 |
Plan Review Details - Permit 05091686
| Plan Review Stops For Permit 05091686 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2007-09-24 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2007-09-24 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2007-09-24 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2007-09-24 09:49:29 | NEW SITE ADDRESS HAS BEEN ASSIGNED TO BUILDING 2 AS 355 | | | COURTNEY LAKES CIR , WEST PALM BEACH, FL 33401. | | | | | | LACRAMIOARA URSU | | | MIS - GIS SUPPORT SPECIALIST | | | CITY OF WEST PALM BEACH | | | OFFICE:822-1239 | | | FAX: 822-1249 | | | E-MAIL:[email protected] |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2006-03-01 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2006-03-01 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2006-03-01 |
Time |
15:18 |
Sent To |
|
|
| Notes |
| 2006-03-01 00:00:00 | SITE PLAN MUST BE SUBMITTED FOR | | | ADDRESSING ISSUES. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-10-15 |
|
|
Cont ID |
|
| Sent By |
jjohnsto |
Date |
2007-10-15 |
Time |
16:26 |
Rev Time |
16.00 |
| Received By |
jjohnsto |
Date |
2007-10-15 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2007-10-15 16:26:15 | CONSTRUCTION SERVICES DEPARTMENT | | | 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH, | | | FLORIDA33401 | | | TEL:561-805-6713FAX: | | | 561-805-6731 | | | | | | JAMES JOHNSTON, PERMIT NO 05091686 | | | BUILDING PLAN EXAMINERII PROJECT | | | NAME COURTNEY LAKES, BLDG. 2 | | | E-MAIL:JJOHNSTON @WPB.ORG ADDRESS | | | 355 COURTNEY LAKES CIRCLE | | | DATE OCTOBER 10, 2007 | | | | | | BUILDINGPLANREVIEW | | | FLORIDA BUILDING CODE 2001 | | | | | | | | | 1. PRODUCT APPROVALS | | | COMMENTTHE FLORIDA PRODUCT APPROVAL COVER SHEET | | | SHALL INCLUDE THE APPROVAL INFORMATION FOR THE PRODUCT | | | SELECTED.SEE ATTACHED SAMPLE INCLUDED. | | | THE DESIGNER OF RECORD SHALLREVIEW EACH APPROVAL?S | | | SPECIFICATION PACKETAND ACKNOWLEDGE SAME ON THE | | | APPROVAL COVER SHEETBY NAME DATE AND STATEMENT OF | | | ACCEPTANCE | | | | | | WINDOWS / DOORS PRODUCT APPROVALS | | | WPB ADMINISTRATIVE CODE 106.3 REGULATED BY DCA RULE | | | 9B-72FLORIDA PRODUCT APPROVAL | | | SUBMIT TWO COPIES OF EACH APPROVAL WITH FLORIDA PRODUCT | | | APPROVAL COVER SHEET THE ARCHITECT?S / ENGINEER?S | | | SIGNATURE AS APPLICABLE, STATING ?TO THE BEST OF THEIR | | | KNOWLEDGE THE PRODUCT APPROVAL COMPLIES WITH THE PLANS | | | AND SPECIFICATIONS.SEE:WEB SITE | | | WWW.FLORIDABUILDING.COM | | | NOTE: SEE DIVISION FACTOR TO BE USED IN DESIGN PRESSURE | | | BY LEGACYFPA | | | COMMENT-FOR YOUR INFORMATION | | | | | | SUBMIT PRODUCT APPROVALS WITH FLORIDA PRODUCT APPROVAL | | | COVER | | | PAGE FOR THE FOLLOWING | | | OPERABLE WINDOWS | | | FIXED GLASS | | | MULLION TUBES | | | PANEL WALLS | | | STORE FRONT GLAZING SYSTEM | | | ALUMINUM OUT -SWING DOORS | | | HOLLOW METAL DOORS | | | TRUSS ANCHORS | | | ROOFINGCOMPONENTS | | | SHUTTERS | | | SKYLIGHTS | | | OVERHEAD GARAGE DOOR | | | COMMENT-PLEASE COMPLY | | | | | | | | | 2. 3RD REQUEST ? | | | COMMENT-FURNISH THE FOLLOWING PRODUCT REPORTS | | | TRACO OPERABLE WINDOWSNON IMPACT 0? TO 30?,LARGE | | | MISSLE 30? TO 60? | | | TRACO FIXED WINDOWS | | | MULLIONS | | | EXTERIOR HOLLOW METAL DOORS | | | EXTERIOR GLAZED DOORS | | | EXTERIOR LOUVER DOORS | | | EXTERIOR RAILINGS, ENGINEERING REQUIRED | | | LOUVERS,NO REPORT SUBMITTED | | | ROOF ASSEMBLIES, DENSE DECK, ATTACHMENTS, INSULATION, | | | UNDERLAYMENT,ROOF TILE,ROOF SYSTEM | | | IDENTIFY EACH COMPONENT TO BE USED | | | RATIONAL ANALYSIS FOR ZONE 2 AND THREE | | | EFIS WALL SYSTEM (IF USED) | | | 5/8? AQUA ROCK SHEATHING | | | ROLL UP DOOR | | | WOOD BASE STRUCTURAL PANELSFBC 2315.1.11 | | | | | | PROVIDE DESIGN LOADS ON ALL WINDOW , DOOR, COMPONENTS | | | ON SCHEDULE | | | 2405.3.2.1 THE DESIGN LOADS SHALL BE COMBINED AS | | | FOLLOWS: | | | | | | 1. NEGATIVE WIND LOAD - DEAD LOAD | | | | | | 2. POSITIVE WIND LOAD + DEAD LOAD | | | | | | 3. DEAD LOAD + 1/2 POSITIVE WIND LOAD | | | | | | WIND LOADS SHALL BE DETERMINED FROM 1606. THE DEAD LOAD | | | FOR THE GLASS IN LB/SQ FT SHALL BE TAKEN AS THE TOTAL | | | THICKNESS OF THE GLASS PANES AND PLIES IN INCHES X 13. | | | THIS APPLIES FOR GLASS 30 DEGREES OR LESS FROM | | | HORIZONTAL. FOR OTHER SLOPES THE GLASS DEAD LOAD IS | | | EQUAL TO THIS VALUE TIMES THE COSINE OF ITS SLOPE FROM | | | HORIZONTAL. | | | | | | 3 2411.3.1.4 THE ARCHITECT OR PROFESSIONAL ENGINEER OF | | | RECORD SHALL BE | | | REQUIRED TO SPECIFY THE DESIGN WIND PRESSURE, | | | DETERMINED IN ACCORDANCE | | | WITH CHAPTER 16 (HIGH VELOCITY HURRICANE ZONES), | | | FOR ALL GARAGE DOORS, | | | SKYLIGHTS OPERATIVE WINDOWS AND FIXED GLAZING. | | | THE DESIGN WIND PRESSURE | | | FOR EACH COMPONENT OF THE EXTERIOR BUILDING | | | SURFACE, SHALL BE | | | INCORPORATED INTO THE BUILDING DESIGN DRAWING SO | | | AS TO ALLOW THE | | | RESPECTIVE MANUFACTURER TO SIZE THE PREFABRICATED | | | ASSEMBLY FOR THE | | | PROPER WIND PRESSURES. | | | COMMENTPLEASE PROVIDE THIS INFORMATION ON THE | | | ELEVATIONS | | | | | | 4 1804.2.2 QUESTIONABLE SOIL. WHERE THE BEARING | | | CAPACITY OF THE SOIL IS | | | NOT DEFINITELY KNOWN OR IS IN QUESTION, THE BUILDING | | | OFFICIAL MAY REQUIRE | | | LOAD TESTS OR OTHER ADEQUATE PROOF AS TO THE | | | PERMISSIBLE SAFE BEARING | | | CAPACITY AT THAT PARTICULAR LOCATION.TO DETERMINE | | | THE SAFE BEARING | | | CAPACITY OF SOIL, IT SHALL BE TESTED AT SUCH | | | LOCATIONS AND LEVELS AS | | | CONDITIONS WARRANT, BY LOADING AN AREA NOT LESS THAN | | | 4 SQ FT (0.37 M{2}) | | | TO NOT LESS THAN TWICE THE MAXIMUM BEARING CAPACITY | | | DESIRED FOR USE.SUCH | | | DOUBLE LOAD SHALL BE SUSTAINED BY THE SOIL FOR A | | | PERIOD OF NOT LESS THAN | | | 48 HOURS WITH NO ADDITIONAL SETTLEMENT TAKING PLACE, | | | IN ORDER THAT SUCH | | | DESIRED BEARING CAPACITY MAY BE USED.SUBSOIL | | | CONDITIONS SHALL BE | | | EXAMINED AT THE EXPENSE OF THE OWNER, WHEN DEEMED | | | NECESSARY BY THE | | | BUILDING OFFICIAL. | | | COMMENT PLEASE FURNISH THE SOIL TEST REPORT | | | 5 105.13 THRESHOLD BUILDING | | | 105.13.2 THE SPECIAL INSPECTOR SHALL INSPECT THE | | | SHORING AND RESHORING | | | FOR CONFORMANCE TO THE SHORING AND RESHORING PLANS | | | SUBMITTED TO THE | | | ENFORCING AGENCY.A FEE SIMPLE TITLE OWNER OF A | | | BUILDING WHICH DOES NOT | | | MEET THE MINIMUM SIZE, HEIGHT, OCCUPANCY, OCCUPANCY | | | CLASSIFICATION OR | | | NUMBER-OF-STORIES CRITERIA WHICH WOULD RESULT IN | | | CLASSIFICATION AS A | | | THRESHOLD BUILDING UNDER ?553.71(7) FLORIDA | | | STATUTES, MAY DESIGNATE | | | SUCH BUILDING AS A THRESHOLD BUILDING, SUBJECT TO | | | MORE THAN THE MINIMUM | | | NUMBER OF INSPECTIONS REQUIRED BY THE FLORIDA | | | BUILDING CODE, BUILDING. | | | COMMENTPLEASE FURNISH A SHORING AND RESHORING PLAN | | | | | | | | | | | | 6 SITE PLAN AND ASSOCIATED COMPONENTS REQUIRED3RD | | | REQUEST(NOT INCLUDED) | | | | | | COMMENTPLEASE FURNISH A SEPARATE SITE PLAN FOR | | | BUILDING NO II INCLUDED WITHTHE ARCHITECTURAL | | | DRAWINGS FOR THE FOLLOWING | | | (A) PARKING SPACES LOCATED OUTSIDE AND UNDERNEATH THE | | | BUILDING. CURBING, RAMPS, ACCESSIBLE ISLES FOR THE | | | HANDICAP, SIGNAGE, SIDEWALKS, CURB CUTS, PEDESTRIAN | | | CROSS WALKS (B) HANDICAP SPACES LOCATED OUTSIDE AND | | | UNDERNEATH THE BUILDING PERIMETER. IDENTIFY ALL | | | HANDICAP PARKING SPACES AS DEFINED BY THEAMERICANS | | | WITH DISABILITIES FLORIDA BUILDING CODE CHAPTER 11 | | | ANDFAIR HOUSING ACT GUIDELINES | | | (C) IDENTIFY THE ACCESSIBLE ROUTE AS DEFINED BY | | | THE AMERICANS WITH DISABILITIES- FLORIDA BUILDING | | | CODE CHAPTER 11 AND FAIR HOUSING ACT GUIDELINES | | | (D) IDENTIFY VAN ACCESSIBLE PARKING SPACES UNDER | | | BUILDING AND EXTERIOR IN COMPLIANCE WITH | | | THE AMERICANS WITH DISABILITIES FLORIDA BUILDING CODE | | | CHAPTER 11ANDFAIR HOUSING ACT | | | GUIDELINES | | | (E) ONE ACCESSIBLE ROUTE FAIR HOUSING, FROM THE | | | BOUNDARY SITES PUBLIC TRANSPORTATION STOP TO AN | | | ACCESSIBLE BUILDING ENTRANCE. CHAPTER 11, PART B ? | | | ANSI A117.1,502.6 | | | | | | | | | 7 APA6.30, A6.31,A6.35 | | | COMMENTPLEASE IDENTIFY WINDOWS, DOORS, OVERHEAD | | | DOORS ON THE BUILDING ELEVATIONS TO CORRESPOND WITH | | | THE INFORMATION PROVIDED ONA9.03 | | | | | | 8 SHEET A-5.50WALL SECTIONS A3, A3A,B,C,D | | | COMMENTIDENTIFY EACH WALL SECTION ON FLOOR PLANS | | | | | | 9 SHEET A5.51 UNIT INFORMATION FOR WALLS DOES NOT MATCH | | | FLOOR PLAN PROVIDED A5.30, A5.31 | | | REFERENCING EXTERIOR WALLS. | | | COMMENTIDENTIFY EACH UNIT?S WALL TAGS SECTION ON | | | THESE PAGES FOR INFORMATION RELATING TO SHEET GN A1.04 | | | UNIT B-2END WALL IS TAGGED WF9. FLOOR PLAN SHEET | | | A5.30 AND A5.31 IDENTIFY THE WALLS AS EXTERIOR | | | | | | 10 SHEER AP.701WALL SECTION 2 DOES NOT IDENTIFY THE | | | LOW WALL STRUCTURAL REFERENCE FOR ANCHORING, CONCRETE | | | IN FILL OR REINFORCING.SHEET S4.32 SHOWS A DETAIL OF | | | THIS BALCONY WALL WITHOUT REFERENCE ON THE OTHER | | | DRAWINGS | | | | | | 11 ARCHITECTURAL TRIM1401.1 | | | COMMENT-A7.02IDENTIFY THE FASTENING HARDWARE TO | | | BE USED IN SECURING THE FOAM TRIM TO THE BUILDING | | | EXTERIOR SURFACE | | | | | | 12 SHEET GN-A1.05,GN-A1.06 | | | COMMENTPLEASE PROVIDELEGIBLE INFORMATION ON | | | THESE SHEETS | | | | | | 13 SHEET AP ? S3.05 | | | COMMENT PLEASE IDENTIFY ADHESIVE ANCHOR SYSTEM AND | | | RELATED NOMENCLATURE | | | 14 SHEET GN ? A1.02 AND SHEET AP ? S3.01 | | | EXPOSURE IS IN CONFLICT WITH THE INFORMATION PROVIDED | | | | | | 15 FBC105.11SOIL TREATMENT | | | COMMENTIDENTIFY THE CHEMICAL SOIL TREATMENT TO | | | BE USED IN THE SLAB NOTES SHEET APS3.21 | | | | | | 16 FBC411.2 AUTOMOBILE PARKING GARAGES | | | | | | 411.2.1 AUTOMOBILE PARKING GARAGES SHALL BE CLASSIFIED | | | AS EITHER OPEN, AS DEFINED IN 411.3, OR ENCLOSED AND | | | SHALL MEET THE APPROPRIATE CRITERIA OF 411.3 OR 411.4. | | | COMMENTPLEASE VERIFY OPEN OR ENCLOSED WITH THE CODE | | | SECTIONS PROVIDED | | | | | | FBC411.3ENCLOSED PARKING GARAGES | | | | | | FBC 411.4.1 ENCLOSED AUTOMOBILE PARKING GARAGES AND | | | PORTIONS THEREOF WHICH DO NOT MEET THE DEFINITION OF | | | OPEN PARKING GARAGES SHALL BE LIMITED TO THE ALLOWABLE | | | HEIGHTS AND AREAS SPECIFIED IN TABLE 500 FOR GROUP S | | | BUILDINGS. | | | | | | 411.4.2 A MECHANICAL VENTILATION SYSTEM FOR THE | | | REMOVAL OF THE PRODUCTS OF COMBUSTION SHALL BE | | | PROVIDED IN ENCLOSED AUTOMOBILE PARKING GARAGES. THE | | | MECHANICAL SYSTEM SHALL BE CAPABLE OF PROVIDING AT | | | LEAST 6 AIR CHANGES PER HOUR FOR EACH LEVEL. UNDER | | | NORMAL USE THE VENTILATION OF THE | | | ENCLOSED AUTOMOBILE PARKING GARAGE SHALL COMPLY WITH | | | THE VENTILATION REQUIREMENTS OF 411.5. | | | 411.2.2 THE CLEAR HEIGHT OF EACH FLOOR LEVEL IN | | | VEHICLE AND PEDESTRIAN TRAFFIC AREAS SHALL NOT BE LESS | | | THAN 7? | | | | | | FBC 411.3 OPEN PARKING GARAGES | | | | | | 411.3.1 OPEN AUTOMOBILE PARKING GARAGES WITH ROOF | | | PARKING MAY BE CONSTRUCTED TO THE ALLOWABLE HEIGHTS | | | AND AREAS SPECIFIED IN TABLE 411.3.1. TO BE CONSIDERED | | | OPEN, THE GARAGE SHALL MEET THE REQUIREMENTS OF | | | 411.3.2,411.3.3 AND411.3.4. | | | | | | 411.3.2 THE EXTERIOR AND INTERIOR WALLS OF THE GARAGE | | | SHALL BE DESIGNED IN ACCORDANCE WITH ONE OF THE | | | FOLLOWING: | | | | | | 1. AT LEAST 50 PERCENT OF THE CLEAR HEIGHT BETWEEN | | | FLOORS SHALL BE OPEN TO THE ATMOSPHERE FOR THE FULL | | | LENGTH OF AT LEAST TWO EXTERIOR WALLS, EXCLUDING | | | REQUIRED STAIR AND ELEVATOR WALLS AND STRUCTURAL | | | COLUMNS. INTERIOR WALL LINES AND COLUMN LINES SHALL BE | | | AT LEAST 20 PERCENT OPEN AND UNIFORMLY DISTRIBUTED, | | | OR | | | | | | 2. THE EXTERIOR WALLS OF THE STRUCTURE SHALL HAVE | | | UNIFORMLY DISTRIBUTED OPENINGS ON TWO OR MORE SIDES | | | TOTALING NO LESS THAN 40 PERCENT OF THE BUILDING | | | PERIMETER. THE AREA OF SUCH OPENINGS IN THE EXTERIOR | | | WALLS ON EACH LEVEL SHALL BE AT LEAST 20 PERCENT OF | | | THE TOTAL PERIMETER WALL AREA OF EACH LEVEL. INTERIOR | | | WALL LINES AND COLUMN LINES SHALL BE AT LEAST 20 | | | PERCENT OPEN AND UNIFORMLY DISTRIBUTED. | | | | | | 411.3.3 THE DISTANCE FROM ANY POINT ON ANY FLOOR LEVEL | | | TO AN OPEN EXTERIOR WALL FACING ON A STREET, OR TO | | | OTHER PERMANENTLY MAINTAINED OPEN SPACE AT LEAST 20 | | | FT (6096 MM) WIDE EXTENDING FULL WIDTH TO A STREET, | | | SHALL NOT EXCEED 200 FT (61 M). | | | | | | 411.3.4 GARAGES WITHIN 10 FT (3048 MM) OF A COMMON | | | PROPERTY OR BUILDING LINE SHALL BE PROVIDED WITH AN | | | ENCLOSURE WALL ALONG THE LINE OF NOT LESS THAN 1-HOUR | | | FIRE RESISTANCE WITHOUT OPENINGS THEREIN, EXCEPT DOOR | | | OPENINGS MEETING THE REQUIREMENTS OF705.1.3 SHALL BE | | | PERMITTED. | | | | | | | | | | | | | | | | | | 17 11-4.10 ELEVATORS | | | 11-4.10.9 FLOOR PLAN OF ELEVATOR CARS. THE FLOOR AREA | | | OF ELEVATOR CARS SHALL PROVIDE SPACE FOR WHEELCHAIR | | | USERS TO ENTER THE CAR, MANEUVER WITHIN REACH OF | | | CONTROLS, AND EXIT FROM THE CAR. ACCEPTABLE DOOR | | | OPENING AND INSIDE DIMENSIONS SHALL BE AS SHOWN IN | | | FIGURE 11-22. THE CLEARANCE BETWEEN THE CAR PLATFORM | | | SILL AND THE EDGE OF ANY HOIST WAY LANDING SHALL BE NO | | | GREATER THAN 1-1/4 INCHES (32 MM). | | | COMMENTPROVIDE A FLOOR PLAN OF THE ELEVATOR CAB | | | UTILIZING THIS SECTION OF THE ADACHAPTER 11 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-02-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-02-06 |
Time |
17:01 |
Rev Time |
4.44 |
| Received By |
jwitmer |
Date |
2007-02-06 |
Time |
17:01 |
Sent To |
|
|
| Notes |
| 2007-02-06 17:12:38 | BUILDING PLAN REVIEW | | | PERMIT: 05091686 | | | ADD: XXX N. CONGRESS/ W EXECUTIVE CENTER DR | | | CONT: CONTRAVEST BUILDERS | | | TEL: (407)509-2174 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | COURTNEY LAKES APARTMENTS, LLC | | | | | | 2NDREVIEW | | | ACTION: DENIED | | | | | | --- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | NOTE NOC WILL BE NULL & VOID 90 DAYS | | | AFTER RECORDING AT THE CLERK OF THE | | | COURTS OFFICE IF WORK HAS NOT STARTED. | | | FL S S 713.13(2). | | | | | | 2)THIS COMMENT WAS PARTIALLY SATISFIED, FOR THE WHOLE | | | OF THE PROJECT (3 BUILDINGS) | | | THREE SIGNED & SEALED REPORTS WERE SUBMITTED TO THE | | | CITY. THIS WILL SATISFY THE REQUIREMENT | | | TO HAVE (1 ) REPORT WITH EACH PERMIT OR BUILDING. THE | | | NEED STILL ARISES TO HAVE AT LEAST ONE SIGNED/ SEALED | | | ORIGINAL FOR THE CONTRACTOR AS WELL AS THE THRESHOLD | | | INSPECTOR. | | | AN ADDTIONAL 2 ORIGINAL SOILS REPORTS SIGNED & SEALED | | | SHALL BE REQUIRED. | | | FL BLD CODE 1804.2.2 QUESTIONABLE | | | SOILS, WHERE THE BEARING CAPACITY IS | | | NOT DEFINETLY KNOWN OR IS IN QUESTION. | | | WHERE THE BEARING CAPACITY OF THE SOIL | | | IS NOT DEFINITLY KNOWN OR IS IN QUESTION | | | THE BUILDING | | | | | | 3-4)COMPLIED. | | | | | | 5)BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 6) THE SUBMITTED THRESHOLD INSPECTION PLANS HAVE | | | PHOTO-COPIED SIGNATURES, THE SIGNED | | | THRESHOLD INSPECTION PLANS ARE TO BE ORIGINAL | | | SIGNATURES WITH RAISED SEAL. | | | PLANS, SPECIFICATIONS, REPORTS OR | | | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND | | | BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | | TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | | | | FL S. S. 553.71(7) " THRESHOLD | | | BUILDING" MEANING ANY BUILDING WHICH IS | | | GREATER THAN (3) STORIES OR 50 FT IN | | | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN | | | CY CLASSIFICATION AS DEINED IN THE | | | FLORIDA BUILDING CODE WHICH EXCEEDS | | | 5,000 SQ FT IN AREA AND AN OCCUPANT | | | CONTENT OF GREATER THAN 500 PERSONS. | | | | | | 105.13.1 THE ENFORCING AGENCY SHALL | | | REQUIRE A SPECIAL INSPECTOR TO PERFORM | | | SRUCTURAL INSPECTIONS ON A THRESHOLD | | | BUILDING PURSUANT TO A STRUCTURAL INSPEC | | | TION PLAN PREPARED BY THE ENGINEER OF | | | RECORD. THE STRUCTURAL INSPECTION PLAN | | | MUST BE SUBMITTED TO THE ENFORCING AGEN- | | | CY