AT THE END OF
 PREVIOUS REVIEW COMMENTS AND WILL BE INDICATED WITH
 **** NEW NOTES**.
  
  
 1) NOTE: OK. SEE NOTES.
  
 2) NOTE: OK
  
 3) NOTE:NO, PLEASE SEE RESPONSE MENTIONS PLANS
 DESIGNED UNDER THE CODES AS NOTED, HOWEVER ALL CODES
 RELEVANT TO THE DESIGN IN WHICH THE BUILDING IS
 PERMITTED UNDER SHALL BE STATED ON PLANS. PLEASE SEE
 THIS IS REQUIRED OF ARCHITECTURAL SHEETS AS WELL AS
 ELECTRICAL AND FIRE. PLEASE SEE ANY OTHER NOTES WITH
 RESPECT TO THIS FROM OTHER TRADES.
 THE FOLLOWING SHALL BE STATED. 2002 NEC/NFPA-70, 2002
 NFPA-72, 2003 NFPA-20 AND 2003 NFPA-101. (THE CORRECT
 NFPA-101 IS NOTED )
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE TO CORRECT THE CURRENT NEC/ NFPA-70 IN
 EFFECT.
 PLEASE KNOW, AS OF JULY 1ST, 2003 THE STATE OF FLORIDA
 ADOPTED THE 2002
 NFPA-70 (NEC). PLANS REFERENCE 1999. PLEASE SEE SOME
 ELECTRICAL COMMENTS WHICH WILL AFFECT THIS.
 PLEASE SEE NEXT COMMENT WITH RESPECT TO PERMITS APPLIED
 FOR UNDER THE 2001 FBC BEFORE OCT 1ST, 2005 AND PERMITS
 ON OCT 1ST, 2005.
  
 4) NOTE: N/A, SEE NEW NOTES FOR EACH BUILDING.
  
  
 5) NOTE: N/A, SEE NEW NOTES UNDER EACH BUILDING.
  
 6) NOTE:NO, PLEASE SEE THERE ARE SEVERAL AREAS WHICH
 CIRCUITING IS NOT COMPLETE INCLUDING UNITS FOR SMOKE
 DEVICES AND MANY AREAS OF HOUSE/COMMON AREAS/ SITE ETC.
 PLEASE SEE MANY NEW COMMENTS BASED ON PLANS SUBMITTED.
 PLEASE SHOW ALL AND CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULES. SEE NEW NOTES.
 FBC ADMIN SECTION 104.1.2
  
 PLEASE COMPLETE ALL CIRCUITING ON PLANS IN ORDER TO
 REVIEW CODE COMPLIANCE FOR AREAS OF UNITS AND COMMON
 AREAS.
  
 7) NOTE: NO, SAME COMMENT. THIS IS NOT EXPLAINED ANY
 FURTHER. PLEASE HOWEVER ALSO SEE NEW COMMENTS BASED ON
 PLANS SUBMITTED.
 ** PLEASE KNOW THERE ARE AREAS OF PLANS WITH
 DESIGNATIONS, ITEMS FOR CODE COMPLIANCE FOR CIRCUITING
 TO THOSE AREAS CAN NOT BE VERIFIED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE ROOM AND AREA DESIGNATIONS ON PLANS,
 INCLUSIVE OF ALL UNITS AND COMMON AREAS.
 REVIEW FOR SOME CODE COMPLIANCE ITEMS CAN NOT BE DONE
 AT THIS TIME.
  
 8) NOTE:NO, PLEASE SEE RESPONSE LETTER MENTIONS TO
 SEE SHEET AP E16.00A, YET PLEASE KNOW COMPLETED
 PHOTO-METRICS SHALL BE SUBMITTED IN EACH SUBMITTED
 PLANS FOR EACH BUILDING AS EACH BUILDING IS ITS OWN
 LEGAL RECORD.
 PLEASE ALSO SEE PREVIOUS NOTES, PLEASE SEE ONLY PARTIAL
 PHOTO-METRICS WERE SUBMITTED. PLEASE SEE NOTE WHICH
 REQUIRES ALL UNDER NORMAL AND EMERGENCY AND FOR ALL
 EGRESS AREAS. PLEASE SEE ONLY SOME ARE BEING SHOWN IN
 THE PLANS UNDER BUILDING ONE. PLEASE KNOW THESE CAN BE
 TYPICAL, HOWEVER THEY SHALL ALSO BE SPECIFIC TO EACH
 AREA IF THE LAYOUT OF THESE AREAS CHANGES WHICH THEY
 DO. NOT ALL AREAS ARE THE LIKE.
 PLEASE SEE NEW NOTES ALSO FOR EGRESS FROM UNITS AND
 PLEASE SEE NEW NOTES PERTAINING TO PARKING LOT, AND
 SITE LIGHTING.
 PLEASE KNOW AS THE SWIMMING POOL IS NOT UNDER THIS
 PERMIT FOR THE BUILDING, STAMPED PLANS FROM PALM BEACH
 COUNTY HEALTH DEPT IS NOT REQUIRED AT THIS TIME UNDER
 THIS PERMIT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE COMPLETE PHOTO-METRICS FOR ALL COMMON
 AREAS, GARAGE AREA, COMMON AREA CORRIDORS, STAIR TOWERS
 ETC.
 PLEASE SEE 2003 NFPA-101 7.8.1.3 AND 7.9.2.2 WHICH
 REQUIRE A MIN OF 10FT CANDLES FOR STAIR TOWERS UNDER
 NORMAL OPERATION AS WALK SURFACE AND A MIN OF 1FT
 CANDLE AT WALK SURFACE UNDER EMERGENCY CONDITIONS.
 PLEASE ALSO SEE OTHER WALK AREAS, GARAGE, CORRIDORS ETC
 AND THE MIN OF 1FT CANDLE.
 **PLEASE SEE PALM BEACH COUNTY SECURITY CODE ORDINANCE
 WITH RESPECT TO MIN DESIGN OF PARKING LOT LIGHTING
 LEVELS UNDER NORMAL CONDITIONS. (ONLY NOTED FOR DESIGN)
 NOT REQUIRED. PLEASE SEE ANY REQUIREMENTS FROM INS
 CARRIER WHICH REQUIRES A MIN LEVEL OF LIGHTING.
 ** PLEASE SEE PHOTO-METRICS OR SITE PLAN WAS NOT
 SUBMITTED FOR PROPOSED POOL AREA. THE POOL STRUCTURE IS
 REQUIRED TO BE UNDER A SEPARATE PERMIT. PLEASE KNOW,
 THE PHOTO-METRICS FOR POOL AREA WILL BE REQUIRED AND
 WILL ALSO BE REQUIRED TO BE REVIEWED AND STAMPED BY THE
 PALM BEACH COUNTY HEALTH DEPT FOR ANY PROPOSED
 NIGHT-TIME SWIMMING.
  
 7) NOTE: NO, PLEASE SEE EACH SET OF PLANS SHALL CONTAIN
 A SITE LIGHTING PLAN SHOWING ALL CIRCUITING AND
 CORRELATE WITH EACH OF THE HOUSE PANELS FOR EACH
 BUILDING IN WHICH THEY ARE BEING CIRCUITED TO. PLEASE
 SEE ALL SITE LIGHTING AS SHOWN IN THE SET OF PLANS FOR
 BUILDING ONE. PLEASE SEE THE CIRCUITING AS SHOWN DOES
 NOT CORRELATE WITH HOUSE PANEL FOR BUILDING THREE IN
 ANY WAY. PLEASE SEE HOUSE PANEL FOR THESE CIRCUITS ARE
 IN FACT BLANK AND SHOWS THE WORDING OF "SPACE". PLEASE
 KNOW AT THIS TIME THERE ARE MANY ITEMS PERTAINING TO
 SITE LIGHTING WHICH CAN NOT BE VERIFIED FOR VOLTAGE
 DROP, CIRCUITS, OVER CURRENT PROTECTION, CONDUCTOR
 SIZES ETC.
 PLEASE SEE NO INFORMATION WAS SUBMITTED OR SHOWN FOR
 WIND LOADS ON POLES.
 240.4, 310.16, 408.4, FBC 104.2.1,104.21.2
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NO "ELECTRICAL SITE-PLAN" WAS SUBMITTED FOR
 ANY SITE LIGHTING, LANDSCAPE LIGHTING ETC.
 PLEASE KNOW, IF NOT SUBMITTED UNDER THIS PERMIT AND
 VALUES ADJUSTED ACCORDINGLY, SEPARATE PERMIT , PLANS
 AND FEES WILL BE REQUIRED FOR ALL SITE LIGHTING,
 LANDSCAPE LIGHTING WORK.
 ** ALSO NOTE: IN THAT COMPLETE WIND LOADING
 CALCULATIONS FOR LT POLES INCLUSIVE OF THE ATTACHMENT
 OF LT FIXTURES WILL BE REQUIRED TO BE SUBMITTED WITH
 PLANS AND PERMIT APPLICATION FOR REVIEW.
  
 8) NOTE: NO, PLEASE SEE ONCE AGAIN NOT ALL ROOMS ARE
 DONE AS REQUIRED. PLEASE SEE MAIN ELECTRICAL ROOM FOR
 THIS BUILDING ALONE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INCLUDE AN EMERGENCY BATTERY BACK UP LT OF SOME
 SORT IN ALL ELECTRICAL ROOMS, FIRE PUMP ROOM, AND
 ELEVATOR MACHINE RMS. SOME ARE SHOWN, BUT NOT ALL.
 7.8,7.9, 700.16 ETC
  
 9) NOTE:NO, PLEASE SEE NOT ONLY ARE MANY CIRCUITS NOT
 SHOWN ON PLANS NO CHANGES FOR THE REQUIRED DEDICATED
 CIRCUITS HAVE BEEN MADE. PLEASE SEE PLANS AND CORRELATE
 WITH THE HOUSE PANEL FOR THIS BUILDING.
 PLEASE SEE 620.22,23,24 AND 620.51 ETC
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 620.23, AND 620.24 FOR REQUIRED DEDICATED
 BRANCH CIRCUITS FOR ELEVATOR PITS, AND ELEVATOR MACHINE
 RMS/EQUIPMENT AREAS.
 PLEASE ADJUST HOUSE PANELS AS NEEDED.
  
 10) NOTE: NO, PLEASE SEE NO INFORMATION WAS LOCATED ON
 RISER SHEETS. PLEASE SEE NO INFORMATION WAS SHOWN ON FP
 FOR THE FIRE PUMP, SIZE, FUEL CONSUMPTION, TIME OF
 OPERATION UNDER THE AMOUNT OF FUEL ETC. PLEASE SEE THE
 SPECS/CUT SHEETS SUBMITTED CONTAIN MULTIPLE UNITS AND
 NO REVIEW FOR CODE COMPLIANCE OF THE UNIT FOR EACH
 BUILDING BASED ON THE NUMEROUS PUMPS SUBMITTED. PLEASE
 ALSO SEE MISSING FIRE PUMP CONTROLLER SPECS. PLEASE
 ALSO SEE MISSING THE RELEVANT CODES ON FP SHEETS.
 PLEASE KNOW BASED ON THE PLANS SUBMITTED AND SPEC/CUT
 SHEETS SUBMITTED, REVIEW FOR COMPLIANCE CAN NOT BE DONE
 AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE ELECTRICAL RISER SHOULD "NOTE" FIRE PUMP
 AS DIESEL AS NOTED ON FP SHEETS.
 PLEASE SUBMIT ALL MANUFACTURES SPEC/CUT SHEETS FOR FIRE
 PUMP CONTROLLER AS REVIEW FOR CODE COMPLIANCE UNDER
 2003 NFPA-20 IS REQUIRED.
 PLEASE ALSO SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS
 FOR FUEL TANK.
 PLEASE SEE NFPA-20 9.6.2.2 AS THE FUEL CAPACITY IS
 REQUIRED TO BE SIZED BASE ON THE 100% RATED LOAD FOR A
 MIN OF 8HRS, OR TIME SO DETERMINED BY THE FIRE
 MARSHAL'S OFFICE DEPENDING ON OCCUPANCY.
 FUEL SYSTEMS WILL BE UNDER OTHER TRADE REVIEW(S). (FIRE
 AND MECH).
  
 11) NOTE: NO, RESPONSE MENTIONS THIS WAS DONE, HOWEVER
 PLEASE SEE UNIT PANEL SCHEDULES AND HOUSE PANEL
 SCHEDULE DOES NOT CONTAIN AND CONDUCTOR SIZES. PLEASE
 KNOW BASED ON COMMENTS ABOVE WITH RESPECT TO AREA
 DESIGNATIONS, CIRCUITING MISSING ON PLANS, REVIEW OF
 THIS CAN NOT BE DONE AT THIS TIME.408.4 , FBC 104.1.2
 ADMINSECTION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INCLUDE ALL MINIMUM CONDUCTOR SIZES ON ALL
 PANELS, UNITS AND HOUSE PANELS. REVIEW FOR THESE ITEMS
 OF CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME.
 310.16, 240.4,215.5
  
 12) NOTE:NO, AS CIRCUITING FOR THIS BUILDING IS NOT
 COMPLETE AT THIS TIME, THE OVER CURRENT PROTECTIVE
 DEVICES CAN NOT BE VERIFIED AT THIS TIME. THIS COMMENT
 WAS MAINLY FOR THE OCP DEVICES WHICH WERE BEING SHOWN
 ON BUILDING #1'S PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE GARAGE/HOUSE LIGHTING BEING INDICATED ON 30A
 AND 50A CIRCUITS.
 PLEASE SEE CODE DOES LIMIT THE OCP FOR UNIT FIXTURES
 FOR PROTECTION OF FIXTURES ON A BRANCH CIRCUIT. PLEASE
 ADJUST CIRCUITING AS NEEDED.
 PLEASE ALSO SEE A FIXTURE SCHEDULE CONTAINING WATTAGES,
 VOLTAGES ETC WAS NOT SUBMITTED.
 PLEASE VERIFY IF THESE UNIT FIXTURES ARE RATED TO HAVE
 OCP AT ABOVE MENTIONED.
 240.4, 310.16 ETC
  
 13) NOTE: OK, HOWEVER SEE NOTES.
  