PRIOR TO THE ISSUANCE OF A BUILDING | | | PERMIT FOR THE CONSTRUCTION OF A THRESH- | | | OLD BUILDING. THE PURPOSE OF THE SRUCTUR | | | AL INSPECTION PLAN IS TO PROVIDE SPECIF- | | | IC INSPECTION PROCEDURES AND SCHEDULES | | | SO THAT THE BUILDING CAN BE ADEQUATELY | | | INSPECTED FOR COMPLIANCE WITH THE | | | PERMITTED DOCUMENTS. | | | | | | 7) 2ND REQUEST, THIS WILL REMAIN A COMMENT UNTIL | | | COMPLIANCE, | | | WPB AMENDMENT 105.13.6. W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT | | | REQUEST FOR THRESHOLD BUILDINGS A | | | SPECIAL INSPECTOR AS REQUIRED BY S. | | | 553.79(5) FLORIDA STATUTES TO THE MIN- | | | IMUM INSPECTIONS REQUIRED BY THIS CODE. | | | CONTACT HAROLD PISKURA MANAGER OF THE | | | SPECIAL INSPECTOR PROGRAM AT (561) | | | 805-6711 FOR FURTHER INFORMATION BEFORE | | | THE PERMIT MAY BE ISSUED. | | | | | | 8) COMPLIED. | | | | | | 9A) 2ND REQUEST, CONTACT LILI URSA FOR ADDRESSING | | | REQUIREMENTS@ (561)822-1239. | | | | | | 9B) 2ND REQUEST, PLEASE PROVIDE A COPY OF THE NEW PLAT, | | | THE LOT HAS BEEN SUBDIVIDED. | | | | | | 9C) 2ND REQUEST, ON ALL (3) PERMIT APPLICATIONS CORRECT | | | THE PROPERTY CONTROL NUMBER TO THE NEW LOT. | | | | | | 9D) 2ND REQUEST, PROVIDE A SITE PLAN WITH LOCATION OF | | | THE PROPOSED STRUCTURES WITH DIMENSIONS FOR TABLE 600 | | | ISSUES. | | | GNA2.01 HAS NO DIMENSIONS, AND THERE ARE NO CIVIL PLANS | | | IN THIS SET. THIS IS A STAND ALONE PERMIT AND WILL | | | REQUIRE | | | THIS INFORMATION BEFORE A PERMIT CAN BE ISSUED. | | | | | | 10A-G ) COMPLIED. | | | | | | 11 A-B) COMPLIED. | | | | | | 12) SITE PLAN A2.01 | | | NEW COMMENT THAT DEALS WITH THE OVER ALL PARKING SPACES | | | AND THE REQUIRED NUMBER OF ACCESSIBLE SPACES. THE PLANS | | | INDICATE A TOTAL OF 912 SPACES WHERE AS IT APPEARS TO | | | BE 1008 PARKING SPACES IF THIS IS TRUE THE REQUIRED | | | NUMBER OF ACCESSIBLE SPACES WOULD BE 21. | | | CHAPTER 11 PARTB- 4PARKING AND PASSENGER | | | LOADING:ACCESSIBLE PARKING ON A ROUTE ACCESSIBLE TO | | | WHEELCHAIRS FOR AT LEAST 2% OF THE COVERED DWELLING | | | UNITS: ACCESSIBLE VISITOR PARKING SUFFICIENT TO PROVIDE | | | ACCESS TO GRADE LEVEL ENTRANCES OF COVERED MULTIFAMILY | | | DWELLINGS; AND ACCESSIBLE PARKING AT FACILITIES (E.G., | | | SWIMMING POOLS) THAT SERVE ACCESSIBLE BUILDINGS. | | | | | | 12A) BLDG# 2 SHEET A5.30 THE ACCESSIBLE PARKING SPACE | | | DOES INDICATE THE ACCESS AISLE NOW BUT COLUMN LINE C-8 | | | DOESN,T LEAVE OR SHOW A 36" ACCESSIBLE PATH TO THE | | | ELEVATOR. | | | NOTE IF COLUMN C-8 IS< 24" THAN THE | | | ACCESSIBLE ROUTE COULD BE 32".ANSI A117.1-98TABLE | | | 403.5. | | | | | | 12B) 2ND REQUEST, ACCESSIBLE ROUTE, | | | FAIR HOUSING ACT AT LEAST ONE ACCESSIBLE ROUTE SHALL | | | BE | | | PROVIDED WITHIN THE BOUNDARY OF THE SITE | | | FROM PUBLIC TRANSPORTATION STOPS, | | | ACCESSIBLE PARKING SPACES, PASSENGER | | | LOADING ZONES IF PROVIDED, AND PUBLIC | | | STREETS OR SIDEWALKS, TO AN ACCESSIBLE | | | BUILDING ENTRANCE. | | | RESPONSE THAT THE CIVIL ENGINEER IS TO RESPOND? | | | | | | 12B)(1) PLEASE PROVIDE INFORMATION WHICH ACCESSIBLE | | | PARKING SPACES WILL BE THE VAN ACCESSIBLE SPACES? | | | CHAPTER 11 PART B ANSI A117-1 502.5 PARKING SPACESFOR | | | VANS SHALL HAVE A VERTICAL CLEARENCE OF 98" MINIMUM AT | | | THE SPACE AND ALONG THE VEHICULAR ROUTE THERETO. | | | | | | 12B)(2) PLEASE PROVIDE SIGNAGE FOR ALL ACCESSIBLE | | | PARKING SPACES . CHAPTER 11 PART B ANSI A117.1502.6. | | | | | | 12C) 2ND REVIEW, THE SITE PLAN DOES NOT PROVIDE ANY | | | INFORMATION AS TO CURB CUTS, PEDESTRIAN CROSS WALKS, | | | ETC. | | | | | | 13) SHEET A5.30 | | | | | | 13A) THE PLANS NOW DO SHOW DOOR IDENTIFICATION AND | | | RATINGS WITH THE EXCEPTION OF THE ENTRY DOORS TO THE | | | INDIVIDUAL UNITS NOR THE ELEVATOR MACHINE ROOM | | | DOORSHEET A5.31 . | | | SEE A9.01 DOOR SCHEDULE | | | | | | 13B)COMPLIED. | | | | | | 13C-F) COMPLIED. | | | | | | 14) SHEETA5.31: | | | | | | 14A)COMPLIED. | | | | | | 14B) THE CORRIDOR COMMON TO THE 2ND FLOOR THROUGH TO | | | THE 5TH FLOOR DOES NOT PROVIDE A CUT SECTION THROUGH | | | THE WALL OR IS THERE ANY WALL TAGS IDENTIFYING THE FIRE | | | RATING OF THIS WALL. | | | THE ENDS OF THE CORRIDOR DO HAVE 50% OPENINGS MEETING | | | THE REQUIEMENTS OF 1014.1.1. BUT NO MENTION OF WALL OR | | | DOOR RATINGS TO THE INDIVIDUAL UNITS.TABLE 704.2.4 THE | | | SECOND ISSUE IS THE FIRE SPRINKLER PLANS DO NOT | | | INDICATE ANY HEADS CEILING OR WALL MOUNT FOR THIS SAME | | | REGION? | | | | | | 15-16) COMPLIED. | | | | | | 17) 2ND REQUEST,PRODUCT APPROVALS SUBMITTED | | | WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 18) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, | | | PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) OPEABLE WINDOWS | | | FL 3485TRACO TR-6800 -OK | | | FL 3044.3TRACO HS-HC 65 NON-IMPACT WINDOW | | | REQUIRED 0-30'LARGE MISSLE, 30'-60'SMALL MISSLE - | | | DENIED | | | FL 3044.4TRACO HS-AW 55NON-IMPACT WINDOW | | | REQUIRED 0-30'LARGE MISSLE, 30'-60'SMALL MISSLE - | | | DENIED | | | FL 3044.5TRACO HS-AW55 NON-IMPACT WINDOW | | | REQUIRED 0-30'LARGE MISSLE, 30'-60'SMALL MISSLE - | | | DENIED | | | | | | B) FIXED WINDOWS | | | FL 3487TRACOTR-3800 - OK | | | FL 632KAWNEEREXPIRED NOA NON-IMPACT | | | REQUIRED 0-30'LARGE MISSLE, 30'-60'SMALL MISSLE - | | | DENIED | | | | | | C) MULLIONS MAY OR MAY NOT BE INCLUDED IN THE PRODUCT | | | APPROVALS | | | | | | D) EXTERIOR HOLLOW METAL DOORS | | | FL3078 AMWELD DENIEDLOW PRESSURESSINGLE & | | | PAIRS | | | | | | E) EXTERIOR GLAZED DOORS | | | FL 3038TRACO 03-0829.06 SMALL MISSLE ONLY, NO | | | PRESSURE TEST - DENIED | | | FL 3038.3TRACO 03-0422.04 TR-8910 SMALL MISSLE | | | TEST NO PRESSURE TEST - DENIED | | | FL 3038.4TRACO 03-0422.04 TR-8910 LARGE MISSLE | | | HIGHLIGHT ANCHOR FASTENING SCHEDULR MAY COMPLY | | | FL3477TRACO TR-8300SLIDING GLASS DOOR | | | NON-IMPACTREQUIRES 0-30' LARGE MISSLE, 30'-60' SMALL | | | MISSLE - DENIED | | | | | | F) EXTERIOR LOUVERED DOORS NO REPORT SUBMITTED | | | | | | G) EXTERIOR RAILINGS- WILL ONLY NEED ENGINEERING NOT A | | | PRODUCT APPROVAL | | | | | | H) LOUVERS NO REPORT SUBMITTED. | | | | | | I) TRUSS ANCHORS NO REPORT SUBMITTED. | | | | | | J) ROOF ASSEMBLIES INCLUDING DENSE DECK, INSULATION, | | | UNDERLAYMENTS, ROOF TILE AND ATTACHMENT METHODS. FL | | | 1559 SINGLE PLY ROOF SYSTEMS- HIGHLIGHT WHICH | | | SUB-SYSTEM TO BE USED. | | | NOTE ZONES 2 & 3 MAY REQUIRE ENHANCED FASTENING | | | PROVIDE RATIONAL ANALYSIS BY QUALIFIED PROFESSIONAL | | | | | | K) EFIS WALL SYSTEMS IF USED | | | | | | L)5/8" FIBER TOUGH AQUA ROCK SHEATHING | | | | | | M ) PRE-MANUFACTURED ROOF A/C STANDS- OK | | | | | | N) ROLL UP DOOR - NO REPROT SUBMITTED | | | | | | O) DENSE DECK- MAY BE INCORPORATED IN A PRODUCT | | | APPROVAL | | | | | | P) ROOF TILE - NO REPORT SUBMITTED- CIRCLE OR HIGHLIGHT | | | WHAT ANCHOR METHOD TO INSTALLROOF TILE | | | | | | 19-21)NO SHUTTERS ON PROJECT, AS PER THE DESIGN TEAM, | | | COMPLIED. | | | | | | 22- 27) COMPLIED. | | | | | | 28) IMPACT FEES COVERED UNDER ITEM# 5. | | | | | | 29A) DEALS WITH ROOF DECKING MATERIALS, YOUR RESPONSE | | | INDICATED SEE A7.02, A7.03 & A7.10FOR DECKING | | | REQUIREMENTS. | | | THESE SECTIONSSHOW THE DENSE DECK FASTENED DIRECTLY | | | TO THE STEEL TRUSSES, WHERE AS DETAIL2 S4.31 INDICATES | | | THE USE OF STEEL DECK AND DENSE DECK ABOVE THE | | | STRUCTURAL DECK. | | | PLEASE CLARIFY WHICH METHOD DENSE DECK WILL BE | | | INSTALLED? | | | | | | 29B) COMPLIED. | | | | | | 29C) 2ND REQUEST, 1404.1.1 STATES THAT ARCHITECURAL | | | TRIM TYPE I, II AND IV CONSTRUCTION CAN HAVE | | | COMBUSTIBLE TRIM. | | | | | | NOTE: CALCULTED VALUE $3,358,171.00 | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-02-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2006-02-06 |
Time |
14:53 |
Rev Time |
8.00 |
| Received By |
jwitmer |
Date |
2006-02-06 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2006-02-06 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 05091686 BLDG# 4 | | | ADD:XXX N CONGRESS | | | 74-43-43-20-00-000-3010 | | | CONT: E. A. LANDERS | | | TEL: (305)823-3938 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | * WEST PALM BEACH AMENDMENTS | | | | | | COURTNEY LAKES APARTMENTS, LLC | | | | | | ARCH: FORUM ARCHITECTURE & INTERIOR | | | | | | DESIGN | | | (407)830-1400 | | | STRUC: ROBERT PLOWFIELD & ASSOC | | | (407)657-6657 | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | ***IMPORTANT*** | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | | | | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | NOTE NOC WILL BE NULL & VOID 90 DAYS | | | AFTER RECORDING AT THE CLERK OF THE | | | COURTS OFFICE IF WORK HAS NOT STARTED. | | | FL S S 713.13(2). | | | | | | 2) FL BLD CODE 1804.2.2 QUESTIONABLE | | | SOILS, WHERE THE BEARING CAPACITY IS | | | NOT DEFINETLY KNOWN OR IS IN QUESTION. | | | WHERE THE BEARING CAPACITY OF THE SOIL | | | IS NOT DEFINITLY KNOWN OR IS IN QUESTION | | | THE BUILDING OFFICIAL MAY REQUIRE EXPLOR | | | ATIONS, TEST OR OTHER ADEQUATE PROOF AS | | | TO THE PERMISSIBLE SAFE BEARING | | | CAPACITY. REQUIRED TEST AND RECOMMENDA- | | | TIONS SUBMITTED TO VERIFY BEARING CAPA- | | | CITY SHALL BE CERTIFIED BY A GEOTECH- | | | NICALREPORT FROM A DESIGN PROFESSIONAL | | | PROPERLY LICENSED IN THE STATE OF | | | FLORIDA. | | | | | | 3) FL BLD CODE CHAP 13 ENERGY EFFICENCY | | | PROVIDE ENERGY CALS/ W MANUAL "J" | | | | | | 4) ARCHITECTURAL PAGES DO NOT HAVE A | | | RAISED SEAL. | | | PLANS, SPECIFICATIONS,REPORTS OR | | | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND | | | BEING FILED FOR PUBLIC | | | RECORD SHALL HAVE THE SIGNATURE AND | | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | | TO THE DOCUMENT. | | | FL STATE STAT: 61G15-23.002 ENGINEERS | | | FL ATATE STAT: 61G16.003 ARCHITECTS | | | | | | 5)BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 6)FL S. S. 553.71(7) " THRESHOLD | | | BUILDING" MEANING ANY BUILDING WHICH IS | | | GREATER THAN (3) STORIES OR 50 FT IN | | | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN | | | CY CLASSIFICATION AS DEINED IN THE | | | FLORIDA BUILDING CODE WHICH EXCEEDS | | | 5,000 SQ FT IN AREA AND AN OCCUPANT | | | CONTENT OF GREATER THAN 500 PERSONS. | | | | | | 105.13.1 THE ENFORCING AGENCY SHALL | | | REQUIRE A SPECIAL INSPECTOR TO PERFORM | | | SRUCTURAL INSPECTIONS ON A THRESHOLD | | | BUILDING PURSUANT TO A STRUCTURAL INSPEC | | | TION PLAN PREPARED BY THE ENGINEER OF | | | RECORD. THE STRUCTURAL INSPECTION PLAN | | | MUST BE SUBMITTED TO THE ENFORCING AGEN- | | | CY PRIOR TO THE ISSUANCE OF A BUILDING | | | PERMIT FOR THE CONSTRUCTION OF A THRESH- | | | OLD BUILDING. THE PURPOSE OF THE SRUCTUR | | | AL INSPECTION PLAN IS TO PROVIDE SPECIF- | | | IC INSPECTION PROCEDURES AND SCHEDULES | | | SO THAT THE BUILDING CAN BE ADEQUATELY | | | INSPECTED FOR COMPLIANCE WITH THE | | | PERMITTED DOCUMENTS. | | | | | | 7) WPB AMENDMENT 105.13.6. W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT | | | REQUEST FOR THRESHOLD BUILDINGS A | | | SPECIAL INSPECTOR AS REQUIRED BY S. | | | 553.79(5) FLORIDA STATUTES TO THE MIN- | | | IMUM INSPECTIONS REQUIRED BY THIS CODE. | | | CONTACT HAROLD PISKURA MANAGER OF THE | | | SPECIAL INSPECTOR PROGRAM AT (561) | | | 805-6711 FOR FURTHER INFORMATION BEFORE | | | THE PERMIT MAY BE ISSUED. | | | | | | 8) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS | | | FOR THE BUILDING WHICH ARE REQUIRED TO | | | BE SIGNED AND SEALED BY THE ARCHITECT OR | | | ENGINEER OF RECORD CON- TAIN A STATEMENT | | | THAT, TO THE BEST OF THE ARCHITECT'S PR | | | ENGINEER'S KNOWLEDGE, THE PLANS AND | | | SPECIFICATIONS COMPLY WITH THE | | | APPLICABLE FIRE-SAFETY STANDARDS AS | | | DETERMINED BY THE LOCAL AUTHORITY IN | | | ACCORDANCE WITH THIS SECTION AND 633 | | | FLORIDA STATUTE. | | | | | | 9A) CONTACT LILI URSA FOR ADDRESSING | | | REQUIREMENTS @ (561)822-1239 | | | | | | 9B)PROVIDE A COPY OF THE NEW PLAT, LOT | | | HAS BEEN SUBDIVIDED. | | | | | | 9C) ON ALL (3) PERMIT APPLICATIONS | | | CORRECT THE PROPERTY CONTROL NUMBER TO | | | THE NEW LOT. | | | | | | 9D) PROVIDE A SITE PLAN WITH LOCATION OF | | | | | | THE PROPOSED STRUCTURES WITH DIMENSIONS | | | FOR TABLE 600 ISSUES.A2.01 HAS NO | | | DIMENSIONS! | | | | | | 10A) CORRECT PERMIT APPLICATIONS AS TO | | | DESRIPTION OF WORK FOR THE THREE | | | BUILDINGS, CURRENTLY THERE WILL BE 1350 | | | UNITS ON THIS PROJECT WHEN FINISHED, SEE DESCRIPTION OF | | | PROJECT, EACH APPLICATION | | | FOR BUILDINGS 1, 450 UNITS BUILDING 2 | | | 450 UNITS & BUILDING 3, 450 UNITS | | | TOTALING 1350. . | | | | | | 10B) PLEASE PULL PLANS APART INTO 3 SETS | | | OF PLANS SO ALL PAGES THAT DEAL WITH | | | BUILDING # 1 ARE IN ONE SET ETC. | | | | | | 10C) ADDITIONAL INFORMATION REQUIRED FOR | | | RECORD KEEPING PURPOSES 106.1.2*: | | | 10C)A) FLOOD ZONE | | | 10C)B) FLOOD ELEVATION (IF A ZONE) | | | 10C)C) LOMAR (IF A ZONE) | | | 10C)D) NUMBER OF UNITS | | | 10C)E) NUMBER OF FLOORS | | | 10C)F) NUMBER OF BEDROOMS | | | 10C)G) NUMBER OF ROOMS | | | 10C)H) NUMBER OF BATHROOM | | | 10C)I) SQ FT LIVING SPACE(TOTAL) | | | 10C)J) SQ FT FOOT PRINT | | | 10C)K) SQ FT UNDER ROOF (TOTAL) | | | | | | 10D) THE DESCRIPTION OF BUILDINGS AND | | | PHASING ARE CONFUSING BECAUSE THE | | | TERMINOLOGY, CURRENTLY THE CONTRACTOR | | | HAS PERMIT APPLICATIONS IN FOR BUILDINGS | | | 1,2& 3 NOT 4 NOR 5 AS BUILDINGS ARE | | | DEPICTED ON SHEET A1.02. | | | | | | 10E) THIS REVIEW WILL CONSTITUTE OF | | | BUILDING# 4 OF 44,120 SQ FT. PLANS | | | REFER TO THIS AS BEING BLDG #4. | | | | | | 10F) A1.02 CODE COMPLIANCE FOR APARTMENT BUILDINGS | | | PLANS INDICATE TYPE IV, UNPROTECTED , | | | SPRINKLERED | | | MAXIMUMHEIGHT ALLOWED IS 55' | | | PROPOSED HEIGHT69'-3" | | | PLEASE CORRECT BUILDING TYPE!!!!!! | | | 503.2.2 ALLOWED THE DEDUCTION OF 1 STORY | | | FOR THE PARKING GARAGE IF TYPE I OR TYPE | | | II BUILDING. | | | | | | 10G) DISCREPANCY A1.02 CONSTRUCTION TYPE | | | IV UNPROTECTED VS A1.21 FIRE RATING | | | IV I HR RATED. | | | | | | 11) SHEET A1.05 | | | | | | 11A) PLEASE PROVIDE THE LISTING FOR | | | RATED WALLS, U.L. OR OTHER | | | RECOGNIZED LISTING AGENCY. | | | | | | 11B) PLANS INDICATE USE OF RINKER BLOCK, | | | PROVIDE FROM THE MANUCATURER THE | | | EQIVALENT THICKNESS OF BLOCK,709.3.1.1 | | | THE FIRE RESISTANCE RATING OF WALLS AND | | | PARTITIONS CONSTRUCTED OF CONCRETE | | | MASONRY UNITS SHALL BE DETERMINED FROM | | | TABLE 709.3.1.THE RATING SHALL BE | | | BASED ON THE EQUIVALENT THICKNESS OF THE | | | MASONRY AND TYPE OF AGGREGATE USED. | | | | | | 12)SITE PLAN A2.01 | | | | | | 12A)SHEET A5.30 HANDICAPPED SPACES BLDG# | | | 4 DOESN'T INDICATE ACCESS EGRESS ISLES? | | | | | | 12B) ACCESSIBLE ROUTE: FAIR HOUSING ACT | | | LEAST ONE ACCESSIBLE ROUTE SHALL BE | | | PROVIDED WITHIN THE BOUNDARY OF THE SITE | | | FROM PUBLIC TRANSPORTATION STOPS, | | | ACCESSIBLE PARKING SPACES, PASSENGER | | | LOADING ZONES IF PROVIDED, AND PUBLIC | | | STREETS OR SIDEWALKS, TO AN ACCESSIBLE | | | BUILDING ENTRANCE. | | | | | | 12C) SITE PLAN DOES NOT PROVIDE ANY | | | INFORMATION AS TO CURB CUTS, PEDSTRIAN | | | CROSS WALKS, ETC. | | | | | | 13) SHEET A5.30: | | | | | | 13A) WHEN CHECKING DOORS FOR THE | | | COMPLETE BUILDING AGAINST THE DOOR | | | SCHEDULE ON A9.01 NOT A SINGLE DOOR | | | SHOWS FIRE RESISTANCE RATING. | | | | | | 13B) GARARE LEVEL THE ELEVATOR LOBBY | | | DOOR 4.001 SWINGS THE WRONG WAY FOR | | | EXITING, NO RATING. | | | | | | 13C) TRASH REFUSE ROOM # 4 NO DOOR | | | IDENTICATION, NO RATING. | | | | | | 13D) FIRE PUMP ROOM NO RATING OF DOOR | | | | | | 13E) PARKING GARAGE TO BE CONSIDERED AN | | | ENCLOSED PARKING GARAGE PROVIDE | | | COMPLIANCE WITH 6 AIRCHANGES PER | | | HR.411.4.2. | | | | | | 13F) MAILBOXES SEE DETAIL A5.56 DETAIL | | | # 7, PROVIDE DIMENSIONS (ELE) TO COMPLY | | | WITH SIDE REACH RANGES. | | | | | | 14) SHEET A5.31 | | | | | | 14A) THIS SHEET INDICATES IT IS COMMON | | | TO THIS FLOOR AND THE NEXT THREE FLOORS | | | ABOVE. THIS SHEET INDICATES A SPIRAL | | | STAIR WITHIN DWELLING UNITS THAT WOULD | | | THEN CONNECT ALL FLOORS AND MAKE A | | | ATRIUM BETWEEN ALL HABITABLE FLOORS ON | | | THAT SIDE OF THE BUILDING?THERE IS | | | ALSO NO SECURITY THEN BETWEEN UNITS? | | | | | | 14B) THIS SHEET NEEDS MORE CUT SECTIONS | | | DEPICTING AREAS AT THE END OF THE EXIT | | | ACCESS CORRIDOR BY ROOM A3. IT APPEARS | | | THAT THIS MAY BE A WINDOW OR AN OPENING | | | WITH HANDRAIL, IT IS NOT CLEAR? | | | | | | 14C)THE 2 STAIRWELLS DO NOT HAVE WALLS | | | AND DOORS TO ENCLOSE THEM MAKING A | | | SHAFT. THEY DO NOT HAVE ENOUGH OPENNESS | | | TO BE CONSIDERED AN OPEN STAIR | | | ENCLOSURE. PLANS INDICATE A DETAIL ON | | | A8.01 DETAIL# 2 - NO SUCH DETAIL. | | | IF THE STAIRWELL WERE TO BE CONSIDERED | | | OPEN, SEE 1006.1.3.2 CODE COMMENTARY FOR | | | RATED OPENINGS WITHIN 10 FT OF STAIRWELL | | | WALLS. 3/4 HR OPENING PROTECTIVES. | | | | | | 14D) UNITS A3/ B4 ARE ON A DEAD END | | | CORRIDOR SINGLE MEANS OF EGRESS WILL | | | REQUIRE RATED DOORS, 1006.2.2. | | | | | | 15) S SHEETS DO NOT PROVIDE INFORMATION | | | FOR BUILDING 4 OR 5 SEE INDEX A1.01. | | | | | | 16)ELEVATIONS ONLY SHOW 2 WALLS OF | | | BUILDING SEE AA6.05. | | | | | | 17) PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | | | | 18) FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | A) OPARATABLE WINDOWS | | | B) FIXED WINDOWS | | | C) MULLION | | | D) EXTERIOR DOORS SOLID | | | E) EXTERIOR DOORS GLAZED | | | F) EXTERIOR DOORS LOUVERED | | | G) STORM SHUTTERS | | | H) EXTERIOR RAILINGS | | | I) LOUVERS | | | J) TRUSS ANCHORS | | | K) ROOFING ASSEMBLIES | | | L) EFIS SYSTEMS | | | | | | 19) AN INTERPRETATION FROM THE BUILDING | | | OFFICIAL ON STORM SHUTTERS THAT ARE USED | | | ON LARGE PROJECTS: | | | QUESTION# 13) RECOGNIZING SUCH CONCERNS | | | AS ABSENTEE OWNERS, OR CASES WHERE | | | LONGER TIME AND EFFORT IS NECESSARY TO | | | SECURE SHUTTERS ON LARGE OR MULTI-STORY | | | BUILDINGS, WHAT MEASURES ARE BEING | | | RECOMMENDED OR IMPLEMENTED TO ENSURE | | | THAT COMPLETE INSTALLATION OR SECURING | | | IS DONE SUFFICIENTLY IN ADVANCE OF THE | | | HURRICANE EVENT? | | | | | | IN MATTERS FLORIDA BUILDING CODE, 2004 | | | EDITION, PROVIDES THE ABILITY FOR THE | | | BUILDING OFFICIAL TO IMPLEMENT | | | REQUIREMENTS FOR ENSURING STABILITY, | | | STRENGTH, AND PROPER OPERATION OF | | | EXISTING BUILDINGS. | | | | | | IN ORDER TO ASSURE THE SECURING OF | | | SHUTTERS ON LARGE OR MULTI-STORY | | | BUILDING, OR MULTIPLE BUILDINGS ON THE | | | SAME PROPERTY, PRE-STORM PREPARATION | | | PLANS MUST BE SUBMITTED BY THE PROPERTY | | | OWNERS OR MANAGING AGENTS FOR REVIEW BY | | | THE CONSTRUCTION SERVICES DEPARTMENT. | | | ANY SUCH PLAN SHALL INCLUDE, AT A | | | MINIMUM, ON-SITE LOCATION OF SHUTTERS, | | | PARTY RESPONSIBLE FOR SECURING THE | | | SHUTTERS (SAID PARTIES MUST BE LOCATED | | | WITHIN PALM BEACH COUNTY), TOTAL NUMBER | | | OF OPENINGS TO BE PROTECTED AND TOTAL | | | TIME REQUIRED TO SECURE ALL OPENINGS. | | | PROTECTION OF OPENINGS SHALL BE | | | ACCOMPLISHED WITHIN TWELVE (12) HOURS OR | | | LESS OF THE OFFICIAL NOTIFICATION BY THE | | | NATIONAL WEATHER SERVICE OF A HURRICANE | | | WATCH. | | | | | | PROVISIONS IN THE BUILDING CODES (AND | | | THIS STANDARD) ARE NOT INTENDED TO | | | PROHIBIT THE USE OF ALTERNATIVE | | | MATERIALS AND METHODS, AND ALLOW THE | | | BUILDING OFFICIAL TO REVIEW AND APPROVE | | | ANY ALTERNATE DEEMED EQUIVALENT IN | | | QUALITY, STRENGTH, EFFECTIVENESS, FIRE | | | RESISTANCE, DURABILITY AND SAFETY | | | PRESCRIBED BY CODE. BASED UPON THIS CODE PROVISION, | | | ACCEPTANCE OF ALTERNATE | | | MATERIALS AND METHODS MAY BE APPROVED ON | | | A CASE-BY-CASE BASIS AND SHALL REQUIRE | | | SUFFICIENT EVIDENCE OR PROOF TO | | | SUBSTANTIATE ANY CLAIM MADE REGARDING | | | THE ALTERNATE. | | | | | | QUESTION# 14) ARE REMOVABLE STORM PANELS APPROPRIATE | | | FOR USE ON VERY LARGE, MID | | | OR HIGH-RISE STRUCTURES? | | | | | | NO, EXCEPT ON THE GROUND FLOOR. ON | | | COMMERCIAL AND MULTI-UNIT RESIDENTIAL | | | STRUCTURES, ABOVE THE FIRST LEVEL, | | | IMPACT RESISTANT GLAZING OR PERMANENTLY | | | AFFIXED PROTECTIVE DEVICES SHALL BE | | | INSTALLED. PERMANENTLY AFFIXED | | | PROTECTIVE DEVICES SHALL REQUIRE THE | | | WRITTEN APPROVAL OF THE BUILDING | | | OFFICIAL. | | | | | | 20) PROVIDE STORM PANEL INFORMATION WITH INSTALLATION | | | SCHEDULE AND KEY PLAN WITH | | | SPECIFIC ANCHORS AND MOUNTING TO BE USED | | | FOR ALL NON-IMPACT GLAZING. | | | FBC 1606.1.4. | | | | | | 21) FL BLD CODE 2001 SECTION 103.6, | | | 1606.1.4, 1707.4 & 3401.7.2.4. | | | PROCEDURES: 1(B) A COMPLETE INSTALLATION | | | SCHEDULE SUMMARIZING & IDENTIFYING | | | OPENING SIZES, STORY HEIGHTS, UNIT MARK | | | NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM | | | BAR REINFORCING REQUIREMENTS, WALL PRES- | | | SURE ZONES, SLAT TYPES, ETC., SHALL BE | | | SUBMITTED AT TIME OF PERMIT APPLICATION | | | TO FACILITATE PLAN REVIEW AND PERMIT | | | ISSUANCE. | | | | | | 22) PLANS DO NOT INDICATE ANY MECHANICAL | | | ROOM FOR THE ELEVATOR ON THE GARAGE | | | FLOOR, THE COMMON SHEET 2-5 NOR THE | | | ROOF LEVEL SHEET? | | | | | | 23)3003.6.1 VENTS. HOISTWAYS OF ELEVA- | | | TORS SERVING MORE THAN 3 FLOORS SHALL BE | | | PROVIDED WITH MEANS OF VENTING SMOKE AND | | | HOT GASES TO THE OUTER AIR IN CASE OF | | | FIRE. | | | | | | 24) 3003.6.2 VENTS SHALL BE LOCATED | | | BELOW THE FLOOR OR FLOORS AT THE TOP OF | | | THE HOISTWAY, AND SHALL BE EITHER DIR- | | | ECTLY TO THE OUTER AIR OR THROUGH NON- | | | COMBUSTIBLE DUCTS TO THE OUTER AIR. | | | | | | 25) 3003.6.3 THE AREA OF THE VENTS SHALL | | | BE NOT LESS THAN 3 SQ FT FOR EACH | | | ELEVATOR CAR, WHICHEVER IS GREATER. | | | | | | 26) A5.32: | | | | | | 26A) PLANS DO NOT INDICATE WHAT TYPE OF | | | STRUCTURES (4) ARE2 LOCATED 1/3RD THE | | | DISTANCE IN FROM THE END? | | | | | | 26B) 1511.7 ROOF MOUNTED MECHANICAL | | | UNITS SHALL BE MOUNTED ON CURBS RAISED A | | | MINIMUM OF 8 INCHES ABOVE THE ROOF SUR- | | | FACE, OR WHERE ROOFING MATERIALS EXTEND | | | BENEATH THE UNIT, ON RAISED EQUIPMENT | | | SUPPORTS PROVIDING A MINIMUM CLEARENCE | | | HEIGHT IN ACCORDANCE WITH TABLE 1511.7. | | | | | | | | | 27) 1503.4.4 PROTECTION AGAINST DECAY & | | | TERMITES. CONDENSATE LINES & ROOF DOWN | | | SPOUTS SHALL DISCHARGE AT LEAST 1 FT. | | | AWAY FROM THE STRUCTURE SIDEWALL, | | | WHETHER BY UNDERGROUND PIPING, TAIL EX- | | | TENSIONS, OR SPLASH BLOCKS. | | | | | | 28)BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 29) VARIOUS SHEETS ON BUILD 4 | | | INDICATE A DETAIL SECTION# 23 SHEET | | | A7.10. | | | | | | 29A) THIS SECTION INDICATES METAL | | | TRUSSES TO BE USED BUT NO INFORMATION | | | AS TO THE ROOF DECKING MATERIAL TO BE | | | USED? TYPE IV UNPROTECTED- NC | | | TYPE IV 1HR- IHR PROTECTED | | | | | | 29B) PROVIDE A DETAIL INDICATING ACCESS | | | TO ATTIC AREA. | | | | | | 29C) THIS SAME SECTION INDICATES USE OF | | | FOAM TRIM ON THE EXTERIOR OF THE | | | BUILDING ABOVE 40'.1404.1.1 | | | ARCHITECTURAL TRIM ON BUILDINGS OF TYPE | | | I, II AND IV CONSTRUCTION NOT MORE THAN | | | THREE STORIES OR 40 FT (12.2 M) HIGH MAY | | | BE OFTYPE VI CONSTRUCTION, AND MAY BE | | | OF TYPE VI CONSTRUCTION ON ALL BUILDINGS | | | OF TYPE III, V AND VI CONSTRUCTION. | | | TRIM SHALL BE SECURED TO THE WALL WITH | | | METAL OR OTHER APPROVED BRACKETS OR | | | FASTENERS.WHEN ARCHITECTURAL TRIM IS | | | LOCATED ALONG THE TOP OF EXTERIOR WALLS, | | | IT SHALL BE COMPLETELY BACKED BY THE | | | EXTERIOR WALL AND SHALL NOT EXTEND OVER | | | THE TOP OF EXTERIOR WALLS. | | | | | | | | | | | | | | | PLANS NEED TO BE BROKEN OUT TOO | | | BUILDINGS TYPE, ONCE PLANS ARE | | | RESUBMITTED WITH RESPONCE SHEET | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE | | | NOT ON THE FIRST REVIEW. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-09-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-09-18 |
Time |
08:11 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-09-16 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2007-09-19 13:06:28 | *** NOTES ADDED** | | | | | | **) PLEASE SEE NOTES ADDED UNDER BUILDING #3 FOR FIRE | | | PUMP. | | | **) PLEASE SEE NOTES ADDED UNDER BUILDIGN#3 FOR | | | POSSIBLE CONCERNS WITH EGRESS LIGHITNG FROM UNITS, B4, | | | C-3 SPIRAL STAIRS.MAY NOT USE SWITCHED RECEPTACLE. | | | THIS COMMENT WAS NOT MADE ON PREVIOUS REVIEW AS THESE | | | AREAS AND USE IS NOW MORE CLEAR. | | | **) PLEASE SEE NOTES ON ELECTRICAL RISER NEEDS TO MEET | | | AND CORRELATE WITH RISER. EXAMPLE, SEE NOTE #10 WHICH | | | MENTIONS POWER COMPANY TO INSTALL CONDUCTORS, HOWEVER | | | PLEASE KNOW THE POWER COMPANY DOES NOT TYPICALLY | | | INSTALL CONDUCTORS AFTER METERING DEVICES. | | 2007-09-18 08:12:07 | 2007-09-18 08:12:07 | | | | | | ** DENIED 3RD REVIEW** | | | | | | ** PLEASE SEE THERE ARE SOME ITEMS FROM PREVIOUS REVIEW | | | WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE ALSO SEE | | | THERE ARE SOME NEW COMMENTS BASED ON REVISED | | | PLANS/PLANS AND DOCUMENTS NOW SUBMITTED. | | | ** SOME ITEMS COULD HAVE BEEN REDLINED/PROVISO, HOWEVER | | | SOME CAN NOT BE AT THIS TIME. | | | | | | 1) NOTE:PLEASE SEE THE PLANS DO NOT INDICATE FIXTURE | | | DESIGNATIONS FOR ALL LIGHTING. | | | PLEASE SEE COMMON AREAS WHICH THE LEGEND ON ELECTRICAL | | | PLANS COULD NOT BE FOUND. | | | PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORT FOR | | | EXTERIOR LIGHTING ALSO NEEDS TO CORRELATE WITH PLANS. | | | THE LIGHTING, TYPES, NUMBER OF FIXTURES, ETC IS NOT | | | STATED ON THE IDR AS ON PLANS. | | | PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED AS THE | | | INPUT DATA REPORT DOES NOT CORRELATE WITH ALL | | | ELECTRICAL LIGHTING WHICH IS ON PLANS. PLEASE SEE | | | MISSING A SUBSTANTIAL AMOUNT OF LIGHTING ON THE INPUT | | | DATE REPORT. | | | 13-415.0, 415.1.ABCD, 415.1.A, 415.2 | | | | | | 2) NOTE: PLEASE SEE ONLY ONE COPY OF THE ENERGY | | | CALCULATIONS (1.22 VERSION) SUBMITTED ACTUALLY CONTAINS | | | AN ORIGINAL SIGNATURE AND DATE. PLEASE SEE THAT TWO | | | SETS CONTAIN A RAISED SEAL OVER A PHOTO-COPIED | | | SIGNATURE AND THE THIRD DOES NOT CONTAIN A RAISED | | | SEALED OR ORIGINAL SIGNATURE. | | | **PLEASE KNOW THIS COMMENT HAS BEEN MADE TO THIS DESIGN | | | PROFESSIONAL ON SEVERAL PROJECTS SUBMITTED TO THIS | | | JURISDICTION. THIS COMMENT WILL ALSO BE UNDER BUILDINGS | | | 1 AND 3. | | | PLEASE KNOW THIS OFFICE IS RETAINING ALL COPIES | | | SUBMITTED FOR POSSIBLE SUBMISSION TO THE FLORIDA BOARD | | | OF ENGINEERS. | | | THIS IS A FLORIDA STATUTE AND IS ALSO STATED IN THE | | | FLORIDA ADMINISTRATIVE CODE.FS 471.025, FAC | | | 61G15-23.002., FBC 103.1. | | | ** WHEN PLANS WERE RE-SUBMITTED THIS REVIEWER NOTICED | | | THE INCORRECT VERSION ON THE CALCULATIONS SUBMITTED AND | | | NEW CALCULATIONS WITH THE CORRECT VERSION WAS SENT VIA | | | FED-EX. PLEASE SEE THAT THE ONES DONE UNDER THE 2004 | | | FBC WERE ALSO NOT SIGNED, DATED AND SEALED CORRECTLY | | | AND AS REQUIRED. | | | | | | | | | 3) NOTE: PLEASE SEE INFORMATION FOR SITE LIGHTING POLES | | | DO NOT CONTAIN THE MINIMUM WIND LOAD INFORMATION. | | | PLEASE KNOW IF THIS INFORMATION IS NOT COMPLETE UNDER | | | BASE PLANS, THESE WILL BE REQUIRED TO BE UNDER SEPARATE | | | PERMITS, PLANS AND FEES. | | | PLEASE KNOW HOWEVER THE LIGHTING INFORMATION AS NOTED | | | ABOVE IN NOTE #1 FOR THE ENERGY CALCULATIONS WILL STILL | | | NEED TO BE CORRECTED. | | | | | | 4) NOTE: PLEASE SEE THE SYMBOL LEGEND STILL INDICATES | | | *SMOKE DETECTORS*. THIS COULD BE REDLINED IF AND WHEN | | | ALL OTHER COMMENTS AS ADDRESSED. PLEASE KNOW IF THERE | | | ARE ANY COMMENTS HOWEVER WHICH MAY AFFECT THE SAME | | | SHEET(S), PLEASE CORRECT AT THIS TIME. E16.01 | | | | | | 5) NOTE: PLEASE SEE SHEET E16.04 AS THE MAIL ROOM DOES | | | NOT CONTAIN ANY DOORS, OPENINGS, OR LIGHTING. PLEASE | | | SEE THE SHEET A1.30 DOES NOT INDICATE THE SAME LAYOUT | | | FOR THIS AREA. PLEASE CORRELATE THE TWO AS THESE | | | LAYOUTS DO NOT MATCH AT THIS TIME. | | | PLEASE SEE ANY CHANGES IN LIGHTING ETC. | | | FBC 104.1.2 (2001) ADMIN SECTION FOR ADDITIONAL | | | INFORMATION AND COORDINATION OF PLANS. | | | | | | 6) NOTE: PLEASE SEE DISHWASHER AND DISPOSAL WHICH IS | | | BEING SHOWN WITH A J-BOX. ARE THESE ITEMS GOING TO BE | | | HARDWIRED? | | | PLEASE SEE 422.30, 422.31 FOR REQUIRED DISCONNECTING | | | MEANS. | | | ARE THESE NOT CORD AND PLUG TYPE APPLIANCES WHICH WOULD | | | PLUG IN? | | | | | | | | | ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES | | | WHICH MAY AFFECT ELECTRICAL PLANS. | | | | | | ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. | | | | | | *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS | | | OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. | | | IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY | | | WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, | | | PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND | | | THIS REVIEWER. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2007-09-16 13:36:05 | 2007-09-16 13:36:05 | | | | | | REVIEW TO CONTINUE ON 9/17> REVIEWNOTES TO FOLLOW | | | ONCE REVIEW IS COMPLETED. | | | THERE WILL BE ITEMS THAT NEED TO BE ADDRESSED. | | 2007-09-16 13:01:25 | 2007-09-16 13:01:25 | | | | | | IN ELEC FOR REVIEW |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-01-01 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-01-01 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-12-31 |
Time |
20:34 |
Sent To |
|
|
| Notes |
| 2007-01-01 09:01:37 | **** UNSAT2ND REVIEW ******** | | | | | | COURTNEY LAKES BUILDING #2 | | | N. CONGRESS. | | | | | | ** PLEASE SEE MANY OF THE SAME COMMENTS FROM THE | | | PREVIOUS REVIEW STILL NEED TO BE ADDRESSED. | | | | | | ** PLEASE SEE AS THREE SEPARATE BUILDING PERMITS AND | | | PLANS ARE NOW SEPARATED FOR EACH, PLEASE ALSO SEE NEW | | | COMMENTS BASED ONE THE PLANS NOW SUBMITTED INTO EACH | | | SET. | | | | | | ** PLEASE ALSO SEE THERE ARE SOME NEW NOTES BASED ON | | | PLANS SUBMITTED. | | | | | | ** PLEASE SEE BELOW ARE SOME OF THE NOTES FROM THE | | | PREVIOUS REVIEW ARE BEING NOTED IF ADDRESSED OR NOT BY | | | A "NO, OK, NO/OK, N/A OR SEE NEW ". | | | 1) NO WILL HAVE FURTHER EXPLANATION IN AN ATTEMPT TO | | | BETTER EXPLAIN COMMENT MADE. | | | 2) OK, WILL HAVE PREVIOUS NOTE REMOVED. | | | 3) NO/OK, MEANS PART OF THE COMMENT MAY HAVE BEEN | | | ADDRESSED, HOWEVER NOT ALL. THIS WILL ALSO BE FOLLOWED | | | BY FURTHER EXPLANATION OF PREVIOUS NOTE. | | | 4) N/A, THIS MEANS THE COMMENT NO LONGER APPLIES TO | | | THIS BUILDING AND PREVIOUS NOTE IS REMOVED. | | | | | | ** PLEASE SEE ALL NEW NOTES WILL BE NOTED AT THE END OF | | | PREVIOUS REVIEW COMMENTS AND WILL BE INDICATED WITH | | | **** NEW NOTES**. | | | | | | | | | 1) NOTE: NO, PLEASE SEE THE SETS ARE NOT BOUND TOGETHER | | | IN A FASHION TO SECURE ALL SHEETS. PLEASE SEE THE | | | STAPLES BEING USED DO NOT GO THROUGH ALL SHEETS. PLEASE | | | SEE SOME SETS WERE ALREADY COMING APART BEFORE THEY | | | WERE OPENED FOR REVIEW. PLEASE SEE THIS IS REQUIRED FOR | | | ALL SETS AND FOR ALL PLANS. PLEASE OBTAIN A METHOD TO | | | SECURE AND BOUND PLANS TOGETHER.IF PLANS COME BACK IN | | | THE SAME FASHION, THE CONTRACTOR WILL BE CALLED TO COME | | | IN AND PICK UP PLANS TO BE CORRECTED BEFORE PROCESSING | | | FOR REVIEW WILL TAKE PLACE. | | | THE STAPLES IN SOME HAVE ALREADY COME COMPLETELY OUT. | | | THIS COMMENT IS FOR ALL WHETHER OR NOT COMMENT IS MADE | | | FOR OTHER BUILDINGS OR BY OTHER TRADES. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SUBMIT COMPLETED PLANS BOUND TOGETHER IN AN | | | APPROPRIATE FASHION. PLEASE SEE ALL SHEETS WERE | | | SUBMITTED LOOSELY AND NOT BOUND IN SETS. | | | | | | | | | | | | 2) NOTE: OK | | | | | | 3) NOTE:NO, PLEASE SEE RESPONSE MENTIONS PLANS | | | DESIGNED UNDER THE CODES AS NOTED, HOWEVER ALL CODES | | | RELEVANT TO THE DESIGN IN WHICH THE BUILDING IS | | | PERMITTED UNDER SHALL BE STATED ON PLANS. PLEASE SEE | | | THIS IS REQUIRED OF ARCHITECTURAL SHEETS AS WELL AS | | | ELECTRICAL AND FIRE. PLEASE SEE ANY OTHER NOTES WITH | | | RESPECT TO THIS FROM OTHER TRADES. | | | THE FOLLOWING SHALL BE STATED. 