 14) NOTE:NO/OK, PLEASE SEE PART OF THIS COMMENT SEEMS
 TO HAVE BEEN ADDRESSED, HOWEVER PLEASE SEE NOTES ON
 RISER AND RISER NOTES WHICH STILL DO NOT CORRELATE.
 PLEASE SEE SEVERAL NOTE #1'S, YET ON RISER NOTES NOT
 ALL OF THESE NOTE #1'S CAN POSSIBLY APPLY. PLEASE
 ADJUST ALL NOTE SON RISER AND NOTES NOTED AS RISER
 NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 , PLEASE SEE PLEASE SEE MAX OCP TO BE SIZED FOR
 PANELS/EQUIPMENT BEING FED BY SAID OCP.
 PLEASE SEE MANY UNIT PANELS ARE SHOWN AS 100A MLO, WITH
 125A OCP AS LISTED ON RISER ETC.
 PLEASE ALSO SEE RISER NOTE #4 WHICH INDICATES 125A
 2-POLE ETC, HOWEVER PLEASE SEE RISER AS THIS NOTE #4
 COULD NOT BE LOCATED. (APPEARS TO BE MISPRINTED FOR
 "NOTE#7" ON RISER) 240.4,408,310.16,215.5 ETC.
  
 15) NOTE: N/A, NOT PART OF THESE PLANS FOR THIS
 BUILDING. SEE NEW NOTES.
  
 16) NOTE: N/A, NOT PART OF THESE PLANS FOR THIS
 BUILDING. SEE NEW NOTES.
  
 17) NOTE: N/A, NOT PART OF THESE PLANS FOR THIS
 BUILDING. SEE NEW NOTES.
  
 18) NOTE: NO/OK, SOME SHEETS SHOW NOTE, HOWEVER NOT ALL
 FOR UNITS. CIRCUITING IS NOT YET COMPLETE TO REVIEW
 THESE FOR CODE COMPLIANCE. PLEASE LABEL ALL CIRCUITS ON
 PANEL SCHEDULE WHICH CONTAIN AFCI PROTECTION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THESE SHEETS ALSO REFERENCE "ARC FAULT"
 PROTECTION FROM THE 1999 NEC, WHICH ONLY REQUIRED
 PROTECTION OF RECEPTS.
 PLEASE SEE THE 2002 NEC WHICH REQUIRES PROTECTION FOR
 ALL "OUTLETS" IN BEDRMS. THIS IS INCLUSIVE OF RECEPTS,
 LTS, FANS, SMOKE DETECTORS ETC. PLEASE SEE NOTE ON UNIT
 PLANS AND ADJUST.
  
 19) NOTE:THIS IS UNCLEAR AT THIS TIME, AS PERMIT
 APPLICATION FOR BUILDING #3 INDICATES 450 UNITS, YET
 METER CALCULATIONS CONTAINS NOTE OF 40 METERS FOR EACH
 METER CENTER. PLEASE CORRELATE PLANS, PERMIT
 APPLICATIONS AND ADJUST PLANS AS NEEDED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE LOADS, UNITS, PANELS, AND
 BUILDING/METER LOAD CALCULATIONS:
 A) PLEASE SEE PANEL SCHEDULE/LOAD CALCULATIONS FOR UNIT
 "B-3" SHOWN ON
 16.26, HOWEVER THIS UNIT TYPE OR LOADS COULD NOT BE
 LOCATED ON BLDG LOAD CALCULATIONS ON 16.25?
 B) PLEASE ALSO SEE THE SAME COMMENT ABOVE FOR UNIT
 "C-2" WHICH IS ALSO SHOWN ON
 16.26 BUT NOT IN CALCS ON 16.25??
 ** PLEASE ADJUST ALL AS NEEDED.
  
 20) NOTE: OK, HOWEVER STILL NOT ADDED TO RISER, ONLY
 SHOWN IN GROUNDING DETAIL. PLEASE EXPLAIN RATIONAL OF
 TWO GROUNDING ELECTRODE SYSTEMS SHOWN?
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INCLUDE THE REQUIRED FOOTER STEEL ON THE
 GROUNDING ELECTRODE RISER DETAIL. PLEASE ALSO SHOW ON
 RISER.
 250.50.
  
 21) NOTE: NO, PREVIOUS NOTE REQUESTED A NOTE/DETAIL
 WHICH WOULD ACTUALLY PROVIDE A LITTLE MORE INFORMATION
 FOR THIS REQUIREMENT. PLEASE EXPAND ON NOTE.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE PROVIDE A DETAIL/NOTE FOR ALL RACEWAY SEALS AS
 REQUIRED PER
 230.8
  
 22) NOTE: N/A.
  
 23) NOTE: N/A.
  
 24) NOTE: N/A
  
 25) NOTE: OK.
  
 26) NOTE: OK.
  
 27) NOTE: OK.
  
 28) NOTE: NO, PLEASE SEE THE 2001 FBC 905.2 WHICH DOES
 NOT MENTION THE EXCEPTION AS PERMITTED BY NFPA-72. THE
 MORE RESTRICTIVE SHALL APPLY. PLEASE SEE NEW NOTES FOR
 THESE DEVICES AND CIRCUITING.
  
 ** PREVIOUS REVIEW NOTE **
 SMOKE DETECTORS ARE REQUIRED INSIDE AND OUTSIDE ALL
 SLEEPING ROOMS.
 PLEASE SEE 2002 NFPA-72 11.5.3.1
 PLEASE ADJUST NOTE FOR SD'S ON PLANS AS
 SD'S ARE REQUIRED 3' FROM BATH/KITCHEN DOORS, 3' FROM
 SUPPLY AIR DIFFUSERS, 5' FROM R/A GRILLES AND 20' FROM
 KITCHEN COOKING APPLIANCES. W/ EXCEPTIONS FOR DISTANCES
 FROM COOKING APPLIANCES. (PHOTO-ELECTRIC AND RESETTING
 TYPE)
 ** PLEASE SEE PREVIOUS NOTES WITH RESPECT TO ARC FAULT
 PROTECTION OF SD'S AND CIRCUITING.
  
 29) NOTE: N/A PER THIS BUILDING REVIEW.
  
 30) NOTE: NO, AS CIRCUITING IS NOT YET COMPLETE FOR ALL
 COMMON AREAS THIS CAN NOT BE VERIFIED.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE 700.12E FOR CIRCUITING OF ALL EM/EXT LTS,
 WHICH REQUIRES THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT, SHALL BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCHES.
 THIS IS NOTED ON SOME SHEETS, HOWEVER CIRCUITING FOR
 THESE IS NOT SHOWN.
 215.5
  
 31) NOTE: OK.
  
 32) NOTE:NO, PLEASE SE SOME UNITS ARE STILL MISSING
 GFI RECEPTS TO SERVE KITCHEN COUNTER SPACE AS
 REQUIRED.
 UNIT(S) A 1, A-2 ETC. PLEASE GO THROUGH ALL.
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SEE 210.52C1-C5 FOR REQUIRED GFI RECEPTS ALONG
 KITCHEN COUNTER SPACE. PLEASE SEE SOME ARE SHOWN ON
 WHAT APPEARS TO BE A WALL ON THE OTHER SIDE OF THE
 COUNTER SPACE.
 PLEASE SEE B-2, B-4ETC.
 PLEASE SEE OTHER WHICH ARE REQUIRED TO BE WITHIN 2' OF
 THE END OF THE COUNTER SPACE/FROM SINK EDGE ETC. PLEASE
 SEE THESE AREAS REDLINED ON SHEETS.
  
 33) NOTE:NO, PLEASE SEE RESPONSE MENTIONS THIS IS FOR
 SECURITY AND IT IS NOT A PLUG-IN TYPE TRANSFORMER. IF
 THIS IS NOT A PLU-IN TYPE, PLEASE INDICATE ON PLANS
 WHAT TYPE IT IS AND/OR WILL BE. PLEASESUBMIT OR
 RELOCATE THE RECEPTACLES LOCATED ABOVE CLOTHES CLOSET
 SHELVING OR IN THE NEAR VICINITY AS PREVIOUSLY STATED
 THIS AHJ HAS SEEN TOO MANY INSTANCE WHERE FIRES HAVE
 STARTED BASED ON SOME TYPES OF THESE UNITS AND IN THE
 INTEREST OF LIFE SAFETY AND PROPERTY DAMAGE, THESE WILL
 NOT BE PERMITTED AS SHOWN IN SOME UNITS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE WHAT APPEARS TO BE A RECEPT LOCATED IN THE
 CLOTHES CLOSET FOR PERHAPS A LV PLUG-IN TYPE
 TRANSFORMER?
 PLEASE KNOW, THE ONLY LOCATION A RECEPT IS PERMITTED IN
 A CLOTHES CLOSET FOR THIS PURPOSE, MUST BE LOCATED
 DIRECTLY ABOVE DOOR AWAY FROM COMBUSTIBLES.
 MANY PLUG-IN TYPE TRANSFORMERS BECOME VERY HOT AND
 HAVE MELTED OR CAUSED FIRES IN THIS JURISDICTION.
 PLEASE KNOW, MANY ITEMS IN A CLOTHES CLOSET ARE AN
 ACCELERANT.
 THESE RECEPTS MAY BE MOVED TO UTILITY RM IF SO
 DESIRED.
 110.26, 240.24, 90.4 ETC
  
 34) NOTE: OK.
  
 35) NOTE: OK.
  
 ** NEW NOTES FOR THIS REVIEW **
  
 1) NOTE: PLEASE CORRELATE LAYOUT OF THE BUILDING FOR
 ALL ROOMS AND AREAS. PLEASE SEE THE ELECTRICAL PLANS DO
 NOT CORRELATE WITH THE ARCHITECTURAL SHEETS AND THE
 FIRE SPRINKLER SHEETS ALSO HAVE SOME AREAS WHICH DO NOT
 CORRELATE WITH EITHER. PLEASE SEE FOR INSTANCE THE FIRE
 PUMP ROOM LAYOUT.
  
 2) NOTE: PLEASE CORRELATE HOUSE PANEL DESIGNATION ON
 PLANS WITH THE ACTUAL HOUSE PANEL DESIGNATION ON PANEL
 SCHEDULE.
 408.4.
  
 3) NOTE: PLEASE SEE THE THRESHOLD INSPECTION PLANS
 SUBMITTED ALL CONTAIN A RAISED SEAL OVER A PHOTO-COPIED
 SIGNATURE FROM THE ENGINEER. PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA STATUTES
 471.025 AS AN ORIGINAL SIGNATURE IS REQUIRED. PLEASE
 KNOW THESE MAY BE RETAINED BY THIS OFFICE FOR POSSIBLE
 REVIEW FROM THEFLORIDA BOARD OF PROFESSIONAL
 ENGINEERS. IF THERE ARE ANY QUESTIONS ON THIS PLEASE
 CONTACTTHIS OFFICE ORTHE BOARD.
 **THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE.
  
 4) NOTE: PLEASE SEE NFPA-72 DEFINITIONS FOR SMOKE
 DEVICES. IF THESE ARE INDEED (SD) FOR SMOKE DETECTORS
 THEN THEY WOULD DETECT AND CAUSE AN ALARM TO HORN/SIREN
 DEVICE OF SOME TYPE. PLEASE SEE PLANS CALL FOR THESE AS
 120V UNITS, WHICH IF (SA) SMOKE ALARMS WHICH WOULD
 DETECT AND SOUND, THEN THE DESIGNATIONS NEED TO BE
 ADJUSTED ALONE WITH ALL NOTES WHICH CURRENTLY STATE
 SMOKE DETECTORS. PLEASE KNOW THIS WAS NOT A COMMENT ON
 THE PREVIOUS REVIEW, HOWEVER AS INFORMATION WAS GIVEN
 FROM NFPA DIRECTLY, PLANS MUST CONTAIN THE CORRECT
 DESIGNATIONS.
  
 5) NOTE: PLEASE SEE THE BASE FA SYSTEM SHALL BE SHOWN
 AND ALL HORN/STROBE DEVICES SHALL STATE THE MINIMUM
 LEVELS AS REQUIRED PER FBC 11-4.28.1, .2, AND .3(4).
 THIS WAS NOT PART OF THE ELECTRICAL REVIEWERS REVIEW
 WHEN PLANS WERE SUBMITTED PREVIOUSLY HOWEVER THIS HAS
 NOW BECOME PART OF THE ELECTRICAL REVIEWERS REVIEW.
 PLEASE SHOW.
  