2002 NEC/NFPA-70, 2002 | | | NFPA-72, 2003 NFPA-20 AND 2003 NFPA-101. (THE CORRECT | | | NFPA-101 IS NOTED ) | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE BE SURE TO CORRECT THE CURRENT NEC/ NFPA-70 IN | | | EFFECT. | | | PLEASE KNOW, AS OF JULY 1ST, 2003 THE STATE OF FLORIDA | | | ADOPTED THE 2002 | | | NFPA-70 (NEC). PLANS REFERENCE 1999. PLEASE SEE SOME | | | ELECTRICAL COMMENTS WHICH WILL AFFECT THIS. | | | PLEASE SEE NEXT COMMENT WITH RESPECT TO PERMITS APPLIED | | | FOR UNDER THE 2001 FBC BEFORE OCT 1ST, 2005 AND PERMITS | | | ON OCT 1ST, 2005. | | | | | | 4) NOTE: N/A, SEE NEW NOTES FOR EACH BUILDING. | | | | | | | | | 5) NOTE: N/A, SEE NEW NOTES UNDER EACH BUILDING. | | | | | | 6) NOTE:NO, PLEASE SEE THERE ARE SEVERAL AREAS WHICH | | | CIRCUITING IS NOT COMPLETE INCLUDING UNITS FOR SMOKE | | | DEVICES AND MANY AREAS OF HOUSE/COMMON AREAS/ SITE ETC. | | | PLEASE SEE MANY NEW COMMENTS BASED ON PLANS SUBMITTED. | | | PLEASE SHOW ALL AND CORRELATE WITH THE SUBMITTED PANEL | | | SCHEDULES. SEE NEW NOTES ALSO. | | | PLEASE SEE HOUSE CIRCUITS AND NEW NOTES FOR THIS. FBC | | | ADMIN SECTION 104.2.1.2, NEC 408.4, 310.16, 240.4 | | | | | | PLEASE COMPLETE ALL CIRCUITING ON PLANS IN ORDER TO | | | REVIEW CODE COMPLIANCE FOR AREAS OF UNITS AND COMMON | | | AREAS. | | | | | | 7) NOTE: NO, SAME COMMENT. THIS IS NOT EXPLAINED ANY | | | FURTHER. PLEASE HOWEVER ALSO SEE NEW COMMENTS BASED ON | | | PLANS SUBMITTED. | | | ** PLEASE KNOW THERE ARE AREAS OF PLANS WITH | | | DESIGNATIONS, ITEMS FOR CODE COMPLIANCE FOR CIRCUITING | | | TO THOSE AREAS CAN NOT BE VERIFIED. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE PROVIDE ROOM AND AREA DESIGNATIONS ON PLANS, | | | INCLUSIVE OF ALL UNITS AND COMMON AREAS. | | | REVIEW FOR SOME CODE COMPLIANCE ITEMS CAN NOT BE DONE | | | AT THIS TIME. | | | | | | 8) NOTE:NO, PLEASE SEE RESPONSE LETTER MENTIONS TO | | | SEE SHEET AP E16.00A, YET PLEASE KNOW COMPLETED | | | PHOTO-METRICS SHALL BE SUBMITTED IN EACH SUBMITTED | | | PLANS FOR EACH BUILDING AS EACH BUILDING IS ITS OWN | | | LEGAL RECORD. | | | PLEASE SEE THE LAYOUT IN THIS BUILDING IS NOT THE SAME | | | AS OTHER AND SEPARATE EGRESS PATHS ARE PRESENT. PLEASE | | | ALSO SEE NEW NOTES PERTAINING TO ELEVATOR CORRIDOR. | | | PLEASE ALSO SEE PREVIOUS NOTES, PLEASE SEE ONLY PARTIAL | | | PHOTO-METRICS WERE SUBMITTED. PLEASE SEE NOTE WHICH | | | REQUIRES ALL UNDER NORMAL AND EMERGENCY AND FOR ALL | | | EGRESS AREAS. PLEASE SEE ONLY SOME ARE BEING SHOWN IN | | | THE PLANS UNDER BUILDING ONE. PLEASE KNOW THESE CAN BE | | | TYPICAL, HOWEVER THEY SHALL ALSO BE SPECIFIC TO EACH | | | AREA IF THE LAYOUT OF THESE AREAS CHANGES WHICH THEY | | | DO. NOT ALL AREAS ARE THE LIKE. | | | PLEASE SEE NEW NOTES ALSO FOR EGRESS FROM UNITS AND | | | PLEASE SEE NEW NOTES PERTAINING TO PARKING LOT, AND | | | SITE LIGHTING. | | | PLEASE KNOW AS THE SWIMMING POOL IS NOT UNDER THIS | | | PERMIT FOR THE BUILDING, STAMPED PLANS FROM PALM BEACH | | | COUNTY HEALTH DEPT IS NOT REQUIRED AT THIS TIME UNDER | | | THIS PERMIT. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE PROVIDE COMPLETE PHOTO-METRICS FOR ALL COMMON | | | AREAS, GARAGE AREA, COMMON AREA CORRIDORS, STAIR TOWERS | | | ETC. | | | PLEASE SEE 2003 NFPA-101 7.8.1.3 AND 7.9.2.2 WHICH | | | REQUIRE A MIN OF 10FT CANDLES FOR STAIR TOWERS UNDER | | | NORMAL OPERATION AS WALK SURFACE AND A MIN OF 1FT | | | CANDLE AT WALK SURFACE UNDER EMERGENCY CONDITIONS. | | | PLEASE ALSO SEE OTHER WALK AREAS, GARAGE, CORRIDORS ETC | | | AND THE MIN OF 1FT CANDLE. | | | **PLEASE SEE PALM BEACH COUNTY SECURITY CODE ORDINANCE | | | WITH RESPECT TO MIN DESIGN OF PARKING LOT LIGHTING | | | LEVELS UNDER NORMAL CONDITIONS. (ONLY NOTED FOR DESIGN) | | | NOT REQUIRED. PLEASE SEE ANY REQUIREMENTS FROM INS | | | CARRIER WHICH REQUIRES A MIN LEVEL OF LIGHTING. | | | ** PLEASE SEE PHOTO-METRICS OR SITE PLAN WAS NOT | | | SUBMITTED FOR PROPOSED POOL AREA. THE POOL STRUCTURE IS | | | REQUIRED TO BE UNDER A SEPARATE PERMIT. PLEASE KNOW, | | | THE PHOTO-METRICS FOR POOL AREA WILL BE REQUIRED AND | | | WILL ALSO BE REQUIRED TO BE REVIEWED AND STAMPED BY THE | | | PALM BEACH COUNTY HEALTH DEPT FOR ANY PROPOSED | | | NIGHT-TIME SWIMMING. | | | | | | 7) NOTE: NO, PLEASE SEE EACH SET OF PLANS SHALL CONTAIN | | | A SITE LIGHTING PLAN SHOWING ALL CIRCUITING AND | | | CORRELATE WITH EACH OF THE HOUSE PANELS FOR EACH | | | BUILDING IN WHICH THEY ARE BEING CIRCUITED TO. PLEASE | | | SEE ALL SITE LIGHTING AS SHOWN IN THE SET OF PLANS FOR | | | BUILDING ONE. PLEASE SEE THE CIRCUITING AS SHOWN DOES | | | NOT CORRELATE WITH HOUSE PANEL FOR BUILDING THREE IN | | | ANY WAY. | | | PLEASE SEE THERE ARE CIRCUITS SHOWN IN THIS BUILDING | | | ALSO WHICH ARE SHOWN CIRCUITED TO H PANELS NOT IN THESE | | | SETS OF PLANS. | | | PLEASE SEE HOUSE PANEL FOR THESE CIRCUITS ARE IN FACT | | | BLANK AND SHOWS THE WORDING OF "SPACE". PLEASE KNOW AT | | | THIS TIME THERE ARE MANY ITEMS PERTAINING TO SITE | | | LIGHTING WHICH CAN NOT BE VERIFIED FOR VOLTAGE DROP, | | | CIRCUITS, OVER CURRENT PROTECTION, CONDUCTOR SIZES | | | ETC. | | | PLEASE SEE NO INFORMATION WAS SUBMITTED OR SHOWN FOR | | | WIND LOADS ON POLES. | | | 240.4, 310.16, 408.4, FBC 104.2.1,104.21.2 | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE NO "ELECTRICAL SITE-PLAN" WAS SUBMITTED FOR | | | ANY SITE LIGHTING, LANDSCAPE LIGHTING ETC. | | | PLEASE KNOW, IF NOT SUBMITTED UNDER THIS PERMIT AND | | | VALUES ADJUSTED ACCORDINGLY, SEPARATE PERMIT , PLANS | | | AND FEES WILL BE REQUIRED FOR ALL SITE LIGHTING, | | | LANDSCAPE LIGHTING WORK. | | | ** ALSO NOTE: IN THAT COMPLETE WIND LOADING | | | CALCULATIONS FOR LT POLES INCLUSIVE OF THE ATTACHMENT | | | OF LT FIXTURES WILL BE REQUIRED TO BE SUBMITTED WITH | | | PLANS AND PERMIT APPLICATION FOR REVIEW. | | | | | | 8) NOTE: NO, PLEASE SEE ONCE AGAIN NOT ALL ROOMS ARE | | | DONE AS REQUIRED. PLEASE SEE MAIN ELECTRICAL ROOM FOR | | | THIS BUILDING ALONE AND ELEVATOR EQUIPMENT ROOM? PLEASE | | | SEE NEW NOTES PERTAINING TO THE ELEVATOR EQUIPMENT | | | ROOM. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE INCLUDE AN EMERGENCY BATTERY BACK UP LT OF SOME | | | SORT IN ALL ELECTRICAL ROOMS, FIRE PUMP ROOM, AND | | | ELEVATOR MACHINE RMS. SOME ARE SHOWN, BUT NOT ALL. | | | 7.8,7.9, 700.16 ETC | | | | | | 9) NOTE:NO, PLEASE SEE NOT ONLY ARE MANY CIRCUITS NOT | | | SHOWN ON PLANS NO CHANGES FOR THE REQUIRED DEDICATED | | | CIRCUITS HAVE BEEN MADE. PLEASE SEE PLANS AND CORRELATE | | | WITH THE HOUSE PANEL FOR THIS BUILDING. | | | PLEASE ALSO SEE NEW NOTES PERTAINING TO THE EQUIPMENT | | | ROOM. | | | PLEASE SEE 620.22,23,24 AND 620.51 ETC | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE 620.23, AND 620.24 FOR REQUIRED DEDICATED | | | BRANCH CIRCUITS FOR ELEVATOR PITS, AND ELEVATOR MACHINE | | | RMS/EQUIPMENT AREAS. | | | PLEASE ADJUST HOUSE PANELS AS NEEDED. | | | | | | 10) NOTE: NO, PLEASE SEE NO INFORMATION WAS LOCATED ON | | | RISER SHEETS. PLEASE SEE NO INFORMATION WAS SHOWN ON FP | | | FOR THE FIRE PUMP, SIZE, FUEL CONSUMPTION, TIME OF | | | OPERATION UNDER THE AMOUNT OF FUEL ETC. PLEASE SEE THE | | | SPECS/CUT SHEETS SUBMITTED CONTAIN MULTIPLE UNITS AND | | | NO REVIEW FOR CODE COMPLIANCE OF THE UNIT FOR EACH | | | BUILDING BASED ON THE NUMEROUS PUMPS SUBMITTED. PLEASE | | | ALSO SEE MISSING FIRE PUMP CONTROLLER SPECS. PLEASE | | | ALSO SEE MISSING THE RELEVANT CODES ON FP SHEETS. | | | PLEASE SEE THAT THIS BUILDING DOES NOT SEEM TO BE FULLY | | | SPRINKLED. PLEASE SEE THE FP SHEETS STILL INDICATE A | | | FIRE PUMP; HOWEVER NO FIRE PUMP ROOM CAN BE FOUND ON | | | ELECTRICAL OR ARCHITECTURAL PLANS? PLEASE CORRELATE AS | | | AT THIS TIME, IF THIS BUILDING IS GOING TO CONTAIN A | | | FIRE PUMP, THEN REVIEW FOR ROOM, CONSTRUCTION OF ROOM | | | AND ELECTRICAL IN SAID ROOM CAN NOT BE DONE. PLEASE SEE | | | NFPA-20 FOR ALL REQUIREMENTS FOR ROOM.PLEASE KNOW | | | BASED ON THE PLANS SUBMITTED AND SPEC/CUT SHEETS | | | SUBMITTED, REVIEW FOR COMPLIANCE CAN NOT BE DONE AT | | | THIS TIME. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE ELECTRICAL RISER SHOULD "NOTE" FIRE PUMP | | | AS DIESEL AS NOTED ON FP SHEETS. | | | PLEASE SUBMIT ALL MANUFACTURES SPEC/CUT SHEETS FOR FIRE | | | PUMP CONTROLLER AS REVIEW FOR CODE COMPLIANCE UNDER | | | 2003 NFPA-20 IS REQUIRED. | | | PLEASE ALSO SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS | | | FOR FUEL TANK. | | | PLEASE SEE NFPA-20 9.6.2.2 AS THE FUEL CAPACITY IS | | | REQUIRED TO BE SIZED BASE ON THE 100% RATED LOAD FOR A | | | MIN OF 8HRS, OR TIME SO DETERMINED BY THE FIRE | | | MARSHAL'S OFFICE DEPENDING ON OCCUPANCY. | | | FUEL SYSTEMS WILL BE UNDER OTHER TRADE REVIEW(S). (FIRE | | | AND MECH). | | | | | | 11) NOTE: NO, RESPONSE MENTIONS THIS WAS DONE, HOWEVER | | | PLEASE SEE UNIT PANEL SCHEDULES AND HOUSE PANEL | | | SCHEDULE DOES NOT CONTAIN AND CONDUCTOR SIZES. PLEASE | | | KNOW BASED ON COMMENTS ABOVE WITH RESPECT TO AREA | | | DESIGNATIONS, CIRCUITING MISSING ON PLANS, REVIEW OF | | | THIS CAN NOT BE DONE AT THIS TIME.408.4 , FBC 104.1.2 | | | ADMINSECTION. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE INCLUDE ALL MINIMUM CONDUCTOR SIZES ON ALL | | | PANELS, UNITS AND HOUSE PANELS. REVIEW FOR THESE ITEMS | | | OF CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME. | | | 310.16, 240.4,215.5 | | | | | | 12) NOTE:NO, AS CIRCUITING FOR THIS BUILDING IS NOT | | | COMPLETE AT THIS TIME, THE OVER CURRENT PROTECTIVE | | | DEVICES CAN NOT BE VERIFIED AT THIS TIME. THIS COMMENT | | | WAS MAINLY FOR THE OCP DEVICES WHICH WERE BEING SHOWN | | | ON BUILDING #1'S PLANS. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE GARAGE/HOUSE LIGHTING BEING INDICATED ON 30A | | | AND 50A CIRCUITS. | | | PLEASE SEE CODE DOES LIMIT THE OCP FOR UNIT FIXTURES | | | FOR PROTECTION OF FIXTURES ON A BRANCH CIRCUIT. PLEASE | | | ADJUST CIRCUITING AS NEEDED. | | | PLEASE ALSO SEE A FIXTURE SCHEDULE CONTAINING WATTAGES, | | | VOLTAGES ETC WAS NOT SUBMITTED. | | | PLEASE VERIFY IF THESE UNIT FIXTURES ARE RATED TO HAVE | | | OCP AT ABOVE MENTIONED. | | | 240.4, 310.16 ETC | | | | | | 13) NOTE: OK, HOWEVER SEE NOTES. | | | | | | 14) NOTE:NO/OK, PLEASE SEE PART OF THIS COMMENT SEEMS | | | TO HAVE BEEN ADDRESSED, HOWEVER PLEASE SEE NOTES ON | | | RISER AND RISER NOTES WHICH STILL DO NOT CORRELATE. | | | PLEASE SEE SEVERAL NOTE #1'S, YET ON RISER NOTES NOT | | | ALL OF THESE NOTE #1'S CAN POSSIBLY APPLY. PLEASE | | | ADJUST ALL NOTE SON RISER AND NOTES NOTED AS RISER | | | NOTES. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | , PLEASE SEE PLEASE SEE MAX OCP TO BE SIZED FOR | | | PANELS/EQUIPMENT BEING FED BY SAID OCP. | | | PLEASE SEE MANY UNIT PANELS ARE SHOWN AS 100A MLO, WITH | | | 125A OCP AS LISTED ON RISER ETC. | | | PLEASE ALSO SEE RISER NOTE #4 WHICH INDICATES 125A | | | 2-POLE ETC, HOWEVER PLEASE SEE RISER AS THIS NOTE #4 | | | COULD NOT BE LOCATED. (APPEARS TO BE MISPRINTED FOR | | | "NOTE#7" ON RISER) 240.4,408,310.16,215.5 ETC. | | | | | | 15) NOTE: N/A, NOT PART OF THESE PLANS FOR THIS | | | BUILDING. SEE NEW NOTES. | | | | | | 16) NOTE: N/A, NOT PART OF THESE PLANS FOR THIS | | | BUILDING. SEE NEW NOTES. | | | | | | 17) NOTE: N/A, NOT PART OF THESE PLANS FOR THIS | | | BUILDING. SEE NEW NOTES. | | | | | | 18) NOTE: NO/OK, SOME SHEETS SHOW NOTE, HOWEVER NOT ALL | | | FOR UNITS. CIRCUITING IS NOT YET COMPLETE TO REVIEW | | | THESE FOR CODE COMPLIANCE. PLEASE LABEL ALL CIRCUITS ON | | | PANEL SCHEDULE WHICH CONTAIN AFCI PROTECTION. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE THESE SHEETS ALSO REFERENCE "ARC FAULT" | | | PROTECTION FROM THE 1999 NEC, WHICH ONLY REQUIRED | | | PROTECTION OF RECEPTS. | | | PLEASE SEE THE 2002 NEC WHICH REQUIRES PROTECTION FOR | | | ALL "OUTLETS" IN BEDRMS. THIS IS INCLUSIVE OF RECEPTS, | | | LTS, FANS, SMOKE DETECTORS ETC. PLEASE SEE NOTE ON UNIT | | | PLANS AND ADJUST. | | | | | | 19) NOTE:THIS IS UNCLEAR AT THIS TIME, AS PERMIT | | | APPLICATION FOR BUILDING #2 INDICATES 450 UNITS AND | | | THAT IS WHAT WAS ORIGINALLY APPLIED FOR ON ORIGINAL | | | APPLICATION AND ENTERED INTO OUR SYSTEM, PLEASE SEE THE | | | NEW PERMIT APPLICATION FOR THE NEW CONTRACTOR DOES NOT | | | DESCRIBE WORK IN DETAIL PROPOSED FOR THIS PARTICULAR | | | BUILDING. ONLY MENTIONS NEW CONSTRUCTION FOR APARTMENT | | | COMPLEX. PLEASE BE SURE TO CORRELATE EACH APPLICATION | | | FOR EACH BUILDING AND BE SURE ALL INFORMATION IS | | | COORDINATED WITH THE BUILDING. PLEASE CORRELATE PLANS, | | | PERMIT APPLICATIONS AND ADJUST PLANS AS NEEDED. FBC | | | 104.2.1.2 ADMIN SECTION. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE CORRELATE LOADS, UNITS, PANELS, AND | | | BUILDING/METER LOAD CALCULATIONS: | | | A) PLEASE SEE PANEL SCHEDULE/LOAD CALCULATIONS FOR UNIT | | | "B-3" SHOWN ON | | | 16.26, HOWEVER THIS UNIT TYPE OR LOADS COULD NOT BE | | | LOCATED ON BLDG LOAD CALCULATIONS ON 16.25? | | | B) PLEASE ALSO SEE THE SAME COMMENT ABOVE FOR UNIT | | | "C-2" WHICH IS ALSO SHOWN ON | | | 16.26 BUT NOT IN CALCS ON 16.25?? | | | ** PLEASE ADJUST ALL AS NEEDED. | | | | | | 20) NOTE: OK, HOWEVER STILL NOT ADDED TO RISER, ONLY | | | SHOWN IN GROUNDING DETAIL. PLEASE EXPLAIN RATIONAL OF | | | TWO GROUNDING ELECTRODE SYSTEMS SHOWN? | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE INCLUDE THE REQUIRED FOOTER STEEL ON THE | | | GROUNDING ELECTRODE RISER DETAIL. PLEASE ALSO SHOW ON | | | RISER. | | | 250.50. | | | | | | 21) NOTE: NO, PREVIOUS NOTE REQUESTED A NOTE/DETAIL | | | WHICH WOULD ACTUALLY PROVIDE A LITTLE MORE INFORMATION | | | FOR THIS REQUIREMENT. PLEASE EXPAND ON NOTE. | | | | | | ** PREVIOUS REVIEW NOTE** | | | PLEASE PROVIDE A DETAIL/NOTE FOR ALL RACEWAY SEALS AS | | | REQUIRED PER | | | 230.8 | | | | | | 22) NOTE: N/A. | | | | | | 23) NOTE: N/A. | | | | | | 24) NOTE: N/A | | | | | | 25) NOTE: OK. | | | | | | 26) NOTE: OK. | | | | | | 27) NOTE: OK. | | | | | | 28) NOTE:NO, PLEASE SEE THIS BUILDING DOES NOT SEEM | | | TO BE FULLY SPRINKLED. PLEASE SEE LAYOUTS PROVIDED ON | | | FP SHEETS DOES NOT INDICATE HEADS IN ANY OF THE UNITS | | | ON PLANS. THERE ARE NOTES FOR SOME CLOSETS AND | | | BATHROOMS; HOWEVER THOSE DO NOT CORRELATE WITH PLANS AS | | | NO HEADS ARE SHOWN FOR COVERAGE. PLEASE SEE FIRE | | | MARSHAL?S REVIEW AS THE BASE SYSTEM IS REQUIRED UNDER | | | THE BUILDING PERMITTED SET OF PLANS EVEN THOUGH THE FS | | | PERMIT WILL BE SEPARATE WITH SEPARATE PLANS ETC. PLEASE | | | ALSO SEE NOTES PERTAINING TO CIRCUITING AND PLEASE SEE | | | NEW NOTES FOR THESE DEVICES AND TYPES SHOWN. | | | PLEASE SEE THE 2001 FBC 905.2 WHICH DOES NOT MENTION | | | THE EXCEPTION AS PERMITTED BY NFPA-72. THE MORE | | | RESTRICTIVE SHALL APPLY. AND DEVICES WILL BE REQUIRED | | | INSIDE SLEEPING ROOMS. PLEASE SEE NEW NOTES FOR THESE | | | DEVICES AND CIRCUITING. | | | | | | | | | ** PREVIOUS REVIEW NOTE ** | | | SMOKE DETECTORS ARE REQUIRED INSIDE AND OUTSIDE ALL | | | SLEEPING ROOMS. | | | PLEASE SEE 2002 NFPA-72 11.5.3.1 | | | PLEASE ADJUST NOTE FOR SD'S ON PLANS AS | | | SD'S ARE REQUIRED 3' FROM BATH/KITCHEN DOORS, 3' FROM | | | SUPPLY AIR DIFFUSERS, 5' FROM R/A GRILLES AND 20' FROM | | | KITCHEN COOKING APPLIANCES. W/ EXCEPTIONS FOR DISTANCES | | | FROM COOKING APPLIANCES. (PHOTO-ELECTRIC AND RESETTING | | | TYPE) | | | ** PLEASE SEE PREVIOUS NOTES WITH RESPECT TO ARC FAULT | | | PROTECTION OF SD'S AND CIRCUITING. | | | | | | 29) NOTE: N/A PER THIS BUILDING REVIEW. | | | | | | 30) NOTE: NO, AS CIRCUITING IS NOT YET COMPLETE FOR ALL | | | COMMON AREAS THIS CAN NOT BE VERIFIED. | | | | | | ** PREVIOUS REVIEW NOTE** | | | PLEASE SEE 700.12E FOR CIRCUITING OF ALL EM/EXT LTS, | | | WHICH REQUIRES THE BRANCH CIRCUIT FEEDING THE UNIT | | | EQUIPMENT, SHALL BE THE SAME BRANCH CIRCUIT AS THAT | | | SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED | | | AHEAD OF ANY LOCAL SWITCHES. | | | THIS IS NOTED ON SOME SHEETS, HOWEVER CIRCUITING FOR | | | THESE IS NOT SHOWN. | | | 215.5 | | | | | | 31) NOTE: OK. | | | | | | 32) NOTE:NO, PLEASE SE SOME UNITS ARE STILL MISSING | | | GFI RECEPTS TO SERVE KITCHEN COUNTER SPACE AS | | | REQUIRED. | | | UNIT(S) A 1, A-2, C1, C3 ETC. PLEASE GO THROUGH ALL. | | | | | | **PREVIOUS REVIEW NOTE ** | | | PLEASE SEE 210.52C1-C5 FOR REQUIRED GFI RECEPTS ALONG | | | KITCHEN COUNTER SPACE. PLEASE SEE SOME ARE SHOWN ON | | | WHAT APPEARS TO BE A WALL ON THE OTHER SIDE OF THE | | | COUNTER SPACE. | | | PLEASE SEE B-2, B-4ETC. | | | PLEASE SEE OTHER WHICH ARE REQUIRED TO BE WITHIN 2' OF | | | THE END OF THE COUNTER SPACE/FROM SINK EDGE ETC. PLEASE | | | SEE THESE AREAS REDLINED ON SHEETS. | | | | | | 33) NOTE:NO, PLEASE SEE RESPONSE MENTIONS THIS IS FOR | | | SECURITY AND IT IS NOT A PLUG-IN TYPE TRANSFORMER. IF | | | THIS IS NOT A PLUG-IN TYPE, PLEASE INDICATE ON PLANS | | | WHAT TYPE IT IS AND/OR WILL BE. PLEASESUBMIT OR | | | RELOCATE THE RECEPTACLES LOCATED ABOVE CLOTHES CLOSET | | | SHELVING OR IN THE NEAR VICINITY AS PREVIOUSLY STATED | | | THIS AHJ HAS SEEN TOO MANY INSTANCE WHERE FIRES HAVE | | | STARTED BASED ON SOME TYPES OF THESE UNITS AND IN THE | | | INTEREST OF LIFE SAFETY AND PROPERTY DAMAGE, THESE WILL | | | NOT BE PERMITTED AS SHOWN IN SOME UNITS. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE WHAT APPEARS TO BE A RECEPT LOCATED IN THE | | | CLOTHES CLOSET FOR PERHAPS A LV PLUG-IN TYPE | | | TRANSFORMER? | | | PLEASE KNOW, THE ONLY LOCATION A RECEPT IS PERMITTED IN | | | A CLOTHES CLOSET FOR THIS PURPOSE, MUST BE LOCATED | | | DIRECTLY ABOVE DOOR AWAY FROM COMBUSTIBLES. | | | MANY PLUG-IN TYPE TRANSFORMERS BECOME VERY HOT AND | | | HAVE MELTED OR CAUSED FIRES IN THIS JURISDICTION. | | | PLEASE KNOW, MANY ITEMS IN A CLOTHES CLOSET ARE AN | | | ACCELERANT. | | | THESE RECEPTS MAY BE MOVED TO UTILITY RM IF SO | | | DESIRED. | | | 110.26, 240.24, 90.4 ETC | | | | | | 34) NOTE: OK. | | | | | | 35) NOTE: OK. | | | | | | ** NEW NOTES FOR THIS REVIEW ** | | | | | | 1) NOTE: PLEASE CORRELATE LAYOUT OF THE BUILDING FOR | | | ALL ROOMS AND AREAS. PLEASE SEE THE ELECTRICAL PLANS DO | | | NOT CORRELATE WITH THE ARCHITECTURAL SHEETS AND THE | | | FIRE SPRINKLER SHEETS ALSO HAVE SOME AREAS WHICH DO NOT | | | CORRELATE WITH EITHER. PLEASE SEE FOR INSTANCE THE FIRE | | | PUMP ROOM LAYOUT AS NOTED ABOVE. PLEASE ALSO SEE THAT | | | THE SHEET E16.05 IS NOT COMPLETE WITH ANY WALLS, | | | CORRIDORS, ROOMS ETC. PLEASE SEE THE ENTIRE SHEET IS | | | MISSING ANY STRUCTURAL LAYOUT. | | | | | | 2) NOTE: PLEASE SEE SOME CIRCUITING STILL MISSING FROM | | | THE UNIT C-3, KITCHEN. ETC | | | 104.2.1.2, ADMIN SECTION | | | NEC 408.4, 240.4, 310.16 TO BE VERIFIED. | | | | | | 3) NOTE: PLEASE SEE THE THRESHOLD INSPECTION PLANS | | | SUBMITTED ALL CONTAIN A RAISED SEAL OVER A PHOTO-COPIED | | | SIGNATURE FROM THE ENGINEER. PLEASE SEE FLORIDA | | | ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA STATUTES | | | 471.025 AS AN ORIGINAL SIGNATURE IS REQUIRED. PLEASE | | | KNOW THESE MAY BE RETAINED BY THIS OFFICE FOR POSSIBLE | | | REVIEW FROM THE FLORIDA BOARD OF PROFESSIONAL | | | ENGINEERS. IF THERE ARE ANY QUESTIONS ON THIS PLEASE | | | CONTACT THIS OFFICE OR THE BOARD. | | | **THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY | | | ANY OTHER TRADE. | | | | | | 4) NOTE: PLEASE SEE NFPA-72 DEFINITIONS FOR SMOKE | | | DEVICES. IF THESE ARE INDEED (SD) FOR SMOKE DETECTORS | | | THEN THEY WOULD DETECT AND CAUSE AN ALARM TO HORN/SIREN | | | DEVICE OF SOME TYPE. PLEASE SEE PLANS CALL FOR THESE AS | | | 120V UNITS, WHICH IF (SA) SMOKE ALARMS WHICH WOULD | | | DETECT AND SOUND, THEN THE DESIGNATIONS NEED TO BE | | | ADJUSTED ALONE WITH ALL NOTES WHICH CURRENTLY STATE | | | SMOKE DETECTORS. PLEASE KNOW THIS WAS NOT A COMMENT ON | | | THE PREVIOUS REVIEW, HOWEVER AS INFORMATION WAS GIVEN | | | FROM NFPA DIRECTLY, PLANS MUST CONTAIN THE CORRECT | | | DESIGNATIONS. | | | | | | 5) NOTE: PLEASE SEE THE BASE FA SYSTEM SHALL BE SHOWN | | | AND ALL HORN/STROBE DEVICES SHALL STATE THE MINIMUM | | | LEVELS AS REQUIRED PER FBC 11-4.28.1, .2, AND .3(4). | | | THIS WAS NOT PART OF THE ELECTRICAL REVIEWERS REVIEW | | | WHEN PLANS WERE SUBMITTED PREVIOUSLY HOWEVER THIS HAS | | | NOW BECOME PART OF THE ELECTRICAL REVIEWERS REVIEW. | | | PLEASE SHOW. | | | | | | 6) NOTE: PLEASE CLARIFY STAIRS SHOWN ON SOME UNITS. | | | PLEASE SEE MISSING WHAT WOULD BE EGRESS LIGHTING AND | | | CONTROLS IF INSIDE UNIT AND/OR OUTSIDE UNIT. PLEASE SEE | | | NEC 210.70, LS 101 7.8, (7.9 WHERE APPLICABLE). | | | | | | 7) NOTE: PLEASE SEE SEVERAL HOUSE CIRCUITS AS NOTED | | | ABOVE WITH RESPECT TO CORRELATION OF CIRCUITING SEEM TO | | | BE INDICATE ON THESE PLANS TO PANELS WHICH WOULD BE ON | | | OTHER BUILDINGS? PLEASE SEE MISSING WHAT APPEARS TO BE | | | A TRASH ROOM AND ANY CIRCUITING FOR LIGHTS, COMPACTOR | | | ETC. | | | 240.4, 310.16, 408.4, ETC | | | | | | 8) NOTE: PLEASE SEE NOTES ABOVE ON PREVIOUS REVIEW AND | | | SECOND REVIEW NOTES WITH RESPECT TO ROOM/AREA | | | DESIGNATIONS. PLEASE SEE 210.52B1, 210.11C1 AND 220.16 | | | FOR DINING ROOMS, DINING AREAS, BREAKFAST AREAS, | | | KITCHEN AREAS AND THE LIKE. PLEASE SEE THAT SOME | | | RECEPTS ARE BEING SHOWN IN AREAS WHICH WOULD APPEAR TO | | | BE AREAS OF THE LIKE AS REFERENCED ABOVE, HOWEVER SOME | | | OF THESE RECEPTS ARE BEING SHOWN ON LIGHTING CIRCUITS | | | OF 15A'S ETC. PLEASE SEE THAT ANY OF THESE AREAS OF THE | | | LIKE WILL BE REQUIRED TO CONTAIN THESE RECEPTACLES ON | | | THE ONE OR MORE CIRCUITS AS NOTED. | | | PLEASE ADJUST PLANS FOR PREVIOUS NOTE AND THIS NOTE. | | | | | | 9) NOTE:PLEASE SEE ELEVATOR CORRIDOR ON 2ND LEVEL AND | | | ANY POSSIBLEBUILDING CODE COMMENTS BASED ON DEAD-END | | | CORRIDORS AND DISTANCES PERMITTED ETC WITH AND OR WITH | | | OUT BEING SPRINKLED. | | | THIS IS ONLY BEING NOTED AS IF THE LAYOUT HAS TO CHANGE | | | FOR ANY REASON, THIS WILL AFFECT THE ELECTRICAL PLANS. | | | | | | 10) NOTE: PLEASE PROVIDE NOTE ON FIRST FLOOR MAIN | | | ELECTRICAL ROOM PLANS WHICH WILL REQUIRE DOOR TO | | | CONTAIN PANIC HARDWARE. | | | 110.26/90.4 | | | | | | 11) NOTE: PLEASE SEE THE VOLTAGE DROP FOR 30A CU'S, AT | | | THIS TIME CAN NOT BE VERIFIED. PLEASE SEE SOME UNITS | | | INDICATE #10 ALREADY YET THESE WILL BE OVER 75FT AND | | | THERE IS NO NOTE FOR THESE UNITS TO UPGRADE TO #8 OR ? | | | PLEASE ADJUST AND PROVIDE ADDITIONAL INFORMATION. FBC | | | 104.2.1.2 FOR ADDITIONAL INFORMATION. | | | NEC 310.16, 240.4 ETC. | | | | | | 12) NOTE: PLEASE SEE NOTES ABOVE WHICH REQUESTS FOR THE | | | RISER NOTES TO CORRELATE WITH THE DESIGNATIONS ON | | | RISER. PLEASE SEE NOTE #1. | | | 104.2.1.2 FBC ADMIN SECTION. | | | | | | 13) NOTE: PLEASE PROVIDE A DETAIL FOR THE ROOF TOP | | | DISCONNECT AS BEING NOTED AND HOW THIS WILL BE MOUNTED? | | | (NOT TO UNIT) | | | 440.11. THIS CAN BE A TYPICAL DETAIL. | | | | | | 14) NOTE: PLEASE SEE ATTACHED COPY OF FLORIDA STATUTES | | | 553.80(2)(B) WITH RESPECT TO REPEAT CODE COMPLIANCE | | | COMMENTS. THIS IS ONLY A NOTICE GIVEN AT THIS TIME. | | | | | | 15) NOTE: PLEASE SEE MISSING FIRST FLOOR ELECTRICAL FOR | | | UNITS WITH STAIRS. 210.70,210.52 ETC | | | | | | 16) NOTE: PLEASE BE SURE ALL FIXTURE DESIGNATIONS ARE | | | ON PLANS AND CORRELATE WITH THE FIXTURE LEGEND | | | PROVIDED. | | | | | | *** PLEASE KNOW THAT THERE MAY BE NEW COMMENTS ON THE | | | NEXT REVIEW DUE TO INFORMATION NOT SUBMITTED OR | | | COORDINATION OF PLANS/INFORMATION SUBMITTED FOR REVIEW | | | | | | | | | ** PLEASE SEE ANY COMMENTS FROM OTHER REVIEWER(S) WHICH | | | MAY HAVE AN AFFECT ON ELECTRICAL PLANS. | | | | | | ** PLEASE KNOW, A TYPE WRITTEN RESPONSE LETTER FROM | | | DESIGN PROFESSIONAL(S) FOR EACH COMMENT ON HOW/WHERE | | | CORRECTIONS ARE MADE OR IF COMMENTS ON REVIEW WILL HELP | | | IN EXPEDITING THE PLAN REVIEW PROCESS. THIS WAS DONE, | | | AND SHOULD BE DONE FOR THIS REVIEW AS WELL. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2007-01-01 08:04:06 | 2007-01-01 08:04:06 | | | REVIEW IN PROGRESS | | 2006-12-31 20:33:26 | 2006-12-31 20:33:26 | | | REVIEW STOPPED, REVIEW TO CONTINUE ON 1/1 | | 2006-12-31 19:59:44 | 2006-12-31 19:59:44 | | | IN ELEC FOR REVIEW |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2005-12-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2005-12-26 |
Time |
13:20 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2005-12-25 |
Time |
17:52 |
Sent To |
|
|
| Notes |
| 2005-12-26 00:00:00 | ************ UNSAT ************ | | | | | | COURTNEY LAKES | | | N. CONGRESS. | | | | | | | | | 1)NOTE: PLEASE SUBMIT COMPLETED PLANS | | | BOUND TOGETHER IN APPROPRIATE FASHION. | | | PLEASE SEE ALL SHEETS WERE SUBMITTED | | | LOOSELY AND NOT IN BOUND STES. | | | | | | 2)NOTE: PLEASE BE SURE ALL PLANS ARE | | | SIGNED, DATED AND SEALED BY ALL DESIGN | | | PROFESSIONALS AS REQUIRED UDNER FS | | | 481.221 AND 471.025. | | | (PLEASE SEE A-SHEETS, ONLY SIGNED). | | | | | | 3)NOTE: PLEASE BE SURE TO CORRECT THE | | | CURRENT NEC/ NFPA-70 IN EFFECT. | | | PLEASE KNOW, AS OF JULY 1ST, 2003 THE | | | STATE OF FLORIDA ADOPTED THE 2002 | | | NFPA-70 (NEC). PLANS REFERENCE 1999. | | | PLEASE SEE SOME ELECTRICAL COMMENTS | | | WHICH WILL AFFECT THIS. | | | PLEASE SEE NEXT COMMENT WITH RESPECT TO | | | PERMITS APPLIED FOR UNDER THE 2001 FBC | | | BEFORE OCT 1ST, 2005 AND PERMITS ON OCT | | | 1ST, 2005. | | | | | | 4)NOTE: PLEASESEE THAT THREE SEPARATE | | | PERMIT APPLICATIONS WERE SUBMITTED AND | | | NOTED FOR BLDG'S 1,2 AND 3, HOWEVER | | | PLANS SHOWS BLDG TYPES 1.2&3 STRUCTUALLY | | | ONLY ONE BUILDING. | | | PLEASE SEE PERMIT APPLICATIONS ALL | | | REFLECT THIS ONE 450 UNIT BLDG. | | | PLEASE SEE THIS CONTRADICTS THE "PHASING | | | PLAN" SUBMITTED ON A1.04 AS THIS PHASING | | | PLAN INDICATES WORK ON BLDGS 4 AND 5 | | | BEFORE COMPLETION OF BLDGS 1, 2 AND 3. | | | PLEASE SEE COMMENTS FROM BLDG, FIRE AND | | | OTHER REVIEWERS, ASCERTIFICATES OF | | | OCCUPANCY(CO'S) FOR THESE CAN NOT BE | | | GRANTED IN THIS ORDER AS THE FIRST | | | "STRUCTURED BLDG"(1,2&3) WOULD NOT BE | | | COMPLETE. | | | PLEASE ALSO SEE COMMENTS WITH RESPECT TO | | | "TEMPORARY CO'S" WHICH MAY ALLOW | | | OCCUPANCY OF SOME PARTS OF BLDGS, | | | HOWEVER THESE TCO'S ARE ONLY GOOD FOR 30 | | | DAYS AND A MAX OF 3 TCO'S MAY ONLY BE | | | GRANTED BY THE BLDG OFFICAL. | | | PLEASE KNOW, IN ANY CASE, ALL LIFE | | | SAFTEY, FIRE PROTECTION SYSTEMS, FIRE | | | SPRINKLERS (FULLY CHARGED),ELECTRICAL | | | SYSTEMS ETC SHALL BE COMPLETE IN THE | | | BASE BLDG FOR BLDG TYPE 1, 2& 3 BEFORE A | | | TCO,/CO CAN BE GRANTED. | | | ************************************* | | | ALSO NOTED THAT BLDG'S TYPE 4 AND 5 | | | WHICH ARE SEPARATE STRUCTURES AND | | | INDEPENDANT OF EACH OTHER WERE NOT | | | SUBMITTED FOR PERMIT. | | | PLEASE SEE ALL PERMITS SUBMITTED AFTER | | | OCT. 1ST, 2005 SHALL FALL UNDER THE | | | 2004 FBC, WITH ALL OTHER CODES ADOPTED | | | BY SAID CODE AND STATE OF FLORIDA. | | | ************************************ | | | PLEASE SEE COMMENTS FROM OTHER | | | REVIEWER(S) WITH RESPECT TO THIS. | | | ************************************* | | | PLEASE ALSO SEE NEXT COMMENT WITH | | | RESPECT TO THE MAINS, SERVICES, AND | | | METER RMS AS PROPOSED. | | | ** SEE ALL NOTES FROM ALL REVIEWERS | | | WHICH MAY ALSO AFFECT THIS SEQUENCE OF | | | CONSTUCTION. | | | | | | 5)NOTE: PLEASE SEE METER RMS AS SHOWN | | | WOULD BE OK, HOWEVER STRUCTURE AS SHOWN | | | FOR BLDG TYPE 1,2 AND 3 (ONE BLDG) WOULD | | | REQUIRE MAINS TO BE GROUPED. | | | 90.4,230.2,230.70,230.72,230.76,230.79 | | | ETC. | | | BLDG'S LARGE ENOUGH TO CONTAIN MORE THAN | | | ONE SERVICE AT SEPARATE LOCATIONS SHALL | | | BE DIVIDED INTO SECTIONS AND SHALL HAVE | | | THOSE SECTIONS DIVIDED BY "FIRE WALLS". | | | PLEASE SEE FBC FOR DEFINITION OF "FIRE | | | WALLS". | | | PLEASE KNOW, STRUCTURE CONSTRUCTED AS | | | SHOWN IN PLANS, WOULD REQUIRE MAIN | | | DISCONNECTS GROUPED, WHICH WOULD THEN | | | IN-TURN FEED METER ROOMS. | | | OTHER DESIGN CHANGES IN THE "ONE BLDG" | | | MAY ALSO PERMIT INDIVIDUAL SERVICES. | | | PLEASE SEE BLDG TYPE #4 AND #5 ARE SHOWN | | | AS SEPARATE BLDGS WITH STAND ALONE | | | SERVICES AND ALL MAINS ARE GROUPED. | | | PLEASE KNOW THAT BLDGS 4 AND 5 WILL HAVE | | | REVIEWS DONE UNDER THOSE PERMIT | | | APPLICATIONS. | | | ** PLEASE SEE SOME OF THESE COMMENTS | | | WOULD ALSO APPLY. | | | | | | 6)NOTE: PLEASE COMPLETE ALL CIRCUITING | | | ON PLANS IN ORDER TO REVIEW CODE | | | COMPLIANCEFOR AREAS OF UNITS AND | | | COMMON AREAS. | | | | | | 7)NOTE: PLEASE PROVIDE ROOM AND AREA | | | DESIGNATIONS ON PLANS, INCLUSIVE OF ALL | | | UNITS AND COMMON AREAS. | | | REVIEW FOR SOME CODE COMPLIANCE ITEMS | | | CAN NOT BE DONE AT THIS TIME. | | | | | | 8)NOTE: PLEASE PROVIDE COMPLETE | | | PHOTOMETRICS FOR ALL COMMON AREAS, | | | GARAGE AREA,COMMON AREA CORRIDORS, | | | STAIR TOWERS ETC. | | | PLEASE SEE 2003 NFPA-101 7.8.1.3 AND | | | 7.9.2 WHICH REQUIRES A MIN OF 10FT | | | CANDLES FOR STAIR TOWERS UNDER NORMAL | | | OPERATION AS WALK SURFACE AND A MIN OF | | | 1FT CANDLE AT WALK SURFACE UNDER | | | EMERGENCY CONDTIONS. PLEASE ALSO SEE | | | OTHER WALK AREAS, GARAGE, CORRIDORS ETC | | | AND THE MIN OF 1FT CANDLE. | | | **PLEASE SEE PALM BEACH COUNTY SECURITY | | | CODE ORDIANCE WITH RESPECT TO MIN DESIGN | | | OF PARKING LOT LIGHTING LEVELS UNDER | | | NORMAL CONDITIONS. (ONLY NOTED FOR | | | DESIGN)NOT REQUIRED. PLEASE SEE ANY | | | REQUIREMENTS FROM INS CARRIER WHICH | | | REQUIE A MIN LEVEL OF LIGHTING. | | | ** PLEASE SEE PHOTOMETRICS OR SITE PLAN | | | WAS NOT SUBMITTED FOR PROPOSED POOL | | | AREA. THE POOL STRUCTURE IS REQUIRED TO | | | BE UNDER A SEPARATE PERMIT. PLEASE KNOW, | | | THE PHOTOMETRICS FOR POOL AREA WILL BE | | | REQUIRED AND WILL ALSO BE REQUIRED TO BE | | | REVIEWED AND STAMPED BY THE PALM BEACH | | | COUNTY HEALTH DEPT FOR ANY PROPOSED | | | NIGHT-TIME SWIMMING. | | | | | | 7)NOTE: PLEASE SEE NO "ELECTRICAL | | | SITE-PLAN" WAS SUBMITTED FOR ANY SITE | | | LIGHTING, LANDSCAPE LIGHTING ETC. | | | PLEASE KNOW, IF NOT SUBMITTED UNDER THIS | | | PERMIT AND VALUES ADJUSTED ACCORDINGLY, | | | SSEPARATE PERMIT , PLANS AND FEES WILL | | | BE REQUIRED FOR ALL SITE LIGHTING, | | | LANDSCAPE LIGHTING WORK. | | | ** ALSO NOTE: IN THAT COMPLETE WIND | | | LOADING CALCULATIONS FOR LT POLES | | | INCLUSIVE FO THE ATTACHMENT OF LT | | | FIXTURES WILL BE REQUIRED TO BE | | | SUBMITTED WITH PLANS AND PERMIT | | | APPLICATION FOR REVIEW. | | | | | | 8)NOTE: PLEASE INCLUDE AN EMERGENCY | | | BATTERY BACK UP LT OF SOME SORT IN ALL | | | ELECTRICAL ROOMS, FIRE PUMP ROOM, | | | ELEVATOR MACHINE RMS. SOME ARE SHOWN, | | | BUT NOT ALL. | | | 7.8,7.9,700.16 ETC | | | | | | 9)NOTE: PLEASE SEE 620.23, AND 620.24 | | | FOR REQUIRED DEDICATED BRANCH CIRCUITS | | | FOR ELEVATOR PITS, AND ELEVATOR MACHINE | | | RMS/EQUIPMENT AREAS. | | | PLEASE ADJUST HOUSE PANELS AS NEEDED. | | | | | | 10)NOTE: PLEASE SEE ELECTRICAL RISER | | | SHOULD "NOTE" FIRE PUMP AS DIESEL AS | | | NOTED ON FP SHEETS. | | | PLEASE SUBMIT ALL MANUAFCTURES SPEC/CUT | | | SHEETS FOR FIRE PUMP CONTROLLER AS | | | REVIEW FOR CODE COMPLIANCE UNDER 2002 | | | NFPA-20 IS REQUIRED. | | | PLEASE ALSO SUBMIT ALL MANUFACTURES | | | SPECS/CUT SHEETS FOR FUEL TANK. | | | PLEASE SEE NFPA-20 9.6.2.2 AS THE FUEL | | | CAPACITY IS REQUIRED TO BE SIZED BASE ON | | | THE 100% RATED LOAD FOR A MIN OF 8HRS, | | | OT TIME SO DETERMIND BY THE FIRE | | | MARSHAL'S OFFICE DEPENDING ON OCCUPANCY. | | | FUEL SYSTEMS WILL BE UNDER OTHER TRADE | | | REVIEW(S). (FIRE AND MECH). | | | | | | 11)NOTE: PLEASE INCLUDE ALL MIN | | | CONDUCTOR SIZES ON ALL PANELS,UNITS AND | | | HOUSE PANELS. REVIEW FOR THESE ITEMS OF | | | CODE COMPLIANCE CAN NOT BE DONE AT THIS | | | TIME. 310.16,240.4,215.5 | | | | | | 12)NOTE: PLEASE SEE GARAGE/HOUSE | | | LIGHTING BEING INDICATED ON 30A AND 50A | | | CIRCUITS. | | | PLEASE SEE CODE DOES LIMIT THE OCP FOR | | | UNIT FIXTURES FOR PROTECTION OF FIXTURES | | | ON A BRANCH CIRCUIT. | | | PLEASE ADJUST CIRCUITING AS NEEDED. | | | PLEASE ALSO SEE A FIXTURE SCHEDULE | | | CONTAINING WATTAGES, VOLTAGES ETC WAS | | | NOT SUBMITTED. | | | PLEASE VERIFY IF THESE UNIT FIXTURES ARE | | | RATED TO HAVE OCP AT ABOVE MENTIONED. | | | 240.4, 310.16 ETC | | | | | | 13)NOTE: PLEASE CORRELATE ALL OCP | | | DEVICES FOR UNITS AND FEEDERS BEING | | | LISTED IN "RISER NOTES". | | | PLEASE SEE SOME FEEDERS SHOWN AS #4'S ON | | | 125A BREAKER? | | | SEE 310.16,240.4 | | | PLEASE SEE OCP FOR ALL UNITS IS LISTED | | | AS 125A'S. | | | SEE NEXT COMMENT. | | | | | | 14)NOTE: PLEASE SEE MAX OCP TO BE SIZED | | | FOR PANELS/EQUIPMNET BEING FED BY SAID | | | OCP. | | | PLEASE SEE MANY UNIT PANELS ARE SHOWN AS | | | 100A MLO, WITH 125A OCP AS LISTED ON | | | RISER ETC. | | | PLEASE ALSO SEE RISER NOTE #4 WHICH | | | INDICATES 125A 2-POLE ETC, HOWEVER | | | PLEASE SEE RISER AS THIS NOTE #4 COULD | | | NOT BE LOCATED. (APPEARS TO BE | | | MISPRINTED FOR "NOTE#7" ON RISER) | | | 240.4,408,310.16,215.5 ETC. | | | | | | 15)NOTE: PLEASE SEE 16.26 AND 16.27 | | | WHICH CONTAIN THE SAME EXACT "HOUSE | | | PANELS" ?? H1, H1A , H2, AND H2A. | | | PLEASE SEE SHEET 16.27 MAY BE DELETED IF | | | PANELSCHEDULES FOR "CA" AND"CB" ARE | | | MOVED TO 16.26. | | | | | | 16)NOTE: PLEASE CORRELATE LOADS SHOWN | | | FOR H1A WITH LOAD SHOWN ON H1. | | | THIS DOES NOT MATCH. | | | | | | 17)NOTE: PLEASE CORRELATE LOADS ON PANEL | | | H2A WITH LOADS SHOWN ON H2> | | | THESE ALSO DO NOT MATCH. | | | | | | 18)NOTE: PLEASE SEE THESE SHEETS ALSO | | | REFERENCE "ARC FAULT" PROTECTION FROM | | | THE 1999 NEC, WHICH ONLY REQUIRED | | | PROTECTION OF RECEPTS. | | | PLEASE SEE 2002 NEC WHICH REQUIRES | | | PROTECTION FOR ALL "OUTLETS" IN BEDRMS. | | | THIS IS INCLUSIVE OF RECEPTS, LTS, FANS, | | | SMOKE DETECTORS ETC. | | | PLEASE SEE NOTE ON UNIT PLANS AND | | | ADJUST. | | | | | | 19)NOTE: PLEASE CORRELATE LOADS , UNITS, | | | PANELS, AND BUILDING/METER LOAD | | | CALCULATIONS: | | | A) PLEASE SEE PANEL SCHEDULE/LOAD | | | CALCULATIONS FOR UNIT "B-3" SHOWN ON | | | 16.26, HOWEVER THIS UNIT TYPE OR LOADS | | | COULD NOT BE LOCATED ON BLDG LOAD | | | CALCULATIONS ON 16.25? | | | B)PLEASE ALSO SEE THE SAME COMMENT ABOVE | | | FOR UNIT "C-2" WHICH IS ALSO SHOWN ON | | | 16.26 BUT NOT IN CALCS ON 16.25?? | | | ** PLEASE ADJUST ALL AS NEEDED. | | | | | | 20)NOTE: PLEASE INCLUDE THE REQUIRED | | | FOOTER STEEL ON THE GROUNDING ELECTRODE | | | RISER DETAIL. | | | PLEASE ALSO SHOW ON RISER. | | | 250.50. | | | | | | 21)NOTE: PLEASE PROVIDE A DETAIL/NOTE | | | FOR ALL RACEWAY SEALS AS REQUIRED PER | | | 230.8 | | | | | | 22)NOTE: PLEASE SEE RISER WHICH SHOWS A | | | POOL PANEL BEING FED FROM PANEL "CA", | | | HOWEVER PANEL "CA" , DOES NOT SHOW SUCH | | | PANEL. | | | 215.5 | | | | | | 23)NOTE: PLEASE PROVIDE "FUTURE" POOL | | | PANEL ON RISER AND PANEL SCHEDULE. | | | 215.5 | | | | | | 24)NOTE: PLEASE SEE RISER NOTE #12 WHICH | | | IS SHOWN FOR FEED FROM PANEL "CA" TO | | | PANEL "CB". THIS IS SHOWN AS 500MCM'S, | | | ALTHOUGH OCP ON CA IS ONLY SHOWN AS | | | 200A'S? THIS IS PERMITTED, HOWEVER THE | | | 200A DEVICE MAY NOT ACCEPT 500MCM'S. | | | 215.5 | | | | | | 25)NOTE: PLEASE SEE REDLINED ITEMS ON | | | PLANS FOR "EQUIPMENT GROUNDING | | | CONDUCTORS" BEING SHOWN BEFORE THE FIRST | | | MEANS OF DISCONNECT. | | | PLEASE SEE 250.6, 250.24. | | | PLEASE SEE HOUSE METER #2, SEE RISER | | | NOTE #12 AND #13 SHOWS AN "EQUIPMENT | | | GROUNDING" CONDUCTOR WHICH IS | | | PARALLELING THE NEUTRAL. | | | | | | 26)NOTE: PLEASE SEE MIN OCP FOR WATER | | | HEATERS TO BE SIZED AT 125%.424.13 | | | PLEASE SEE UNITS CONTAINING 5KW WH @ | | | 208V'S WOULD INCREASE THIS BRKR TO A | | | 2-P35A. PLEASE ALSO ADJUST ANY AWG PER | | | 310.16,240.4 | | | | | | 27)NOTE: PLEASE SEE UNIT LOAD | | | CALCULATIONS SHOWS THE LOADS FOR A/C'S | | | AFTER THE PERMITTED DERATING, HOWEVER | | | PLEASE SHOWLOADS FOR THESE BEFORE | | | DERATING. | | | PLEASE BE SURE TO CORRELATE WITH LOADS | | | FOR COOLING AND HEAT ON MECHANICAL PLAN. | | | 215.5 | | | | | | 28)NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | PLEASE SEE 2002 NFPA-72 11.5.3.1 | | | PLEASE ADJUST NOTE FOR SD'S ON PLANS AS | | | SD'S ARE REQUIRED 3' FROM BATH/KTICHEN | | | DOORS, 3' FROM SUPPLY AIR DIFFUSERS, 5' | | | FROM R/A GRILLES AND 20' FROM KITCHEN | | | COOKING APPLIANCES. W/ EXCEPTIONS FOR | | | DISTANCES FROM COOKING APPLIANCES. | | | (PHOTOELECTRIC AND RESETTING TYPE) | | | ** PLEASE SEE PRIVIOUS NOTES WITH | | | RESPECT TO ARC FAULT PROTECTION OF SD'S | | | AND CIRCUTING. | | | | | | 29)NOTE: PLEASE SEE ALL RECEPTS IN | | | CLUBHOUSE KITCHEN PER 210.8B3 WHICH | | | REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT | | | RECEPTACLES IN NONDWELLING-TYPE KITCHENS | | | TO BE GFCI PROTECTED. THIS REQUIREMENT | | | APPLIES TO EACH AND EVERY 15- AND | | | 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE, | | | WHETHER OR NOT THE RECEPTACLE SERVES | | | COUNTERTOP APPLIANCES. | | | | | | 30)NOTE: PLEASE SEE 700.12E FOR | | | CIRCUITING OF ALL EM/EXT LTS, WHICH | | | REQUIRES THE BRANCH CIRCUIT FEEDING THE | | | UNIT EQUIPMENT SHALL BE THE SAME BRANCH | | | CIRCUIT AS THAT SERVING THE NORMAL | | | LIGHTING IN THE AREA AND CONNECTED AHEAD | | | OF ANY LOCAL SWITCHES. | | | THIS IS NOTED ON SOME SHEETS, HOWEVER | | | CIRCUITING FOR THESE IS NOT SHOWN. | | | 215.5 | | | | | | 31)NOTE: PLEASE CLARIFY THE "CT" AS | | | LABLED ALONG KITCHEN RECEPTS. THIS | | | ABBREVIATION COULD NOT BE LOCATED ON | | | SYMBOL LEGEND? | | | | | | 32)NOTE: PLEASE SEE 210.52C1-C5 FOR | | | REQUIRED GFI RECEPTS ALONG KTICHEN | | | COUNTERSPACE. PLEASE SEE SOME ARE SHOWN | | | ON WHAT APPEARS TO BE A WALL ON THE | | | OTHER SIDE OF THE COUNTERSPACE. | | | PLEASE SEE B-2, B-4ETC. | | | PLEASE SEE OTHER WHICH ARE REQUIRED TO | | | BE WITHIN 2' OF THE END OF THE | | | COUNTERSPACE/FROM SINK EDGE ETC. | | | PLEASE SEE THESE AREAS REDLINED ON | | | SHEETS. | | | | | | 33)NOTE: PLEASE SEE WHAT APPEARS TO BE A | | | RECEPT LOCATED IN THE CLOTHES CLOSET FOR | | | PERHAPS A LV PLUG-IN TYPE TRANSFORMER? | | | PLEASE KNOW, THE ONLY LOCATION A RECEPT | | | IS PERMITTED IN A CLOTHES CLOSET FOR | | | THIS PURPOSE, MUST BE LOCATED DIRECTLY | | | ABOVE DOOR AWAY FROM COMBUSTIBLES. | | | MANY PLUG-IN TYPE TRANSFORMERS BECOME | | | VERY HOT AND HAVE MELTED OR CAUSED FIRES | | | IN THIS JURISTICTION. PLEASE KNOW, MANY | | | ITEMS IN A CLOTHES CLOSET ARE AN | | | ACCELERANT. | | | THESE RECEPTS MAY BE MOVED TO UTILITY RM | | | IS SO DESIRED. | | | 110.26, 240.24, 90.4 ETC | | | | | | 34)NOTE: PLEASE SEE RELDINED PLANS FOR | | | ANY RECEPTS WHICH MAY BE REQUIRED PER | | | 210.52 (A-2). MOST ALL SPACING IS OK. | | | | | | 35)NOTE:PLEASE MAKE NOTE FOR ALL MIN | | | FAIR HOUSING ACT REQUIREMENTS FOR DEVICE | | | HEIGHTS. | | | 24 CFR 100.205 | | | | | | ** PLEASE KNOW, SOME REVIEW OF CODE | | | COMPLIANT ITEMS MAY NOT BE DONE AT THIS | | | TIME DUE TO SOME INFORMATION NOT ON | | | PLANS. | | | | | | ** PLEASE SEE ANY COMMENTS FROM OTHER | | | REVIEWER(S) WHICH MAY HAVE AN AFFETC ON | | | ELECTRICAL PLANS. | | | | | | ** PLEASE KNOW, A TYPE WRITTEN RESPONSE | | | LETTER FROM DESIGN PROFESSIONL(S) FOR | | | EACH COMMENT ON HOW/WHERE CORRECTIONS | | | ARE MADE OR IF COMMENTS ON REVIEW WILL | | | HELP IN EXPEDITING THE PLAN REVIEW | | | PROCESS. | | | | | | ** PLEASE KNOW THAT A MEETING TO GO OVER | | | FIRST COMMENTS FOR DESIGN/PHASING OF | | | BLDGWITH ALL REVIEWERS IS SUGGESTED | | | BEFORE PERHAPS SUBMITTING PLANS BACK FOR | | | REVIEW. | | | PLEASE KNOW, ALL REVIEWS AFTER THE 1ST | | | FREE "RE-SUB" IS SUBJECT TO A 10% RESUB | | | FEE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | | | 2005-12-25 00:00:00 | ONE ROLL IN ELECTRIC FOR REVIEW. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2007-09-28 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2007-09-28 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2007-09-28 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2007-09-28 14:22:16 | ****FAILED***** | | | | | | 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI). | | | PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR | | | NOI. | | | YOU CAN GET NOI INFO FROM | | | WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/ | | | NOTICE OF INTENT DEP FORM 62-621.300(4)(B), | | | EFFECTIVE MAY 1, 2003 | | | 2. PLEASE SHOW ON CIVIL DRAWING THE EXACT MAILING | | | ADDRESS, BUILDING NAME, OR NUMBER, YOU TALKING ABOUT 3 | | | PERMITS, PLEASE IDENTIFY EACH BUILDING ON THE DRAWING. | | | 3.PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE | | | DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION | | | MUST BE ACCESSIBLE FOR PICKUP TRUCK. | | | 4.PLEASE SHOW FINISH FLOOR ELEVATION ON DRAWING . | | | PLEASE EXPLAIN IN DETERMINING FIRST FLOOR ELEVATION, | | | PLEASE SHOW IN YOUR CALCULATION THAT YOU CONSIDERED | | | CENTER LINE OF ROAD , FLOOD ZONE OF THIS SITE,& 5,10, | | | 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST | | | FLOOR ELEVATION, PLEASE SHOW ALL THESE IN YOUR STORM | | | WATER CALS.PLEASE ALSO SHOW ON DRAWINGS THE MAXIMUN | | | AND MINIMUM PARKING LOT ELEVATIONS. | | | | | | 5. PLEASE SHOW ON DRAWINGTHE SITE AREA, YOU ARE | | | DEVELOPING FOR THIS PROJECT . PLEASE ALSO SHOW TOTAL | | | PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT, | | | LAKE,SIDEWALK, PARKING,BUILDING AREA ETC. MAKE SURE | | | THESE AREAS SHOWN ON DRAWINGS MUST MATCH WITH AND USED | | | IN STORM WATER QUALITY CALCULATIONS. | | | 6. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE | | | SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM | | | ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE | | | CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING | | | ELEVATION, ETC ON DRAWINGS, CALCULATION FOR | | | EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET | | | DETENTION AREAS IN STORM WATER CALS.AFTER CONTROL | | | STRUCTURE WHERE STORM WATER GOES?? | | | 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND | | | YOUR SITE FOR STORM WATER DRAIN. | | | 8. PLEASE RESUBMIT A COPY OF SFWMD PERMIT,, & GEO TECH | | | REPORT,STORM WATER CALS MUST BE APPROVED FROM 1000 | | | 45TH STREET ENGINEERING SERVICES. | | | 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH | | | STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED. | | | 10. PLEASE KEEP SEPARATE CIVIL DRAWINGS SO I CAN REVIEW | | | QUICK. | | | | | | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR | | | PERMITTING PROCESS | | | | | | RASIK CHOKSHI805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2005-10-31 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2005-10-31 |
Time |
11:11 |
Rev Time |
0.50 |
| Received By |
mamini |
Date |
2005-10-31 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2005-10-31 00:00:00 | FAILED: | | | | | | 1. PLEASE SUBMIT CIVIL PLANS FOR OUR | | | REVIEW AND APPROVAL.NOTE THAT CIVIL | | | PLANS FOR THIS WERE REVIEWED UNDER OLD | | | PERMIT APPLICATIONS # 04021308,04021305, | | | 04021300 WHICH EXPIRED.COPY OF THE | | | REVIEW NOTES INCLUDED FOR YOUR USE. | | | | | | IF ANY QUESTION PLEASE CONTACT 805-6723 | | | MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2007-11-07 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-11-07 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-11-07 |
Time |
13:17 |
Sent To |
|
|
| Notes |
| 2007-11-07 13:33:39 | ***PROVISO*** | | | | | | COMMENTS HAVE BEEN ADDRESSED FROM THE PREVIOUS REVIEW. | | | PLEASE SEE ADDITIONAL COMMENTS: | | | | | | 1) DESIGN CRITERIA REFERS TO NFPA 13 AND SHEET FP 13.02 | | | REFERS TO NFPA 13R IN SHEET NOTES. PLEASE CORRELATE OR | | | EXPLAIN. | | | | | | 2) PLEASE SEE CORRECTION FROM PREVIOUS REVIEW COMMENTS. | | | MULTI-FAMILY RESIDENTIAL BUILDINGS TO COMPLY WITH | | | COMMERCIAL REQUIREMENTS FOR ADDRESSING. MINIMUM OF 6" | | | IN HEIGHT AND 1" IN WIDTH. SEPARATE UNIT CHARACTERS TO | | | COMPLY WITH 3" REQUIREMENT. | | | | | | 3) PLANS DON'T SEEM TO ILLUSTRATE ANY POST INDICATING | | | VALVE DETAIL. A NOTE DOES REFERENCE PIV TAMPER SWITCHES | | | ON SHEET FP 13.06. WHAT MEANS WILL BE PROVIDED WHERE | | | THE STATUS OF (1) BUILDING WON'T IMPACT OTHER | | | BUILDINGS? PLEASE PROVIDE DETAIL AND ILLUSTRATE ON FP | | | SITE PLAN. | | | | | | 4) PLEASE INDICATE IF ANY ELEVATORS WILL MEET | | | REQUIREMENTS FOR STRETCHER ACCESSIBILITY. | | | | | | | | | PLANS WILL BE STAMPED WHEN RETURNED AND ADDRESSED FOR | | | FIRE COMMENTS IN ADDITION TO OTHER REVIEW NOTES. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-02-27 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-02-27 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-02-27 |
Time |
15:48 |
Sent To |
|
|
| Notes |
| 2007-02-27 15:49:02 | ***DENIED*** | | | | | | IN ORDER TO HELP EXPEDITE THE PLAN REVIEW PROCESS, | | | PLEASE SEE THE FOLLOWING: | | | | | | 1) PLEASE REFER TO THE FIRST FIRE REVIEW COMMENTS. MANY | | | COMMENTS WERE ANSWERED OR ADDRESSED WITH COMMENT NOTED. | | | THIS DOES NOT DEMONSTRATE THAT COMPLIANCE WILL BE MET. | | | IT WOULD BE HELPFUL IF THE CHANGE OR ADDED NOTE IS | | | CLEARLY SHOWN ON DRAWINGS, AND THE CORRECT SHEET NUMBER | | | IS INDICATED. SOME RESPONSES WERE FOUND ON SHEETS THAT | | | WERE DIFFERENT FROM WHAT WAS INDICATED IN THE RESPONSE | | | LETTER. FOR EXAMPLE, COMMENT #1 INDICATES THAT | | | REFERENCE HAS BEEN ADDED TO FP13.17, BUT WAS ACTUALLY | | | FOUND ON A 1.02. PLEASE KNOW THAT IT IS UNDERSTOOD THAT | | | SOME COMMENTS MAY BE ACKNOWLEDGED, BUT SHOULD BE SHOWN | | | ON PLANS TO ELLIMINATE CONFUSION IN THE FUTURE DURING | | | THE INSPECTION PROCESS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW(561) 805-6722 | | | FIRE PREVENTION(561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2005-12-28 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-12-28 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-12-28 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2005-12-28 00:00:00 | ******DENIED****** | | | | | | 1) NFPA 101 AND NFPA 1, 2003 EDITION | | | SHALL BE REFERENCED. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER SYSTEM | | | WHICH SHALL BE UL CERTIFIED FOR CENTRAL | | | STATION SERVICE. | | | | | | 3) PLEASE NOTE THAT INTENDED SCOPE OF | | | WORK FOR THIS PROJECT IN RELATION TO THE | | | PERMIT APPLICATIONS IS CONFUSING. | | | | | | 4) WHENS PLANS ARE RESUBMITTED, PLEASE | | | ASSURE THAT ALL SHEETS ARE BOUND | | | TOGETHER AND ORGANIZED. | | | | | | 5) CONSTRUCTION, ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | 6) STAIRS ARE TO BE KEPT UP WITH | | | CONSTRUCTION. | | | | | | 7) TEMPORARY STANDPIPES ARE REQUIRED | | | WHEN THE BUILDING REACHES 3 STORIES OR | | | 30' IN HEIGHT. | | | | | | 8) IN REGARDS TO PHASING, PLEASE BE | | | ADVISED THAT ALL LIFE SAFETY COMPONENTS | | | MUST BE INSPECTED, TESTED AND APPROVED | | | PRIOR TO OCCUPANCY OF BUILDINGS. | | | | | | 9) PARKING AREAS MUST BE IN COMPLIANCE | | | WITH APPLICABLE BUILDING CODES AND NFPA | | | 88A. MINIMUM TWO HOUR SEPARATION TO | | | OTHER PARTS OF BUILDING IS REQUIRED. | | | | | | 10) WET FIRE HYDRANTS TO BE OPERATION | | | PRIOR TO, DURING AND AFTER CONSTRUCTION. | | | | | | 11) PLEASE NOTE THAT ALL LIFE SAFETY | | | EQUIPMENT, FIRE SPRINKLER AND FIRE ALARM | | | AND ALL OTHER BUILDING SERVICES SHALL BE | | | SEPARATE IF BUILDINGS MEET THE CRITERIA | | | FOR SEPARATE STRUCTURES. | | | | | | 12) ALL ACCESS ROADS SHALL BE AT LEAST | | | 20' IN CLEAR , UNOBSTRUCTED WIDTH FOR | | | EMERGENCY VEHICLES, AND SHALL MEET ALL | | | OTHER REQUIREMENTS OF NFPA 1. | | | | | | 13) PLEASE INDICATE ALL LOCATION OF FIRE | | | HYDRANTS. | | | | | | 14) NFPA 13, 2002 EDITION SHALL BE | | | REFERENCED. SHT. A5.01. | | | | | | 15) LOCKING KNOX BOX CAPS ARE REQUIRED | | | ON FIRE DEPARTMENT CONNECTIONS. | | | | | | 16) IN ADDITION TO ELECTRONIC SWITCHES, | | | THE DOUBLE CHECK DETECTOR ASSEMBLIES | | | SHALL BE SECURED WITH A CHAIN AND LOCK. | | | | | | 17) AS NOTED ON SHT, A5.02, FIRE | | | EXTINGUISHERS SHALL BE MOUNTED AT | | | DISTANCES TO SATISFY THE 75' TRAVEL | | | DISTANCE REQUIREMENT. | | | | | | 18) ALL DOORS SHALL SWING IN THE | | | DIRECTION OF TRAVEL WHEN SERVING AREAS | | | WITH OCCUPANT LOADS OF GREATER THAN 50. | | | | | | 19) ELEVATORS TO COMPLY WITH ASME A17.1. | | | | | | 20) PENETRATIONS INTO , AND OPENINGS | | | THROUGH STAIRWELLS SHALL BE LIMITED TO | | | AND IN COMPLIANCE WITH NFPA 101, SECTION | | | 7.1.3.2.1 (6). | | | | | | 21) PLEASE CLARIFY ALL EXIT DISCHARGING | | | FROM STAIRWELLS THAT LEAD DIRECTLY TO | | | THE OUTSIDE. | | | | | | 22) SOME ACHITECTUAL DRAWINGS SHOW | | | STAIRWELL DOORS, AND OTHERS DON'T.??? | | | | | | 23) THIS PERMIT APPLICATION PROCESS | | | ILLUSTRATES 3 BUILDINGS AND OTHER | | | BUILDINGS, 4&5 ARE SHOWN ON PLANS. | | | PLEASE CLARIFY. | | | | | | 24) PLEASE ILLUSTRATE THE TOTAL OCCUPANT | | | LOAD FOR THE CLUBHOUSE. | | | | | | 25) IN ADDITION TO THE ALREADY NOTED | | | REQUIREMENTS FOR ADDRESSING, PLEASE NOTE | | | THAT THE HEIGHT OF THE ADDRESS SHALL BE | | | AT LEAST 3" IN HEIGHT FOR RESIDENTIAL | | | BUILDINGS. | | | | | | 26) PLEASE REFER TO DOOR SCHEDULE AND | | | VERIFY CORRECT AMOUNT OF FIRE RATED | | | DOORS. DOORS SERVINGS AREAS WITH | | | OCCUPANT LOADS GREATER THAN 100 SHALL | | | HAVE PANIC HARDWARE. | | | | | | 27) FIRE PROTECTION SITE PLAN DOESN'T | | | APPEAR COMPLETE ON SHT FP13.01. | | | | | | 28) FIRE DEPARTMENT VALVES SHALL BE 2 | | | 1/2" TO 1 1/2" REDUCER WITH CHAINS. | | | | | | 29) MORE INFORMATION AND MANUFACTURER | | | SPEC SHEETS REQUIRED FOR FIRE PUMP AND | | | ASSOCIATED EQUIPMENT. | | | | | | 30) FIRE PROTECTION SHEETS DON'T SHOW | | | ANY FIRE SPRINKLER SYSTEM. ???? FIRE | | | SPRINKLER DESIGN AND LAY OUT MUST BE | | | ILLUSTRATED. | | | | | | 31) IF A FIRE HYDRANT FLOW TEST HASN'T | | | BEEN DONE WITHIN ONE YEAR, ANOTHER TEST | | | WILL BE REQUIRED FOR FIRE SPRINKLER | | | CALC. PLEASE CONTACT THE BUREAU OF FIRE | | | PREVENTION AT (561) 805-4724. | | | | | | 32) PLEASE INDICATE ALL SMOKE DETECTOR | | | LOCATIONS IN ACCORDANCE WITH NFPA 101, | | | SECTION 30.3.4.5. | | | | | | 33) EXIT LIGHTS TO BE MOUNTED AT | | | DISTANCES NOT TO EXCEED 100'. IT APPEARS | | | THAT MORE EXIT SIGNS ARE NEEDED IN | | | CORRIDORS. | | | | | | 34) FIRE ALARM SHALL BE CLASS A, STYLE D | | | OR FULLY ADDRESSABLE. | | | | | | 35) ARE SMOKE DETECTORS TIED INTO THE | | | FIRE ALARM SYSTEM PLANNED FOR CORRIDORS? | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-08-05 |
|
|
Cont ID |
|
| Sent By |
amckenzi |
Date |
2008-08-05 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
amckenzi |
Date |
2008-08-05 |
Time |
09:32 |
Sent To |
|
|
| Notes |
| 2008-08-05 09:33:05 | TO EXTEND APPLICATION UNTIL 11/5/08 PER NKM/AMM |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-08-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-14 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-14 |
Time |
14:21 |
Sent To |
|
|
| Notes |
| 2007-09-07 16:18:27 | TO "COMM" BD#55/PLANS ON RACK--15 ROLLS | | 2007-08-14 14:22:04 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-11-29 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2006-11-29 |
Time |
19:32 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2006-11-29 |
Time |
19:32 |
Sent To |
|
|
| Notes |
| 2006-12-08 15:29:49 | TO "COMM" BD#41--3 APPL. PLANS ON RACK--7 ROLLS | | 2006-11-29 19:33:02 | WAITING FOR "COMM" BOARD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-08-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-08-31 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-08-31 |
Time |
11:33 |
Sent To |
|
|
| Notes |
| 2006-08-31 00:00:00 | WAITING FOR "COMM" BD-ROLLS BY MIRELLE'S | | | CUBE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2006-03-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-10-03 |
Time |
16:33 |
Sent To |
|
|
| Notes |
| 2005-10-12 00:00:00 | TO "COMM" BD#49/PLANS ON RACK | | 2005-10-03 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2007-10-30 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-10-30 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-10-30 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2007-10-30 15:10:49 | REVIEW #: 3 | | | ACTION: DENIED | | | | | | FBC 2001 CODES W/ 2003 REVISIONS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRRESPOND WITH | | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S | | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | | | 1. OK | | | | | | 2. RETURN AIR TRANSFERS AND JUMPERS ARE STILL NOT | | | DESIGNED TO MEET THE EXCEPTIONS AS LISTED UNDER FBC,M | | | 601.4. EXAMPLE: UNIT B2 SHOWS AN 8 INCH ROUND (50 | | | SQ.IN) R/A JUMPER FOR 7 INCH (38.5 SQ.IN) AND 4 INCH | | | (13 SQ.IN) ROUND SUPPLY DROPS IN MASTER BEDROOM. THE | | | R/A JUMPER MUST BE 1.5 TIMES THE SIZE OF THE SUPPLY | | | DROPS IN THE MASTER TO MEET EXCEPTION 1 UNDER FBC,M | | | 601.4. THE 7IN PLUST THE 4IN DUCTS TOTAL 51.5 SQ. IN. | | | THE TRANSFER IS SMALLER THAN THE TWO SUPPLY DUCTS | | | RATHER THAN 1.5 TIMES LARGER. THE EXCEPTION HAS NOT | | | BEEN MET. IF THE DESIGNER CHOOSES NOT TO DESIGN TO MEET | | | THE EXCEPTIONS, A FIELD TEST WILL BE REQUIRED AT FINAL | | | INSPECTION TO DEMONSTRATE A MAX. PRESSURE DIFFERENTIAL | | | OF 0.01IN. W.C. ACROSS THE CLOSED BEDROOM DOORS AS | | | REQUIRED BY FBC,M 601.4. | | | | | | 3. OK | | | | | | 4. OK | | | | | | 5. M15.06: CONDENSATE TRAP DETAIL FOR NON-DUCTED RETURN | | | UNITS, THE SECONDARY DRAIN LINE FROM THE AUXILIARY | | | DRAIN PAN SHALL NOT BE CONNECTED TO THE PRIMARY | | | CONDENSATE RISER. A SEPARATE DRAIN LINE SHALL EXTEND | | | FROM THE PAN TO A CONSPICUOUS POINT AND SERVE AS AN | | | ALARM WHICH INDICATES THAT THE PRIMARY DRAIN IS | | | RESTRICTED.AS AN ALTERNATIVE TO A SEPARATE DRAIN | | | LINE, AN APPROVED WATER LEVEL DETECTOR OR FLOAT SWITCH | | | DEVICE SHALL BE USED TO CONTROL OVERFLOW BY | | | AUTOMATICALLY SHUTTING DOWN THE EQUIPMENT OR APPLIANCE | | | THAT PRODUCES THE CONDENSATE. THE FLOAT SWITCH ON THE | | | SECONDARY DRAIN OUTLET AT THE AHU MAY BE INSTALLED | | | (ALTHOUGH IT'S NOT NECESSARY) BUT IT CAN NOT REPLACE | | | THE SEPARATE SECONDARY DRAIN LINE OR THE FLOAT SWITCH | | | REQUIRED ON THE AUXILIARY DRAIN PAN. THE FLOAT SWITCH | | | ON THE SECONDARY DRAIN OUTLET AT THE AHU IS ACCEPTABLE | | | AS OVERFLOW PROTECTION ONLY ON THE DUCTED RETURN UNITS | | | WHERE AN AUXILIARY DRAIN PAN CAN NOT BE INSTALLED UNDER | | | THE AHU. FBC,M 307.2.3 AND 307.2.4 | | | | | | 6 THROUGH 10: OK | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2006-12-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-12-29 |
Time |
08:01 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-12-29 |
Time |
07:11 |
Sent To |
|
|
| Notes |
| 2006-12-29 08:58:28 | DENIED:BUILDING #2 / 2001 FBC | | | | | | RESPONSE TO COMMENTS FROM REVIEW DATED 1-31-06 | | | | | | COMMENT 1:OK | | | | | | COMMENT 2:RESPONSE INDICATES NOTE FOR RETURN AIR ON | | | SHEETS M15.01 THROUGH M15.03.PLEASE NOTE THE R/A | | | INDICATED ON THE PLAN IS CONSIDERED A TRANSFER UNDER | | | 2001 FMC 601.4 EXCEPTION 2 NOT 1.PLEASE VERIFY GRILLE | | | SIZES.ALL AIR INTO THE MASTER SUITE IS TO BE INCLUDED | | | IN THE CALCULATION (I.E. BATHROOM, CLOSET, ETC). PLEASE | | | ALSO NOTE WALL CAVITIES USED FOR TRANSPORTING R/A SHALL | | | BE LINED WITH AN AIR BARRIER AND SEALED IN ACCORDANCE | | | WITH 2001 FBC CHAPTER 13 SUB-CHAPTER 410.1.ABCD.3.7. | | | | | | COMMENT 3:RESPONSE INDICATES AHU CLOSET DOOR IS | | | NON-COMBUSTIBLE BUT THE DOOR SCHEDULE ON SHEET A9.02 | | | STILL INDICATES A WOOD DOOR.PLEASE CLARIFY. | | | | | | COMMENT 4:RESPONSE STATES THE CLEARANCE AROUND THE | | | AHU EXCEEDS THE 4" REQUIREMENT UNDER 2001 FMC | | | 603.1.3.4.THE DETAIL ON PLAN SHEET M15.06 DOES NOT | | | REFLECT OR ANNOTATE 4" CLEARANCE.PLEASE ALSO NOTE, | | | THE CONDENSATE LINE SHALL BE OF NON-COMBUSTIBLE | | | MATERIAL (NO PVC IN AHU CLOSET). | | | | | | COMMENT 5:RESPONSE REFERS TO "CONDENSATE TRAP DETAIL" | | | ON SHEET M15.09.THE DETAIL IS ACTUALLY ON SHEET | | | M15.06.PER 2001 FMC 307.2.3 & 307.2.4 AN AUXILLARY | | | DRAIN PAN IS REQUIRED.PLEASE CONTACT HAROLD MOSER, | | | CHIEF MECHANICAL INSPECTOR WITH REGARDS TO THIS | | | APPLICATION.HAROLD MOSER CAN BE REACHED AT | | | (561)805-6732. | | | | | | COMMENT 6:OK | | | | | | COMMENT 7:OK | | | | | | COMMENT 8:OK | | | | | | COMMENT 9:OK | | | | | | COMMENT 10: OK | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | | AT (561)805-6719 OF E-MAIL [email protected]. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-01-31 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-01-31 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-01-31 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2006-01-31 00:00:00 | DENIED:2001 FLORIDA BUILDING CODE | | | | | | 1.PLAN SHEET AP A6.01 THROUGH A701, IT | | | APPEARS THE COORIDORS HAVE OPENINGS AT | | | CERTAIN POINTS.PLEASE INDICATE TOTAL | | | SQUARE FOOTAGE AS REQUIRED FOR 'NATURAL | | | VENTILATION'.THE OUTSIDE AIR | | | CALCULATIONS INDICATED ON PLAN SHEET | | | M15.13 DO NOT SHOW TOTAL SQUARE FOOTAGE. | | | | | | 2.PLANS INDICATE RETURN AIR JUMPERS | | | FROM THE BEDROOM AREAS.PLEASE NOTE, | | | THE RETURN AIR JUMPERS ARE TO BE SIZED | | | IN ACCORDANCE WITH 2001 FMC 601.4 | | | EXCEPTION 1 & 3.PLEASE REVISE RETURN | | | TO INCREASE TO THE REQUIRED MINIMUM. | | | | | | 3.PLANS INDICATE LOUVERED DOOR.THE | | | DOOR SCHEDULE INDICATES THIS AS BEING A | | | WOOD DOOR.THE AHU CLOSET IS CONSIDERED | | | A RETURN AIR PLENUM.THE DOOR MUST ALSO | | | MEET THE REQUIREMENT OF NON-COMBUSTIBLE | | | OR SHALL HAVE A FLAME SPREAD INDEX OF | | | NOT MORE THAN 25 AND A SMIKE DEVELOPED | | | INDEX OF NOT MORE THAN 50 WHEN TESTED IN | | | ACCORDANCE WITH ASTM E 84.PLEASE | | | PROVIDE DOCUMENTATION ON THE DOORS. | | | | | | 4.PLEASE NOTE, PER 2001 FMC 603.1.3 4" | | | CLEARANCE AROUND THE AIR HANDLER IS | | | REQUIRED. | | | | | | 5.PLAN SHEET M15.12 DETAILS FOR THE | | | AHUDOES NOT INDICATE AN AUXILIARY | | | DRAIN PAN WITH OVERFLOW PROTECTION AS | | | REQUIRED BY 2001 FMC 307.2.3.PLEASE | | | REVISE. | | | | | | 6.CONDENSING UNIT STANDS SHALL COMPLY | | | WITH 2001 FBC 1511.7 FOR HEIGHT | | | REQUIREMENT ABOVE FINISHED ROOF. | | | | | | 7.CONDENSING UNIT STANDS SHALL COMPLY | | | WITH 2001 FMC 301.13 & CHAPTER 15 OF THE | | | FBC FOR WIND PRESSURES. | | | | | | 8.PLEASE PROVIDE LINE SIZES FOR THE | | | REFRIGERANT LINES AS WELL AS THE | | | CONDENSATE. | | | | | | 9.PLEASE INDICATE TERMINATION OF THE | | | CONDENSATE. | | | | | | 10. PLEASE PROVIDE ENERGY AND MANUAL J | | | CALCULATIONS IN ACCORDANCE WITH 2001 FBC | | | CHAPTER 13. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2007-11-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-11-15 |
Time |
12:46 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-11-15 |
Time |
12:45 |
Sent To |
|
|
| Notes |
| 2007-11-15 14:43:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 BUILDING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FHA-98 DESIGN MANUAL | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | FROM PREVIOUS REVIEW. THE COMMENT NUMBER | | | SHALL STAY THE SAME AS THE FIRST REVIEW: | | | | | | ******FROM PREVIOUS REVIEWS: (3RD REVIEW) | | | | | | A. OK | | | B. OK | | | 1. OK | | | 2. OK | | | | | | 3. SHT AP/A5.12 SUBMIT CALCULATIONS FOR | | | PRIMARY AND SECONDARY ROOF DRAINS PER | | | SECTIONS 1106 & 1107 AND ALL | | | SUBSECTIONS. SHOW SF DRAINED FOR EACH | | | AREA ALONG WITH 1/2 AREA OF ALL VERTICAL | | | WALLS, INCLUDING PARAPETS, AND THE AREA | | | OF ANY ROOFS THAT DRAIN ONTO THE ROOF | | | AREAS FROM ABOVE. - SHOW THE LOCATION OF | | | ALL SECONDARY ROOF DRAINS OR SCUPPERS. | | | IF SCUPPERS ARE USED, SUBMIT A DETAIL | | | SHOWING HEIGHT, WIDTH, AND DISTANCE TO | | | FLOW LINE OFF THE ROOF. SECTION 1503.4.2 ****RESPONSE | | | NOTED, BUT SHEETS A5.05, | | | A5.13, A5.25 WERE NOT SUBMITTED, AND NO CALCULATIONS | | | WITH INFORMATION REQUESTED | | | HAS BEEN LOCATED. | | | ******RESPONSE NOTED, BUT THE SECONDARY ROOF DRAINAGE | | | HAS NOT BEEN PROPERLY ADDRESSED. WHEN THE DOWNSPOUT HAS | | | A BLOCKAGE, AND WHILE IT IS TRUE THAT THE STORM WATER | | | CAN DRAIN OVER THE TOP OF THE COLLECTOR HEAD, THE | | | CONCERN IS THAT WHEN THE SCUPPER OPENING IS BLOCKED | | | THEN NEITHER THE PRIMARY NOR THE SECONDARY ROOF DRAIN | | | WILL BE ABLE TO WORK. SECTION 1107.2 SEPARATE SYSTEMS | | | ARE REQUIRED AND THE OVERFLOW SCUPPER SHALL BE SIZED | | | PER SECTION 1107.3. | | | | | | 4. SHTS AP/A5.61 & AP/A5.62 INDICATE | | | SPECIFICATION "A" OR "B" FOR EACH UNIT | | | OR BATHROOM AS REQUIRED IN FHA DESIGN | | | MANUAL PAGES 7.34 & 7.35. - LAVS SHALL | | | BE A MINIMUM OF 2' OFF THE WALL IN ORDER | | | TO BE CENTERED ON THE 48" LENGTH OF THE | | | CLEAR FLOOR SPACE. PLEASE INDICATE ON | | | PLANS. FHA DESIGN MANUAL PAGES 7.47 AND | | | 7.48. - WATER CLOSET OPENING SHALL BE A | | | MINIMUM OF 33" WITH THE WATER CLOSET 18" | | | OFF ONE FIXTURE AND 15" OFF THE OTHER | | | FIXTURE TO THE CENTER OF THE W/C. FHA | | | DESIGN MANUAL PAGES 7.43, 7.44, & 7.45. ****RESPONSE | | | NOTED, BUT SPECIFICATION | | | "A" OR "B" HAS NOT BEEN INDICATED. ALSO | | | THE WATER CLOSET OPENING MEASUREMENTS | | | HAS NOT BEEN SHOWN ON THE FLOOR PLAN. ******RESPONSE | | | NOTED, BUT SPECIFICATION "A" OR "B" HAS NOT BEEN | | | INDICATED. | | | | | | 5. OK | | | 6. OK | | | 7. OK | | | 8. OK - N/A | | | 9. OK | | | 10. OK | | | 11. OK | | | 12. OK | | | 13. OK | | | | | | 14. AN RPZV BACKFLOW IS REQUIRED ON THE | | | WATER SERVICE TO THE BUILDING. SECTION | | | 608.13.2. | | | ****RESPONSE NOTED, BUT COMMENT NOT | | | ADDRESSED. EACH BUILDING IS REQUIRED TO | | | HAVE ITS OWN RPZV BACKFLOW. INDICATE ON | | | PLANS AT THE WATER SERVICE TO THE | | | BUILDING. | | | ******RESPONSE NOTED, BUT THERPZV BACKFLOW FOR THIS | | | BUILDING IS NOT INDICATED ON SHEET 10 OF THE CIVIL | | | PLANS. | | | | | | 15. SUBMIT A WATER LAYOUT FOR BUILDING | | | AND WATER RISER DIAGRAMS. SHOW ALL PIPE | | | SIZES, VALVES, WATER HAMMER ARRESTORS, | | | (INSTALLED IN AN "EFFECTIVE RANGE" NOT | | | IN THE CEILING). SECTIONS 104.3.1.1, | | | 606.1, 606.2, 608.13.2 & PDI-WH 201. | | | ****RESPONSE NOTED, BUT THE WATER RISER | | | DIAGRAM SHALL BE SUBMITTED IN ISOMETRIC | | | FORM. WATER HAMMER ARRESTORS AND | | | REQUIRED VALVES CAN NOT BE SHOWN ON A | | | FLAT PIPING LAYOUT. | | | ******RESPONSE NOTED, BUT THE VERTICAL RISER DIAGRAMS | | | FROM THE FIRST FLOOR THUR THE 5TH FLOOR HAVE NOT BEEN | | | SUBMITTED. | | | | | | | | | 16. OK | | | 17. OK | | | 18. OK | | | | | | **************NEW COMMENTS************** | | | | | | 1B. ALL ARCHITECTURAL SHEETS. THE TITLE | | | BLOCK SHALL CONTAIN THE PRINTED NAME OF | | | THE PERSON SEALING THE DOCUMENT. FAC 61G1-16.004(6) & | | | FS F81.2055. | | | ******RESPONSE NOTED, BUT THE PRINTED NAME IS NOT | | | INDICATED ON SHEET GN/A1.04. | | | | | | 2B. SHT AP P14.04 PIPING FOR THE | | | FIXTURES ON THE SECOND THRU 4TH FLOORS | | | SHALL BE SHOWN ON THE FLOOR PLAN WITH | | | THE FIXTURES, (SHT P14.05). SECTION | | | 104.2.1.3. | | | ******RESPONSE NOTED, BUT PIPING NOT SHOWN FOR ALL | | | RISERS. | | | | | | 3B. OK N/A | | | | | | 4B. SUBMIT A DETAIL FOR THE DOWNSPOUTS | | | AND THE COLLECTOR HEAD AT THE TOP. | | | INDICATE SIZE OF DOWNSPOUT, LENGTH, | | | WIDTH & HEIGHT OF COLLECTOR HEAD. | | | INDICATE ON ROOF PLAN SQUARE FOOTAGE | | | DRAINING INTO EACH DOWNSPOUT. | | | ******RESPONSE NOTED, BUT THE DETAIL DOES NOT SHOW | | | LENGHT, WIDTH OR HEIGHT. SUBMIT AN ELEVATION DETAIL | | | SHOWING THESE MEASUREMENTS AS WELL AS A CUT SECTION. | | | SECTION 1106.3. | | | | | | 5B. SECONDARY DRAINAGE AND SEPARATE | | | SYSTEMS ARE REQUIRED FOR THE ROOF | | | DRAINAGE PER SECTIONS 1107.1 & 1107.2. | | | PLEASE INDICATE THE LOCATION AND SIZE OF | | | THE SECONDARY ROOF DRAINAGE. SUBMIT A | | | DETAIL FOR THE SECONDARY ROOF DRAINS. ******RESPONSE | | | NOTED, BUT THE INTENT OF THE CODE SECTION HAS NOT BEEN | | | ADDRESSED. WHEN THE DOWNSPOUT HAS A BLOCKAGE, AND WHILE | | | IT IS TRUE THAT THE STORM WATER CAN DRAIN OVER THE TOP | | | OF THE COLLECTOR HEAD, THE CONCERN IS THAT WHEN THE | | | SCUPPER OPENING IS BLOCKED THEN NEITHER THE PRIMARY NOR | | | THE SECONDARY ROOF DRAIN WILL BE ABLE TO WORK. SECTION | | | 1107.2 SEPARATE SYSTEMS ARE REQUIRED AND THE OVERFLOW | | | SCUPPER SHALL BE SIZED PER SECTION 1107.3. SHOW THE | | | LOCATION OF THE EMERGENCY OVERFLOW SCUPPERS. | | | | | | 6B. OK | | | | | | ********NEW COMMENTS 3RD REVIEW******** | | | | | | 1C. SHT AP/P14.01 ALL WATER RISERS. WATER HAMMER | | | ARRESTORS ARE REQUIRED ON THE WATER LINE TO THE DISH | | | WASHER. SECTION 604.9.