 6) NOTE: PLEASE CLARIFY STAIRS SHOWN ON SOME UNITS.
 PLEASE SEE MISSING WHAT WOULD BE EGRESS LIGHTING AND
 CONTROLS IF INSIDE UNIT AND/OR OUTSIDE UNIT. PLEASE SEE
 NEC 210.70, LS 101 7.8, (7.9 WHERE APPLICABLE).
  
 7) NOTE: PLEASE SEE SEVERAL HOUSE CIRCUITS AS NOTED
 ABOVE WITH RESPECT TO CORRELATION OF CIRCUITING SEEM TO
 BE INDICATE ON THESE PLANS TO PANELS WHICH WOULD BE ON
 OTHER BUILDINGS? PLEASE SEE MISSING TRASH COMPACTOR AS
 ONE ITEM ALONE.
 240.4, 310.16, 408.4, ETC
  
 8) NOTE: PLEASE SEE NOTES ABOVE ON PREVIOUS REVIEW AND
 SECOND REVIEW NOTES WITH RESPECT TO ROOM/AREA
 DESIGNATIONS. PLEASE SEE 210.52B1, 210.11C1 AND 220.16
 FOR DINING ROOMS, DINING AREAS, BREAKFAST AREAS,
 KITCHEN AREAS AND THE LIKE. PLEASE SEE THAT SOME
 RECEPTS ARE BEING SHOWN IN AREAS WHICH WOULD APPEAR TO
 BE AREAS OF THE LIKE AS REFERENCED ABOVE, HOWEVER SOME
 OF THESE RECEPTS ARE BEING SHOWN ON LIGHTING CIRCUITS
 OF 15A'S ETC.
 PLEASE ADJUST PLANS FOR PREVIOUS NOTE AND THIS NOTE.
  
 9) NOTE: PLEASE SEE SHEET FOR ELECTRICAL FOR 3RD AND
 4TH FLOORS WHICH ARE SHEETS LABELED AS AP P16.06 FOR
 PLUMBING. PLEASE CORRECT FBC 104.2.1.2
  
 10) NOTE: PLEASE PROVIDE NOTE ON FIRST FLOOR MAIN
 ELECTRICAL ROOM PLANS WHICH WILL REQUIRE DOOR TO
 CONTAIN PANIC HARDWARE.
 110.26/90.4
  
 11) NOTE: PLEASE SEE THE VOLTAGE DROP FOR 30A CU'S, AT
 THIS TIME CAN NOT BE VERIFIED. PLEASE SEE SOME UNITS
 INDICATE #10 ALREADY YET THESE WILL BE OVER 75FT AND
 THERE IS NO NOTE FOR THESE UNITS TO UPGRADE TO #8 OR ?
 PLEASE ADJUST AND PROVIDE ADDITIONAL INFORMATION. FBC
 104.2.1.2, NEC 310.16, 240.4 ETC.
  
 12) NOTE: PLEASE SEE NOTES ABOVE WHICH REQUESTS FOR THE
 RISER NOTES TO CORRELATE WITH THE DESIGNATIONS ON
 RISER. PLEASE SEE NOTE #1.
 104.2.1.2 FBC ADMIN SECTION.
  
 13) NOTE: PLEASE PROVIDE A DETAIL FOR THE ROOF TOP
 DISCONNECT AS BEING NOTED AND HOW THIS WILL BE MOUNTED?
 (NOT TO UNIT)
 440.11. THIS CAN BE A TYPICAL DETAIL.
  
 14) NOTE: PLEASE SEE ATTACHED COPY OF FLORIDA STATUTES
 553.80(2)(B) WITH RESPECT TO REPEAT CODE COMPLIANCE
 COMMENTS. THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
 15) NOTE: PLEASE SEE MISSING FIRST FLOORELECTRICAL
 FOR UNITS WITH STAIRS. 210.70,210.52 ETC
  
 *** PLEASE KNOW THAT THERE MAY BE NEW COMMENTS ON THE
 NEXT REVIEW DUE TO INFORMATION NOT SUBMITTED OR
 COORDINATION OF PLANS/INFORMATION SUBMITTED FOR REVIEW
  
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY HAVE AN AFFECT ON ELECTRICAL PLANS.
  
 ** PLEASE KNOW, A TYPE WRITTEN RESPONSE LETTER FROM
 DESIGN PROFESSIONAL(S) FOR EACH COMMENT ON HOW/WHERE
 CORRECTIONS ARE MADE OR IF COMMENTS ON REVIEW WILL HELP
 IN EXPEDITING THE PLAN REVIEW PROCESS. THIS WAS DONE,
 AND SHOULD BE DONE FOR THIS REVIEW AS WELL.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-26 Cont ID  
Sent By dpalmer Date 2005-12-26 Time 13:21 Rev Time 0.00
Received By dpalmer Date 2005-12-25 Time 17:53 Sent To  
Notes
2005-12-26 00:00:00************ UNSAT ************
  
 COURTNEY LAKES
 N. CONGRESS.
  
  
 1)NOTE: PLEASE SUBMIT COMPLETED PLANS
 BOUND TOGETHER IN APPROPRIATE FASHION.
 PLEASE SEE ALL SHEETS WERE SUBMITTED
 LOOSELY AND NOT IN BOUND STES.
  
 2)NOTE: PLEASE BE SURE ALL PLANS ARE
 SIGNED, DATED AND SEALED BY ALL DESIGN PROFESSIONALS AS
 REQUIRED UDNER FS
 481.221 AND 471.025.
 (PLEASE SEE A-SHEETS, ONLY SIGNED).
  
 3)NOTE: PLEASE BE SURE TO CORRECT THE
 CURRENT NEC/ NFPA-70 IN EFFECT.
 PLEASE KNOW, AS OF JULY 1ST, 2003 THE
 STATE OF FLORIDA ADOPTED THE 2002
 NFPA-70 (NEC). PLANS REFERENCE 1999.
 PLEASE SEE SOME ELECTRICAL COMMENTS
 WHICH WILL AFFECT THIS.
 PLEASE SEE NEXT COMMENT WITH RESPECT TO
 PERMITS APPLIED FOR UNDER THE 2001 FBC
 BEFORE OCT 1ST, 2005 AND PERMITS ON OCT
 1ST, 2005.
  
 4)NOTE: PLEASESEE THAT THREE SEPARATE
 PERMIT APPLICATIONS WERE SUBMITTED AND
 NOTED FOR BLDG'S 1,2 AND 3, HOWEVER
 PLANS SHOWS BLDG TYPES 1.2&3 STRUCTUALLY
 ONLY ONE BUILDING.
 PLEASE SEE PERMIT APPLICATIONS ALL
 REFLECT THIS ONE 450 UNIT BLDG.
 PLEASE SEE THIS CONTRADICTS THE "PHASING
 PLAN" SUBMITTED ON A1.04 AS THIS PHASING
 PLAN INDICATES WORK ON BLDGS 4 AND 5
 BEFORE COMPLETION OF BLDGS 1, 2 AND 3.
 PLEASE SEE COMMENTS FROM BLDG, FIRE AND
 OTHER REVIEWERS, ASCERTIFICATES OF
 OCCUPANCY(CO'S) FOR THESE CAN NOT BE
 GRANTED IN THIS ORDER AS THE FIRST
 "STRUCTURED BLDG"(1,2&3) WOULD NOT BE
 COMPLETE.
 PLEASE ALSO SEE COMMENTS WITH RESPECT TO "TEMPORARY
 CO'S" WHICH MAY ALLOW
 OCCUPANCY OF SOME PARTS OF BLDGS,
 HOWEVER THESE TCO'S ARE ONLY GOOD FOR 30
 DAYS AND A MAX OF 3 TCO'S MAY ONLY BE
 GRANTED BY THE BLDG OFFICAL.
 PLEASE KNOW, IN ANY CASE, ALL LIFE
 SAFTEY, FIRE PROTECTION SYSTEMS, FIRE
 SPRINKLERS (FULLY CHARGED),ELECTRICAL
 SYSTEMS ETC SHALL BE COMPLETE IN THE
 BASE BLDG FOR BLDG TYPE 1, 2& 3 BEFORE A
 TCO,/CO CAN BE GRANTED.
 *************************************
 ALSO NOTED THAT BLDG'S TYPE 4 AND 5
 WHICH ARE SEPARATE STRUCTURES AND
 INDEPENDANT OF EACH OTHER WERE NOT
 SUBMITTED FOR PERMIT.
 PLEASE SEE ALL PERMITS SUBMITTED AFTER
 OCT. 1ST, 2005 SHALL FALL UNDER THE
 2004 FBC, WITH ALL OTHER CODES ADOPTED
 BY SAID CODE AND STATE OF FLORIDA.
 ************************************
 PLEASE SEE COMMENTS FROM OTHER
 REVIEWER(S) WITH RESPECT TO THIS.
 *************************************
 PLEASE ALSO SEE NEXT COMMENT WITH
 RESPECT TO THE MAINS, SERVICES, AND
 METER RMS AS PROPOSED.
 ** SEE ALL NOTES FROM ALL REVIEWERS
 WHICH MAY ALSO AFFECT THIS SEQUENCE OF CONSTUCTION.
  
 5)NOTE: PLEASE SEE METER RMS AS SHOWN
 WOULD BE OK, HOWEVER STRUCTURE AS SHOWN
 FOR BLDG TYPE 1,2 AND 3 (ONE BLDG) WOULD
 REQUIRE MAINS TO BE GROUPED.
 90.4,230.2,230.70,230.72,230.76,230.79
 ETC.
 BLDG'S LARGE ENOUGH TO CONTAIN MORE THAN
 ONE SERVICE AT SEPARATE LOCATIONS SHALL
 BE DIVIDED INTO SECTIONS AND SHALL HAVE
 THOSE SECTIONS DIVIDED BY "FIRE WALLS".
 PLEASE SEE FBC FOR DEFINITION OF "FIRE
 WALLS".
 PLEASE KNOW, STRUCTURE CONSTRUCTED AS
 SHOWN IN PLANS, WOULD REQUIRE MAIN
 DISCONNECTS GROUPED, WHICH WOULD THEN
 IN-TURN FEED METER ROOMS.
 OTHER DESIGN CHANGES IN THE "ONE BLDG"
 MAY ALSO PERMIT INDIVIDUAL SERVICES.
 PLEASE SEE BLDG TYPE #4 AND #5 ARE SHOWN
 AS SEPARATE BLDGS WITH STAND ALONE
 SERVICES AND ALL MAINS ARE GROUPED.
 PLEASE KNOW THAT BLDGS 4 AND 5 WILL HAVE
 REVIEWS DONE UNDER THOSE PERMIT
 APPLICATIONS.
 ** PLEASE SEE SOME OF THESE COMMENTS
 WOULD ALSO APPLY.
  
 6)NOTE: PLEASE COMPLETE ALL CIRCUITING
 ON PLANS IN ORDER TO REVIEW CODE
 COMPLIANCEFOR AREAS OF UNITS AND
 COMMON AREAS.
  
 7)NOTE: PLEASE PROVIDE ROOM AND AREA
 DESIGNATIONS ON PLANS, INCLUSIVE OF ALL
 UNITS AND COMMON AREAS.
 REVIEW FOR SOME CODE COMPLIANCE ITEMS
 CAN NOT BE DONE AT THIS TIME.
  
 8)NOTE: PLEASE PROVIDE COMPLETE
 PHOTOMETRICS FOR ALL COMMON AREAS,
 GARAGE AREA,COMMON AREA CORRIDORS,
 STAIR TOWERS ETC.
 PLEASE SEE 2003 NFPA-101 7.8.1.3 AND
 7.9.2 WHICH REQUIRES A MIN OF 10FT
 CANDLES FOR STAIR TOWERS UNDER NORMAL
 OPERATION AS WALK SURFACE AND A MIN OF
 1FT CANDLE AT WALK SURFACE UNDER
 EMERGENCY CONDTIONS. PLEASE ALSO SEE
 OTHER WALK AREAS, GARAGE, CORRIDORS ETC
 AND THE MIN OF 1FT CANDLE.
 **PLEASE SEE PALM BEACH COUNTY SECURITY
 CODE ORDIANCE WITH RESPECT TO MIN DESIGN
 OF PARKING LOT LIGHTING LEVELS UNDER
 NORMAL CONDITIONS. (ONLY NOTED FOR
 DESIGN)NOT REQUIRED. PLEASE SEE ANY
 REQUIREMENTS FROM INS CARRIER WHICH
 REQUIE A MIN LEVEL OF LIGHTING.
 ** PLEASE SEE PHOTOMETRICS OR SITE PLAN
 WAS NOT SUBMITTED FOR PROPOSED POOL
 AREA. THE POOL STRUCTURE IS REQUIRED TO
 BE UNDER A SEPARATE PERMIT. PLEASE KNOW,
 THE PHOTOMETRICS FOR POOL AREA WILL BE
 REQUIRED AND WILL ALSO BE REQUIRED TO BE
 REVIEWED AND STAMPED BY THE PALM BEACH
 COUNTY HEALTH DEPT FOR ANY PROPOSED
 NIGHT-TIME SWIMMING.
  
 7)NOTE: PLEASE SEE NO "ELECTRICAL
 SITE-PLAN" WAS SUBMITTED FOR ANY SITE
 LIGHTING, LANDSCAPE LIGHTING ETC.
 PLEASE KNOW, IF NOT SUBMITTED UNDER THIS
 PERMIT AND VALUES ADJUSTED ACCORDINGLY,
 SSEPARATE PERMIT , PLANS AND FEES WILL
 BE REQUIRED FOR ALL SITE LIGHTING,
 LANDSCAPE LIGHTING WORK.
 ** ALSO NOTE: IN THAT COMPLETE WIND
 LOADING CALCULATIONS FOR LT POLES
 INCLUSIVE FO THE ATTACHMENT OF LT
 FIXTURES WILL BE REQUIRED TO BE
 SUBMITTED WITH PLANS AND PERMIT
 APPLICATION FOR REVIEW.
  
 8)NOTE: PLEASE INCLUDE AN EMERGENCY
 BATTERY BACK UP LT OF SOME SORT IN ALL
 ELECTRICAL ROOMS, FIRE PUMP ROOM,
 ELEVATOR MACHINE RMS. SOME ARE SHOWN,
 BUT NOT ALL.
 7.8,7.9,700.16 ETC
  
 9)NOTE: PLEASE SEE 620.23, AND 620.24
 FOR REQUIRED DEDICATED BRANCH CIRCUITS
 FOR ELEVATOR PITS, AND ELEVATOR MACHINE RMS/EQUIPMENT
 AREAS.
 PLEASE ADJUST HOUSE PANELS AS NEEDED.
  
 10)NOTE: PLEASE SEE ELECTRICAL RISER
 SHOULD "NOTE" FIRE PUMP AS DIESEL AS
 NOTED ON FP SHEETS.
 PLEASE SUBMIT ALL MANUAFCTURES SPEC/CUT
 SHEETS FOR FIRE PUMP CONTROLLER AS
 REVIEW FOR CODE COMPLIANCE UNDER 2002
 NFPA-20 IS REQUIRED.
 PLEASE ALSO SUBMIT ALL MANUFACTURES
 SPECS/CUT SHEETS FOR FUEL TANK.
 PLEASE SEE NFPA-20 9.6.2.2 AS THE FUEL
 CAPACITY IS REQUIRED TO BE SIZED BASE ON
 THE 100% RATED LOAD FOR A MIN OF 8HRS,
 OT TIME SO DETERMIND BY THE FIRE
 MARSHAL'S OFFICE DEPENDING ON OCCUPANCY.
 FUEL SYSTEMS WILL BE UNDER OTHER TRADE
 REVIEW(S). (FIRE AND MECH).
  
 11)NOTE: PLEASE INCLUDE ALL MIN
 CONDUCTOR SIZES ON ALL PANELS,UNITS AND
 HOUSE PANELS. REVIEW FOR THESE ITEMS OF
 CODE COMPLIANCE CAN NOT BE DONE AT THIS
 TIME. 310.16,240.4,215.5
  
 12)NOTE: PLEASE SEE GARAGE/HOUSE
 LIGHTING BEING INDICATED ON 30A AND 50A
 CIRCUITS.
 PLEASE SEE CODE DOES LIMIT THE OCP FOR
 UNIT FIXTURES FOR PROTECTION OF FIXTURES
 ON A BRANCH CIRCUIT.
 PLEASE ADJUST CIRCUITING AS NEEDED.
 PLEASE ALSO SEE A FIXTURE SCHEDULE
 CONTAINING WATTAGES, VOLTAGES ETC WAS
 NOT SUBMITTED.
 PLEASE VERIFY IF THESE UNIT FIXTURES ARE
 RATED TO HAVE OCP AT ABOVE MENTIONED.
 240.4, 310.16 ETC
  
 13)NOTE: PLEASE CORRELATE ALL OCP
 DEVICES FOR UNITS AND FEEDERS BEING
 LISTED IN "RISER NOTES".
 PLEASE SEE SOME FEEDERS SHOWN AS #4'S ON
 125A BREAKER?
 SEE 310.16,240.4
 PLEASE SEE OCP FOR ALL UNITS IS LISTED
 AS 125A'S.
 SEE NEXT COMMENT.
  
 14)NOTE: PLEASE SEE MAX OCP TO BE SIZED
 FOR PANELS/EQUIPMNET BEING FED BY SAID
 OCP.
 PLEASE SEE MANY UNIT PANELS ARE SHOWN AS
 100A MLO, WITH 125A OCP AS LISTED ON
 RISER ETC.
 PLEASE ALSO SEE RISER NOTE #4 WHICH
 INDICATES 125A 2-POLE ETC, HOWEVER
 PLEASE SEE RISER AS THIS NOTE #4 COULD
 NOT BE LOCATED. (APPEARS TO BE
 MISPRINTED FOR "NOTE#7" ON RISER)
 240.4,408,310.16,215.5 ETC.
  
 15)NOTE: PLEASE SEE 16.26 AND 16.27
 WHICH CONTAIN THE SAME EXACT "HOUSE
 PANELS" ?? H1, H1A , H2, AND H2A.
 PLEASE SEE SHEET 16.27 MAY BE DELETED IF
 PANELSCHEDULES FOR "CA" AND"CB" ARE
 MOVED TO 16.26.
  
 16)NOTE: PLEASE CORRELATE LOADS SHOWN
 FOR H1A WITH LOAD SHOWN ON H1.
 THIS DOES NOT MATCH.
  
 17)NOTE: PLEASE CORRELATE LOADS ON PANEL
 H2A WITH LOADS SHOWN ON H2>
 THESE ALSO DO NOT MATCH.
  
 18)NOTE: PLEASE SEE THESE SHEETS ALSO
 REFERENCE "ARC FAULT" PROTECTION FROM
 THE 1999 NEC, WHICH ONLY REQUIRED
 PROTECTION OF RECEPTS.
 PLEASE SEE 2002 NEC WHICH REQUIRES
 PROTECTION FOR ALL "OUTLETS" IN BEDRMS.
 THIS IS INCLUSIVE OF RECEPTS, LTS, FANS,
 SMOKE DETECTORS ETC.
 PLEASE SEE NOTE ON UNIT PLANS AND
 ADJUST.
  
 19)NOTE: PLEASE CORRELATE LOADS , UNITS,
 PANELS, AND BUILDING/METER LOAD
 CALCULATIONS:
 A) PLEASE SEE PANEL SCHEDULE/LOAD
 CALCULATIONS FOR UNIT "B-3" SHOWN ON
 16.26, HOWEVER THIS UNIT TYPE OR LOADS
 COULD NOT BE LOCATED ON BLDG LOAD
 CALCULATIONS ON 16.25?
 B)PLEASE ALSO SEE THE SAME COMMENT ABOVE
 FOR UNIT "C-2" WHICH IS ALSO SHOWN ON
 16.26 BUT NOT IN CALCS ON 16.25??
 ** PLEASE ADJUST ALL AS NEEDED.
  
 20)NOTE: PLEASE INCLUDE THE REQUIRED
 FOOTER STEEL ON THE GROUNDING ELECTRODE
 RISER DETAIL.
 PLEASE ALSO SHOW ON RISER.
 250.50.
  
 21)NOTE: PLEASE PROVIDE A DETAIL/NOTE
 FOR ALL RACEWAY SEALS AS REQUIRED PER
 230.8
  
 22)NOTE: PLEASE SEE RISER WHICH SHOWS A
 POOL PANEL BEING FED FROM PANEL "CA",
 HOWEVER PANEL "CA" , DOES NOT SHOW SUCH
 PANEL.
 215.5
  
 23)NOTE: PLEASE PROVIDE "FUTURE" POOL
 PANEL ON RISER AND PANEL SCHEDULE.
 215.5
  
 24)NOTE: PLEASE SEE RISER NOTE #12 WHICH
 IS SHOWN FOR FEED FROM PANEL "CA" TO
 PANEL "CB". THIS IS SHOWN AS 500MCM'S,
 ALTHOUGH OCP ON CA IS ONLY SHOWN AS
 200A'S? THIS IS PERMITTED, HOWEVER THE
 200A DEVICE MAY NOT ACCEPT 500MCM'S.
 215.5
  
 25)NOTE: PLEASE SEE REDLINED ITEMS ON
 PLANS FOR "EQUIPMENT GROUNDING
 CONDUCTORS" BEING SHOWN BEFORE THE FIRST
 MEANS OF DISCONNECT.
 PLEASE SEE 250.6, 250.24.
 PLEASE SEE HOUSE METER #2, SEE RISER
 NOTE #12 AND #13 SHOWS AN "EQUIPMENT
 GROUNDING" CONDUCTOR WHICH IS
 PARALLELING THE NEUTRAL.
  
 26)NOTE: PLEASE SEE MIN OCP FOR WATER
 HEATERS TO BE SIZED AT 125%.424.13
 PLEASE SEE UNITS CONTAINING 5KW WH @
 208V'S WOULD INCREASE THIS BRKR TO A
 2-P35A. PLEASE ALSO ADJUST ANY AWG PER 310.16,240.4
  
 27)NOTE: PLEASE SEE UNIT LOAD
 CALCULATIONS SHOWS THE LOADS FOR A/C'S
 AFTER THE PERMITTED DERATING, HOWEVER
 PLEASE SHOWLOADS FOR THESE BEFORE
 DERATING.
 PLEASE BE SURE TO CORRELATE WITH LOADS
 FOR COOLING AND HEAT ON MECHANICAL PLAN.
 215.5
  
 28)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 PLEASE SEE 2002 NFPA-72 11.5.3.1
 PLEASE ADJUST NOTE FOR SD'S ON PLANS AS
 SD'S ARE REQUIRED 3' FROM BATH/KTICHEN
 DOORS, 3' FROM SUPPLY AIR DIFFUSERS, 5'
 FROM R/A GRILLES AND 20' FROM KITCHEN
 COOKING APPLIANCES. W/ EXCEPTIONS FOR
 DISTANCES FROM COOKING APPLIANCES.
 (PHOTOELECTRIC AND RESETTING TYPE)
 ** PLEASE SEE PRIVIOUS NOTES WITH
 RESPECT TO ARC FAULT PROTECTION OF SD'S
 AND CIRCUTING.
  
 29)NOTE: PLEASE SEE ALL RECEPTS IN
 CLUBHOUSE KITCHEN PER 210.8B3 WHICH
 REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT RECEPTACLES IN
 NONDWELLING-TYPE KITCHENS
 TO BE GFCI PROTECTED. THIS REQUIREMENT
 APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE,
 WHETHER OR NOT THE RECEPTACLE SERVES
 COUNTERTOP APPLIANCES.
  
 30)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF ALL EM/EXT LTS, WHICH
 REQUIRES THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 THIS IS NOTED ON SOME SHEETS, HOWEVER
 CIRCUITING FOR THESE IS NOT SHOWN.
 215.5
  
 31)NOTE: PLEASE CLARIFY THE "CT" AS
 LABLED ALONG KITCHEN RECEPTS. THIS
 ABBREVIATION COULD NOT BE LOCATED ON
 SYMBOL LEGEND?
  
 32)NOTE: PLEASE SEE 210.52C1-C5 FOR
 REQUIRED GFI RECEPTS ALONG KTICHEN
 COUNTERSPACE. PLEASE SEE SOME ARE SHOWN
 ON WHAT APPEARS TO BE A WALL ON THE
 OTHER SIDE OF THE COUNTERSPACE.
 PLEASE SEE B-2, B-4ETC.
 PLEASE SEE OTHER WHICH ARE REQUIRED TO
 BE WITHIN 2' OF THE END OF THE
 COUNTERSPACE/FROM SINK EDGE ETC.
 PLEASE SEE THESE AREAS REDLINED ON
 SHEETS.
  
 33)NOTE: PLEASE SEE WHAT APPEARS TO BE A
 RECEPT LOCATED IN THE CLOTHES CLOSET FOR
 PERHAPS A LV PLUG-IN TYPE TRANSFORMER?
 PLEASE KNOW, THE ONLY LOCATION A RECEPT
 IS PERMITTED IN A CLOTHES CLOSET FOR
 THIS PURPOSE, MUST BE LOCATED DIRECTLY
 ABOVE DOOR AWAY FROM COMBUSTIBLES.
 MANY PLUG-IN TYPE TRANSFORMERS BECOME
 VERY HOT AND HAVE MELTED OR CAUSED FIRES
 IN THIS JURISTICTION. PLEASE KNOW, MANY
 ITEMS IN A CLOTHES CLOSET ARE AN
 ACCELERANT.
 THESE RECEPTS MAY BE MOVED TO UTILITY RM
 IS SO DESIRED.
 110.26, 240.24, 90.4 ETC
  
 34)NOTE: PLEASE SEE RELDINED PLANS FOR
 ANY RECEPTS WHICH MAY BE REQUIRED PER
 210.52 (A-2). MOST ALL SPACING IS OK.
  
 35)NOTE: PLEASE MAKE NOTE FOR ALL MIN
 FAIR HOUSING ACT REQUIREMENTS FOR DEVICE
 HEIGHTS.
 24 CFR 100.205
  
 ** PLEASE KNOW, SOME REVIEW OF CODE
 COMPLIANT ITEMS MAY NOT BE DONE AT THIS
 TIME DUE TO SOME INFORMATION NOT ON
 PLANS.
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY HAVE AN AFFETC ON
 ELECTRICAL PLANS.
  
 ** PLEASE KNOW, A TYPE WRITTEN RESPONSE
 LETTER FROM DESIGN PROFESSIONL(S) FOR
 EACH COMMENT ON HOW/WHERE CORRECTIONS
 ARE MADE OR IF COMMENTS ON REVIEW WILL
 HELP IN EXPEDITING THE PLAN REVIEW
 PROCESS.
  
 ** PLEASE KNOW THAT A MEETING TO GO OVER
 FIRST COMMENTS FOR DESIGN/PHASING OF
 BLDGWITH ALL REVIEWERS IS SUGGESTED
 BEFORE PERHAPS SUBMITTING PLANS BACK FOR
 REVIEW.
 PLEASE KNOW, ALL REVIEWS AFTER THE 1ST
 FREE "RE-SUB" IS SUBJECT TO A 10% RESUB
 FEE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
2005-12-25 00:00:00ONE ROLL IN ELECTRIC FOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-09-28 Cont ID  
Sent By rchokshi Date 2007-09-28 Time 14:25 Rev Time 0.00
Received By rchokshi Date 2007-09-28 Time 14:25 Sent To  
Notes
2007-09-28 14:25:24****FAILED*****
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON CIVIL DRAWING THE EXACT MAILING
 ADDRESS, BUILDING NAME, OR NUMBER, YOU TALKING ABOUT 3
 PERMITS, PLEASE IDENTIFY EACH BUILDING ON THE DRAWING.
 3.PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 4.PLEASE SHOW FINISH FLOOR ELEVATION ON DRAWING .
 PLEASE EXPLAIN IN DETERMINING FIRST FLOOR ELEVATION,
 PLEASE SHOW IN YOUR CALCULATION THAT YOU CONSIDERED
 CENTER LINE OF ROAD , FLOOD ZONE OF THIS SITE,& 5,10,
 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST
 FLOOR ELEVATION, PLEASE SHOW ALL THESE IN YOUR STORM
 WATER CALS.PLEASE ALSO SHOW ON DRAWINGS THE MAXIMUN
 AND MINIMUM PARKING LOT ELEVATIONS.
  
 5. PLEASE SHOW ON DRAWINGTHE SITE AREA, YOU ARE
 DEVELOPING FOR THIS PROJECT . PLEASE ALSO SHOW TOTAL
 PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT,
 LAKE,SIDEWALK, PARKING,BUILDING AREA ETC. MAKE SURE
 THESE AREAS SHOWN ON DRAWINGS MUST MATCH WITH AND USED
 IN STORM WATER QUALITY CALCULATIONS.
 6. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS.AFTER CONTROL
 STRUCTURE WHERE STORM WATER GOES??
 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
 8. PLEASE RESUBMIT A COPY OF SFWMD PERMIT,, & GEO TECH
 REPORT,STORM WATER CALS MUST BE APPROVED FROM 1000
 45TH STREET ENGINEERING SERVICES.
 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
 10. PLEASE KEEP SEPARATE CIVIL DRAWINGS SO I CAN REVIEW
 QUICK.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2005-10-31 Cont ID  
Sent By mamini Date 2005-10-31 Time 11:18 Rev Time 0.50
Received By mamini Date 2005-10-31 Time 11:18 Sent To  
Notes
2005-10-31 00:00:00FAILED:
  
 1. PLEASE SUBMIT CIVIL PLANS FOR OUR
 REVIEW AND APPROVAL.NOTE THAT CIVIL
 PLANS FOR THIS WERE REVIEWED UNDER OLD
 PERMIT APPLICATIONS # 04021308,04021305,
 04021300 WHICH EXPIRED.COPY OF THE
 REVIEW NOTES INCLUDED FOR YOUR USE.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-11-07 Cont ID  
Sent By mwennerg Date 2007-11-07 Time 15:04 Rev Time 0.00
Received By mwennerg Date 2007-11-07 Time 15:04 Sent To  
Notes
2007-11-07 15:04:55***PROVISO***
  
 COMMENTS HAVE BEEN ADDRESSED FROM THE PREVIOUS REVIEW.
 PLEASE SEE ADDITIONAL COMMENTS:
  
 1) DESIGN CRITERIA REFERS TO NFPA 13 AND SHEET FP 13.02
 REFERS TO NFPA 13R IN SHEET NOTES. PLEASE CORRELATE OR
 EXPLAIN.
  
 2) PLEASE SEE CORRECTION FROM PREVIOUS REVIEW COMMENTS.
 MULTI-FAMILY RESIDENTIAL BUILDINGS TO COMPLY WITH
 COMMERCIAL REQUIREMENTS FOR ADDRESSING. MINIMUM OF 6"
 IN HEIGHT AND 1" IN WIDTH. SEPARATE UNIT CHARACTERS TO
 COMPLY WITH 3" REQUIREMENT.
  
 3) PLANS DON'T SEEM TO ILLUSTRATE ANY POST INDICATING
 VALVE DETAIL. A NOTE DOES REFERENCE PIV TAMPER SWITCHES
 ON SHEET FP 13.10. WHAT MEANS WILL BE PROVIDED WHERE
 THE STATUS OF (1) BUILDING WON'T IMPACT OTHER
 BUILDINGS? PLEASE PROVIDE DETAIL AND ILLUSTRATE ON FP
 SITE PLAN.
  
 4) PLEASE INDICATE IF ANY ELEVATORS WILL MEET
 REQUIREMENTS FOR STRETCHER ACCESSIBILITY.
  
  
 PLANS WILL BE STAMPED WHEN RETURNED AND ADDRESSED FOR
 FIRE COMMENTS IN ADDITION TO OTHER REVIEW NOTES.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-02-27 Cont ID  
Sent By mwennerg Date 2007-02-27 Time 15:53 Rev Time 0.00
Received By mwennerg Date 2007-02-27 Time 15:53 Sent To  
Notes
2007-02-27 15:53:51***DENIED***
  
 IN ORDER TO HELP EXPEDITE THE PLAN REVIEW PROCESS,
 PLEASE SEE THE FOLLOWING:
  
 1) PLEASE REFER TO THE FIRST FIRE REVIEW COMMENTS. MANY
 COMMENTS WERE ANSWERED OR ADDRESSED WITH COMMENT NOTED.
 THIS DOES NOT DEMONSTRATE THAT COMPLIANCE WILL BE MET.
 IT WOULD BE HELPFUL IF THE CHANGE OR ADDED NOTE IS
 CLEARLY SHOWN ON DRAWINGS, AND THE CORRECT SHEET NUMBER
 IS INDICATED. SOME RESPONSES WERE FOUND ON SHEETS THAT
 WERE DIFFERENT FROM WHAT WAS INDICATED IN THE RESPONSE
 LETTER. FOR EXAMPLE, COMMENT #1 INDICATES THAT
 REFERENCE HAS BEEN ADDED TO FP13.17, BUT WAS ACTUALLY
 FOUND ON A 1.02. PLEASE KNOW THAT IT IS UNDERSTOOD THAT
 SOME COMMENTS MAY BE ACKNOWLEDGED, BUT SHOULD BE SHOWN
 ON PLANS TO ELLIMINATE CONFUSION IN THE FUTURE DURING
 THE INSPECTION PROCESS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW(561) 805-6722
 FIRE PREVENTION(561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-12-28 Cont ID  
Sent By mwennerg Date 2005-12-28 Time 14:16 Rev Time 0.00
Received By mwennerg Date 2005-12-28 Time 14:16 Sent To  
Notes
2005-12-28 00:00:00******DENIED******
  
 1) NFPA 101 AND NFPA 1, 2003 EDITION
 SHALL BE REFERENCED.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER SYSTEM
 WHICH SHALL BE UL CERTIFIED FOR CENTRAL
 STATION SERVICE.
  
 3) PLEASE NOTE THAT INTENDED SCOPE OF
 WORK FOR THIS PROJECT IN RELATION TO THE
 PERMIT APPLICATIONS IS CONFUSING.
  
 4) WHENS PLANS ARE RESUBMITTED, PLEASE
 ASSURE THAT ALL SHEETS ARE BOUND
 TOGETHER AND ORGANIZED.
  
 5) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 6) STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 7) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES 3 STORIES OR
 30' IN HEIGHT.
  
 8) IN REGARDS TO PHASING, PLEASE BE
 ADVISED THAT ALL LIFE SAFETY COMPONENTS
 MUST BE INSPECTED, TESTED AND APPROVED
 PRIOR TO OCCUPANCY OF BUILDINGS.
  
 9) PARKING AREAS MUST BE IN COMPLIANCE
 WITH APPLICABLE BUILDING CODES AND NFPA
 88A. MINIMUM TWO HOUR SEPARATION TO
 OTHER PARTS OF BUILDING IS REQUIRED.
  
 10) WET FIRE HYDRANTS TO BE OPERATION
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
  
 11) PLEASE NOTE THAT ALL LIFE SAFETY
 EQUIPMENT, FIRE SPRINKLER AND FIRE ALARM
 AND ALL OTHER BUILDING SERVICES SHALL BE
 SEPARATE IF BUILDINGS MEET THE CRITERIA
 FOR SEPARATE STRUCTURES.
  
 12) ALL ACCESS ROADS SHALL BE AT LEAST
 20' IN CLEAR , UNOBSTRUCTED WIDTH FOR
 EMERGENCY VEHICLES, AND SHALL MEET ALL
 OTHER REQUIREMENTS OF NFPA 1.
  
 13) PLEASE INDICATE ALL LOCATION OF FIRE
 HYDRANTS.
  
 14) NFPA 13, 2002 EDITION SHALL BE
 REFERENCED. SHT. A5.01.
  
 15) LOCKING KNOX BOX CAPS ARE REQUIRED
 ON FIRE DEPARTMENT CONNECTIONS.
  
 16) IN ADDITION TO ELECTRONIC SWITCHES,
 THE DOUBLE CHECK DETECTOR ASSEMBLIES
 SHALL BE SECURED WITH A CHAIN AND LOCK.
  
 17) AS NOTED ON SHT, A5.02, FIRE
 EXTINGUISHERS SHALL BE MOUNTED AT
 DISTANCES TO SATISFY THE 75' TRAVEL
 DISTANCE REQUIREMENT.
  
 18) ALL DOORS SHALL SWING IN THE
 DIRECTION OF TRAVEL WHEN SERVING AREAS
 WITH OCCUPANT LOADS OF GREATER THAN 50.
  
 19) ELEVATORS TO COMPLY WITH ASME A17.1.
  
 20) PENETRATIONS INTO , AND OPENINGS
 THROUGH STAIRWELLS SHALL BE LIMITED TO
 AND IN COMPLIANCE WITH NFPA 101, SECTION
 7.1.3.2.1 (6).
  
 21) PLEASE CLARIFY ALL EXIT DISCHARGING
 FROM STAIRWELLS THAT LEAD DIRECTLY TO
 THE OUTSIDE.
  
 22) SOME ACHITECTUAL DRAWINGS SHOW
 STAIRWELL DOORS, AND OTHERS DON'T.???
  
 23) THIS PERMIT APPLICATION PROCESS
 ILLUSTRATES 3 BUILDINGS AND OTHER
 BUILDINGS, 4&5 ARE SHOWN ON PLANS.
 PLEASE CLARIFY.
  
 24) PLEASE ILLUSTRATE THE TOTAL OCCUPANT
 LOAD FOR THE CLUBHOUSE.
  
 25) IN ADDITION TO THE ALREADY NOTED
 REQUIREMENTS FOR ADDRESSING, PLEASE NOTE
 THAT THE HEIGHT OF THE ADDRESS SHALL BE
 AT LEAST 3" IN HEIGHT FOR RESIDENTIAL
 BUILDINGS.
  
 26) PLEASE REFER TO DOOR SCHEDULE AND
 VERIFY CORRECT AMOUNT OF FIRE RATED
 DOORS. DOORS SERVINGS AREAS WITH
 OCCUPANT LOADS GREATER THAN 100 SHALL
 HAVE PANIC HARDWARE.
  
 27) FIRE PROTECTION SITE PLAN DOESN'T
 APPEAR COMPLETE ON SHT FP13.01.
  
 28) FIRE DEPARTMENT VALVES SHALL BE 2
 1/2" TO 1 1/2" REDUCER WITH CHAINS.
  
 29) MORE INFORMATION AND MANUFACTURER
 SPEC SHEETS REQUIRED FOR FIRE PUMP AND
 ASSOCIATED EQUIPMENT.
  
 30) FIRE PROTECTION SHEETS DON'T SHOW
 ANY FIRE SPRINKLER SYSTEM. ???? FIRE
 SPRINKLER DESIGN AND LAY OUT MUST BE
 ILLUSTRATED.
  
 31) IF A FIRE HYDRANT FLOW TEST HASN'T
 BEEN DONE WITHIN ONE YEAR, ANOTHER TEST
 WILL BE REQUIRED FOR FIRE SPRINKLER
 CALC. PLEASE CONTACT THE BUREAU OF FIRE
 PREVENTION AT (561) 805-4724.
  
 32) PLEASE INDICATE ALL SMOKE DETECTOR
 LOCATIONS IN ACCORDANCE WITH NFPA 101,
 SECTION 30.3.4.5.
  
 33) EXIT LIGHTS TO BE MOUNTED AT
 DISTANCES NOT TO EXCEED 100'. IT APPEARS
 THAT MORE EXIT SIGNS ARE NEEDED IN
 CORRIDORS.
  
 34) FIRE ALARM SHALL BE CLASS A, STYLE D
 OR FULLY ADDRESSABLE.
  
 35) ARE SMOKE DETECTORS TIED INTO THE
 FIRE ALARM SYSTEM PLANNED FOR CORRIDORS?
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-08-05 Cont ID  
Sent By amckenzi Date 2008-08-05 Time 09:34 Rev Time 0.00
Received By amckenzi Date 2008-08-05 Time 09:34 Sent To  
Notes
2008-08-05 09:35:45TO EXTEND APPLICATION UNTIL 11/5/08 PER NKM/AMM

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-08-14 Cont ID  
Sent By adarroug Date 2007-08-14 Time 14:29 Rev Time 0.00
Received By adarroug Date 2007-08-14 Time 14:29 Sent To  
Notes
2007-09-07 16:18:45TO "COMM" BD#55/PLANS ON RACK--15 ROLLS
2007-08-14 14:29:20WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-29 Cont ID  
Sent By spalmer Date 2006-11-29 Time 19:33 Rev Time 0.00
Received By spalmer Date 2006-11-29 Time 19:33 Sent To  
Notes
2006-12-08 15:30:12TO "COMM" BD#41--3 APPL. PLANS ON RACK--7 ROLLS
2006-11-29 19:33:34WAITING FOR "COMM" BOARD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-11 Cont ID  
Sent By adarroug Date 2006-09-11 Time 08:51 Rev Time 0.00
Received By adarroug Date 2006-09-11 Time 08:51 Sent To  
Notes
2006-09-11 00:00:00TO "COMM" BD#51/PLANS ON RACK-7 ROLLS
 AND PAPERWORK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-31 Cont ID  
Sent By adarroug Date 2006-08-31 Time 11:31 Rev Time 0.00
Received By adarroug Date 2006-08-31 Time 11:31 Sent To  
Notes
2006-08-31 00:00:00WAITING FOR "COMM" BD-ROLLS BY MIRELLE'S
 CUBE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-03-03 Time   Rev Time 0.00
Received By adarroug Date 2005-10-12 Time 14:14 Sent To  
Notes
2005-10-12 00:00:00TO "COMM" BD#49/PLANS ON RACK
2005-10-03 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-10-30 Cont ID  
Sent By rregueir Date 2007-10-30 Time 15:27 Rev Time 0.00
Received By rregueir Date 2007-10-30 Time 15:27 Sent To  
Notes
2007-10-30 15:27:09REVIEW #: 3
 ACTION: DENIED
  
 FBC 2001 CODES W/ 2003 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. RETURN AIR TRANSFERS AND JUMPERS ARE STILL NOT
 DESIGNED TO MEET THE EXCEPTIONS AS LISTED UNDER FBC,M
 601.4. EXAMPLE: UNIT B2 SHOWS AN 8 INCH ROUND (50
 SQ.IN) R/A JUMPER FOR 7 INCH (38.5 SQ.IN) AND 4 INCH
 (13 SQ.IN) ROUND SUPPLY DROPS IN MASTER BEDROOM. THE
 R/A JUMPER MUST BE 1.5 TIMES THE SIZE OF THE SUPPLY
 DROPS IN THE MASTER TO MEET EXCEPTION 1 UNDER FBC,M
 601.4. THE 7IN PLUST THE 4IN DUCTS TOTAL 51.5 SQ. IN.
 THE TRANSFER IS SMALLER THAN THE TWO SUPPLY DUCTS
 RATHER THAN 1.5 TIMES LARGER. THE EXCEPTION HAS NOT
 BEEN MET. IF THE DESIGNER CHOOSES NOT TO DESIGN TO MEET
 THE EXCEPTIONS, A FIELD TEST WILL BE REQUIRED AT FINAL
 INSPECTION TO DEMONSTRATE A MAX. PRESSURE DIFFERENTIAL
 OF 0.01IN. W.C. ACROSS THE CLOSED BEDROOM DOORS AS
 REQUIRED BY FBC,M 601.4.
  
 3. OK
  
 4. OK
  
 5. M15.06: CONDENSATE TRAP DETAIL FOR NON-DUCTED RETURN
 UNITS, THE SECONDARY DRAIN LINE FROM THE AUXILIARY
 DRAIN PAN SHALL NOT BE CONNECTED TO THE PRIMARY
 CONDENSATE RISER. A SEPARATE DRAIN LINE SHALL EXTEND
 FROM THE PAN TO A CONSPICUOUS POINT AND SERVE AS AN
 ALARM WHICH INDICATES THAT THE PRIMARY DRAIN IS
 RESTRICTED.AS AN ALTERNATIVE TO A SEPARATE DRAIN
 LINE, AN APPROVED WATER LEVEL DETECTOR OR FLOAT SWITCH
 DEVICE SHALL BE USED TO CONTROL OVERFLOW BY
 AUTOMATICALLY SHUTTING DOWN THE EQUIPMENT OR APPLIANCE
 THAT PRODUCES THE CONDENSATE. THE FLOAT SWITCH ON THE
 SECONDARY DRAIN OUTLET AT THE AHU MAY BE INSTALLED
 (ALTHOUGH IT'S NOT NECESSARY) BUT IT CAN NOT REPLACE
 THE SEPARATE SECONDARY DRAIN LINE OR THE FLOAT SWITCH
 REQUIRED ON THE AUXILIARY DRAIN PAN. THE FLOAT SWITCH
 ON THE SECONDARY DRAIN OUTLET AT THE AHU IS ACCEPTABLE
 AS OVERFLOW PROTECTION ONLY ON THE DUCTED RETURN UNITS
 WHERE AN AUXILIARY DRAIN PAN CAN NOT BE INSTALLED UNDER
 THE AHU. FBC,M 307.2.3 AND 307.2.4
  
 6 THROUGH 10: OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-12-21 Cont ID  
Sent By pkrauss Date 2006-12-21 Time 12:54 Rev Time 0.00
Received By pkrauss Date 2006-12-21 Time 08:49 Sent To  
Notes
2006-12-21 11:32:34DENIED:BUILDING #3 / 2001 FBC
  
 RESPONSE COMMENTS FROM REVIEW DATED 1-31-06:
  
 COMMENT #1: OK
  
 COMMENT #2: RESPONSE INDICATES NOTE FOR RETURN AIR
 ON SHEETS M15.01 THROUGH M15.03.PLEASE NOTE, THE R/A
 INDICATED ON THE PLAN IS CONSIDERED A TRANSFER UNDER
 2001 FMC 601.4 EXCEPTION 2 NOT 1.PLEASE VERIFY GRILLE
 SIZE INTO THE MASTER SUITE.ALL AIR INTO THE MATER
 SUITE IS TO BE INCLUDED IN THE CALCULATION (I.E.,
 BATHROOM, CLOSET, ETC.)PLEASE ALSO NOTE WALL CAVITIES
 USED FOR TRANSPORTING R/A SHALL BE LINED WITH AN AIR
 BARRIER & SEALED IN ACCORDANCE WITH 2001 FBC CHAPTER 13
 SUB-CHAPTER 410.1.ABCD.3.7.
  
 COMMENT #3:RESPONSE INDICATES AHU CLOSET DOOR IS
 NON-COMBUSTIBLE BUT THE DOOR SCHEDULE ON SHEET A9.02
 STILL INDICATES A WOOD DOOR.PLEASE CLARIFY.
  
 COMMENT #4:RESPONSE STATES THE CLEARANCE AROUND THE
 AHU EXCEEDS THE 4" REQUIREMENT UNDER 2001 FMC
 603.1.3.4.THE DETAIL ON PLAN SHEET M15.09 DOES NOT
 REFLECT OR ANNOTATE A 4" CLEARANCE.PLEASE ALSO NOTE,
 THE CONDENSATE LINE SHALL BE OF NON-COMBUSTIBLE
 MATERIAL (NO PVC IN AHU CLOSET).
  
 COMMENT #5:RESPONSE REFERS TO "CONDENSATE TRAP
 DETAIL" ON SHEET M15.09.PER 2001 FMC 307.2.3 &
 307.2.4 AN AUXILIARY DRAIN PAN IS REQUIRED.PLEASE
 CONTACT HAROLD MOSER, CHIEF MECHANICAL INSPECTOR WITH
 REGARDS TO INSTALLATION OF FLOAT SWITCH IN THE
 AUXILIARY DRAIN OUTLET (TRAP).HAROLD MOSER MAY BE
 CONTACTED AT (561)805-6732.
  
 COMMENT #6:OK
  
 COMMENT #7:OK
  
 COMMENT #8:OK
  
 COMMENT #9:OK
  
 COMMENT #10: OK
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL AT [email protected].
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-01-31 Cont ID  
Sent By pkrauss Date 2006-01-31 Time 10:43 Rev Time 0.00
Received By pkrauss Date 2006-01-31 Time 10:43 Sent To  
Notes
2006-01-31 00:00:00DENIED:2001 FLORIDA BUILDING CODE
  
 1.PLAN SHEET AP A6.01 THROUGH A701, IT
 APPEARS THE COORIDORS HAVE OPENINGS AT
 CERTAIN POINTS.PLEASE INDICATE TOTAL
 SQUARE FOOTAGE AS REQUIRED FOR 'NATURAL
 VENTILATION'.THE OUTSIDE AIR
 CALCULATIONS INDICATED ON PLAN SHEET
 M15.13 DO NOT SHOW TOTAL SQUARE FOOTAGE.
  
 2.PLANS INDICATE RETURN AIR JUMPERS
 FROM THE BEDROOM AREAS.PLEASE NOTE,
 THE RETURN AIR JUMPERS ARE TO BE SIZED
 IN ACCORDANCE WITH 2001 FMC 601.4
 EXCEPTION 1 & 3.PLEASE REVISE RETURN
 TO INCREASE TO THE REQUIRED MINIMUM.
  
 3.PLANS INDICATE LOUVERED DOOR.THE
 DOOR SCHEDULE INDICATES THIS AS BEING A
 WOOD DOOR.THE AHU CLOSET IS CONSIDERED
 A RETURN AIR PLENUM.THE DOOR MUST ALSO
 MEET THE REQUIREMENT OF NON-COMBUSTIBLE
 OR SHALL HAVE A FLAME SPREAD INDEX OF
 NOT MORE THAN 25 AND A SMIKE DEVELOPED
 INDEX OF NOT MORE THAN 50 WHEN TESTED IN
 ACCORDANCE WITH ASTM E 84.PLEASE
 PROVIDE DOCUMENTATION ON THE DOORS.
  
 4.PLEASE NOTE, PER 2001 FMC 603.1.3 4"
 CLEARANCE AROUND THE AIR HANDLER IS
 REQUIRED.
  
 5.PLAN SHEET M15.12 DETAILS FOR THE
 AHUDOES NOT INDICATE AN AUXILIARY
 DRAIN PAN WITH OVERFLOW PROTECTION AS
 REQUIRED BY 2001 FMC 307.2.3.PLEASE
 REVISE.
  
 6.CONDENSING UNIT STANDS SHALL COMPLY
 WITH 2001 FBC 1511.7 FOR HEIGHT
 REQUIREMENT ABOVE FINISHED ROOF.
  
 7.CONDENSING UNIT STANDS SHALL COMPLY
 WITH 2001 FMC 301.13 & CHAPTER 15 OF THE
 FBC FOR WIND PRESSURES.
  
 8.PLEASE PROVIDE LINE SIZES FOR THE
 REFRIGERANT LINES AS WELL AS THE
 CONDENSATE.
  
 9.PLEASE INDICATE TERMINATION OF THE
 CONDENSATE.
  
 10. PLEASE PROVIDE ENERGY AND MANUAL J
 CALCULATIONS IN ACCORDANCE WITH 2001 FBC
 CHAPTER 13.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-11-16 Cont ID  
Sent By kstevens Date 2007-11-16 Time 08:10 Rev Time 0.00
Received By kstevens Date 2007-11-15 Time 19:04 Sent To  
Notes
2007-11-16 09:16:46DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW. THE COMMENT NUMBER
 SHALL STAY THE SAME AS THE FIRST REVIEW:
  
 ******FROM PREVIOUS REVIEWS: 3RD REVIEW******
  
 A. OK
 B. OK
 1. OK
 2. OK
  
 3. SHT AP/A5.12 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. SHOW SF DRAINED FOR EACH
 AREA ALONG WITH 1/2 AREA OF ALL VERTICAL
 WALLS, INCLUDING PARAPETS, AND THE AREA
 OF ANY ROOFS THAT DRAIN ONTO THE ROOF
 AREAS FROM ABOVE. - SHOW THE LOCATION OF
 ALL SECONDARY ROOF DRAINS OR SCUPPERS.
 IF SCUPPERS ARE USED, SUBMIT A DETAIL
 SHOWING HEIGHT, WIDTH, AND DISTANCE TO
 FLOW LINE OFF THE ROOF. SECTION 1503.4.2 ****RESPONSE
 NOTED, BUT SHEETS A5.05,
 A5.13, A5.25 WERE NOT SUBMITTED, AND NO CALCULATIONS
 WITH INFORMATION REQUESTED
 HAS BEEN LOCATED.
 ******RESONSE NOTED, BUT THE SECONDARY ROOF DRAINAGE
 HAS NOT BEEN PROPERLY ADDRESSED. WHEN THE DOWNSPOUT HAS
 A BLOCKAGE, AND WHILE IT IS TRUE THAT THE STORM WATER
 CAN DRAIN OVER THE TOP OF THE COLLECTOR HEAD, THE
 CONCERN IS THAT WHEN THE SCUPPER OPENING IS BLOCKED
 THEN NEITHER THE PRIMARY NOR THE SECONDARY ROOF DRAIN
 WILL BE ABLE TO WORK. SECTION 1107.2 SEPARATE SYSTEMS
 ARE REQUIRED AND THE OVERFLOW SCUPPER SHALL BE SIZED
 PER SECTION 1107.3.
  
 4. SHTS AP/A5.61 & AP/A5.62 INDICATE
 SPECIFICATION "A" OR "B" FOR EACH UNIT
 OR BATHROOM AS REQUIRED IN FHA DESIGN
 MANUAL PAGES 7.34 & 7.35. - LAVS SHALL
 BE A MINIMUM OF 2' OFF THE WALL IN ORDER
 TO BE CENTERED ON THE 48" LENGTH OF THE
 CLEAR FLOOR SPACE. PLEASE INDICATE ON
 PLANS. FHA DESIGN MANUAL PAGES 7.47 AND
 7.48. - WATER CLOSET OPENING SHALL BE A
 MINIMUM OF 33" WITH THE WATER CLOSET 18"
 OFF ONE FIXTURE AND 15" OFF THE OTHER
 FIXTURE TO THE CENTER OF THE W/C. FHA
 DESIGN MANUAL PAGES 7.43, 7.44, & 7.45. ****RESPONSE
 NOTED, BUT SPECIFICATION
 "A" OR "B" HAS NOT BEEN INDICATED. ALSO
 THE WATER CLOSET OPENING MEASUREMENTS
 HAS NOT BEEN SHOWN ON THE FLOOR PLAN. ******RESPONSE
 NOTED, BUT SPECIFICATION "A" OR "B" HAS NOT BEEN
 INDICATED.
  
 5. OK
 6. OK
 7. OK
 8. OK N/A
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
  
 14. AN RPZV BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING. SECTION
 608.13.2.
 ****RESPONSE NOTED, BUT COMMENT NOT
 ADDRESSED. EACH BUILDING IS REQUIRED TO
 HAVE ITS OWN RPZV BACKFLOW. INDICATE ON
 PLANS AT THE WATER SERVICE TO THE
 BUILDING.
 ******RESPONSE NOTED, BUT THERPZV BACKFLOW FOR THIS
 BUILDING IS NOT INDICATED ON SHEET 10 OF THE CIVIL
 PLANS.
  
 15. SUBMIT A WATER LAYOUT FOR BUILDING
 AND WATER RISER DIAGRAMS. SHOW ALL PIPE
 SIZES, VALVES, WATER HAMMER ARRESTORS,
 (INSTALLED IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING). SECTIONS 104.3.1.1,
 606.1, 606.2, 608.13.2 & PDI-WH 201.
 ****RESPONSE NOTED, BUT THE WATER RISER
 DIAGRAM SHALL BE SUBMITTED IN ISOMETRIC
 FORM. WATER HAMMER ARRESTORS AND
 REQUIRED VALVES CAN NOT BE SHOWN ON A
 FLAT PIPING LAYOUT.
 ******RESPONSE NOTED, BUT THIS IS UNIT ISOMETRIC RISER
 DIAGRAMS ONLY. PLEASE SUBMIT THE WATER MAIN PIPING FROM
 THE ENTRANCE OF THE BUILDING, ALL HORIZONTAL MAINS, ALL
 RISERS THRU THE 5TH FLOOR. (ALL PIPING OTHER THAT UNIT
 RISER DIAGRAMS IN ISOMETRIC RISER DIAGRAM FORM).
  
 16. SUBMIT A BUILDING SANITARY DRAIN
 ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE
 SIZES, TRAPS, OFFSETS, RISER LOCATIONS
 WITH RISER NUMBERS, DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM ETC. SECTION
 104.3.1.1.
 ***COMMENT RESPONSE NOTED, BUT COMMENT
 NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN WHERE THE LAST TWO BRANCH LINES
 CONNECT TO THE BUILDING DRAIN, AT THE FLOOR DRAIN, AND
 THE RISER PRIOR TO THE FLOOR DRAIN. ALSO THE FLOOR
 DRAIN IS NOT VENTED AS PIPED ON THE FLOOR PLAN.--
 SHOW CLEANOUTS REQUIRED BY SECTION 708.3.3 ON THE RISER
 DIAGRAM AND THE FLOOR PLAN.--NO RISER DESIGNATION
 NUMBERS WERE GIVEN FOR THE RISERS. THIS IS REQUIRED TO
 TRACK THE RISERS FROM THE BUILDING DRAIN THRU THE 5TH
 FLOOR.
  
 17. SUBMIT A BUILDING STORM DRAIN
 ISOMETRIC RISER DIAGRAM, SHOWING ALL
 PIPE SIZES, RISER LOCATIONS WITH RISER
 NUMBERS, AND SQUARE FEET AS IT
 ACCUMULATES IN THE SYSTEM. SECTION
 104.3.1.1.
 ****RESPONSE NOTED, BUT NOT ADDRESSED. ******RESPONSE
 NOTED, BUT THE STORM ISOMETRIC RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. SOME PIPE SIZES ARE DIFFERENT,
 CLEANOUTS, ETC.--P-TRAPS ARE NOT REQUIRED IN THE
 STORM PIPING SYSTEM.--SHOW ALL CLEANOUTS REQUIRED
 BY SECTION 1101.8.
  
 18. OK
  
 **************NEW COMMENTS**************
  
 1B. ALL ARCHITECTURAL SHEETS. THE TITLE
 BLOCK SHALL CONTAIN THE PRINTED NAME OF
 THE PERSON SEALING THE DOCUMENT. FAC 61G1-16.004(6) &
 FS F81.2055.
 ******RESPONSE NOTED, BUT SHT GN/A1.04 IS STILL MISSING
 THE PRINTED NAME.
  
 2B. SHT AP P14.04 PIPING FOR THE
 FIXTURES ON THE SECOND THRU 4TH FLOORS
 SHALL BE SHOWN ON THE FLOOR PLAN WITH
 THE FIXTURES, (SHT P14.05). SECTION
 104.2.1.3.
 ******RESPONSE NOTED, BUT MANY RISER NUMBERS ARE NOT
 SHOWN AS WELL AS THE PIPING IN ABOUT 6 OR 7 UNITS IS
 NOT SHOWN.
  
 3B. OK
  
 4B. SUBMIT A DETAIL FOR THE DOWNSPOUTS
 AND THE COLLECTOR HEAD AT THE TOP.
 INDICATE SIZE OF DOWNSPOUT, LENGTH,
 WIDTH & HEIGHT OF COLLECTOR HEAD.
 INDICATE ON ROOF PLAN SQUARE FOOTAGE
 DRAINING INTO EACH DOWNSPOUT.
 ******RESPONSE NOTED, BUT THE DETAIL DOES NOT SHOW
 LENGHT, WIDTH OR HEIGHT. SUBMIT AN ELEVATION DETAIL
 SHOWING THESE MEASUREMENTS AS WELL AS A CUT SECTION.
 SECTION 1106.3.
  
 5B. SECONDARY DRAINAGE AND SEPARATE
 SYSTEMS ARE REQUIRED FOR THE ROOF
 DRAINAGE PER SECTIONS 1107.1 & 1107.2.
 PLEASE INDICATE THE LOCATION AND SIZE OF
 THE SECONDARY ROOF DRAINAGE. SUBMIT A
 DETAIL FOR THE SECONDARY ROOF DRAINS. ******RESPONSE
 NOTED, BUT THE INTENT OF THE CODE SECTION HAS NOT BEEN
 ADDRESSED. WHEN THE DOWNSPOUT HAS A BLOCKAGE, AND WHILE
 IT IS TRUE THAT THE STORM WATER CAN DRAIN OVER THE TOP
 OF THE COLLECTOR HEAD, THE CONCERN IS THAT WHEN THE
 SCUPPER OPENING IS BLOCKED THEN NEITHER THE PRIMARY NOR
 THE SECONDARY ROOF DRAIN WILL BE ABLE TO WORK. SECTION
 1107.2 SEPARATE SYSTEMS ARE REQUIRED AND THE OVERFLOW
 SCUPPER SHALL BE SIZED PER SECTION 1107.3. SHOW THE
 LOCATION OF THE EMERGENCY OVERFLOW SCUPPERS.
  
 6B. OK
  
 ********NEW COMMENTS 3RD REVIEW********
  
 1C. THE STRUCTURAL SHEETS ONE SET HAVE NOT BEEN SIGNED,
 SEALED & DATED. FAC 61G15-23.002(1) & FS 471.025.
  
 2C. SOME ARCHITECTURAL SHEETS IN ONE SET HAVE NOT BEEN
 SIGNED, SEALED & DATED. FAC 61G1-16.003, FAC
 61G1-16.004(5) & FS 481.2055.
  
 3C. SHT AP/P14.01 AND OTHER PLUMBING SHEETS REVISION 1
 HAS BEEN DELETED FROM THE TITLE BLOCK REVISION INDEX.
 PLEASE SHOW THE COMPLETE HISTORY OF REVISIONS ON THE
 REVISION INDEX FOR ACCURATE RECORD KEEPING. SECTION
 104.2.1.3.
  
 4C. SHT AP/P14.03 THE FLOOR DRAIN IN THE PUMP ROOM CAN
 NOT DRAIN TO STORM. ARTICLE III SECTION 90-203 CITY WPB
 MUNICIPAL CODE. CONNECT ALL FLOOR DRAINS TO THE
 SANITARY SYSTEM.
  
 5C. SHT AP/P14.08 STORM ISOMETRIC RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. SOME PIPE SIZES ARE
 DIFFERENT, CLEANOUTS, ETC.--P-TRAPS ARE NOT
 REQUIRED IN THE STORM PIPING SYSTEM.--SHOW ALL
 CLEANOUTS REQUIRED BY SECTION 1101.8.
  
 6C. SHT AP/P14.10 WATER HEATER DETAIL. A FULL OPEN
 VALVE IS REQUIRED ON THE SUPPLY LINE TO THE WATER
 HEATER. SECTION 606.1(7). PLEASE SHOW ON DETAIL.--
 SANITARY RISER #7 HAS 24 DFU'S, NOT 20 AS INDICATED.
 TABLE 709.1. PLEASE CORRECT DFU'S.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6713
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-10-11 Cont ID  
Sent By kstevens Date 2006-10-11 Time 10:00 Rev Time 0.00
Received By kstevens Date 2006-10-11 Time 10:00 Sent To  
Notes
2006-10-11 10:03:16DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW. THE COMMENT NUMBER
 SHALL STAY THE SAME AS THE FIRST REVIEW:
  
 A. OK
 B. OK
 1. OK
 2. OK
  
 3. SHT AP/A5.12 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. SHOW SF DRAINED FOR EACH
 AREA ALONG WITH 1/2 AREA OF ALL VERTICAL
 WALLS, INCLUDING PARAPETS, AND THE AREA
 OF ANY ROOFS THAT DRAIN ONTO THE ROOF
 AREAS FROM ABOVE. - SHOW THE LOCATION OF
 ALL SECONDARY ROOF DRAINS OR SCUPPERS.
 IF SCUPPERS ARE USED, SUBMIT A DETAIL
 SHOWING HEIGHT, WIDTH, AND DISTANCE TO
 FLOW LINE OFF THE ROOF. SECTION 1503.4.2 ****RESPONSE
 NOTED, BUT SHEETS A5.05,
 A5.13, A5.25 WERE NOT SUBMITTED, AND NO CALCULATIONS
 WITH INFORMATION REQUESTED
 HAS BEEN LOCATED.
  
 4. SHTS AP/A5.61 & AP/A5.62 INDICATE
 SPECIFICATION "A" OR "B" FOR EACH UNIT
 OR BATHROOM AS REQUIRED IN FHA DESIGN
 MANUAL PAGES 7.34 & 7.35. - LAVS SHALL
 BE A MINIMUM OF 2' OFF THE WALL IN ORDER
 TO BE CENTERED ON THE 48" LENGTH OF THE
 CLEAR FLOOR SPACE. PLEASE INDICATE ON
 PLANS. FHA DESIGN MANUAL PAGES 7.47 AND
 7.48. - WATER CLOSET OPENING SHALL BE A
 MINIMUM OF 33" WITH THE WATER CLOSET 18"
 OFF ONE FIXTURE AND 15" OFF THE OTHER
 FIXTURE TO THE CENTER OF THE W/C. FHA
 DESIGN MANUAL PAGES 7.43, 7.44, & 7.45. ****RESPONSE
 NOTED, BUT SPECIFICATION
 "A" OR "B" HAS NOT BEEN INDICATED. ALSO
 THE WATER CLOSET OPENING MEASUREMENTS
 HAS NOT BEEN SHOWN ON THE FLOOR PLAN.
  
 5. SHT AP/A5.56 INDICATE MATERIAL FOR
 GRAB BAR BLOCKING. SECTION 104.2.1.
 ***RESPONSE NOTED, (SEE AP A5.56), BUT
 SHT AP/A5.56 HAS NOT BEEN SUBMITTED.
 PLEASE CLARIFY.
  
 6. OK
 7. OK
  
 8. SUBMIT A DETAIL FOR THE COMMON USE
 TOILET ROOMS SHOWING COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.19, & 11-4.22 AND
 ALL SUBSECTIONS.
 ****RESPONSE NOTED, (SEE SHEET A5.70 AND
 A5.71), BUT THOSE SHEETS HAVE NOT BEEN
 SUBMITTED.
  
 9. SHTS AP/P14.02 UNITS B3 & B4 MAXIMUM
 4 FU ON A 2" WET VENT IN MASTER BATH.
 TABLE 909.3.
 ****RESPONSE NOTED, BUT NOT THE RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN
 AS THE FLOOR PLAN SHOWS 3" AND THE RISER
 DIAGRAM SHOWS 2-1/2" FOR THE WET VENT.
 CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1.
  
 10. OK
  
 11. SHT AP/P14.26 OFFSETS IN THE SANT.
 SHALL BE SHOWN ON EITHER BLDG. DRAIN
 ISOMETRIC RISER DIAGRAM, OR SANT. RISER
 DIAGRAMS. SECTION 104.2.1.
 ****RESPONSE NOTED, BUT WHEN THE SANT.
 RISER FROM UNDERGROUND IS ABOVE THE
 CEILING OF THE FIRST FLOOR, THE RISER
 SPLITS AND OFFSETS INTO OTHER RISERS.
 (EXAMPLE RISER 2,3,6 COMES OUT OF THE
 GROUND AND OFFSETS ABOVE THE CEILING AND
 SPLITS INTO THREE SEPARATE RISERS.
 BUILDING DRAIN ISOMETRIC RISER SHALL
 REFLECT THIS PIPING. SECTION 104.3.1.1.
  
 12. OK
 13. OK
  
 14. AN RPZV BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING. SECTION
 608.13.2.
 ****RESPONSE NOTED, BUT COMMENT NOT
 ADDRESSED. EACH BUILDING IS REQUIRED TO
 HAVE ITS OWN RPZV BACKFLOW. INDICATE ON
 PLANS AT THE WATER SERVICE TO THE
 BUILDING.
  
 15. SUBMIT A WATER LAYOUT FOR BUILDING
 AND WATER RISER DIAGRAMS. SHOW ALL PIPE
 SIZES, VALVES, WATER HAMMER ARRESTORS,
 (INSTALLED IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING). SECTIONS 104.3.1.1,
 606.1, 606.2, 608.13.2 & PDI-WH 201.
 ****RESPONSE NOTED, BUT THE WATER RISER
 DIAGRAM SHALL BE SUBMITTED IN ISOMETRIC
 FORM. WATER HAMMER ARRESTORS AND
 REQUIRED VALVES CAN NOT BE SHOWN ON A
 FLAT PIPING LAYOUT.
  
 16. SUBMIT A BUILDING SANITARY DRAIN
 ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE
 SIZES, TRAPS, OFFSETS, RISER LOCATIONS
 WITH RISER NUMBERS, DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM ETC. SECTION
 104.3.1.1.
 ***COMMENT RESPONSE NOTED, BUT COMMENT
 NOT ADDRESSED.
  
 17. SUBMIT A BUILDING STORM DRAIN
 ISOMETRIC RISER DIAGRAM, SHOWING ALL
 PIPE SIZES, RISER LOCATIONS WITH RISER
 NUMBERS, AND SQUARE FEET AS IT
 ACCUMULATES IN THE SYSTEM. SECTION
 104.3.1.1.
 ****RESPONSE NOTED, BUT NOT ADDRESSED.
 SEE COMMENT RESPONSE TO COMMENT #10.
  
 18. OK
  
 **************NEW COMMENTS**************
  
 1B. ALL ARCHITECTURAL SHEETS. THE TITLE
 BLOCK SHALL CONTAIN THE PRINTED NAME OF
 THE PERSON SEALING THE DOCUMENT. FAC 61G1-16.004(6) &
 FS F81.2055.
  
 2B. SHT AP P14.04 PIPING FOR THE
 FIXTURES ON THE SECOND THRU 4TH FLOORS
 SHALL BE SHOWN ON THE FLOOR PLAN WITH
 THE FIXTURES, (SHT P14.05). SECTION
 104.2.1.3.
  
 3B. SHTS AP A5.60, AP A5.61, AP A5.62
 REFER TO SHEET A5.58. THIS SHEET HAS NOT
 BEEN SUBMITTED. PLEASE CLARIFY. SECTION
 104.2.1.
  
 4B. SUBMIT A DETAIL FOR THE DOWNSPOUTS
 AND THE COLLECTOR HEAD AT THE TOP.
 INDICATE SIZE OF DOWNSPOUT, LENGTH,
 WIDTH & HEIGHT OF COLLECTOR HEAD.
 INDICATE ON ROOF PLAN SQUARE FOOTAGE
 DRAINING INTO EACH DOWNSPOUT.
  
 5B. SECONDARY DRAINAGE AND SEPARATE
 SYSTEMS ARE REQUIRED FOR THE ROOF
 DRAINAGE PER SECTIONS 1107.1 & 1107.2.
 PLEASE INDICATE THE LOCATION AND SIZE OF
 THE SECONDARY ROOF DRAINAGE. SUBMIT A
 DETAIL FOR THE SECONDARY ROOF DRAINS.
  
 6B. SHT AP A5.32 ROOF PLAN SHOWS UNITS
 AND FIXTURES. PLEASE CLARIFY. SECTION
 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6713
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-01-18 Cont ID  
Sent By kstevens Date 2006-01-18 Time 10:32 Rev Time 0.00
Received By kstevens Date 2006-01-18 Time 10:32 Sent To  
Notes
2006-01-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A. PLANS WERE SUBMITTED AS LOOSE SHEETS
 AND AS SUCH IS NOT ACCEPTABLE. PLEASE
 SUBMIT PLANS IN BOUND SETS. SECTION
 104.2.1.3.
 B. PERMITS INDICATE 3 SEPARATE
 BUILDINGS, BUT PLANS INDICATE ONE
 BUILDING. PLEASE CLARIFY. SECTION
 104.2.1.
 1. ALL ARCHITECTURAL SHEETS, (EXCEPT FOR
 STRUCTURAL), ARE NOT SEALED AS REQUIRED
 IN SECTION 104.2.2 & FAC 61G1-16.003
 61G1-16.004(5) & FS 481.2055.
 2. SHTS AP/A1.02 & AP/A1.03 SHOWN IN
 DRAWING INDEX ON SHT AP/A1.01 HAVE NOT
 BEEN SUBMITTED. SECTION 104.2.1.
 3. SHTS AP/A5.24 & AP/A5.25 SUBMIT
 CALCULATIONS FOR PRIMARY AND SECONDARY
 ROOF DRAINS PER SECTIONS 1106 & 1107 AND
 ALL SUBSECTIONS. SHOW SF DRAINED FOR
 EACH AREA ALONG WITH 1/2 AREA OF ALL
 VERTICAL WALLS, INCLUDING PARAPETS, AND
 THE AREA OF ANY ROOFS THAT DRAIN ONTO
 THE ROOF AREAS FROM ABOVE. - SHOW THE
 LOCATION OF ALL SECONDARY ROOF DRAINS OR
 SCUPPERS. IF SCUPPERS ARE USED, SUBMIT A
 DETAIL SHOWING HEIGHT, WIDTH, AND
 DISTANCE TO FLOW LINE OFF THE ROOF.
 SECTION 1503.4.2
 4. SHTS AP/A5.61 & AP/A5.62 INDICATE
 SPECIFICATION "A" OR "B" FOR EACH UNIT
 OR BATHROOM AS REQUIRED IN FHA DESIGN
 MANUAL PAGES 7.34 & 7.35. - LAVS SHALL
 BE A MINIMUM OF 2' OFF THE WALL IN ORDER
 TO BE CENTERED ON THE 48" LENGTH OF THE
 CLEAR FLOOR SPACE. PLEASE INDICATE ON
 PLANS. FHA DESIGN MANUAL PAGES 7.47 AND
 7.48. - WATER CLOSET OPENING SHALL BE A
 MINIMUM OF 33" WITH THE WATER CLOSET 18"
 OFF ONE FIXTURE AND 15" OFF THE OTHER
 FIXTURE TO THE CENTER OF THE W/C. FHA
 DESIGN MANUAL PAGES 7.43, 7.44, & 7.45.
 5. SHT AP/A5.56 INDICATE MATERIAL FOR
 GRAB BAR BLOCKING. SECTION 104.2.1.
 6. SHTS AP/A5.50 THRU AP/A5.55 LAV SHALL
 BE 34" TO TOP OF FIXTURE RIM, NOT 36" AS
 SHOWN. FHA DESIGN MANUAL PAGE 7.52.
 7. SHTS AP/A6.01 THRU AP/A6.04 INDICATE
 THE BLDG. NUMBERS FOR EACH OF THE
 BUILDING ELEVATIONS.
 8. SUBMIT A DETAIL FOR THE COMMON USE
 TOILET ROOMS SHOWING COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.19, & 11-4.22 AND
 ALL SUBSECTIONS.
 9. SHTS AP/P14.02 UNITS B3 & B4 MAXIMUM
 4 FU ON A 2" WET VENT IN MASTER BATH.
 TABLE 909.3
 10. SHT AP/P14.05 VENTS ARE REQUIRED FOR
 THE FLOOR DRAINS. SECTION 901.2.1. -
 CLEANOUTS ARE REQUIRED IN THE SANT.
 BUILDING DRAIN AT ALL CHANGES OF
 DIRECTION OVER 45 DEGREES. SECTION
 708.3.3.
 11. SHT AP/P14.26 OFFSETS IN THE SANT.
 SHALL BE SHOWN ON EITHER BLDG. DRAIN
 ISOMETRIC RISER DIAGRAM, OR SANT. RISER
 DIAGRAMS. SECTION 104.2.1.
 12. SHT AP/P14.27 SANT. RISER S/9,
 PLEASE INDICATE FIXTURE TYPE FOR FIXTURE
 L-3. THIS IS NOT SHOWN ON PLUMBING
 FIXTURE SCHEDULE. SECTION 104.2.1.
 13. SHT AP/P14.27 WATER HEATER PIPING
 DETAIL, THERMAL EXPANSION CONTROL IS
 REQUIRED PER SECTION 607.3.2. PLEASE
 INDICATE METHOD. - DIELECTRIC UNIONS ARE
 NOT APPROVED FOR WATER SUPPLY.
 DIELECTRIC COUPLING TO BE USED.
 14. AN RPZV BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING. SECTION
 608.13.2.
 15. SUBMIT A WATER LAYOUT FOR BUILDING
 AND WATER RISER DIAGRAMS. SHOW ALL PIPE
 SIZES, VALVES, WATER HAMMER ARRESTORS,
 (INSTALLED IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING). SECTIONS 104.3.1.1,
 606.1, 606.2, 608.13.2 & PDI-WH 201.
 16. SUBMIT A BUILDING SANITARY DRAIN
 ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE
 SIZES, TRAPS, OFFSETS, RISER LOCATIONS
 WITH RISER NUMBERS, DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM ETC. SECTION
 104.3.1.1.
 17. SUBMIT A BUILDING STORM DRAIN
 ISOMETRIC RISER DIAGRAM, SHOWING ALL
 PIPE SIZES, RISER LOCATIONS WITH RISER
 NUMBERS, AND SQUARE FEET AS IT
 ACCUMULATES IN THE SYSTEM. SECTION
 104.3.1.1.
 18. SUBMIT STORM RISER DIAGRAMS SHOWING
 ALL PIPE SIZES, OFFSETS, AND SQUARE
 FOOTAGE DRAINED FOR EACH RISER.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  

Review Stop X PERMIT EXTENSION
Rev No 1 Status N Date 2008-11-05 Cont ID  
Sent By dfulcher Date 2008-11-05 Time 09:28 Rev Time 0.00
Received By dfulcher Date 2008-11-05 Time 09:27 Sent To  
Notes
2008-11-05 09:28:26EXTEND APP TO 2/3/09 PER RAB

Review Stop Z ZONING
Rev No 2 Status F Date 2006-12-26 Cont ID  
Sent By lfranco Date 2006-12-22 Time 07:51 Rev Time 0.00
Received By lfranco Date 2006-12-22 Time 07:51 Sent To  
Notes
2006-12-26 07:51:29PLANNING AND ZONING**** FAILED ****
  
  
 1.PROVIDE RESPONSES TO COMMENTS IN WRITING AND
 INDICATE THE REVISIONS ON SITE PLAN.
  
 2.A MINOR AMENDMENT TO THE COURTNEY LAKES PB 1402
 PLANNED DEVELOPMENTIS REQUIRED TO REFLECT NUMBER OF
 HANDICAP PARKING SPACES REQUIRED.AN APPLICATION WILL
 NEED TO BE FILED TO THE PLANNING AND ZONING DEPARTMENT
 AND APPROVED PRIOR TO SIGN-OFF OF BUILDING PERMIT.
  
 3.PURSUANT TO SECTION 94-485(O)PAGE CD 94:273 OF THE
 CODE, THE AMOUNT OF DISABLED PARKING SPACES PROPOSED
 DOES NOT COMPLY.THERE ARE TWENTY (20) REQUIRED
 PARKING SPACES THAT NEED TO BE PROVIDED.IN ADDITION,
 THE LOCATION OF THE SPACES SHALL BE LOCATED SO THAT
 USERS ARE NOT COMPELLED TO WALK OR OTHERWISE MOVE
 BEHIND PARKED VEHICLES.WHY ARE THESE SPACES LOCATED
 ACROSS DRIVE AISLES INSTEAD OF CLOSE PROXIMITY TO THE
 BUILDING ACCESS? REVISE ACCORDINGLY.
  
 SHOULD YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1435

Review Stop Z ZONING
Rev No 1 Status F Date 2006-03-03 Cont ID  
Sent By dpalmer Date 2006-03-03 Time 18:21 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2006-03-03 00:00:00REVIEW DONE UNDER 05091684