--UNIT A3 PLUMBING PLAN NOTE | | | STATES "1/2 IN. CW/HW DN", BUT ONLY SHOWS CW LINE. | | | PLEASE CORRELATE.--REVISION 1 DELETED FROM THE | | | TITLE BLOCK REVISION INDEX. PLEASE SHOW THE COMPLETE | | | HISTORY OF REVISIONS ON THE REVISION INDEX FOR ACCURATE | | | RECORD KEEPING. SECTION 104.2.1.3. | | | | | | 2C. SHT AP/P14.02 REVISION 1 DELETED FROM THE TITLE | | | BLOCK REVISION INDEX. PLEASE SHOW THE COMPLETE HISTORY | | | OF REVISIONS ON THE REVISION INDEX FOR ACCURATE RECORD | | | KEEPING. SECTION 104.2.1.3. | | | | | | 3C. SHT AP/P14.03 SHOW ALL PIPING ON EACH TYPICAL FLOOR | | | PLAN. (2ND - 4TH & 5TH FLOORS) . SHOW ALL RISER NUMBERS | | | AS THEY APPEAR ON THE BUILDING DRAIN ISOMETRIC RISER | | | DIAGRAM AS THEY COME UP TO THE 2ND FLOOR. S7 THRU S-15 | | | NOT SHOWN ON THE 2ND FLOOR. INDICATE WHERE THESE RISERS | | | COME THRU THE 2ND FLOOR.SECTION 104.2.1.--MANY | | | PLAN KEY NOTES 1 & 2 DO NOT SHOW RISERS OR RISER | | | NUMBERS.--WHERE DOES THE PIPING IN THE ELEVATOR | | | CORRIDOR PIPE TO?SECTION 104.2.1.--REVISION 1 | | | DELETED FROM THE TITLE BLOCK REVISION INDEX. PLEASE | | | SHOW THE COMPLETE HISTORY OF REVISIONS ON THE REVISION | | | INDEX FOR ACCURATE RECORD KEEPING. SECTION 104.2.1.3. | | | | | | 4C. SHT AP/P14.04 SANITARY RISER DIAGRAM S-5 SHOULD BE | | | 28 DFU'S, NOT 20 DFU'S. (EXTRA TUB OR SHOWER). TABLE | | | 709.1.--CLEANOUTS REQUIRED BY SECTION 1101.8 ARE | | | REQUIRED ON THE STORM RISER DIAGRAM. PLEASE SHOW | | | LOCATION OF ALL REQUIRED C/O'S.--CLEANOUTS REQUIRED | | | BY SECTION 708.3 ARE REQUIRED ON THE SANITARY RISER | | | DIAGRAM. PLEASE SHOW LOCATION OF ALL REQUIRED C/O'S. | | | (CHANGE OF DIRECTION GREATER THAN 45 DEGREES).-- | | | REVISION 1 DELETED FROM THE TITLE BLOCK REVISION INDEX. | | | PLEASE SHOW THE COMPLETE HISTORY OF REVISIONS ON THE | | | REVISION INDEX FOR ACCURATE RECORD KEEPING. REVISION #4 | | | NOT SHOWN. SECTION 104.2.1.3. | | | | | | 5C. SHT AP/P14.05 WATER HEATER DETAIL. A FULL OPEN | | | VALVE IS REQUIRED ON THE SUPPLY LINE TO THE WATER | | | HEATER. SECTION 606.1(7). PLEASE SHOW COMPLIANCE ON THE | | | W/H DETAIL. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6713 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-11-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-10-06 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-10-06 |
Time |
13:14 |
Sent To |
|
|
| Notes |
| 2006-10-06 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 BUILDING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FHA-98 DESIGN MANUAL | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | FROM PREVIOUS REVIEW. THE COMMENT NUMBER | | | SHALL STAY THE SAME AS THE FIRST REVIEW: | | | | | | A. OK | | | B. OK | | | 1. OK | | | 2. OK | | | | | | 3. SHT AP/A5.12 SUBMIT CALCULATIONS FOR | | | PRIMARY AND SECONDARY ROOF DRAINS PER | | | SECTIONS 1106 & 1107 AND ALL | | | SUBSECTIONS. SHOW SF DRAINED FOR EACH | | | AREA ALONG WITH 1/2 AREA OF ALL VERTICAL | | | WALLS, INCLUDING PARAPETS, AND THE AREA | | | OF ANY ROOFS THAT DRAIN ONTO THE ROOF | | | AREAS FROM ABOVE. - SHOW THE LOCATION OF | | | ALL SECONDARY ROOF DRAINS OR SCUPPERS. | | | IF SCUPPERS ARE USED, SUBMIT A DETAIL | | | SHOWING HEIGHT, WIDTH, AND DISTANCE TO | | | FLOW LINE OFF THE ROOF. SECTION 1503.4.2 ****RESPONSE | | | NOTED, BUT SHEETS A5.05, | | | A5.13, A5.25 WERE NOT SUBMITTED, AND NO CALCULATIONS | | | WITH INFORMATION REQUESTED | | | HAS BEEN LOCATED. | | | | | | 4. SHTS AP/A5.61 & AP/A5.62 INDICATE | | | SPECIFICATION "A" OR "B" FOR EACH UNIT | | | OR BATHROOM AS REQUIRED IN FHA DESIGN | | | MANUAL PAGES 7.34 & 7.35. - LAVS SHALL | | | BE A MINIMUM OF 2' OFF THE WALL IN ORDER | | | TO BE CENTERED ON THE 48" LENGTH OF THE | | | CLEAR FLOOR SPACE. PLEASE INDICATE ON | | | PLANS. FHA DESIGN MANUAL PAGES 7.47 AND | | | 7.48. - WATER CLOSET OPENING SHALL BE A | | | MINIMUM OF 33" WITH THE WATER CLOSET 18" | | | OFF ONE FIXTURE AND 15" OFF THE OTHER | | | FIXTURE TO THE CENTER OF THE W/C. FHA | | | DESIGN MANUAL PAGES 7.43, 7.44, & 7.45. ****RESPONSE | | | NOTED, BUT SPECIFICATION | | | "A" OR "B" HAS NOT BEEN INDICATED. ALSO | | | THE WATER CLOSET OPENING MEASUREMENTS | | | HAS NOT BEEN SHOWN ON THE FLOOR PLAN. | | | | | | 5. SHT AP/A5.56 INDICATE MATERIAL FOR | | | GRAB BAR BLOCKING. SECTION 104.2.1. | | | ***RESPONSE NOTED, (SEE AP A5.56), BUT | | | SHT AP/A5.56 HAS NOT BEEN SUBMITTED. | | | PLEASE CLARIFY. | | | | | | 6. OK | | | 7. OK | | | | | | 8. SUBMIT A DETAIL FOR THE COMMON USE | | | TOILET ROOMS SHOWING COMPLIANCE WITH | | | SECTIONS 11-4.16, 11-4.19, & 11-4.22 AND | | | ALL SUBSECTIONS. | | | ****RESPONSE NOTED, (SEE SHEET A5.70 AND | | | A5.71), BUT THOSE SHEETS HAVE NOT BEEN | | | SUBMITTED. | | | | | | 9. SHTS AP/P14.02 UNITS B3 & B4 MAXIMUM | | | 4 FU ON A 2" WET VENT IN MASTER BATH. | | | TABLE 909.3. | | | ****RESPONSE NOTED, BUT NOT THE RISER | | | DIAGRAM DOES NOT REFLECT THE FLOOR PLAN | | | AS THE FLOOR PLAN SHOWS 3" AND THE RISER | | | DIAGRAM SHOWS 2-1/2" FOR THE WET VENT. | | | CORRELATE RISER AND FLOOR PLAN. SECTION | | | 104.2.1. | | | | | | 10. OK | | | | | | 11. SHT AP/P14.26 OFFSETS IN THE SANT. | | | SHALL BE SHOWN ON EITHER BLDG. DRAIN | | | ISOMETRIC RISER DIAGRAM, OR SANT. RISER | | | DIAGRAMS. SECTION 104.2.1. | | | ****RESPONSE NOTED, BUT WHEN THE SANT. | | | RISER FROM UNDERGROUND IS ABOVE THE | | | CEILING OF THE FIRST FLOOR, THE RISER | | | SPLITS AND OFFSETS INTO OTHER RISERS. | | | (EXAMPLE RISER 2,3,6 COMES OUT OF THE | | | GROUND AND OFFSETS ABOVE THE CEILING AND | | | SPLITS INTO THREE SEPARATE RISERS. | | | BUILDING DRAIN ISOMETRIC RISER SHALL | | | REFLECT THIS PIPING. SECTION 104.3.1.1. | | | | | | 12. OK | | | 13. OK | | | | | | 14. AN RPZV BACKFLOW IS REQUIRED ON THE | | | WATER SERVICE TO THE BUILDING. SECTION | | | 608.13.2. | | | ****RESPONSE NOTED, BUT COMMENT NOT | | | ADDRESSED. EACH BUILDING IS REQUIRED TO | | | HAVE ITS OWN RPZV BACKFLOW. INDICATE ON | | | PLANS AT THE WATER SERVICE TO THE | | | BUILDING. | | | | | | 15. SUBMIT A WATER LAYOUT FOR BUILDING | | | AND WATER RISER DIAGRAMS. SHOW ALL PIPE | | | SIZES, VALVES, WATER HAMMER ARRESTORS, | | | (INSTALLED IN AN "EFFECTIVE RANGE" NOT | | | IN THE CEILING). SECTIONS 104.3.1.1, | | | 606.1, 606.2, 608.13.2 & PDI-WH 201. | | | ****RESPONSE NOTED, BUT THE WATER RISER | | | DIAGRAM SHALL BE SUBMITTED IN ISOMETRIC | | | FORM. WATER HAMMER ARRESTORS AND | | | REQUIRED VALVES CAN NOT BE SHOWN ON A | | | FLAT PIPING LAYOUT. | | | | | | 16. SUBMIT A BUILDING SANITARY DRAIN | | | ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE | | | SIZES, TRAPS, OFFSETS, RISER LOCATIONS | | | WITH RISER NUMBERS, DFU'S AS THEY | | | ACCUMULATE IN THE SYSTEM ETC. SECTION | | | 104.3.1.1. | | | ***COMMENT RESPONSE NOTED, BUT COMMENT | | | NOT ADDRESSED. | | | | | | 17. SUBMIT A BUILDING STORM DRAIN | | | ISOMETRIC RISER DIAGRAM, SHOWING ALL | | | PIPE SIZES, RISER LOCATIONS WITH RISER | | | NUMBERS, AND SQUARE FEET AS IT | | | ACCUMULATES IN THE SYSTEM. SECTION | | | 104.3.1.1. | | | ****RESPONSE NOTED, BUT NOT ADDRESSED. | | | SEE COMMENT RESPONSE TO COMMENT #10. | | | | | | 18. OK | | | | | | **************NEW COMMENTS************** | | | | | | 1B. ALL ARCHITECTURAL SHEETS. THE TITLE | | | BLOCK SHALL CONTAIN THE PRINTED NAME OF | | | THE PERSON SEALING THE DOCUMENT. FAC 61G1-16.004(6) & | | | FS F81.2055. | | | | | | 2B. SHT AP P14.04 PIPING FOR THE | | | FIXTURES ON THE SECOND THRU 4TH FLOORS | | | SHALL BE SHOWN ON THE FLOOR PLAN WITH | | | THE FIXTURES, (SHT P14.05). SECTION | | | 104.2.1.3. | | | | | | 3B. SHTS AP A5.60, AP A5.61, AP A5.62 | | | REFER TO SHEET A5.58. THIS SHEET HAS NOT | | | BEEN SUBMITTED. PLEASE CLARIFY. SECTION | | | 104.2.1. | | | | | | 4B. SUBMIT A DETAIL FOR THE DOWNSPOUTS | | | AND THE COLLECTOR HEAD AT THE TOP. | | | INDICATE SIZE OF DOWNSPOUT, LENGTH, | | | WIDTH & HEIGHT OF COLLECTOR HEAD. | | | INDICATE ON ROOF PLAN SQUARE FOOTAGE | | | DRAINING INTO EACH DOWNSPOUT. | | | | | | 5B. SECONDARY DRAINAGE AND SEPARATE | | | SYSTEMS ARE REQUIRED FOR THE ROOF | | | DRAINAGE PER SECTIONS 1107.1 & 1107.2. | | | PLEASE INDICATE THE LOCATION AND SIZE OF | | | THE SECONDARY ROOF DRAINAGE. SUBMIT A | | | DETAIL FOR THE SECONDARY ROOF DRAINS. | | | | | | 6B. SHT AP A5.32 ROOF PLAN SHOWS UNITS | | | AND FIXTURES. PLEASE CLARIFY. SECTION | | | 104.2.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6713 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-01-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-01-18 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-01-18 |
Time |
10:30 |
Sent To |
|
|
| Notes |
| 2006-01-18 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 BUILDING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FHA-98 DESIGN MANUAL | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | A. PLANS WERE SUBMITTED AS LOOSE SHEETS | | | AND AS SUCH IS NOT ACCEPTABLE. PLEASE | | | SUBMIT PLANS IN BOUND SETS. SECTION | | | 104.2.1.3. | | | B. PERMITS INDICATE 3 SEPARATE | | | BUILDINGS, BUT PLANS INDICATE ONE | | | BUILDING. PLEASE CLARIFY. SECTION | | | 104.2.1. | | | 1. ALL ARCHITECTURAL SHEETS, (EXCEPT FOR | | | STRUCTURAL), ARE NOT SEALED AS REQUIRED | | | IN SECTION 104.2.2 & FAC 61G1-16.003 | | | 61G1-16.004(5) & FS 481.2055. | | | 2. SHTS AP/A1.02 & AP/A1.03 SHOWN IN | | | DRAWING INDEX ON SHT AP/A1.01 HAVE NOT | | | BEEN SUBMITTED. SECTION 104.2.1. | | | 3. SHT AP/A5.12 SUBMIT CALCULATIONS FOR | | | PRIMARY AND SECONDARY ROOF DRAINS PER | | | SECTIONS 1106 & 1107 AND ALL | | | SUBSECTIONS. SHOW SF DRAINED FOR EACH | | | AREA ALONG WITH 1/2 AREA OF ALL VERTICAL | | | WALLS, INCLUDING PARAPETS, AND THE AREA | | | OF ANY ROOFS THAT DRAIN ONTO THE ROOF | | | AREAS FROM ABOVE. - SHOW THE LOCATION OF | | | ALL SECONDARY ROOF DRAINS OR SCUPPERS. | | | IF SCUPPERS ARE USED, SUBMIT A DETAIL | | | SHOWING HEIGHT, WIDTH, AND DISTANCE TO | | | FLOW LINE OFF THE ROOF. SECTION 1503.4.2 | | | 4. SHTS AP/A5.61 & AP/A5.62 INDICATE | | | SPECIFICATION "A" OR "B" FOR EACH UNIT | | | OR BATHROOM AS REQUIRED IN FHA DESIGN | | | MANUAL PAGES 7.34 & 7.35. - LAVS SHALL | | | BE A MINIMUM OF 2' OFF THE WALL IN ORDER | | | TO BE CENTERED ON THE 48" LENGTH OF THE | | | CLEAR FLOOR SPACE. PLEASE INDICATE ON | | | PLANS. FHA DESIGN MANUAL PAGES 7.47 AND | | | 7.48. - WATER CLOSET OPENING SHALL BE A | | | MINIMUM OF 33" WITH THE WATER CLOSET 18" | | | OFF ONE FIXTURE AND 15" OFF THE OTHER | | | FIXTURE TO THE CENTER OF THE W/C. FHA | | | DESIGN MANUAL PAGES 7.43, 7.44, & 7.45. | | | 5. SHT AP/A5.56 INDICATE MATERIAL FOR | | | GRAB BAR BLOCKING. SECTION 104.2.1. | | | 6. SHTS AP/A5.50 THRU AP/A5.55 LAV SHALL | | | BE 34" TO TOP OF FIXTURE RIM, NOT 36" AS | | | SHOWN. FHA DESIGN MANUAL PAGE 7.52. | | | 7. SHTS AP/A6.01 THRU AP/A6.04 INDICATE | | | THE BLDG. NUMBERS FOR EACH OF THE | | | BUILDING ELEVATIONS. | | | 8. SUBMIT A DETAIL FOR THE COMMON USE | | | TOILET ROOMS SHOWING COMPLIANCE WITH | | | SECTIONS 11-4.16, 11-4.19, & 11-4.22 AND | | | ALL SUBSECTIONS. | | | 9. SHTS AP/P14.02 UNITS B3 & B4 MAXIMUM | | | 4 FU ON A 2" WET VENT IN MASTER BATH. | | | TABLE 909.3 | | | 10. SHT AP/P14.05 VENTS ARE REQUIRED FOR | | | THE FLOOR DRAINS. SECTION 901.2.1. - | | | CLEANOUTS ARE REQUIRED IN THE SANT. | | | BUILDING DRAIN AT ALL CHANGES OF | | | DIRECTION OVER 45 DEGREES. SECTION | | | 708.3.3. | | | 11. SHT AP/P14.26 OFFSETS IN THE SANT. | | | SHALL BE SHOWN ON EITHER BLDG. DRAIN | | | ISOMETRIC RISER DIAGRAM, OR SANT. RISER | | | DIAGRAMS. SECTION 104.2.1. | | | 12. SHT AP/P14.27 SANT. RISER S/9, | | | PLEASE INDICATE FIXTURE TYPE FOR FIXTURE | | | L-3. THIS IS NOT SHOWN ON PLUMBING | | | FIXTURE SCHEDULE. SECTION 104.2.1. | | | 13. SHT AP/P14.27 WATER HEATER PIPING | | | DETAIL, THERMAL EXPANSION CONTROL IS | | | REQUIRED PER SECTION 607.3.2. PLEASE | | | INDICATE METHOD. - DIELECTRIC UNIONS ARE | | | NOT APPROVED FOR WATER SUPPLY. | | | DIELECTRIC COUPLING TO BE USED. | | | 14. AN RPZV BACKFLOW IS REQUIRED ON THE | | | WATER SERVICE TO THE BUILDING. SECTION | | | 608.13.2. | | | 15. SUBMIT A WATER LAYOUT FOR BUILDING | | | AND WATER RISER DIAGRAMS. SHOW ALL PIPE | | | SIZES, VALVES, WATER HAMMER ARRESTORS, | | | (INSTALLED IN AN "EFFECTIVE RANGE" NOT | | | IN THE CEILING). SECTIONS 104.3.1.1, | | | 606.1, 606.2, 608.13.2 & PDI-WH 201. | | | 16. SUBMIT A BUILDING SANITARY DRAIN | | | ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE | | | SIZES, TRAPS, OFFSETS, RISER LOCATIONS | | | WITH RISER NUMBERS, DFU'S AS THEY | | | ACCUMULATE IN THE SYSTEM ETC. SECTION | | | 104.3.1.1. | | | 17. SUBMIT A BUILDING STORM DRAIN | | | ISOMETRIC RISER DIAGRAM, SHOWING ALL | | | PIPE SIZES, RISER LOCATIONS WITH RISER | | | NUMBERS, AND SQUARE FEET AS IT | | | ACCUMULATES IN THE SYSTEM. SECTION | | | 104.3.1.1. | | | 18. SUBMIT STORM RISER DIAGRAMS SHOWING | | | ALL PIPE SIZES, OFFSETS, AND SQUARE | | | FOOTAGE DRAINED FOR EACH RISER. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
X |
PERMIT EXTENSION |
| Rev No |
1 |
Status |
N |
Date |
2008-11-05 |
|
|
Cont ID |
|
| Sent By |
dfulcher |
Date |
2008-11-05 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
dfulcher |
Date |
2008-11-05 |
Time |
09:24 |
Sent To |
|
|
| Notes |
| 2008-11-05 09:26:01 | EXTEND APP TO 2/3/09 PER RAB |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2006-12-26 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2006-12-22 |
Time |
07:48 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2006-12-22 |
Time |
07:47 |
Sent To |
|
|
| Notes |
| 2006-12-26 07:48:46 | PLANNING AND ZONING**** FAILED **** | | | | | | | | | 1.PROVIDE RESPONSES TO COMMENTS IN WRITING AND | | | INDICATE THE REVISIONS ON SITE PLAN. | | | | | | 2.A MINOR AMENDMENT TO THE COURTNEY LAKES PB 1402 | | | PLANNED DEVELOPMENTIS REQUIRED TO REFLECT NUMBER OF | | | HANDICAP PARKING SPACES REQUIRED.AN APPLICATION WILL | | | NEED TO BE FILED TO THE PLANNING AND ZONING DEPARTMENT | | | AND APPROVED PRIOR TO SIGN-OFF OF BUILDING PERMIT. | | | | | | 3.PURSUANT TO SECTION 94-485(O)PAGE CD 94:273 OF THE | | | CODE, THE AMOUNT OF DISABLED PARKING SPACES PROPOSED | | | DOES NOT COMPLY.THERE ARE TWENTY (20) REQUIRED | | | PARKING SPACES THAT NEED TO BE PROVIDED.IN ADDITION, | | | THE LOCATION OF THE SPACES SHALL BE LOCATED SO THAT | | | USERS ARE NOT COMPELLED TO WALK OR OTHERWISE MOVE | | | BEHIND PARKED VEHICLES.WHY ARE THESE SPACES LOCATED | | | ACROSS DRIVE AISLES INSTEAD OF CLOSE PROXIMITY TO THE | | | BUILDING ACCESS? REVISE ACCORDINGLY. | | | | | | SHOULD YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1435 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-03-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-03-03 |
Time |
18:13 |
Rev Time |
|
| Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2006-03-03 00:00:00 | REVIEW UNDER 05091684 |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |