Plan Review Details - Permit 05091684
Plan Review Stops For Permit 05091684
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2007-09-24 Cont ID  
Sent By lursu Date 2007-09-24 Time 09:51 Rev Time 0.00
Received By lursu Date 2007-09-24 Time 09:51 Sent To  
Notes
2007-09-24 09:52:08NEW SITE ADDRESS HAS BEEN ASSIGNED TO BUILDING 1( CLUB
 HOUSE)AS 344 COURTNEY LAKES CIR , WEST PALM BEACH ,
 FL 33401
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]
  

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2007-02-09 Cont ID  
Sent By lursu Date 2007-02-09 Time 13:22 Rev Time 0.00
Received By lursu Date 2007-02-09 Time 13:22 Sent To  
Notes
2007-02-09 13:32:32BEFORE A SITE ADDRESS CAN BE ISSUED FOR THIS PROJECT
 THE INTERIOR PRIVATE STREETS MUST BE NAMED FIRST.
 PLEASE CONTACT ME FOR MORE INFORMATION .
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-03-01 Cont ID  
Sent By lursu Date 2006-03-01 Time 15:16 Rev Time 0.00
Received By lursu Date 2006-03-01 Time 15:15 Sent To  
Notes
2006-03-01 00:00:00SITE PLAN NEEDED TO ASSIGN NEW
 ADDRESSES;UNITY OF TITLE,PROPESED PLAT.
2005-12-26 00:00:00NEEDS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-10-19 Cont ID  
Sent By jjohnsto Date 2007-10-19 Time 08:27 Rev Time 24.00
Received By jjohnsto Date 2007-10-19 Time 08:26 Sent To  
Notes
2007-10-19 08:30:06CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713FAX:
 561-805-6731
  
 JAMES JOHNSTON, PERMIT NO 05091684
 BUILDING PLAN EXAMINERII PROJECT
 NAME COURTNEY LAKES, BLDG. 1
 E-MAIL:JJOHNSTON @WPB.ORG ADDRESS
 344 COURTNEY LAKES CIRCLE
  DATE OCTOBER 17, 2007
  
 BUILDINGPLANREVIEW
 FLORIDA BUILDING CODE 2001
  
  
 FOR YOUR INFORMATION?.
 THE PLANS SUBMITTED ARE DRAWN FOR THIS PROJECT?S
 BUILDINGS TO BE CONSTRUCTED IN PHASES.PLEASE SEE THE
 2001 CODE RELATED SECTION 104.5.1.104.5.1.1,
 104.5.1.2 -NOTED HEREIN -REFERCENING,?WORK NOT
 COMMENCED WITHIN 6 MONTHS AFTER DATE OF PERMIT ISSUANCE
 THE PERMIT SHALL BE REVOKED AND A NEW PERMIT SHALL BE
 ISSUED.? THE NEW PERMIT SHALL BE ISSUED UNDER THE2004
 BUIDING CODENOT THE 2001, REQUIRING EXISTING PLANS TO
 BE REDRAWN IN COMPLIANCE WITH THIS CODE.
  
 104.5 CONDITIONS OF THE PERMIT
 104.5.1 PERMIT INTENT. A PERMIT ISSUED SHALL BE
 CONSTRUED TO BE A LICENSE TO PROCEED WITH THE WORK AND
 NOT AS AUTHORITY TO VIOLATE, CANCEL, ALTER, OR SET
 ASIDE ANY OF THE PROVISIONS OF THE TECHNICAL CODES, NOR
 SHALL ISSUANCE OF A PERMIT PREVENT THE BUILDING
 OFFICIAL FROM THEREAFTER REQUIRING A CORRECTION OF
 ERRORS IN PLANS, CONSTRUCTION, OR VIOLATIONS OF THIS
 CODE. EVERY PERMIT ISSUED SHALL BECOME INVALID UNLESS
 THE WORK AUTHORIZED BY SUCH PERMIT IS COMMENCED WITHIN
 6 MONTHS AFTER ITS ISSUANCE, OR IF THE WORK AUTHORIZED
 BY SUCH PERMIT IS SUSPENDED OR ABANDONED FOR A PERIOD
 OF 6 MONTHS AFTER THE TIME THE WORK IS COMMENCED.
  
 104.5.1.1 IF WORK HAS COMMENCED AND THE PERMIT IS
 REVOKED, BECOMES NULL AND VOID, OR EXPIRES BECAUSE OF
 LACK OF PROGRESS OR ABANDONMENT, A NEW PERMIT COVERING
 THE PROPOSED CONSTRUCTION SHALL BE OBTAINED BEFORE
 PROCEEDING WITH THE WORK.
  
 104.5.1.2 IF A NEW PERMIT IS NOT OBTAINED WITHIN 180
 DAYS FROM THE DATE THE INITIAL PERMIT BECAME NULL AND
 VOID, THE BUILDING OFFICIAL IS AUTHORIZED TO REQUIRE
 THAT ANY WORK WHICH HAS BEEN COMMENCED OR COMPLETED BE
 REMOVED FROM THE BUILDING SITE. ALTERNATELY, A NEW
 PERMIT MAY BE ISSUED ON APPLICATION, PROVIDING THE WORK
 IN PLACE AND REQUIRED TO COMPLETE THE STRUCTURE MEETS
 ALL APPLICABLE REGULATIONS IN EFFECT AT THE TIME THE
 INITIAL PERMIT BECAME NULL AND VOID AND ANY REGULATIONS
 WHICH MAY HAVE BECOME EFFECTIVE BETWEEN THE DATE OF
 EXPIRATION AND THE DATE OF ISSUANCE OF THE NEW PERMIT.
  
 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL (SEE ALSO SECTION 106.3.5 ).
 COMMENT-SHEETSGN A1.05GN A1.06THESE SHEETS ARE
 NOT LEGIBLE.
  
  
  
 A 1804.2.2 SOIL TEST REPORT
 THE REPORT SUBMITTED IN 2003 REFERENCES A CONCLUSION OF
 BEARING CAPACITY
 FOR A SINGLE STORY STRUCTURE. WHERE THE BEARING
 CAPACITY OF THE SOIL IS
 NOT DEFINITELY KNOWN OR IS IN QUESTION, THE BUILDING
 OFFICIAL MAY REQUIRE
 LOAD TESTS OR OTHER ADEQUATE PROOF AS TO THE
 PERMISSIBLE SAFE BEARING
 CAPACITY AT THAT PARTICULAR LOCATION.TO DETERMINE THE
 SAFE BEARING
 CAPACITY OF SOIL, IT SHALL BE TESTED AT SUCH LOCATIONS
 AND LEVELS AS
 CONDITIONS WARRANT, BY LOADING AN AREA NOT LESS THAN 4
 SQ FT (0.37 M{2})
 TO NOT LESS THAN TWICE THE MAXIMUM BEARING CAPACITY
 DESIRED FOR USE.SUCH
 DOUBLE LOAD SHALL BE SUSTAINED BY THE SOIL FOR A PERIOD
 OF NOT LESS THAN
 48 HOURS WITH NO ADDITIONAL SETTLEMENT TAKING PLACE, IN
 ORDER THAT SUCH
 DESIRED BEARING CAPACITY MAY BE USED.SUBSOIL
 CONDITIONS SHALL BE
 EXAMINED AT THE EXPENSE OF THE OWNER, WHEN DEEMED
 NECESSARY BY THE
 BUILDING OFFICIAL.
 COMMENTPLEASE FURNISH A SOIL TEST REPORT APPLICABLE
 FOR THE THREE BUILDINGS ?FIVE STORIES EACH TO BE
 CONSTRUCTED WITH THE RECOMMENDATIONS FOR PROPER GROUND
 PREPARATION TO ACHIEVE THE DESIRED BEARING CAPACITY
 FOR EACH BUILDING.
 TWO COPIES OF THIS REPORT SHALL BE INCLUDED FOR EACH
 SEPARATE BUILDING PROJECT.THE REPORT IS TO ENCOMPASS
 THE THREE BUILDINGS, TWO COPIES FOR EACH BUILDING
  
 A-1 FBC1816.1SOIL TREATMENT
 COMMENTIDENTIFY THE CHEMICAL SOIL TREATMENT TO BE
 USED IN THE SLAB NOTES SHEET APS3.21
  
  
 B PRODUCT APPROVALS
 COMMENTTHE FLORIDA PRODUCT APPROVAL COVER SHEET
 SHALL INCLUDE THE APPROVAL INFORMATION FOR THE PRODUCT
 SELECTED.SEE ATTACHED SAMPLE INCLUDED.
 THE DESIGNER OF RECORD SHALL REVIEW EACH APPROVAL?S
 SPECIFICATION PACKETAND ACKNOWLEDGE SAME ON THE
 APPROVAL COVER SHEETBY NAME DATE AND STATEMENT OF
 ACCEPTANCE
  
  
 B-1 WINDOWS / DOORS PRODUCT APPROVALS
 WPB ADMINISTRATIVE CODE 106.3 REGULATED BY DCA RULE
 9B-72FLORIDA PRODUCT APPROVAL
 SUBMIT TWO COPIES OF EACH APPROVAL WITH FLORIDA PRODUCT
 APPROVAL COVER SHEET THE ARCHITECT?S / ENGINEER?S
 SIGNATURE AS APPLICABLE, STATING ?TO THE BEST OF THEIR
 KNOWLEDGE THE PRODUCT APPROVAL COMPLIES WITH THE PLANS
 AND SPECIFICATIONS.SEE:WEB SITE
 WWW.FLORIDABUILDING.COM
 NOTE: SEE DIVISION FACTOR TO BE USED IN DESIGN PRESSURE
 BY LEGACYFPA
 COMMENT-FOR YOUR INFORMATION
  
  
 B-2 SUBMIT PRODUCT APPROVALS WITH FLORIDA PRODUCT
 APPROVAL COVER
 PAGE FOR THE FOLLOWING
 OPERABLE WINDOWS
 FIXED GLASS
 MULLION TUBES
 PANEL WALLS
 STORE FRONT GLAZING SYSTEM
 ALUMINUM OUT -SWING DOORS
 HOLLOW METAL DOORS
 TRUSS ANCHORS
 ROOFINGCOMPONENTS
 SHUTTERS
 SKYLIGHTS
 OVERHEAD GARAGE DOOR
 COMMENT-PLEASE COMPLY
  
 B-3 3RD REQUEST ?
 COMMENT-FURNISH THE FOLLOWING PRODUCT REPORTS
 TRACO OPERABLE WINDOWSNON IMPACT 0? TO 30?,LARGE
 MISSILE 30? TO 60?
 TRACO FIXED WINDOWS
 MULLIONS
 EXTERIOR HOLLOW METAL DOORS
 EXTERIOR GLAZED DOORS
 EXTERIOR LOUVER DOORS
 EXTERIOR RAILINGS, ENGINEERING REQUIRED
 LOUVERS,NO REPORT SUBMITTED
 ROOF ASSEMBLIES, DENSE DECK, ATTACHMENTS, INSULATION,
 UNDERLAYMENT,ROOF TILE,ROOF SYSTEM
 IDENTIFY EACH COMPONENT TO BE USED
 RATIONAL ANALYSIS FOR ZONE 2 AND THREE
 EFIS WALL SYSTEM (IF USED)
 5/8? AQUA ROCK SHEATHING
 ROLL UP DOOR
 WOOD BASE STRUCTURAL PANELSFBC 2315.1.11
  
  
 B-4 FBC2405PROVIDE DESIGN LOADS ON ALL WINDOW ,
 DOOR, COMPONENTS ON SCHEDULE
 1. NEGATIVE WIND LOAD - DEAD LOAD
 2. POSITIVE WIND LOAD + DEAD LOAD
 3. DEAD LOAD + 1/2 POSITIVE WIND LOAD
 WIND LOADS SHALL BE DETERMINED FROM 1606. THE DEAD LOAD
 FOR THE GLASS IN LB/SQ FT SHALL BE TAKEN AS THE TOTAL
 THICKNESS OF THE GLASS PANES AND PLIES IN INCHES X 13.
 THIS APPLIES FOR GLASS 30 DEGREES OR LESS FROM
 HORIZONTAL. FOR OTHER SLOPES THE GLASS DEAD LOAD IS
 EQUAL TO THIS VALUE TIMES THE COSINE OF ITS SLOPE FROM
 HORIZONTAL.
  
  
 B-5 FBC2411.3.1.4 THE ARCHITECT OR PROFESSIONAL
 ENGINEER OF RECORD SHALL BE
 REQUIRED TO SPECIFY THE DESIGN WIND PRESSURE,
 DETERMINED IN ACCORDANCE
 WITH CHAPTER 16 (HIGH VELOCITY HURRICANE ZONES), FOR
 ALL GARAGE DOORS,
 SKYLIGHTS OPERATIVE WINDOWS AND FIXED GLAZING.THE
 DESIGN WIND PRESSURE
 FOR EACH COMPONENT OF THE EXTERIOR BUILDING SURFACE,
 SHALL BE
 INCORPORATED INTO THE BUILDING DESIGN DRAWING SO AS TO
 ALLOW THE
 RESPECTIVE MANUFACTURER TO SIZE THE PREFABRICATED
 ASSEMBLY FOR THE
 PROPER WIND PRESSURES.
 COMMENTPLEASE PROVIDE THIS INFORMATION ON THE
 ELEVATIONS
  
  
 C FBC105.13 THRESHOLD BUILDING
 105.13.2 THE SPECIAL INSPECTOR SHALL INSPECT THE
 SHORING AND RE-SHORING
 FOR CONFORMANCE TO THE SHORING AND RE-SHORING PLANS
 SUBMITTED TO THEENFORCING AGENCY.A FEE SIMPLE TITLE
 OWNER OF A BUILDING WHICH DOES NOT MEET THE MINIMUM
 SIZE, HEIGHT, OCCUPANCY, OCCUPANCY CLASSIFICATION OR
 NUMBER-OF-STORIES CRITERIA WHICH WOULD RESULT IN
 CLASSIFICATION AS A THRESHOLD BUILDING UNDER
 ?553.71(7) FLORIDA STATUTES, MAY DESIGNATE SUCH
 BUILDING AS A THRESHOLD BUILDING, SUBJECT TO MORE THAN
 THE MINIMUM
 NUMBER OF INSPECTIONS REQUIRED BY THE FLORIDA BUILDING
 CODE, BUILDING.
 COMMENTPLEASE FURNISH A SHORING AND RE-SHORING PLAN
  
  
  
  
  
  
  
 D SITE PLAN AND ASSOCIATED COMPONENTS REQUIRED3RD
 REQUEST(NOT INCLUDED)
 (A) PARKING SPACES LOCATED OUTSIDE AND UNDERNEATH THE
 BUILDING. CURBING, RAMPS, ACCESSIBLE ISLES FOR THE
 HANDICAP, SIGNAGE, SIDEWALKS, CURB CUTS, PEDESTRIAN
 CROSS WALKS
 (B) HANDICAP SPACES LOCATED OUTSIDE AND UNDERNEATH THE
 BUILDING PERIMETER. IDENTIFY ALL HANDICAP PARKING
 SPACES AS DEFINED BY THEAMERICANS WITH DISABILITIES
 FLORIDA BUILDING CODE CHAPTER 11 PART BANSIA117-1
 ANDFAIR HOUSING ACT GUIDELINES
 (C) IDENTIFY THE ACCESSIBLE ROUTE AS DEFINED BY
 THE AMERICANS WITH DISABILITIES- FLORIDA BUILDING
  CODE CHAPTER 11 AND FAIR HOUSING ACT GUIDELINES
 (D) IDENTIFY VAN ACCESSIBLE PARKING SPACES UNDER
 BUILDING AND EXTERIOR IN COMPLIANCE WITH THE AMERICANS
 WITH DISABILITIES FLORIDA BUILDING CODE CHAPTER 11AND
 FAIR HOUSING ACT GUIDELINES, NOTE PARKING SPACES FOR
 VANS SHALL HAVE VERTICAL CLEARANCE OF 98?
 (E) ONE ACCESSIBLE ROUTE FAIR HOUSING, FROM THE
 BOUNDARY SITES PUBLIC TRANSPORTATION STOP TO AN
  ACCESSIBLE BUILDING ENTRANCE. CHAPTER 11, PART B ?
 ANSI A117.1,502.6
 COMMENTPLEASE FURNISH A SEPARATE SITE PLAN FOR
 BUILDING NO 1. INCLUDE ALL INFORMATION REQUESTED FOR
 COMPLIANCE.
  
 E FBC411.2 AUTOMOBILE PARKING GARAGES
 411.2.1 AUTOMOBILE PARKING GARAGES SHALL BE CLASSIFIED
 AS EITHER OPEN, AS DEFINED IN 411.3, OR ENCLOSED AND
 SHALL MEET THE APPROPRIATE CRITERIA OF 411.3 OR 411.4.
  
  E-1 FBC411.3ENCLOSED PARKING GARAGES
  
  FBC 411.4.1 ENCLOSED AUTOMOBILE PARKING GARAGES AND
 PORTIONS THEREOF WHICH DO NOT MEET THE DEFINITION OF
 OPEN PARKING GARAGES SHALL BE LIMITED TO THE ALLOWABLE
 HEIGHTS AND AREAS SPECIFIED IN TABLE 500 FOR GROUP S
 BUILDINGS.
  411.4.2 A MECHANICAL VENTILATION SYSTEM FOR THE
 REMOVAL OF THE PRODUCTS OF COMBUSTION SHALL BE
  PROVIDED IN ENCLOSED AUTOMOBILE PARKING GARAGES. THE
 MECHANICAL SYSTEM SHALL BE CAPABLE OF PROVIDING AT
 LEAST 6 AIR CHANGES PER HOUR FOR EACH LEVEL. UNDER
 NORMAL USE THE VENTILATION OF THE
  ENCLOSED AUTOMOBILE PARKING GARAGE SHALL COMPLY WITH
 THE VENTILATION REQUIREMENTS OF 411.5.
  411.2.2 THE CLEAR HEIGHT OF EACH FLOOR LEVEL IN
 VEHICLE AND PEDESTRIAN TRAFFIC AREAS SHALL NOT BE LESS
 THAN 7?
  
 E-2 FBC 411.3 OPEN PARKING GARAGES411.3.1
 OPEN AUTOMOBILE PARKING GARAGES WITH ROOF PARKING MAY
 BE CONSTRUCTED TO THE ALLOWABLE HEIGHTS AND AREAS
 SPECIFIED IN TABLE 411.3.1. TO BE CONSIDERED OPEN, THE
 GARAGE SHALL MEET THE REQUIREMENTS OF411.3.2,
 411.3.3 AND411.3.4.
  
 411.3.2 THE EXTERIOR AND INTERIOR WALLS OF THE GARAGE
 SHALL BE DESIGNED IN ACCORDANCE WITH ONE OF THE
 FOLLOWING:
 1. AT LEAST 50 PERCENT OF THE CLEAR HEIGHT BETWEEN
 FLOORS SHALL BE OPEN TO THE ATMOSPHERE FOR THE FULL
 LENGTH OF AT LEAST TWO EXTERIOR WALLS, EXCLUDING
 REQUIRED STAIR AND ELEVATOR WALLS AND STRUCTURAL
  COLUMNS. INTERIOR WALL LINES AND COLUMN LINES SHALL BE
 AT LEAST 20 PERCENT OPEN AND UNIFORMLY DISTRIBUTED, OR
 2. THE EXTERIOR WALLS OF THE STRUCTURE SHALL HAVE
 UNIFORMLY DISTRIBUTED OPENINGS ON TWO OR MORE SIDES
 TOTALING NO LESS THAN 40 PERCENT OF THE BUILDING
 PERIMETER. THE AREA OF SUCH OPENINGS IN THE EXTERIOR
 WALLS ON EACH LEVEL SHALL BE AT LEAST 20 PERCENT OF THE
 TOTAL PERIMETER WALL AREA OF EACH LEVEL. INTERIOR WALL
 LINES AND COLUMN LINES SHALL BE AT LEAST 20 PERCENT
 OPEN AND UNIFORMLY DISTRIBUTED.
 COMMENTPLEASE VERIFY OPEN OR ENCLOSED WITH THE CODE
 SECTIONS PROVIDED HEREIN
  
 F FBC104.3 EXAMINATION OF DOCUMENTS
 104.3.1 PLAN REVIEW. THE BUILDING OFFICIAL SHALL
 EXAMINE OR CAUSE TO BE EXAMINED EACH APPLICATION FOR A
 PERMIT AND THE ACCOMPANYING DOCUMENTS, CONSISTING OF
 DRAWINGS, SPECIFICATIONS, COMPUTATIONS AND ADDITIONAL
 DATA, AND SHALL ASCERTAIN BY SUCH EXAMINATIONS WHETHER
 THE CONSTRUCTION INDICATED AND DESCRIBED IS IN
 ACCORDANCE WITH THE REQUIREMENTS OF THE TECHNICAL CODES
 AND ALL OTHER PERTINENT LAWS OR ORDINANCES.
 COMMENTSHEETAP S3.12PARTIAL 2ND FLOOR PLAN DETAIL
 11-S4.21AT ?SLAB OPEN AREA NO SLAB?
 THIS DETAIL IS FOR THE ELEVATOR AND STAIRWAY, PLEASE
 CLARIFY.
 G FBC106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL (SEE ALSO SECTION 106.3.5 ).
 COMMENT-IDENTIFY EXPANSION JOINT MATERIAL.PROVIDE
 MANUFACTURER SPECIFICATIONS
  
 G-1 COMMENT- DEFINE BUILT UP ROOFING ELEVATIONS FOR
 POSITIVE DRAINAGE ON THE FOLLOWING PLAN SHEETS
 AP-A5.05,AP-A5.10,AP-A5.20
  
 G-2 COMMENT- WALL SECTIONS REFER TO SHEET A1.04.
 PLEASE FURNISH THE I.D. SHEET GN-A1.04
  
 G-3 COMMENT- SOME OF THE WALL SECTIONS ON THE
 ARCHITECTURAL FLOOR PLANS DO NOT MATCH THE INTENDED
 UNIT DETAILS BECAUSE, VARIOUS WALLS ARE END WALLS AND
 OTHERS ARE LOCATED NEAR A STAIRWAY. PLEASE IDENTIFY THE
 WALL SECTIONS ON THE ARCHITECTURAL FLOOR PLANS THAT ARE
 APPLICABLE FOR ITS CONDITION.
  
 G-4 COMMENT- CLUBHOUSE OCCUPANCY IS RATED A. PLEASE
 ADD TO SHEET GN-A1.02
  
 H FLORIDA ACCESSIBILITY CODE CHAPTER 11
  COMMENT-MEN?S BATHROOM WALL PARTITIONS ARE
 ENCROACHING INTO TOILET ROOM SEE ADA FIG 28
 WOMEN?S BATHROOMWALL PARTITIONS ARE ENCROACHING INTO
 TOILET ROOM SEE ADA FIG 28
 DETAIL ALL BATHROOM ACCESSORIES, GRAB BARS, TOILET
 PAPER HOLDER, PAPER TOWEL DISPENSER, MIRROR
 PLEASE NOTE THE BATHROOMS ARE NOT CONSIDERED A STALL
  
 H-1 FLORIDA ACCESSIBLE CODE11-4.10 ELEVATORS
  11-4.10.9 FLOOR PLAN OF ELEVATOR CARS. THE FLOOR AREA
 OF ELEVATOR CARS SHALL PROVIDE SPACE FOR WHEELCHAIR
 USERS TO ENTER THE CAR, MANEUVER WITHIN REACH OF
 CONTROLS, AND EXIT FROM THE CAR. ACCEPTABLE DOOR
 OPENING AND INSIDE DIMENSIONS SHALL BE AS SHOWN IN
 FIGURE 11-22. THE CLEARANCE BETWEEN THE CAR PLATFORM
 SILL AND THE EDGE OF ANY HOIST WAY LANDING SHALL BE NO
 GREATER THAN 1-1/4 INCHES (32 MM).
  COMMENTAP-A8.10 PROVIDE A FLOOR PLAN OF THE
 ELEVATOR CAB UTILIZING THIS SECTION OF THE ADA
  
 H-2 FBC1814.1ELEVATOR PIT
  COMMENTAP-A8.10 WHERE REQUIRED. WHERE A
 GROUNDWATER TABLE INVESTIGATION INDICATES THAT
 HYDROSTATIC PRESSURE CONDITIONS EXIST, WALLS AND FLOORS
 RETAINING EARTH AND ENCLOSING SPACES BELOW FINISHED
 GROUND LEVEL SHALL BE WATERPROOFED IN ACCORDANCE WITH
 ?1814.2. WHERE HYDROSTATIC PRESSURE CONDITIONS DO NOT
 EXIST, DAMP PROOFING AND PERIMETER DRAINAGE SHALL BE
 PROVIDED IN ACCORDANCE WITH 1814.3.
  
 I FBC1003.2
  COMMENT-AP-A8.01SECTION 15? PLEASE DETAIL THE
 STAIRWAYS FOR TREAD DEPTH, CHANGES AT LANDINGS AND
 HEADROOM CLEARANCE FROM TREAD TO BEAM ABOVE.
  
 J FBC1606STRUCTURAL LOADS
  COMMENT-SUBMIT ENGINEERING DESIGN FOR THE BALCONY
 RAILINGS IN COMPLIANCE WITH THIS SECTION.
  
 K FBC1404.1.1ARCHITECTURAL TRIMABOVE 3 STORIES OR
 40 FT
  COMMENT-IDENTIFY THE FASTENING HARDWARE TO BE USED
 IN SECURING THE FOAM TRIM TO THE BUILDING EXTERIOR
 SURFACE
  
 L FBC705PROTECTION OF OPENINGS AP-A8.20
  IDENTIFY THE FIRE RATING FOR THE TRASH CHUTE DOORS
  
  
  
 PREVIOUS PLAN REVIEWER?S COMMENTSDATED5/22/07
  
 12B) 3RD REQUEST:
 PLEASE INCORPORATE THE CIVIL DRAWINGS INTO THIS PLAN
 FOR REVIEW, NOT A NOTE REFERENCING CHAPTER 11.
 THE ACCESSIBLE ROUTE MUST BE DESIGN, REVIEWED AND
 CONSTRUCTED BY THE PLAN.
 SEE THIS PLAN REVIEWER?S COMMENT ITEM ?D?
  
 12B1) PLEASE PROVIDE INFORMATION FOR VAN
 ACCESSIBILITY. SEE THIS PLAN REVIEWER?S COMMENT ITEM
 ?D?
  
 12B2) PLEASE PROVIDE A DETAIL OF THE SIGN WITH THE
 HANDICAP SYMBOLS AND COLORS. PROVIDE A DETAIL OF THE
 POLE HEIGHT FROM THE EXTERIOR GRADE TO THE SIGN AS PER
 FA CHAPTER 11
  
 12C) PLEASE PROVIDE A SITE PLAN WITH PARKING UNDERNEATH
 THE BUILDING, CURB CUTS,PEDESTRIAN CROSS WALKS,
 RAMPS, HANDICAP TEXTURE SURFACES ON THE RAMPS, RAMP
 WIDTH, RAMP PITCH, RAMP CONNECTION TO SIDEWALK.
  
 14E) THIS COMMENT IS REQUESTING A REFERENCE TO A DROP
 CEILING IN THE LEASING OFFICE CLOSET.
  CUT SECTION AP-A7.04 DETAIL IS A STAIR LANDING DETAIL
 ???
  
 22C) ARCHITECTURAL TRIM LOCATED ABOVE 40?.
 SEE THIS PLAN REVIEWER?S COMMENT K. PROVIDE THE TYPE OF
 FASTENERS, SIZE, LENGTH, SPACING OF FASTENERS AND ALL
 RELATED HARDWARE, AS TO GAUGE OF METAL, DESCRIPTION,
  
 23) PRODUCT APPROVALS PLEASE SUBMIT THIS IS THE 3RD
 REQUEST
 SEE THIS PLAN REVIEWER?S COMMENT B
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-02-14 Cont ID  
Sent By jwitmer Date 2007-02-14 Time 09:35 Rev Time 10.00
Received By jwitmer Date 2007-02-06 Time 16:41 Sent To  
Notes
2007-02-14 09:39:42BUILDING PLAN REVIEW
 PERMIT: 05091684 BLDG# 1
 ADD: XXX N CONGRESS
 74-43-43-20-00-000-3010
 CONT: E. A. LANDERS
 TEL: (305)823-3938
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 COURTNEY LAKES APARTMENTS, LLC
  
 ARCH: FORUM ARCHITECTURE & INTERIOR
  
  
 DESIGN
 (407)830-1400
 STRUC: ROBERT PLOWFIELD & ASSOC
 (407)657-6657
  
 2NDREVIEW
 ACTION: DENIED
  
 ***IMPORTANT***
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK OF COURT BEFORE
 A PERMIT CAN BE ISSUED.
 NOTE NOC WILL BE NULL & VOID 90 DAYS AFTER RECORDING AT
 THE CLERK OF THE
 COURTS OFFICE IF WORK HAS NOT STARTED. FL S S
 713.13(2).
  
 2) THIS COMMENT WAS PARTIALLY SATISFIED, FOR THE WHOLE
 OF THE PROJECT (3 BUILDINGS)
 THREE SIGNED & SEALED REPORTS WERE SUBMITTED TO THE
 CITY. THIS WILL SATISFY THE REQUIREMENT
 TO HAVE (1 ) REPORT WITH EACH PERMIT OR BUILDING. THE
 NEED STILL ARISES TO HAVE AT LEAST ONE SIGNED/ SEALED
 ORIGINAL FOR THE CONTRACTOR AS WELL AS THE THRESHOLD
 INSPECTOR.
 AN ADDITIONAL 2 ORIGINAL SOILS REPORTS SIGNED & SEALED
 SHALL BE REQUIRED.
 FL BLD CODE 1804.2.2 QUESTIONABLE SOILS, WHERE THE
 BEARING CAPACITY IS NOT DEFINETLY KNOWN OR IS IN
 QUESTION. WHERE THE BEARING CAPACITY OF THE SOIL IS NOT
 DEFINITLY KNOWN OR IS IN QUESTION THE BUILDING OFFICIAL
 MAY REQUIRE EXPLORATIONS, TEST OR OTHER ADEQUATE PROOF
 AS TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDATIONS SUBMITTED
 TO VERIFY BEARING CAPACITY SHALL BE CERTIFIED BY A
 GEOTECHNICAL REPORT FROM A DESIGN PROFESSIONAL PROPERLY
 LICENSED IN THE STATE OF FLORIDA.
  
 3-4) COMPLIED.
  
 5)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE
 INFORMATION.
  
 6)FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING
 ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANY
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING PURSUANT
 TO A STRUCTURAL INSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST
 BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
 THE THRESHOLD REPORTS SUBMITTED HAVE COPIED
 SIGNATURES.
  
 7) WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY S. 553.79(5) FLORIDA STATUTES
 TO THE MINIMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561) 805-6711 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 8) COMPLIED.
  
 9A) CONTACT LILI URSA FOR ADDRESSING REQUIREMENTS @
 (561)822-1239
  
 9B)PROVIDE A COPY OF THE NEW PLAT, LOT HAS BEEN
 SUBDIVIDED.
  
 9C) ON ALL (3) PERMIT APPLICATIONS CORRECT THE PROPERTY
 CONTROL NUMBER TO
 THE NEW LOT.
  
 9D) PROVIDE A SITE PLAN WITH LOCATION OF THE PROPOSED
 STRUCTURES WITH DIMENSIONS
 FOR TABLE 600 ISSUES.A2.01 HAS NO DIMENSIONS!RESPONSE
 COMMENTS ARE TO SEE CIVIL PLANS ,NO CIVIL PLANS
 PROVIDED IN THIS SET OF PLANS.
  
  
 10A-K) COMPLIED.
  
 11) SHEET A1.05
  
 11A-B) COMPLIED.
  
 12)SITE PLAN A5.01
 NEW COMMENT THAT DEALS WITH THE OVER ALL PARKING SPACES
 AND THE REQUIRED NUMBER OF ACCESSIBLE SPACES. THE PLANS
 INDICATE A TOTAL OF 912 SPACES WHERE AS IT APPEARS TO
 BE 1008 PARKING SPACES IF THIS IS TRUE THE REQUIRED
 NUMBER OF ACCESSIBLE SPACES WOULD BE 21.
 CHAPTER 11 PART B- 4PARKING AND PASSENGER LOADING:
 ACCESSIBLE PARKING ON A ROUTE ACCESSIBLE TO WHEELCHAIRS
 FOR AT LEAST 2% OF THE COVERED DWELLING UNITS:
 ACCESSIBLE VISITOR PARKING SUFFICIENT TO PROVIDE ACCESS
 TO GRADE LEVEL ENTRANCES OF COVERED MULTIFAMILY
 DWELLINGS; AND ACCESSIBLE PARKING AT FACILITIES (E.G.,
 SWIMMING POOLS) THAT SERVE ACCESSIBLE BUILDINGS.
  
 12A) COMPLIED.
  
 12B)2ND REQUEST, THERE ARE NO CIVIL PLANS INCORPORATED
 INTO THIS SET OF PLANS TO REVIEW FOR ACCESSIBILITY.
 ACCESSIBLE ROUTE: FAIR HOUSING AT LEAST ONE ACCESSIBLE
 ROUTE SHALL BE PROVIDED WITHIN THE BOUNDARY OF THE SITE
 FROM PUBLIC TRANSPORTATION STOPS, ACCESSIBLE PARKING
 SPACES, PASSENGER LOADING ZONES IF PROVIDED, AND PUBLIC
 STREETS OR SIDEWALKS, TO AN ACCESSIBLE BUILDING
 ENTRANCE.
 12B)(1) PLEASE PROVIDE INFORMATION WHICH ACCESSIBLE
 PARKING SPACES WILL BE THE VAN A VERTICAL CLEARANCE OF
 98" MINIMUM AT THE SPACE AND ALONG THE VEHICULAR ROUTE
 THERETO.
  
 12B)(2) PLEASE PROVIDE SIGNAGE FOR ALL ACCESSIBLE
 PARKING SPACES . CHAPTER 11 PART B ANSI A117.1502.6.
  
 12C) THE SITE PLAN DOES NOT PROVIDE FOR HANDICAPPED
 PARKING UNDER THE BUILDING
 # 1, ANS1 A117.1, 4.6 PARKING AND PASSENGER LOADING
 ZONES, EQUIVALENT FACILITATION.
  
 12D) SITE PLAN DOES NOT PROVIDE ANYINFORMATION AS TO
 CURB CUTS, PEDESTRIAN CROSS WALKS, ETC.
  
 13) SHEET A5.01;
  
 13A-E) COMPLIED.
  
 13F) 2ND REQUEST, THEFIRE PUMP ROOM NO RATING OF
 WINDOW OR OPENING ?U? NOT IN WINDOW SCHEDULE. DOOR
 1.01IS NOW RATED- OK.
  
 13G-J) COMPLIED.
  
 13K) NEW COMMENT : SHEET A5.05 INDICATES THE ROOF DECK,
 THE PLAN DOESN?T INDENTIFY THE DOORS FROM THE
 STAIRWELLS FOR ROOF ACCESS.
 14)DETAILS ON A5.70:
  
 14A-D) COMPLIED.
  
 14E) 2ND REQUEST, THE LEASING OFFICETHE CUT SECTION
 PROVIDED AP A7.04 DETAIL# 4 DOES INDICATE A DROPPED
 CEILING IN THE CLOSET BUT NO INFORMATION IS PROVIDED AS
 TO THE CEILING AND WALL RATING OF THE CLOSET.1007.1.4.
  
  
 15) SHEET A5.02:
  
 15A-G) COMPLIED.
 15B) UNDERSTOOD THAT THE STAIRS ARE TO BE CONSIDERED
 OPEN STAIRS, BUT THE CORRIDOR WILL STILL REQUIRE A WALL
 RATING, IT CAN NOT BE CONSIDERED AN OPEN BALCONY.
 PLEASE PROVIDE THE RATING FOR THE CORRIDOR. PLANS NOW
 INDICATE THE UNIT ENTRY DOORS BEING FIRE RATED.
  
 15H) SHEET A5.04 TYPICAL 5TH FLOOR ELEVATOR DETAIL
 2/A8.10 :
 NEW COMMENT:SHEET A5.04 INDICATES AN ELEVATOR
 DETAIL 2 /A8.10 , THIS ELEVATOR MACHINE ROOM DOES NOT
 INDICATE WALL OR DOOR RATINGS.
  
 15I) NEW COMMENT: SHEET A5.05 STAIRWELL ACCESS TO ROOF.
 SEE 1008 SUCH STAIRWAY SHALL BE MARKED AT STREET AND
 FLOOR LEVELS WITH A SIGN INDICATING THAT IT CONTINUES
 TO THE ROOF.
  
 15J) NEW COMMENT: SHEET A7.02 WALL SECTION# 3& A7.03
 WALL SECTION# 1, DETAIL#21/ A7.10 INDICATES THE USE
 OF WHAT APPEARS TO BE EFIS WALL SYSTEMS, THERE IS A
 WALL IDENTITY TAG W1-14 , NO SUCH TAG ON SHEET A1.04?
  
 15K) NEW COMMENT: SHEET A7.02 KEY NOTE # 10 NOTES SEE
 STRUCTURAL DRAWINGS FOR ROOF TRUSS ANCHORAGE, NO
 TRUSSES NEAR THE NOTE, WHY IS THE BAT INSULATION ON THE
 FLOOR?
  
 16) SHEET A5.71:
  
 16A-B) COMPLIED.
  
 17) SHEET A5.20. COMPLIED.
  
 18) SHEET A5.10:
  
 18A) 2ND REQUEST, TRASH ROOM DETAIL4 OF A8.20 THE
 DETAIL IS INDICATING THE OPENING FROM THE CHUTE TO THE
 ACCESS ROOM.
 PLANS INDICATE A DETAIL 22 ON SHEET A7.10, SEE KEY NOT
 MARKER 13 & 23, BOTH APPEAR TO BE INCORRECT.
  
 18B) COMPLIED.
  
 18C) 2ND REQUEST THERE IS NO INFORMATION ON THE
 COMBUSTIBILITY OF THE TRASH CHUTE NOR
 ON AUTOMATICALLY CLOSING OPENINGS. 705.2.4.2. LOOKING
 FOR A SPEC INDICATING THE GAUGE OF METAL USED IN THE
 CHUTE, ETC.
  
 18D-E) COMPLIED.
  
 19) SHEET A5.11 IS FOR THE FIRST FLOOR ABOVE THE GARAGE
 FLOOR:
  
 19A-C) COMPLIED.
  
 20) COMPLIED.
  
 21) SHEET A5.22
  
 21A) COMPLIED.
  
 22) VARIOUS SHEETS ON BUILD 1,2 & 3
 INDICATE A DETAIL SECTION# 23 SHEET
 A7.10.
  
 22A) COMPLIED.
  
 22B) COMPLIED.
  
 22C) 2ND REQUEST, THIS SAME SECTION INDICATES USE OF
 FOAM TRIM ON THE EXTERIOR OF THE BUILDING ABOVE 40'.
 1404.1.1 ARCHITECTURAL TRIM ON BUILDINGS OF TYPE I, II
 AND IV CONSTRUCTION NOT MORE THANTHREE STORIES OR 40
 FT (12.2 M) HIGH MAY BE OFTYPE VI CONSTRUCTION, AND
 MAY BE
 OF TYPE VI CONSTRUCTION ON ALL BUILDINGS OF TYPE III, V
 AND VI CONSTRUCTION. TRIM SHALL BE SECURED TO THE WALL
 WITH METAL OR OTHER APPROVED BRACKETS OR FASTENERS.
 WHEN ARCHITECTURAL TRIM IS LOCATED ALONG THE TOP OF
 EXTERIOR WALLS, IT SHALL BE COMPLETELY BACKED BY THE
 EXTERIOR WALL AND SHALL NOT EXTEND OVER THE TOP OF
 EXTERIOR WALLS.
  
 23) PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 24) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 A) OPERABLE WINDOWS
 FL 3485TRACO TR-6800 -OK
 FL 3044.3TRACO HS-HC 65 NON-IMPACT WINDOW
 REQUIRED 0-30'LARGE MISSILE, 30'-60'SMALL MISSILE -
 DENIED
 FL 3044.4TRACO HS-AW 55NON-IMPACT WINDOW
 REQUIRED 0-30'LARGE MISSILE, 30'-60'SMALL MISSILE -
 DENIED
 FL 3044.5TRACO HS-AW55 NON-IMPACT WINDOW
 REQUIRED 0-30'LARGE MISSILE, 30'-60'SMALL MISSILE -
 DENIED
  
 B) FIXED WINDOWS
 FL 3487TRACOTR-3800 - OK
 FL 632KAWNEER EXPIRED NOA NON-IMPACT
 REQUIRED 0-30'LARGE MISSILE, 30'-60'SMALL MISSILE -
 DENIED
  
 C) MULLIONS MAY OR MAY NOT BE INCLUDED IN THE PRODUCT
 APPROVALS
  
 D) EXTERIOR HOLLOW METAL DOORS
 FL3078 AMWELD DENIED LOW PRESSURES SINGLE &
 PAIRS
  
 E) EXTERIOR GLAZED DOORS
 FL 3038TRACO 03-0829.06 SMALL MISSILE ONLY, NO
 PRESSURE TEST - DENIED
 FL 3038.3TRACO 03-0422.04 TR-8910 SMALL
 MISSILE TEST NO PRESSURE TEST - DENIED
 FL 3038.4TRACO 03-0422.04 TR-8910 LARGE
 MISSILE HIGHLIGHT ANCHOR FASTENING SCHEDULE MAY COMPLY
 FL3477TRACO TR-8300SLIDING GLASS DOOR
 NON-IMPACTREQUIRES 0-30' LARGE MISSILE, 30'-60' SMALL
 MISSILE - DENIED
  
 F) EXTERIOR LOUVERED DOORS NO REPORT SUBMITTED
  
 G) EXTERIOR RAILINGS- WILL ONLY NEED ENGINEERING NOT A
 PRODUCT APPROVAL
  
 H) LOUVERS NO REPORT SUBMITTED.
  
 I) TRUSS ANCHORS NO REPORT SUBMITTED.
  
 J) ROOF ASSEMBLIES INCLUDING DENSE DECK, INSULATION,
 UNDERLAYMENT, ROOF TILE AND ATTACHMENT METHODS. FL 1559
 SINGLE PLY ROOF SYSTEMS- HIGHLIGHT WHICH SUB-SYSTEM TO
 BE USED.
 NOTE ZONES 2 & 3 MAY REQUIRE ENHANCED FASTENING
 PROVIDE RATIONAL ANALYSIS BY QUALIFIED PROFESSIONAL
  
 K) EFIS WALL SYSTEMS IF USED
  
 L)5/8" FIBER TOUGH AQUA ROCK SHEATHING
  
 M ) PRE-MANUFACTURED ROOF A/C STANDS- OK
  
 N) ROLL UP DOOR - NO REPORT SUBMITTED
  
 O) DENSE DECK- MAY BE INCORPORATED IN A PRODUCT
 APPROVAL
  
 P) ROOF TILE - NO REPORT SUBMITTED- CIRCLE OR HIGHLIGHT
 WHAT ANCHOR METHOD TO INSTALLROOF TILE
  
 25- 27) COMPLIED, IMPACT GLASS IS SPECIFIED.
  
 28) COMPLIED, IMPACT GLASS IS SPECIFIED.
  
 29- 31) COMPLIED.
  
 32- 35) COMPLIED.
  
 NOTE: CALCULATED VALUE OF THIS TYPE II BUILDING IS
 $39,353,983.00
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
 COURTNEY LAKES BLDG 1 ? 2NDREV.DOC

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-01 Cont ID  
Sent By jwitmer Date 2006-02-01 Time 07:38 Rev Time 22.00
Received By jwitmer Date 2006-02-01 Time 07:38 Sent To  
Notes
2006-01-31 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05091684
 ADD:XXX N CONGRESS
 74-43-43-20-00-000-3010
 CONT: E. A. LANDERS
 TEL: (305)823-3938
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 COURTNEY LAKES APARTMENTS, LLC
  
 ARCH: FORUM ARCHITECTURE & INTERIOR
  
 DESIGN
 (407)830-1400
 STRUC: ROBERT PLOWFIELD & ASSOC
 (407)657-6657
  
 1ST REVIEW
 ACTION: DENIED
  
 ***IMPORTANT***
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 NOTE NOC WILL BE NULL & VOID 90 DAYS
 AFTER RECORDING AT THE CLERK OF THE
 COURTS OFFICE IF WORK HAS NOT STARTED.
 FL S S 713.13(2).
  
 2) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) FL BLD CODE CHAP 13 ENERGY EFFICENCY
 PROVIDE ENERGY CALS/ W MANUAL "J"
  
 4) ARCHITECTURAL PAGES DO NOT HAVE A
 RAISED SEAL.
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 5)BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 SRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL INSPEC
 TION PLAN PREPARED BY THE ENGINEER OF
 RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGEN-
 CY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESH-
 OLD BUILDING. THE PURPOSE OF THE SRUCTUR
 AL INSPECTION PLAN IS TO PROVIDE SPECIF-
 IC INSPECTION PROCEDURES AND SCHEDULES
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 7) WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 8) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO
 BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CON- TAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 9A) CONTACT LILI URSA FOR ADDRESSING
 REQUIREMENTS @ (561)822-1239
  
 9B)PROVIDE A COPY OF THE NEW PLAT, LOT
 HAS BEEN SUBDIVIDED.
  
 9C) ON ALL (3) PERMIT APPLICATIONS
 CORRECT THE PROPERTY CONTROL NUMBER TO
 THE NEW LOT.
  
 9D) PROVIDE A SITE PLAN WITH LOCATION OF
  
 THE PROPOSED STRUCTURES WITH DIMENSIONS
 FOR TABLE 600 ISSUES.A2.01 HAS NO
 DIMENSIONS!
  
 10A) CORRECT PERMIT APPLICATIONS AS TO
 DESRIPTION OF WORK FOR THE THREE
 BUILDINGS, CURRENTLY THERE WILL BE 1350
 UNITS ON THIS PROJECT WHEN FINISHED, SEE DESCRIPTION OF
 PROJECT, EACH APPLICATION
 FOR BUILDINGS 1, 450 UNITS BUILDING 2
 450 UNITS & BUILDING 3, 450 UNITS
 TOTALING 1350. .
  
 10B) PLEASE PULL PLANS APART INTO 3 SETS
 OF PLANS SO ALL PAGES THAT DEAL WITH
 BUILDING # 1 ARE IN ONE SET ETC.
  
 10C) ADDITIONAL INFORMATION REQUIRED FOR
 RECORD KEEPING PURPOSES 106.1.2*:
 10C)A) FLOOD ZONE
 10C)B) FLOOD ELEVATION (IF A ZONE)
 10C)C) LOMAR (IF A ZONE)
 10C)D) NUMBER OF UNITS
 10C)E) NUMBER OF FLOORS
 10C)F) NUMBER OF BEDROOMS
 10C)G) NUMBER OF ROOMS
 10C)H) NUMBER OF BATHROOM
 10C)I) SQ FT LIVING SPACE(TOTAL)
 10C)J) SQ FT FOOT PRINT
 10C)K) SQ FT UNDER ROOF (TOTAL)
  
 10D) THE DESCRIPTION OF BUILDINGS AND
 PHASING ARE CONFUSING BECAUSE THE
 TERMINOLOGY, CURRENTLY THE CONTRACTOR
 HAS PERMIT APPLICATIONS IN FOR BUILDINGS
 1,2& 3 NOT 4 NOR 5 AS BUILDINGS ARE
 DEPICTED ON SHEET A1.02.
  
 10E) A1.04 INDICATES A PHASED PROJECT OF
 5 BUILDINGS SEPERATED BY 4 HR WALLS.
 THEN THERE IS ANOTHER NOTE INDICATING
 TEMPORARY I HR WALLS WITH 45 MIN RATED
 DOORS. THIS PLAN IS NOT CLEAR AS WHAT
 WORK WILL BE COMPLETED WHEN. A MEETING
 WITH ALL CONCERNED WOULD BE GREATLY
 APPRECIATED. CONCERNS ON HOW EGRESS WAYS
 ARE TO BE ADDRESSED. HOW ACTIVE FIRE
 ALARM, FIRE SPRINKLER WILL BE MAITAINED
 WITH THE NEW PHASES BEING BUILT. WORK
 AREA BEING ISSOLATED FROM THE GENERAL
 PUBLIC.A ACCESSIBLE PATH TO THE RIGHT OF
 WAY DURING CONSTRUCTION OF ALL PHASES.
  
 10F) THE PHASING PLAN INDICATED ON SHEET
 A1.04 INDICATES WORK ON BUILDING# 1 THEN
 JUMPING TO TWO OTHER BUILDINGS THEN BACK
 TO BUILDING# 1 JUMPING OVER AREAS TO BE
 PHASED IN LATER VERY IMPARTICAL AS TO
 HOW LIVE SYSTEMS ELECTRIC WATER AND FIRE SPRINKLERS ARE
 TO BE BUILT AND
 MAINTAINED.
  
 10G) THIS REVIEW WILL CONSTITUTE OF
 BUILDING# 1 OF 515,540 SQ FT. PLANS
 REFER TO THIS AS BEING BLDG 1,2 & 3.
  
 10H) A1.02 CODE COMPLIANCE FOR APARTMENT BUILDINGS
 PLANS INDICATE TYPE IV, UNPROTECTED ,
 SPRINKLERED
 MAXIMUMHEIGHT ALLOWED IS 55'
 PROPOSED HEIGHT69'-3"
 PLEASE CORRECT BUILDING TYPE!!!!!!
 503.2.2 ALLOWED THE DEDUCTION OF 1 STORY
 FOR THE PARKING GARAGE IF TYPE I OR TYPE
 II BUILDING.
  
 10I) THE OTHER ISSUE IS THE ALLOWABLE
 AREA FOR A TYPE IV , UNPROTECTED,
 SPREINKLERED BUILDING THE ALLOWABLE
 AREAIS ONLY 24,000 SQ FT / FL.
  
 10J) EVEN IF THE BUILDING WAS CONSIDERED
 A TYPE IV , 1 HR PROTECTED, SPRINKLERED
 BUILDING THE ALLOWABLE AREA INCREASE
 WILL BE 36,000/ FL BUT THE HEIGHT OF 65'
 STILL 4'-3" OF THE OVERALL HEIGH OF THE
 BUILDING, STILL REQUIRING THE 4 FOUR HR
 FIRE WALLS TO MAKE UP THE TOTAL AREA FOR
 THIS ONE BUILDING. THE OTHER ISSUE IS
 THE 4 HR FIRE WALLS DO NOT CONTINUE
 THROUGH THE GARAGE SEPERATING THEM INTO
 SEPERATE BUILDINGS. A 3HR FIRE RATED
 DOOR WOULD BE REQUIRED IN THE GARAGE
 LEVEL. PLEASE CORRECT.
  
 10K) DISCREPANCY A1.02 CONSTRUCTION TYPE
 IV UNPROTECTED VS A1.21 FIRE RATING
 IV I HR RATED.
  
 11) SHEET A1.05
  
 11A) PLEASE PROVIDE THE LISTING FOR
 RATED WALLS, U.L. OR OTHER
 RECOGNIZED LISTING AGENCY.
  
 11B) PLANS INDICATE USE OF RINKER BLOCK,
 PROVIDE FROM THE MANUCATURER THE
 EQIVALENT THICKNESS OF BLOCK,709.3.1.1
 THE FIRE RESISTANCE RATING OF WALLS AND
 PARTITIONS CONSTRUCTED OF CONCRETE
 MASONRY UNITS SHALL BE DETERMINED FROM
 TABLE 709.3.1.THE RATING SHALL BE
 BASED ON THE EQUIVALENT THICKNESS OF THE
 MASONRY AND TYPE OF AGGREGATE USED.
  
 12)SITE PLAN A2.01
  
 12A) INDICATES HANDICAPPED SPACES BLDG#
 1 HAS NO HANDICAPPED PARKING SPACES
 WITHIN THE PARKINGGARAGE?
  
 12B) ACCESSIBLE ROUTE: FAIR HOUSING AT
 LEAST ONE ACCESSIBLE ROUTE SHALL BE
 PROVIDED WITHIN THE BOUNDARY OF THE SITE
 FROM PUBLIC TRANSPORTATION STOPS,
 ACCESSIBLE PARKING SPACES, PASSENGER
 LOADING ZONES IF PROVIDED, AND PUBLIC
 STREETS OR SIDEWALKS, TO AN ACCESSIBLE
 BUILDING ENTRANCE.
  
 12C) THE SITE PLAN DOES NOT PROVIDE FOR HANDICAPPED
 PARKING UNDER THE BUILDING
 # 1, ANS1 A117.1, 4.6 PARKING AND
 PASSENGER LOADING ZONES, EQUIVALENT
 FACILITATION.
  
 12D) SITE PLAN DOES NOT PROVIDE ANY
 INFORMATION AS TO CURB CUTS, PEDSTRIAN
 CROSS WALKS, ETC.
  
 13) SHEET A5.01;
  
 13A) STAIRWELL# 1 DOOR# 1.005 DOOR
 SWINGS THE WRONG WAY AGAINST EGRESS.
 NO HR RATING!
  
 13B) STAIRWELL# 1 EXIT DOOR NO LISTING,
 NO RATING!
  
 13C) STAIRWWELL 2,3&4 ALL LEAD BACK INTO
 THE GARAGE NOT THE EXIT DISCHARGE.
 NO DOOR IDENTIFYCATION! NO RATING!
  
 13D) GARARE LEVEL THE ELEVATOR LOBBY
 DOOR NO IDENTIFACTION, NO RATING.
  
 13E) TRASH REFUSE ROOM 1&2 NO DOOR
 IDENTICATION, NO RATING
  
 13F) FIRE PUMP ROOM NO RATING OF DOOR
  
 13G) PARKING GARAGE TO BE CONSIDERED AN
 ENCLOSED PARKING GARAGE PROVIDE
 COMPLIANCE WITH 6 AIRCHANGES PER
 HR.411.4.2.
  
 13H) MAILBOXES SEE DETAIL A5.56 DETAIL
 # 7, PROVIDE DIMENSIONS (ELE) TO COMPLY
 WITH SIDE REACH RANGES.
  
 13I) PLANS ARE NOT CLEAR IF STAIRWELL
 2 & 4 ARE IN THIS FIRST PHASE OR SECOND
 PHASE. IF LOCATED IN 2ND PHASE DEAD END
 CORRIDORS EXIST.
  
 13J) GARAGE 4 HR FIRE WALL, PROVIDE 3 HR
 FIRE RATED DOOR BETWEEN BUILDINGS,
 INDICATE HOW DOOR WILL ACTIVATE WITH THE
 SMOKE/ FIRE ALARM?
 705.1.3.1 WALL OPENINGS REQUIRED TO BE
 PROTECTED SHALL BE PROTECTED BY APPROVED
 LISTED AND LABELED FIRE DOORS, WINDOWS
 AND SHUTTERS AND THEIR ACCOMPANYING
 HARDWARE, INCLUDING ALL FRAMES, CLOSING
 DEVICES, ANCHORAGE AND SILLS, IN
 ACCORDANCE WITH THE REQUIREMENTS OF NFPA
 80, EXCEPT AS OTHERWISE SPECIFIED IN
 THIS CODE.
  
 14)DETAILS ON A5.70:
  
 14A) DETAILS ON A5.70 AGAIN NO DOOR
 RATINGS.
  
 14B) DOUBLE DOORS: DOUBLE LEAF DOORS,
 ANSI A117.1, 404.2 SHALL COMPLY WITH 32"
 CLEAR, AT LEAST ONE OF THE ACTIVE LEAVES
 OF DOORWAYS WITH 2 INDEPENDENTLY
 OPERATED LEAVES SHALL COMPLY WITH
 SECTION 404.2.3 & 404.2.4.
 404.2.3 32" CLEAR
 404.2.4 MANEUVERING CLEARENCES.
 SEE CH108 & CH115.
  
 14C) PROVIDE ADD INFO TYPE OF ROOM
 EXAMPLE AT DOOR CH-117 OR CH-121? THESE
 DOORS ARE ONLY A 2'-6" DOOR?ANSI A117.1
 404.2.3 OPENINGS MORE THAN 24" DEEP
 SHALL PROVIDE A 36" MINIMUM.
  
 14D) AGAIN THERE ARE VARIOUS CLOSETS
 WITH ONLY 2'-6" DOORS?
  
 14E) LEASING OFFICE PROVIDE A CUT
 SECTION THROUGH THE STAIR, ALSO INCLUDE
 RATED CEILING OF CLOSET, ALSO A 2'-6"
 DOOR.
  
 15) SHEET A5.02:
  
 15A) STAIR # 3 DETAIL A8.01 DETAIL 2 IS
 MISSING PROVIDE WIDTH A1.21 INDICATES A
 54" WIDE STAIR, WHERE IS DETAIL?
 THE SAME SITUATION COMMENT 17A) IS
 MISSING DETAIL, BUT SECOND PHASE A8.10
 DETAIL# 2 INDICATES THE USE OF A
 UNPROTECTED OPENING IN THE STAIRWELL SEE 1006.1.3.2 AND
 705.2.3 FOR OPENING
 PROTECTIVES REQUIRED FOR RATED WALLS,
 SEE COMMENTARY FOR 1006.1.3.2.SEE
 ATTACHMENT.
  
 15B) STAIRWELL 1,2,3&4 ARE MISSING THE
 FIRE RATED WALL & DOOR CREATING THE
 SHAFT ENCLOSURE REQUIRED IN TABLE
 705.1.2.
  
 15C) STAIRWELL 2 & 4 APPEAR NOT TO BE IN
 THIS PHASE, THEY WILL BE REQUIRED TO BE
 IN THIS PHASE OR OTHERWISE DEAD END
 CORRIDOR SITUATION WILL OCCUR.TO MAKE
 THE STAIR TOWER WORK TO THE DEFINITION
 OF FIRE WALL, THE STAIR TOWER WILL HAVE
 TO BE BUILTWITH A 4HR WALL, ROOF
 STRUCTURE INDEPENDENT OF THE OTHER
 BUILDINGS AND DIRECT ACCESS FROM EACH OF
 THE BUILDINGS EXIT ACCESS CORRIDORS,PLUS
 THE REQUIRED 3 HR OPENING PROTECTIVES.
 YOUR BUILDINGS DESIGN WAS BROUGHT TO THE
 BUILDING OFFICIAL FOR HIS INTERPRETATION
  
  
 DEF:WALL, PARTY. A FIRE WALL ON AN
 INTERIOR LOT LINE, USED OR ADAPTED FOR
 JOINT SERVICE BETWEEN TWO BUILDINGS.
  
 SELF-CLOSING. AS APPLIED TO A FIRE DOOR
 OR OTHER OPENING, MEANS NORMALLY CLOSED
 AND EQUIPPED WITH AN APPROVED DEVICE
 WHICH WILL INSURE CLOSING AFTER HAVING
 BEEN OPENED FOR USE.
  
 705.1.3.1 WALL OPENINGS REQUIRED TO BE
 PROTECTED SHALL BE PROTECTED BY APPROVED
 LISTED AND LABELED FIRE DOORS, WINDOWS
 AND SHUTTERS AND THEIR ACCOMPANYING
 HARDWARE, INCLUDING ALL FRAMES, CLOSING
 DEVICES, ANCHORAGE AND SILLS, IN
 ACCORDANCE WITH THE REQUIREMENTS OF NFPA
 80, EXCEPT AS OTHERWISE SPECIFIED IN
 THIS CODE.
  
 705.1.5 OPENING PROTECTION IN STAIRWAY
 ENCLOSURES. OPENING PROTECTIVESIN
 STAIRWAY SHAFTS ARE LIMITED TO
 SELF-CLOSING OR SMOKE ACTUATED,
 AUTOMATIC-CLOSING FIRE DOOR
 ASSEMBLIES.IF SMOKE-ACTUATED CLOSURES
 CLOSE ONE DOOR, ALL DOORS SERVING THAT
 STAIRWAY SHALL CLOSE.
  
 THE OTHER ISSUE IS A UNITY OF TITLE
 WOULD BE REQUIRED EVEN FOR A SINGLE LOT
 AS TO NOT BE ABLE TO SELL OFF A PORTION
 OR BUILDING CREATING A CODE VIOLATION.
  
 15D)THE MENTIONED STAIRWELLS ARE ALSO
 MISSING THE FIRE RATED WALLS AND DOORS.
 TABLE 705.1.2
  
 15E) THE FIRE WALL NEXT TO STAIRWELL
 2 & 4, PHASE H OR BLDG 2 DOES HAVE THE
 FIRE RATED DOORS LABELED BUT ONLY AS
 1 HR. AGAIN SEE TABLE 705.2.1, 4HR FIRE
 WALL /3HR OPENING PROTECTIVES.
 THIS DOOR WILL ALSO NEED TO BE SELF
 CLOSING AND SELF LATCHING NO INFORMATION
 PROVIDE FOR HARDWARE. THIS DOOR AS WELL
 AS OTHER FIRE RATED DOORS WILL REQUIRE
 DOOR SILLS SEE 705.1.3.1 AND NFPA 80.
  
 15F) ENTRY DOORS TO THE INDIVIDUAL UNITS
 ALSO WILL REQUIRE IDENTICATION AND FIRE
 RATING.
  
 15G) ROOM NOT IDENTIFIED DOOR# 1.102?
  
 16) SHEET A5.71:
  
 16A) DOUBLE LEAF DOORS CH203 & 208
 SEECOMMENT 14B.
  
 16B) VARIOUS ROOMS NOT MARKED EXAMPLE
 DOOR CH-211, ALSO A DOORS 2'-6"?
  
 17) SHEET A5.03 HAS THE SAME ISSUES AS
 SHEET A5.02.
  
 17A) STAIR TOWER# 3, SAME COMMENT AS 15A
 A NEW PAGE AND SECTION PROVIDED A8.07
 DETAIL# 2 MISSING. PLEASE PROVIDE.
 REQUIRES OPENING PROTECTIVES.
  
 18) SHEET A5.10:
  
 18A) TRASH ROOM DETAIL 1&2 OF A8.20 THE
 DETAIL IS MISSING THE ENCLOSURE TO THE
 BOTTOM OF THE CHUTE ENCLOSURE.705.2.4.2
 ALL OPENINGS INTO THE SHAFT ENCLOSURE,
 INCLUDING THOSE FROM ACCESS ROOMS AND
 TERMINATION ROOMS, SHALL BE PROTECTED IN ACCORDANCE
 WITH TABLE 705.1.2.SUCH
 OPENING PROTECTIVES SHALL BE
 SELF-CLOSING OR AUTOMATIC-CLOSING UPON
 DETECTION OF SMOKE, EXCEPT THAT THE
 OPENING PROTECTIVE BETWEEN THE SHAFT AND
 THE TERMINATION ROOM MAY BE CLOSED BY A HEAT-ACTIVATED
 DEVICE.
  
 18B) THE TERMINATION ROOM DOOR NO
 INFORMATION ON RATING?
  
 18C) THERE IS NO INFORMATION ON THE
 COMBUSTIBLITY OF THE TRASH CHUTE NOR
 ON AUTOMAICALLY CLOSING OPENINGS
 705.2.4.2.
  
 18D) REFRENCES DETAIL# 22 SHEET A7.10
 PROVIDE THE UL APPROVAL NUMBER WHERE THE
  
 2X 6 PT BLOCKING IS PART OF A 2 HR RATED
 WALL WHEN USED IN THIS APPLICATION, NOT
 COVERED BY ANY DRYWALL?TABLE 705.1.2.
 2 HR RATING.
  
 18E)705.2.4.6 AUTOMATIC SPRINKLERS. AN
 APPROVED AUTOMATIC SPRINKLER SYSTEM
 SHALL BE INSTALLED AT THE TOP AND AT
 ALTERNATE FLOOR LEVELS IN REFUSE AND
 LAUNDRY CHUTES AND IN THE TERMINATION
 AND INCINERATOR ROOMS.
  
 19) SHEET A5.11 IS FOR THE FIRST FLOOR
 ABOVE THE GARAGE FLOOR:
  
 19A)THIS SHEET DOES NOT INDICATE THAT IS
 COMMON FOR FLOORS 2-5.
  
 19B) THE STAIR TOWERS ARE NOT LABELED.
  
 19C) STAIR DETAIL A8.10 DETAIL# 2
 INDICATES OPENINGS IN STAIR TOWER SEE
 COMMENT 15A FOR REQUIRED OPENING
 PROTECTIVES FOR RATED WALLS.
  
 20)SHEET A5.20 & A5.21.
 BUILDING# 3 OR PHASES I,J AND K WILL
 HAVE THE SAME PROBLEMS MENTIONED IN
 BUILDING# 1&2 AS FAR AS PHASING, EGRESS, FIREWALLS,
 FIREDOORS, STAIR TOWERS,
 DOORS NOT LABELED NOR FIRE RATINGS AND
 REFUSE CHUTES.
  
 21) SHEET A5.22
 21A) THIS SHEET COMMON FOR FLOORS 2-5,
 LOOKS LIKE THE WRONG LAYER WAS TURNED ON
 AND NOT COMPLETED.SEE DETAIL 3 SHEET
 A7.03 INDICATES UNITS PLEASE CORRECT.
 WITH NO DETAILS FURTHER COMMENTS MAY
 APEAR ON FUTURE REVIEWS.
  
 22) VARIOUS SHEETS ON BUILD 1,2 & 3
 INDICATE A DETAIL SECTION# 23 SHEET
 A7.10.
  
 22A) THIS SECTION INDICATES METAL
 TRUSSES TO BE USED BUT NO INFORMATION
 AS TO THE ROOF DECKING MATERIAL TO BE
 USED? TYPE IV UNPROTECTED- NC
 TYPE IV 1HR- IHR PROTECTED
  
 22B) PROVIDE A DETAIL INDICATING ACCESS
 TO ATTIC AREA.
  
 22C) THIS SAME SECTION INDICATES USE OF
 FOAM TRIM ON THE EXTERIOR OF THE
 BUILDING ABOVE 40'.1404.1.1
 ARCHITECTURAL TRIM ON BUILDINGS OF TYPE
 I, II AND IV CONSTRUCTION NOT MORE THAN
 THREE STORIES OR 40 FT (12.2 M) HIGH MAY
 BE OFTYPE VI CONSTRUCTION, AND MAY BE
 OF TYPE VI CONSTRUCTION ON ALL BUILDINGS
 OF TYPE III, V AND VI CONSTRUCTION.
 TRIM SHALL BE SECURED TO THE WALL WITH
 METAL OR OTHER APPROVED BRACKETS OR
 FASTENERS.WHEN ARCHITECTURAL TRIM IS
 LOCATED ALONG THE TOP OF EXTERIOR WALLS,
 IT SHALL BE COMPLETELY BACKED BY THE
 EXTERIOR WALL AND SHALL NOT EXTEND OVER
 THE TOP OF EXTERIOR WALLS.
  
 23) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 24) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) OPARATABLE WINDOWS
 B) FIXED WINDOWS
 C) MULLION
 D) EXTERIOR DOORS SOLID
 E) EXTERIOR DOORS GLAZED
 F) EXTERIOR DOORS LOUVERED
 G) STORM SHUTTERS
 H) EXTERIOR RAILINGS
 I) LOUVERS
 J) TRUSS ANCHORS
 K) ROOFING ASSEMBLIES
 L) EFIS SYSTEMS
  
 25) AN INTERPRETATION FROM THE BUILDING
 OFFICIAL ON STORM SHUTTERS THAT ARE USED
 ON LARGE PROJECTS:
 QUESTION# 13) RECOGNIZING SUCH CONCERNS
 AS ABSENTEE OWNERS, OR CASES WHERE
 LONGER TIME AND EFFORT IS NECESSARY TO
 SECURE SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING
 RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING
 IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE EVENT?
  
 IN MATTERS FLORIDA BUILDING CODE, 2004
 EDITION, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT
 REQUIREMENTS FOR ENSURING STABILITY,
 STRENGTH, AND PROPER OPERATION OF
 EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF
 SHUTTERS ON LARGE OR MULTI-STORY
 BUILDING, OR MULTIPLE BUILDINGS ON THE
 SAME PROPERTY, PRE-STORM PREPARATION
 PLANS MUST BE SUBMITTED BY THE PROPERTY
 OWNERS OR MANAGING AGENTS FOR REVIEW BY
 THE CONSTRUCTION SERVICES DEPARTMENT.
 ANY SUCH PLAN SHALL INCLUDE, AT A
 MINIMUM, ON-SITE LOCATION OF SHUTTERS,
 PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS (SAID PARTIES MUST BE LOCATED
 WITHIN PALM BEACH COUNTY), TOTAL NUMBER
 OF OPENINGS TO BE PROTECTED AND TOTAL
 TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE
 ACCOMPLISHED WITHIN TWELVE (12) HOURS OR
 LESS OF THE OFFICIAL NOTIFICATION BY THE
 NATIONAL WEATHER SERVICE OF A HURRICANE
 WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND
 THIS STANDARD) ARE NOT INTENDED TO
 PROHIBIT THE USE OF ALTERNATIVE
 MATERIALS AND METHODS, AND ALLOW THE
 BUILDING OFFICIAL TO REVIEW AND APPROVE
 ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE
 RESISTANCE, DURABILITY AND SAFETY
 PRESCRIBED BY CODE. BASED UPON THIS CODE PROVISION,
 ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON
 A CASE-BY-CASE BASIS AND SHALL REQUIRE
 SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING
 THE ALTERNATE.
  
 QUESTION# 14) ARE REMOVABLE STORM PANELS APPROPRIATE
 FOR USE ON VERY LARGE, MID
 OR HIGH-RISE STRUCTURES?
  
 NO, EXCEPT ON THE GROUND FLOOR. ON
 COMMERCIAL AND MULTI-UNIT RESIDENTIAL
 STRUCTURES, ABOVE THE FIRST LEVEL,
 IMPACT RESISTANT GLAZING OR PERMANENTLY
 AFFIXED PROTECTIVE DEVICES SHALL BE
 INSTALLED. PERMANENTLY AFFIXED
 PROTECTIVE DEVICES SHALL REQUIRE THE
 WRITTEN APPROVAL OF THE BUILDING
 OFFICIAL.
  
 26) PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 27) FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 28) 3003.6.1 VENTS. HOISTWAYS OF ELEVA-
 TORS SERVING MORE THAN 3 FLOORS SHALL BE
 PROVIDED WITH MEANS OF VENTING SMOKE AND
 HOT GASES TO THE OUTER AIR IN CASE OF
 FIRE.
  
 29)3003.6.2 VENTS SHALL BE LOCATED BELOW
 THE FLOOR OR FLOORS AT THE TOP OF THE
 HOISTWAY, AND SHALL BE EITHER DIR- ECTLY
 TO THE OUTER AIR OR THROUGH NON-
 COMBUSTIBLE DUCTS TO THE OUTER AIR.
  
 30) 3003.6.3 THE AREA OF THE VENTS SHALL
 BE NOT LESS THAN 3 SQ FT FOR EACH
 ELEVATOR CAR, WHICHEVER IS GREATER.
  
 31)SHEET S4.00 INDICATES THE ROOF ZONES
 FOR A SIMPLE RECTANGLE. PROVIDE A
 DETAILED ZONE MAP AS IT RELATES TO THIS
 BUILDING INCLUDING PENTHOUSES WITH THE
 APPROPRIATE PRESSURES.
  
 32) A9.03 WINDOW BUCK DETAIL CORRECT:
 1707.4.4.2 TAPERED BUCKS:
 SHALL EXTEND BEYOND THE INTERIOR FACE
 OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS SUPPORTED.
  
 33) S3.51-S3.54
 1511.7 ROOF MOUNTED MECHANICAL UNITS
 SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
  
 34) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 35) ELECTRICAL SHEETS MISSING SMOKE
 ALARMS IN BEDROOMS.905.1.1A FIRE ALARM
 SYSTEM IN ACCORDANCE WITH NFPA 72SHALL
 BE INSTALLED.
  
  
 A COMPLETE REVIEW CAN NOT BE COMPLETED
 AT THIS TIME. DEPENDING ON THE RESPONCES
 FROM THIS REVIEW ADDITIONAL COMMENTS MAY
 APPEAR ON THE NEXT REVIEW.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-09-21 Cont ID  
Sent By dpalmer Date 2007-09-21 Time 12:51 Rev Time 0.00
Received By dpalmer Date 2007-09-16 Time 13:07 Sent To  
Notes
2007-09-21 12:51:222007-09-21 12:51:22
  
 ** DENIED 3RD REVIEW**
  
 BUILDING #1
  
 ** PLEASE SEE THERE ARE SOME ITEMS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE ALSO SEE
 THERE ARE SEVERAL NEW COMMENTS BASED ON REVISED
 PLANS/PLANS AND DOCUMENTS NOW SUBMITTED. PLEASE SEE
 THERE ARE SEVERAL COMMENTS FROM THE TWO PREVIOUS
 REVIEWS WHICH STILL REMAIN. PLEASE SEE FINAL COMMENT
 WITH RESPECT TO FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE.
  
 ***THE PREVIOUS REVIEW MENTIONED THERE MAY BE NEW
 COMMENTS AS THERE WAS A SUBSTANTIAL AMOUNT OF MISSING
 INFORMATION ON PLANS AND DOCUMENTS ETC.
 THE REVIEWS CAN ONLY BE DONE ON THE PLANS AND DOCUMENTS
 SUBMITTED. WHEN INFORMATION ON PLANS IS NOT COMPLETE OR
 MISSING A COMPLETE REVIEW FOR CODE COMPLIANCE IS NOT
 POSSIBLE. THEREFORE THERE ARE NEW COMMENTS.
  
 ** SOME ITEMS COULD HAVE BEEN RED-LINED, HOWEVER MOST
 OF THESE ARE IN NEED OF ADDRESSING AT THIS TIME.
  
 1) NOTE:PLEASE SEE THE PLANS DO NOT INDICATE FIXTURE
 DESIGNATIONS FOR ALL LIGHTING.
 PLEASE SEE THERE ARE SEVERAL AREAS INCLUDING FIRST
 FLOOR AND OTHER FLOORS WHERE FIXTURES ARE STILL MISSING
 DESIGNATIONS.
 PLEASE SEE THE FIXTURE LEGEND COULD NOT BE COORDINATED
 WITH THESE AT THIS TIME.
 PLEASE SEE COMMON AREAS WHICH THE LEGEND ON ELECTRICAL
 PLANS COULD NOT BE FOUND.
 PLEASE SEE THE INFORMATION ON THE INPUT DATA REPORT FOR
 EXTERIOR LIGHTING ALSO NEEDS TO CORRELATE WITH PLANS.
 THE LIGHTING, TYPES, NUMBER OF FIXTURES, ETC IS NOT
 STATED ON THE IDR AS ON PLANS.
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED AS THE
 INPUT DATA REPORT DOES NOT CORRELATE WITH ALL
 ELECTRICAL LIGHTING FOR INTERIOR LIGHTING WHICH IS ON
 PLANS.
  
 PLEASE SEE THE ENERGY CALCULATIONS/INPUT DATA REPORT IS
 MISSING A SUBSTANTIAL AMOUNT OF LIGHTING WHICH IS ON
 THE PLANS.
 PLEASE SEE FOR EXAMPLE ONE ROOM IN THE CLUBHOUSE:
 *FITNESS CENTER* WHICH LISTS ONE FIXTURE BEING
 FLUORESCENT AND 750WATTS ON THE INPUT DATA REPORT, YET
 HOW IS THIS POSSIBLE WHEN THE FIXTURE TYPES ON PLANS
 ARE INCANDESCENT, FLUORESCENT ETC, THERE A SEVERAL
 FIXTURES AND NOT JUST ONE AND THE TOTAL WATTAGE OF THE
 LIGHTING FIXTURES BASED ON THE FIXTURE LEGEND PROVIDED
 FOR THE CLUBHOUSE FAR EXCEEDS THE 750WATTS AS ENTERED?
  
 THIS IS THE SAME OF ALMOST ALL LOCATIONS NOT ONLY THE
 CLUBHOUSE. THERE ARE ACTUALLY HUNDREDS OF FIXTURES ON
 THE PLANS WHICH ARE NOT INCLUDED IN THE ENERGY
 CALCULATIONS.
 THE FIXTURE TYPES DO NOT CORRELATE.
 THE WATTAGE DOES NOT CORRELATE
 THE NUMBER OF FIXTURES DOES NOT CORRELATE.
 THE TOTAL ENERGY CONSUMPTION OF LIGHTING ENTERED IN THE
 INPUT DATA REPORT IS FAR LESS THAN THE LIGHTING AND
 CONSUMPTION OF ENERGY ON PLANS.
 PLEASE KNOW THESE ARE MINIMUM REQUIREMENTS FOR ENERGY
 AND ARE FEDERAL AND STATE REQUIRED.
 13-415.0, 415.1.ABCD, 415.1.A, 415.2, THERE ARE TOO
 NUMEROUS CODE SECTIONS TO LIST, PLEASE SEE CHAPTER 13
 OF THE 2001 FBC.
  
 2) NOTE: PLEASE SEE ONLY ONE COPY OF THE ENERGY
 CALCULATIONS (1.22 VERSION) SUBMITTED ACTUALLY CONTAINS
 AN ORIGINAL SIGNATURE AND DATE. PLEASE SEE THAT TWO
 SETS CONTAIN A RAISED SEAL OVER A PHOTO-COPIED
 SIGNATURE AND THE THIRD DOES NOT CONTAIN A RAISED
 SEALED OR ORIGINAL SIGNATURE.
 **PLEASE KNOW THIS COMMENT HAS BEEN MADE TO THIS DESIGN
 PROFESSIONAL ON SEVERAL PROJECTS SUBMITTED TO THIS
 JURISDICTION. THIS COMMENT WILL ALSO BE UNDER BUILDINGS
 1 AND 3.
 PLEASE KNOW THIS OFFICE IS RETAINING ALL COPIES
 SUBMITTED FOR POSSIBLE SUBMISSION TO THE FLORIDA BOARD
 OF ENGINEERS NOT ONLY FOR THE FACT THIS OFFICE HAS
 REPEATEDLY MADE THIS SAME COMMENT ON NUMEROUS PROJECTS
 TO THE SAME DESIGNER, BUT ALSO FOR INFORMATION ON PLANS
 AND ENERGY CALCULATIONS NOT COORDINATING.
 THIS IS A FLORIDA STATUTE AND IS ALSO STATED IN THE
 FLORIDA ADMINISTRATIVE CODE.FS 471.025, FAC
 61G15-23.002, FBC 103.1.
 ** WHEN PLANS WERE RE-SUBMITTED THIS REVIEWER NOTICED
 THE INCORRECT VERSION ON THE CALCULATIONS SUBMITTED AND
 NEW CALCULATIONS WITH THE CORRECT VERSION WAS SENT VIA
 FED-EX. PLEASE SEE THAT THE ONES DONE UNDER THE 2004
 FBC WERE ALSO NOT SIGNED, DATED AND SEALED CORRECTLY
 AND AS REQUIRED BY THE FLORIDA STATUTES. THIS SHOWS
 SAME NON-COMPLIANCE ON MULTIPLE SETS OF DOCUMENTS. **
 PLEASE BE SURE TO GO OVER ALL AND CORRECT.
  
 3) NOTE: PLEASE SEE INFORMATION FOR SITE LIGHTING POLES
 DO NOT CONTAIN THE MINIMUM WIND LOAD INFORMATION.
 PLEASE KNOW IF THIS INFORMATION IS NOT COMPLETE UNDER
 BASE PLANS, THESE WILL BE REQUIRED TO BE UNDER SEPARATE
 PERMITS, PLANS AND FEES.
 PLEASE KNOW HOWEVER THE LIGHTING INFORMATION AS NOTED
 ABOVE IN NOTE #1 FOR THE ENERGY CALCULATIONS WILL STILL
 NEED TO BE CORRECTED.
 PLEASE IDENTIFY THE CIRCUITS AS SHOWN ON PLANS TO WHICH
 BUILDING HOUSE PANEL THEY TERMINATE. PLEASE SEE THIS IS
 DONE FOR THE SITE LIGHTING CIRCUITS FOR BUILDING #2 BUT
 NOT THE OTHERS.
  
 4) NOTE: PLEASE SEE THE SYMBOL LEGEND STILL INDICATES
 *SMOKE DETECTORS*. THIS COULD BE REDLINED IF AND WHEN
 ALL OTHER COMMENTS AS ADDRESSED. PLEASE KNOW IF THERE
 ARE ANY COMMENTS HOWEVER WHICH MAY AFFECT THE SAME
 SHEET(S), PLEASE CORRECT AT THIS TIME. E16.01 THIS
 COULD BE REDLINED ON THIS SHEET IF NOT OTHER CHANGES IS
 MADE.
 ** THIS IS ALSO SHOWN ON LEGENDS ON OTHER SHEETS.
  
 5) NOTE: PLEASE INDICATE ALL CIRCUITING ON PLANS.
 PLEASE SEE THIS WAS NOTED ON PREVIOUS REVIEW AND
 SPECIFICALLY NOTED TO SEE 700.12E FOR CIRCUITING OF
 EMERGENCY AND EXIT LIGHTS.
 PLEASE SEE THERE IS EMERGENCY AND EXIT LIGHTING
 FIXTURES WHICH ARE STILL MISSING CIRCUITING. (
 CLUBHOUSE)
 FBC 104.1.2 (2001) ADMIN SECTION FOR ADDITIONAL
 INFORMATION AND COORDINATION OF PLANS.
 ** THIS WAS IN PREVIOUS REVIEWS NOTES #6, #7, AND NOTE
 #30 AT A MINIMUM. SPECIFICALLY 700.12E WAS NOTED.
  
 6) NOTE: PLEASE SEE DISHWASHER AND DISPOSAL WHICH IS
 BEING SHOWN WITH A J-BOX. ARE THESE ITEMS GOING TO BE
 HARDWIRED?
 PLEASE SEE 422.30, 422.31 FOR REQUIRED DISCONNECTING
 MEANS.
 ARE THESE NOT CORD AND PLUG TYPE APPLIANCES WHICH WOULD
 PLUG IN?
  
 7) NOTE: PLEASE CLARIFY WHERE THE ROOM AND AREA
 DESIGNATIONS ARE ON PLANS. EXAMPLE: BEDROOM #1, DINING
 ROOM, LIVING ROOM ETC.
 PLEASE KNOW THE PREVIOUS REVIEW REQUESTED FOR ALL
 CIRCUITING TO BE COMPLETED ON PLANS AND TO CORRELATE
 WITH PANEL SCHEDULES HOWEVER AS NOTED IN NOTE #5 ABOVE
 THIS IS STILL NEEDED IN MANY LOCATIONS.
 PLEASE SEE SHEET E16.05, WHICH INDICATES CIRCUITS CB32
 FOR ELEVATOR PIT LIGHTS AND RECEPTACLES AND INDICATES
 CB-30 FOR *H*.
 THE *H* IS NOT KNOWN AND BOTH CIRCUITS ON PANEL
 SCHEDULE CB ARE SHOWN A BLANK/SPARES.
 AS THESE CIRCUITS ARE NOT INDICATED WE CAN NOT
 DETERMINE MINIMUM COMPLIANCE WITH 620.22-620.25 PLEASE
 SEE OTHER ELEVATOR EQUIPMENT ROOMS AND AREAS WHICH SEEM
 TO INDICATE LIGHTING HOWEVER THE LIGHTING IS SHOWN
 CIRCUITED ON THE SAME LIGHTING AS GARAGE AND/OR OTHER
 COMMON AREAS.
 PLEASE VERIFY ALL ON PLANS, AND CORRELATE WITH PANEL
 SCHEDULES. THIS IS NOT ALL LOCATIONS.
 ** THIS WAS NOTED ON PREVIOUS REVIEWS NOTE # 9.
  
 8) NOTE: PLEASE SEE THE MISSING LIGHTING OUTSIDE FIRE
 PUMP ROOM AND STAIR AREA. PLEASE SEE MISSING
 PHOTO-METRICS ETC.
 PLEASE SEE MISSING PHOTO-METRICS FOR CLUBHOUSE STAIR
 AREA UNDER NORMAL AND EMERGENCY.
 PLEASE SEE THE LEVEL OF LIGHTING OUTSIDE MAIN
 ELECTRICAL ROOM FOR BOTH CONDITIONS OF NORMAL AND
 EMERGENCY DOES NOT SEEM TO MEET THE MINIMUM LEVELS
 REQUIRED. PLEASE SEE THE NORMAL LEVEL IS SHOWN ONLY AS
 6.38 AND LESS THAN 1FT CANDLES UNDER EMERGENCY?
 NFPA-101 7.8.1.3, 7.9.2.2.
 PLEASE KNOW AS THERE ARE NO LIGHTING FIXTURES,
 CIRCUITING ETC SHOWN FOR SOME AREAS, PLEASE COMPLETE.
 PLEASE ALSO BE SURE TO GO OVER ALL EGRESS PATHS
 ESPECIALLY STAIR AREAS. THERE ARE OTHER AREAS ALSO.
  
 PLEASE ILL BE REQUIRED TO BE BATTERY BACK UP. THIS IS
 SHOWN AS A *J* FIXTURE. S NO FIXTURE LEGEND WAS
 SUBMITTED THIS CAN NOT BE VERIFIED AT THIS TIME. PLEASE
 ALSO SEE ARE OUT SIDE ELEVATOR EQUIPMENT AREA AND MAIN
 ELECTRICAL ROOM WILL ALSO REQUIRE AN EMERGENCY BATTERY
 BACK UP LIGHTING FIXTURE OF SOME KIND.
 NEC 700.12E, 700.16, LS-101 7.8, 7.9
 ** THIS WAS NOTE ON PREVIOUS REVIEWS NOTE #6
  
 9) NOTE: PLEASE SEE THE PREVIOUS NOTES QUESTIONED THE
 EGRESS PATH FROM CLUBHOUSE INTO THE GARAGE WHICH IS
 MAIL CENTER HALL AS THE EXIT LIGHT AND DOOR ON
 CLUBHOUSE PLANS SHOWS THE EGRESS INTO THIS AREA AND THE
 MAIL CENTER HALL AREA INDICATES EXIT LIGHTS WITH
 DIRECTIONAL INTO THE CLUBHOUSE???
 THERE ARE SEVERAL OTHER LOCATIONS WHERE EXIT LIGHTS ARE
 IN QUESTION BASED ON THE LAYOUTS SHOWN ON THE
 ELECTRICAL PLANS.
 SEE MAIL CENTER AREA ADJACENT TO PARKING AREA WHICH
 DOES NOT INDICATE ANY EXIT LIGHT FIXTURES DIRECTING AN
 OCCUPANT TO THE EXIT.
 THIS HAS BEEN GONE OVER WITH THE BUILDING PLAN REVIEWER
 AND COMMENTS WILL BE NOTED ON THESE LOCATIONS. THE LIFE
 SAFETY PLAN ALSO INDICATES WHAT IS BEING SHOWN AS
 EGRESS PATHS THROUGH PARKING SPACES ETC.
 PLEASE SEE COMMENTS FROM BUILDING REVIEWER, AND FIRE
 MARSHAL.
 PLEASE SEE CHAPTER 10 OF THE FBC AND CHAPTER 7 OF THE
 LIFE SAFETY CODE.
 THE EGRESS PATHS ARE NOT IN REVIEW OF THE ELECTRICAL
 REVIEWER HOWEVER AS MANY OF THE EXIT AND EMERGENCY
 LIGHTING ARE IN QUESTION AND THIS DIRECTLY AFFECTS THE
 ELECTRICAL PLANS THIS IS BEING NOTED FOR INFORMATION AT
 THIS TIME.
  
 10) NOTE: PLEASE SEE PLANS ARE NOT COMPLETE WITH WIND
 LOAD INFORMATION FOR SITE LIGHTING.
 IF NOT INCLUDED IN THE PLANS, THEN THESE WILL ALL BE
 REQUIRED TO BE UNDER SEPARATE PERMITS.
 ** THIS WAS NOTED ON NOTE #7 ON PREVIOUS REVIEWS.
  
 11) NOTE: PLEASE CLARIFY THE FIRE PUMP AND INFORMATION
 AS REQUESTED ON THE PREVIOUS REVIEWS.
 PLEASE SEE NO INFORMATION WAS SUBMITTED WITH RESPECT TO
 THE MINIMUM FUEL REQUIREMENTS AND SIZE OF TANK. PLEASE
 SEE NO TIMES AT 100% RUNNING IS SHOWN.
 PLEASE SEE NFPA-20 9.6.2.2 AND SEE COMMENTS FROM FIRE
 MARSHAL.
 PLEASE SEE THE FUEL NOTE WHICH IS ON SHEET FP13.09 #3,
 DOES NOT CONTAIN THE TEXT FOR CODE.
 PLEASE SEE THE MINIMUM ON THE BASE BUILDING IS REQUIRED
 AT THIS TIME.
 PLEASE SEE THE PREVIOUS NOTES WHICH REQUESTED THIS SAME
 INFORMATION.
 PLEASE SEE THE FP SHEETS INDICATE A DIESEL FIRE PUMP,
 YET THE SUBMITTALS WHICH WERE SUBMITTED WITH PLANS
 INDICATE AN ELECTRICAL FIRE PUMP.
 PLEASE SUBMIT THE ACTUAL DOCUMENTATION AND CORRELATE
 WITH PLANS.
 110.3, 90.7, NFPA-70 695, NFPA-20 2003
 **THIS WAS NOTED ON TWO PREVIOUS REVIEWS ON NOTE #10.
  
 12) NOTE: PLEASE LABEL ALL MAINS, MAIN 1 OF ? , 2OF ?
 /SERVICE #1 MAIN #1, SERVICE #2 MAIN #1, SERVICE #3
 MAIN 1 ETC.
 PLEASE BE SURE TO CONTACT THIS OFFICE WITH RESPECT TO
 PLAGUE DIRECTLY LABELING AND INFORMATION. THIS CAN BE
 GONE OVER WITH THE CHIEF ELECTRICAL INSPECTOR ALSO
 BEFORE PLAGUES ARE INSTALLED.
 PLANS SHOW 7 MAINS AT THIS TIME.
 PLEASE SEE 230.2, (E)
  
 13) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS WITH
 RESPECT TO ELEVATOR PLATFORMS WHICH MAY AFFECT
 ELECTRICAL PLANS AND LAYOUTS.
  
 14) NOTE: PLEASE SEE DOOR SWING FOR METER/ELECTRICAL
 ROOM 1C2, NEEDS TO SWING OUT.
 110.26
  
 15) NOTE: PLEASE SEE THE PREVIOUS REVIEW NOTES GAVE
 NOTICE TO FS 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE.
 PLEASE KNOW AT THIS TIME ONE SET OF PLANS MAY BE
 RETAINED BY THIS OFFICE FOR PEER REVIEW AS THERE ARE
 SOME CODE SECTIONS WHICH HAVE STILL NOT BEEN COMPLIED
 WITH.
 PLEASE KNOW ONE GONE OVER THIS FEE MAY BE ASSESSED
 WHICH IS REQUIRED UNDER THE FLORIDA STATUTES. THIS FEE
 IS NOT TO THE CONTRACTOR/OWNER OR DEVELOPER THIS IS TO
 THE DESIGN PROFESSIONAL(S).
 ** PLEASE BE SURE TO GO OVER COMMENTS.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS
 OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE.
 IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY
 WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND
 THIS REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-20 16:32:342007-09-20 16:32:34
  
 REVIEW COMMENCED
2007-09-16 13:07:432007-09-16 13:07:43
  
 IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-01-01 Cont ID  
Sent By dpalmer Date 2007-01-01 Time 13:54 Rev Time 0.00
Received By dpalmer Date 2007-01-01 Time 09:16 Sent To  
Notes
2007-01-01 13:54:45 
 **** UNSAT2ND REVIEW ********
  
 COURTNEY LAKES BUILDING #1
 N. CONGRESS.
  
 ** PLEASE SEE MANY OF THE SAME COMMENTS FROM THE
 PREVIOUS REVIEW STILL NEED TO BE ADDRESSED.
  
 ** PLEASE SEE AS THREE SEPARATE BUILDING PERMITS AND
 PLANS ARE NOW SEPARATED FOR EACH, PLEASE ALSO SEE NEW
 COMMENTS BASED ONE THE PLANS NOW SUBMITTED INTO EACH
 SET.
 PLEASE SEE THE COMMENTS ON BUILDING ONE ARE DIFFERENT
 IN MANY ASPECTS BASED ON THE DESIGN ALONE AND PROPOSED
 PHASES OF PROJECT.
  
 ** PLEASE ALSO SEE THERE ARE SOME NEW NOTES BASED ON
 PLANS SUBMITTED.
  
 ** PLEASE SEE BELOW ARE SOME OF THE NOTES FROM THE
 PREVIOUS REVIEW ARE BEING NOTED IF ADDRESSED OR NOT BY
 A "NO, OK, NO/OK, N/A OR SEE NEW ".
 1) NO WILL HAVE FURTHER EXPLANATION IN AN ATTEMPT TO
 BETTER EXPLAIN COMMENT MADE.
 2) OK, WILL HAVE PREVIOUS NOTE REMOVED.
 3) NO/OK, MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL. THIS WILL ALSO BE FOLLOWED
 BY FURTHER EXPLANATION OF PREVIOUS NOTE.
 4) N/A, THIS MEANS THE COMMENT NO LONGER APPLIES TO
 THIS BUILDING AND PREVIOUS NOTE IS REMOVED.
  
 ** PLEASE SEE ALL NEW NOTES WILL BE NOTED AT THE END OF
 PREVIOUS REVIEW COMMENTS AND WILL BE INDICATED WITH
 **** NEW NOTES**.
  
  
 1) NOTE: NO, PLEASE SEE THE SETS ARE NOT BOUND TOGETHER
 IN A FASHION TO SECURE ALL SHEETS.
 PLEASE SEE THE PLANS SUBMITTED FOR BUILDING #1 ARE ALL
 FALLING APART AND WERE NOT SECURELY PUT TOGETHER.
 PLEASE SEE THE STAPLES BEING USED DO NOT GO THROUGH ALL
 SHEETS.
 PLEASE SEE SOME SETS WERE ALREADY COMING APART BEFORE
 THEY WERE OPENED FOR REVIEW. PLEASE SEE THIS IS
 REQUIRED FOR ALL SETS AND FOR ALL PLANS.
 PLEASE OBTAIN A METHOD TO SECURE AND BOUND PLANS
 TOGETHER.
 IF PLANS COME BACK IN THE SAME FASHION, THIS OFFICE
 WILL CONTACT THE CONTRACTOR TO COME IN AND PICK UP
 PLANS TO BE CORRECTED BEFORE PROCESSING AND BEFORE
 REVIEW WILL TAKE PLACE.
 THE STAPLES IN SOME HAVE ALREADY COME COMPLETELY OUT.
 THIS COMMENT IS FOR ALL WHETHER OR NOT COMMENT IS MADE
 FOR OTHER BUILDINGS OR BY OTHER TRADES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT COMPLETED PLANS BOUND TOGETHER IN AN
 APPROPRIATE FASHION. PLEASE SEE ALL SHEETS WERE
 SUBMITTED LOOSELY AND NOT BOUND IN SETS.
  
  
  
 2) NOTE: OK, HOWEVER SEE NEW NOTES.
  
 3) NOTE:NO, PLEASE SEE RESPONSE MENTIONS PLANS
 DESIGNED UNDER THE CODES AS NOTED, HOWEVER ALL CODES
 RELEVANT TO THE DESIGN IN WHICH THE BUILDING IS
 PERMITTED UNDER SHALL BE STATED ON PLANS. PLEASE SEE
 THIS IS REQUIRED OF ARCHITECTURAL SHEETS AS WELL AS
 ELECTRICAL AND FIRE. PLEASE SEE ANY OTHER NOTES WITH
 RESPECT TO THIS FROM OTHER TRADES.
 THE FOLLOWING SHALL BE STATED. 2002 NEC/NFPA-70, 2002
 NFPA-72, 2003 NFPA-20 AND 2003 NFPA-101. (THE CORRECT
 NFPA-101 IS NOTED )
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE TO CORRECT THE CURRENT NEC/ NFPA-70 IN
 EFFECT.
 PLEASE KNOW, AS OF JULY 1ST, 2003 THE STATE OF FLORIDA
 ADOPTED THE 2002
 NFPA-70 (NEC). PLANS REFERENCE 1999. PLEASE SEE SOME
 ELECTRICAL COMMENTS WHICH WILL AFFECT THIS.
 PLEASE SEE NEXT COMMENT WITH RESPECT TO PERMITS APPLIED
 FOR UNDER THE 2001 FBC BEFORE OCT 1ST, 2005 AND PERMITS
 ON OCT 1ST, 2005.
  
 4) NOTE:NO, PLEASE SEE THE PREVIOUS NOTES AS THE
 PHASING OF THIS BUILDING #1 WILL STILL BE OF CONCERN.
 AS NOTED ON PLANS, IT IS THE INTENT TO OCCUPY PHASES OF
 THE BUILDING INSTEAD OF COMPLETING ALL AT ONCE. PLEASE
 SEE THERE ARE SEVERAL ISSUES WHICH CREATE AN CONCERN
 FOR LIFE SAFETY OF NOT ONLY THE OCCUPANTS HOWEVER ALSO
 FOR CONSTRUCTION WORKERS PER OSHA REGULATIONS FOR
 GUARDING O LIVE PARTS AND EXPOSEURE TO UNQUALIFIED
 PERSONNEL PER 110.27.
 PLEASE SEE NO INFORMATION FOR SPRINKLER PROTECTION AND
 HOW SYSTEMS WHICH FEED FROMONE TO ANOTHER SECTION
 WILL TAKE PLACE.
 PLEASE SEE THERE ARE CIRCUITS IN PHASES TWO AND THREE
 WHICH ARE BEING FED FROM PANELS ALREADY ENERGIZED UNDER
 PHASE ONE.
 THE HAZARD OF SYSTEMS BEING FED FROM OTHER PARTS OF THE
 BUILDING WHICH ARE FROM EQUIPMENT ALREADY ENERGIZED IS
 OF CONCERN. NO INFORMATION OF SCHEDULE SHUT DOWN BY THE
 DESIGNER AND CONTRACTOR WAS SUBMITTED.
 PLEASE KNOW DUE TO THE CIRCUITING AS SHOWN ON PLANS FOR
 BRANCH CIRCUITS, FEEDERS ETC APPROVAL OF THE WAY THE
 PROPOSED CONSTRUCTION WILL TAKE PLACE IS NOT FINALIZED
 AT THIS TIME. PLEASE ALSO SEE COMMENTS FROM OTHER
 TRADES LIKE THE FIRE MARSHAL AND BUILDING PLAN REVIEW.
  
 ** PREVIOUS REVIEW NOTE **
 4) NOTE: PLEASESEE THAT THREE SEPARATE PERMIT
 APPLICATIONS WERE SUBMITTED AND NOTED FOR BLDG'S 1,2
 AND 3, HOWEVER PLANS SHOWS BLDG TYPES 1.2&3
 STRUCTURALLY ONLY ONE BUILDING.
 PLEASE SEE PERMIT APPLICATIONS ALL REFLECT THIS ONE 450
 UNIT BLDG.
 PLEASE SEE THIS CONTRADICTS THE "PHASING PLAN"
 SUBMITTED ON A1.04 AS THIS PHASING PLAN INDICATES WORK
 ON BLDGS 4 AND 5 BEFORE COMPLETION OF BLDGS 1, 2 AND
 3.
 PLEASE SEE COMMENTS FROM BLDG, FIRE AND OTHER
 REVIEWERS, AS CERTIFICATES OF OCCUPANCY(CO'S) FOR
 THESE CAN NOT BE GRANTED IN THIS ORDER AS THE FIRST
 "STRUCTURED BLDG"(1,2&3) WOULD NOT BE COMPLETE.
 PLEASE ALSO SEE COMMENTS WITH RESPECT TO "TEMPORARY
 CO'S" WHICH MAY ALLOW OCCUPANCY OF SOME PARTS OF BLDGS,
 HOWEVER THESE TCO'S ARE ONLY GOOD FOR 30
 DAYS AND A MAX OF 3 TCO'S MAY ONLY BE GRANTED BY THE
 BLDG OFFICIAL.
 PLEASE KNOW, IN ANY CASE, ALL LIFE SAFETY, FIRE
 PROTECTION SYSTEMS, FIRE SPRINKLERS (FULLY CHARGED),
 ELECTRICAL SYSTEMS ETC SHALL BE COMPLETE IN THE BASE
 BLDG FOR BLDG TYPE 1, 2& 3 BEFORE A TCO,/CO CAN BE
 GRANTED.
 *************************************
 ALSO NOTED THAT BLDG'S TYPE 4 AND 5 WHICH ARE SEPARATE
 STRUCTURES AND INDEPENDENT OF EACH OTHER WERE NOT
 SUBMITTED FOR PERMIT.
 PLEASE SEE ALL PERMITS SUBMITTED AFTER OCT. 1ST, 2005
 SHALL FALL UNDER THE 2004 FBC, WITH ALL OTHER CODES
 ADOPTED BY SAID CODE AND STATE OF FLORIDA.
  
 ************************************
 PLEASE SEE COMMENTS FROM OTHER REVIEWER(S) WITH RESPECT
 TO THIS.
  
 *************************************
 PLEASE ALSO SEE NEXT COMMENT WITH RESPECT TO THE MAINS,
 SERVICES, AND METER RMS AS PROPOSED.
 ** SEE ALL NOTES FROM ALL REVIEWERS WHICH MAY ALSO
 AFFECT THIS SEQUENCE OF CONSTRUCTION.
  
 5) NOTE: NO/OK. PLEASE SEE NOTE #4 ABOVE AND PLEASE
 SEE AS THE RISER HAS BEEN REVISED TO WHAT APPEARS TO BE
 NEW MAINS. PLEASE PROVIDE INFORMATION ON THE MAIN BEING
 SHOWN. RISER AND PLANS MAKE REFERENCE TO THESE BEING
 ?SHUNT-TRIP? WHICH ARE OK, HOWEVER PLEASE BE SURE EACH
 MAIN CONTAINS THE MANUAL MEANS OF DISCONNECT RATED FOR
 THE LOED SERVED AS REQUIRED PER 230.79 AND 230.76.
 PLEASE SEE RISER MENTIONS TO SEE METER CENTER RISER
 NOTES, HOWEVER RISER NOTES EACH METER CENTER WITH MAINS
 ALSO. PLEASE SEE NEW NOTES PERTAINING TO GROUNDING.
 PLEASE SEE PLANS DO NOT CORRELATE WITH THE RISER FOR
 ALL HOUSE PANELS AND EQUIPMENT. PLEASE SEE PLANS STILL
 INDICATE HOUSE METERS AT EACH ELECTRICAL ROOM WHEN THE
 RISER SHOWS ONE HOUSE METER/CT AND ALL HOUSE PANELS ARE
 FED FROM THE NEW DP.
 PLEASE SEE NEW NOTES FOR MANY OF THE REVISED ITEMS ON
 RISER.
 PLEASE SEE THE NOTES ABOVE WITH RESPECT TO PHASING OF
 THE PROJECT AND PANELS/FEEDERS AND BRANCH CIRCUITS
 CROSSING OVER PHASED AREAS.
  
 ** PREVIOUS REVIEW NOTE **
 5) NOTE: PLEASE SEE METER RMS AS SHOWN WOULD BE OK,
 HOWEVER STRUCTURE AS SHOWN FOR BLDG TYPE 1, 2 AND 3
 (ONE BLDG) WOULD REQUIRE MAINS TO BE GROUPED. 90.4,
 230.2, 230.70, 230.72, 230.76, 230.79 ETC.
 BLDG'S LARGE ENOUGH TO CONTAIN MORE THAN ONE SERVICE AT
 SEPARATE LOCATIONS SHALL BE DIVIDED INTO SECTIONS AND
 SHALL HAVE THOSE SECTIONS DIVIDED BY "FIRE WALLS".
 PLEASE SEE FBC FOR DEFINITION OF "FIRE WALLS".
 PLEASE KNOW, STRUCTURE CONSTRUCTED AS SHOWN IN PLANS,
 WOULD REQUIRE MAIN DISCONNECTS GROUPED, WHICH WOULD
 THEN IN-TURN FEED METER ROOMS.
 OTHER DESIGN CHANGES IN THE "ONE BLDG" MAY ALSO PERMIT
 INDIVIDUAL SERVICES.
 PLEASE SEE BLDG TYPE #4 AND #5 ARE SHOWN AS SEPARATE
 BLDGS WITH STAND ALONE SERVICES AND ALL MAINS ARE
 GROUPED.
 PLEASE KNOW THAT BLDGS 4 AND 5 WILL HAVE REVIEWS DONE
 UNDER THOSE PERMIT APPLICATIONS.
 ** PLEASE SEE SOME OF THESE COMMENTS WOULD ALSO APPLY.
  
 6) NOTE:NO, PLEASE SEE THERE ARE SEVERAL AREAS WHICH
 CIRCUITING IS NOT COMPLETE INCLUDING UNITS FOR SMOKE
 DEVICES AND MANY AREAS OF HOUSE/COMMON AREAS/ SITE ETC.
 PLEASE SEE MANY NEW COMMENTS BASED ON PLANS SUBMITTED.
 PLEASE SHOW ALL AND CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULES. SEE NEW NOTES ALSO.
 PLEASE SEE HOUSE CIRCUITS AND NEW NOTES FOR THIS.
 FBC ADMIN SECTION 104.2.1.2, NEC 408.4, 310.16, 240.4
  
 PLEASE COMPLETE ALL CIRCUITING ON PLANS IN ORDER TO
 REVIEW CODE COMPLIANCE FOR AREAS OF UNITS AND COMMON
 AREAS.
  
 7) NOTE: NO, SAME COMMENT. THIS IS NOT EXPLAINED ANY
 FURTHER. PLEASE HOWEVER ALSO SEE NEW COMMENTS BASED ON
 PLANS SUBMITTED.
 ** PLEASE KNOW THERE ARE AREAS OF PLANS WITH
 DESIGNATIONS, ITEMS FOR CODE COMPLIANCE FOR CIRCUITING
 TO THOSE AREAS CAN NOT BE VERIFIED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE ROOM AND AREA DESIGNATIONS ON PLANS,
 INCLUSIVE OF ALL UNITS AND COMMON AREAS.
 REVIEW FOR SOME CODE COMPLIANCE ITEMS CAN NOT BE DONE
 AT THIS TIME.
  
 8) NOTE:NO, PLEASE SEE RESPONSE LETTER MENTIONS TO
 SEE SHEET AP E16.00A, YET PLEASE KNOW COMPLETED
 PHOTO-METRICS SHALL BE SUBMITTED IN EACH SUBMITTED
 PLANS FOR EACH BUILDING AS EACH BUILDING IS ITS OWN
 LEGAL RECORD.
 PLEASE SEE THE LAYOUT IN THIS BUILDING IS NOT THE SAME
 AS OTHER AND SEPARATE EGRESS PATHS ARE PRESENT. PLEASE
 ALSO SEE NEW NOTES PERTAINING TO ELEVATOR CORRIDOR.
 PLEASE ALSO SEE PREVIOUS NOTES, PLEASE SEE ONLY PARTIAL
 PHOTO-METRICS WERE SUBMITTED. PLEASE SEE NOTE WHICH
 REQUIRES ALL UNDER NORMAL AND EMERGENCY AND FOR ALL
 EGRESS AREAS. PLEASE SEE ONLY SOME ARE BEING SHOWN IN
 THE PLANS UNDER BUILDING ONE. PLEASE KNOW THESE CAN BE
 TYPICAL, HOWEVER THEY SHALL ALSO BE SPECIFIC TO EACH
 AREA IF THE LAYOUT OF THESE AREAS CHANGES WHICH THEY
 DO. NOT ALL AREAS ARE THE LIKE.
 PLEASE ALSO SEE MISSING PHOTO-METRICS FOR CLUBHOUSE
 PLANS, STAIRS AND EGRESS PATHS.
 PLEASE SEE NEW NOTES ALSO FOR EGRESS FROM UNITS AND
 PLEASE SEE NEW NOTES PERTAINING TO PARKING LOT, AND
 SITE LIGHTING.
 THIS COMMENT HAS BEEN PRIMARILY THE SAME NOTE FOR ALL
 THREE BUILDING PERMIT APPLICATIONS.
 PLEASE KNOW AS THE SWIMMING POOL IS NOT UNDER THIS
 PERMIT FOR THE BUILDING, STAMPED PLANS FROM PALM BEACH
 COUNTY HEALTH DEPT IS NOT REQUIRED AT THIS TIME UNDER
 THIS PERMIT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE COMPLETE PHOTO-METRICS FOR ALL COMMON
 AREAS, GARAGE AREA, COMMON AREA CORRIDORS, STAIR TOWERS
 ETC.
 PLEASE SEE 2003 NFPA-101 7.8.1.3 AND 7.9.2.2 WHICH
 REQUIRE A MIN OF 10FT CANDLES FOR STAIR TOWERS UNDER
 NORMAL OPERATION AS WALK SURFACE AND A MIN OF 1FT
 CANDLE AT WALK SURFACE UNDER EMERGENCY CONDITIONS.
 PLEASE ALSO SEE OTHER WALK AREAS, GARAGE, CORRIDORS ETC
 AND THE MIN OF 1FT CANDLE.
 **PLEASE SEE PALM BEACH COUNTY SECURITY CODE ORDINANCE
 WITH RESPECT TO MIN DESIGN OF PARKING LOT LIGHTING
 LEVELS UNDER NORMAL CONDITIONS. (ONLY NOTED FOR DESIGN)
 NOT REQUIRED. PLEASE SEE ANY REQUIREMENTS FROM INS
 CARRIER WHICH REQUIRES A MIN LEVEL OF LIGHTING.
 ** PLEASE SEE PHOTO-METRICS OR SITE PLAN WAS NOT
 SUBMITTED FOR PROPOSED POOL AREA. THE POOL STRUCTURE IS
 REQUIRED TO BE UNDER A SEPARATE PERMIT. PLEASE KNOW,
 THE PHOTO-METRICS FOR POOL AREA WILL BE REQUIRED AND
 WILL ALSO BE REQUIRED TO BE REVIEWED AND STAMPED BY THE
 PALM BEACH COUNTY HEALTH DEPT FOR ANY PROPOSED
 NIGHT-TIME SWIMMING.
  
 7) NOTE: NO, PLEASE SEE EACH SET OF PLANS SHALL CONTAIN
 A SITE LIGHTING PLAN SHOWING ALL CIRCUITING AND
 CORRELATE WITH EACH OF THE HOUSE PANELS FOR EACH
 BUILDING IN WHICH THEY ARE BEING CIRCUITED TO. PLEASE
 SEE ALL SITE LIGHTING AS SHOWN IN THE SET OF PLANS FOR
 BUILDING ONE. PLEASE SEE THE CIRCUITING AS SHOWN DOES
 NOT CORRELATE WITH HOUSE PANEL FOR BUILDING THREE IN
 ANY WAY.
 PLEASE SEE THERE ARE CIRCUITS SHOWN IN THIS BUILDING
 ALSO DO NOT CORRELATE WITH THE PANEL SCHEDULE AS
 SUBMITTED.
 PLEASE SEE HOUSE PANEL FOR THESE CIRCUITS ARE IN FACT
 BLANK AND SHOWS THE WORDING OF "SPACE". PLEASE KNOW AT
 THIS TIME THERE ARE MANY ITEMS PERTAINING TO SITE
 LIGHTING WHICH CAN NOT BE VERIFIED FOR VOLTAGE DROP,
 CIRCUITS, OVER CURRENT PROTECTION, CONDUCTOR SIZES
 ETC.
 PLEASE SEE NO INFORMATION WAS SUBMITTED OR SHOWN FOR
 WIND LOADS ON POLES.
 240.4, 310.16, 408.4, FBC 104.2.1,104.21.2
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NO "ELECTRICAL SITE-PLAN" WAS SUBMITTED FOR
 ANY SITE LIGHTING, LANDSCAPE LIGHTING ETC.
 PLEASE KNOW, IF NOT SUBMITTED UNDER THIS PERMIT AND
 VALUES ADJUSTED ACCORDINGLY, SEPARATE PERMIT , PLANS
 AND FEES WILL BE REQUIRED FOR ALL SITE LIGHTING,
 LANDSCAPE LIGHTING WORK.
 ** ALSO NOTE: IN THAT COMPLETE WIND LOADING
 CALCULATIONS FOR LT POLES INCLUSIVE OF THE ATTACHMENT
 OF LT FIXTURES WILL BE REQUIRED TO BE SUBMITTED WITH
 PLANS AND PERMIT APPLICATION FOR REVIEW.
  
 8) NOTE: NO, PLEASE SEE NOT ALL ROOMS AND AREAS ARE
 CLEAR. IT APPEARS FOR THE MOST PART IN BUILDING #1 THIS
 HAS BEEN DONE. THE NOTE WILL REMAIN AS NEW NOTES
 PERTAINING TO FIXTURES AND CIRCUITING MAY AFFECT THESE
 AS SHOWN. PLEASE SEE NEW NOTES PERTAINING TO THE
 ELEVATOR EQUIPMENT ROOM.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INCLUDE AN EMERGENCY BATTERY BACK UP LT OF SOME
 SORT IN ALL ELECTRICAL ROOMS, FIRE PUMP ROOM, AND
 ELEVATOR MACHINE RMS. SOME ARE SHOWN, BUT NOT ALL.
 7.8,7.9, 700.16 ETC
  
 9) NOTE:NO, PLEASE SEE CIRCUITING FOR MANY OF THE
 CIRCUITS NOT SHOWN ON PLANS CAN NOT BE VERIFIED FOR THE
 REQUIRED DEDICATED CIRCUITS. PLEASE SEE PLANS AND
 CORRELATE WITH THE HOUSE PANEL FOR THIS BUILDING.
 PLEASE ALSO SEE NEW NOTES PERTAINING TO THE EQUIPMENT
 ROOM.
 PLEASE SEE 620.22,23,24 AND 620.51 ETC
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 620.23, AND 620.24 FOR REQUIRED DEDICATED
 BRANCH CIRCUITS FOR ELEVATOR PITS, AND ELEVATOR MACHINE
 RMS/EQUIPMENT AREAS.
 PLEASE ADJUST HOUSE PANELS AS NEEDED.
  
 10) NOTE: NO, PLEASE SEE NO INFORMATION WAS LOCATED ON
 RISER SHEETS. PLEASE SEE NOT ENOUGH INFORMATION WAS
 SHOWN ON FP FOR THE FIRE PUMP, SIZE, FUEL CONSUMPTION,
 TIME OF OPERATION UNDER THE AMOUNT OF FUEL ETC. PLEASE
 SEE THE SPECS/CUT SHEETS SUBMITTED CONTAIN MULTIPLE
 UNITS AND NO REVIEW FOR CODE COMPLIANCE OF THE UNIT FOR
 EACH BUILDING BASED ON THE NUMEROUS PUMPS SUBMITTED.
 PLEASE ALSO SEE MISSING FIRE PUMP CONTROLLER SPECS.
 PLEASE ALSO SEE MISSING THE RELEVANT CODES ON FP
 SHEETS.
 PLEASE SEE THAT THIS BUILDING DOES NOT SEEM TO BE
 FULLY SPRINKLED.
 PLEASE SEE A LAYOUT FROM UNITS COULD NOT BE SEEN FOR
 PROTECTION, SEE FIRE REVIEW NOTES. PLEASE ALSO SEE
 NOTES PERTAINING TO SMOKE DETECTOR/ALARM DEVICES
 REQUIREMENTS.
 PLEASE KNOW AS EACH BUILDING IS UNDER A SEPARATE
 PERMIT, THREE SETS OF PLANS SHALL BE ACCOMPANIED BY
 THREE SETS OF ALL SUBMITTALS AS REQUESTED.
 PLEASE SEE NFPA-20 FOR ALL REQUIREMENTS FOR ROOM.
 PLEASE KNOW BASED ON THE PLANS SUBMITTED AND SPEC/CUT
 SHEETS SUBMITTED, REVIEW FOR COMPLIANCE CAN NOT BE DONE
 AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE ELECTRICAL RISER SHOULD "NOTE" FIRE PUMP
 AS DIESEL AS NOTED ON FP SHEETS.
 PLEASE SUBMIT ALL MANUFACTURES SPEC/CUT SHEETS FOR FIRE
 PUMP CONTROLLER AS REVIEW FOR CODE COMPLIANCE UNDER
 2003 NFPA-20 IS REQUIRED.
 PLEASE ALSO SUBMIT ALL MANUFACTURES SPECS/CUT SHEETS
 FOR FUEL TANK.
 PLEASE SEE NFPA-20 9.6.2.2 AS THE FUEL CAPACITY IS
 REQUIRED TO BE SIZED BASE ON THE 100% RATED LOAD FOR A
 MIN OF 8HRS, OR TIME SO DETERMINED BY THE FIRE
 MARSHAL'S OFFICE DEPENDING ON OCCUPANCY.
 FUEL SYSTEMS WILL BE UNDER OTHER TRADE REVIEW(S). (FIRE
 AND MECH).
  
 11) NOTE: NO, RESPONSE MENTIONS THIS WAS DONE, HOWEVER
 PLEASE SEE UNIT PANEL SCHEDULES AND HOUSE PANEL
 SCHEDULE DOES NOT CONTAIN AND CONDUCTOR SIZES. PLEASE
 KNOW BASED ON COMMENTS ABOVE WITH RESPECT TO AREA
 DESIGNATIONS, CIRCUITING MISSING ON PLANS, REVIEW OF
 THIS CAN NOT BE DONE AT THIS TIME.408.4 , FBC 104.1.2
 ADMINSECTION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INCLUDE ALL MINIMUM CONDUCTOR SIZES ON ALL
 PANELS, UNITS AND HOUSE PANELS. REVIEW FOR THESE ITEMS
 OF CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME.
 310.16, 240.4,215.5
  
 12) NOTE:NO, AS CIRCUITING FOR THIS BUILDING IS NOT
 COMPLETE AT THIS TIME, THE OVER CURRENT PROTECTIVE
 DEVICES CAN NOT BE VERIFIED AT THIS TIME. THIS COMMENT
 WAS MAINLY FOR THE OCP DEVICES WHICH WERE BEING SHOWN
 ON BUILDING #1'S PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE GARAGE/HOUSE LIGHTING BEING INDICATED ON 30A
 AND 50A CIRCUITS.
 PLEASE SEE CODE DOES LIMIT THE OCP FOR UNIT FIXTURES
 FOR PROTECTION OF FIXTURES ON A BRANCH CIRCUIT. PLEASE
 ADJUST CIRCUITING AS NEEDED.
 PLEASE ALSO SEE A FIXTURE SCHEDULE CONTAINING WATTAGES,
 VOLTAGES ETC WAS NOT SUBMITTED.
 PLEASE VERIFY IF THESE UNIT FIXTURES ARE RATED TO HAVE
 OCP AT ABOVE MENTIONED.
 240.4, 310.16 ETC
  
 13) NOTE: OK, HOWEVER SEE NOTES.
  
 14) NOTE:NO/OK, PLEASE SEE PART OF THIS COMMENT SEEMS
 TO HAVE BEEN ADDRESSED, HOWEVER PLEASE SEE NOTES ON
 RISER AND RISER NOTES WHICH STILL DO NOT CORRELATE.
 PLEASE SEE TYPICAL NOTE #4 AND #7 DO NOT CORRELATE ON
 RISER.
 PLEASE SEE SEVERAL NOTE #1'S, YET ON RISER NOTES NOT
 ALL OF THESE NOTE #1'S CAN POSSIBLY APPLY.PLEASE SEE
 NEW NOTES FOR NEW MAINS.
 PLEASE ADJUST ALL NOTE SON RISER AND NOTES NOTED AS
 RISER NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 , PLEASE SEE PLEASE SEE MAX OCP TO BE SIZED FOR
 PANELS/EQUIPMENT BEING FED BY SAID OCP.
 PLEASE SEE MANY UNIT PANELS ARE SHOWN AS 100A MLO, WITH
 125A OCP AS LISTED ON RISER ETC.
 PLEASE ALSO SEE RISER NOTE #4 WHICH INDICATES 125A
 2-POLE ETC, HOWEVER PLEASE SEE RISER AS THIS NOTE #4
 COULD NOT BE LOCATED. (APPEARS TO BE MISPRINTED FOR
 "NOTE#7" ON RISER) 240.4,408,310.16,215.5 ETC.
  
 15) NOTE: N/A, NOT PART OF THESE PLANS FOR THIS
 BUILDING. SEE NEW NOTES.
  
 16) NOTE: N/A, NOT PART OF THESE PLANS FOR THIS
 BUILDING. SEE NEW NOTES.
  
 17) NOTE: N/A, NOT PART OF THESE PLANS FOR THIS
 BUILDING. SEE NEW NOTES.
  
 18) NOTE: NO/OK, SOME SHEETS SHOW NOTE, HOWEVER NOT ALL
 FOR UNITS. CIRCUITING IS NOT YET COMPLETE TO REVIEW
 THESE FOR CODE COMPLIANCE.
 PLEASE KNOW THAT IF BUILDING DOES NOT FALL UNDER
 EXEMPTION OF NFPA FOR SMOKE DEVICES REQUIRED INSIDE
 SLEEPING ROOMS, THEN THESE WILL BE REQUIRED TO BE SHOWN
 AND CIRCUITED. PLEASE BE AWARE THAT ONCE THESE DEVICES
 (IF SMOKE ALARMS AT 120V) ARE INSTALLED, THESE WOULD BE
 REQUIRED TO BE ON A ARC FAULT PROTECTED CIRCUIT. PANEL
 SCHEDULE AND/OR CIRCUITING MAY NEED TO BE ADJUSTED.
 PLEASE LABEL ALL CIRCUITS ON PANEL SCHEDULE WHICH
 CONTAIN AFCI PROTECTION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THESE SHEETS ALSO REFERENCE "ARC FAULT"
 PROTECTION FROM THE 1999 NEC, WHICH ONLY REQUIRED
 PROTECTION OF RECEPTS.
 PLEASE SEE THE 2002 NEC WHICH REQUIRES PROTECTION FOR
 ALL "OUTLETS" IN BEDRMS. THIS IS INCLUSIVE OF RECEPTS,
 LTS, FANS, SMOKE DETECTORS ETC. PLEASE SEE NOTE ON UNIT
 PLANS AND ADJUST.
  
 19) NOTE:THIS IS UNCLEAR AT THIS TIME, AS PERMIT
 APPLICATION FOR BUILDING #1 INDICATES 450 UNITS AND
 THAT IS WHAT WAS ORIGINALLY APPLIED FOR ON ORIGINAL
 APPLICATION AND ENTERED INTO OUR SYSTEM.
 PLEASE SEE THE NEW PERMIT APPLICATION FOR THE NEW
 CONTRACTOR DOES NOT DESCRIBE WORK IN DETAIL PROPOSED
 FOR THIS PARTICULAR BUILDING. ONLY MENTIONS NEW
 CONSTRUCTION FOR APARTMENT COMPLEX. PLEASE BE SURE TO
 CORRELATE EACH APPLICATION FOR EACH BUILDING AND BE
 SURE ALL INFORMATION IS COORDINATED WITH THE BUILDING.
 PLEASE CORRELATE PLANS, PERMIT APPLICATIONS AND ADJUST
 PLANS AS NEEDED.
 FBC 104.2.1.2 ADMIN SECTION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE LOADS, UNITS, PANELS, AND
 BUILDING/METER LOAD CALCULATIONS:
 A) PLEASE SEE PANEL SCHEDULE/LOAD CALCULATIONS FOR UNIT
 "B-3" SHOWN ON
 16.26, HOWEVER THIS UNIT TYPE OR LOADS COULD NOT BE
 LOCATED ON BLDG LOAD CALCULATIONS ON 16.25?
 B) PLEASE ALSO SEE THE SAME COMMENT ABOVE FOR UNIT
 "C-2" WHICH IS ALSO SHOWN ON
 16.26 BUT NOT IN CALCS ON 16.25??
 ** PLEASE ADJUST ALL AS NEEDED.
  
 20) NOTE: OK, HOWEVER STILL NOT ADDED TO RISER, ONLY
 SHOWN IN GROUNDING DETAIL. PLEASE EXPLAIN RATIONAL OF
 TWO GROUNDING ELECTRODE SYSTEMS SHOWN?
 PLEASE SEE METER CENTER "SCHEDULE" WHICH INCLUDES A
 3/0, HOWEVER SEE NEW NOTES FOR GROUNDING ELECTRODE,
 EQUIPMENT GROUNDING CONDUCTORS ETC.
 PLEASE ALSO SEE NEW NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INCLUDE THE REQUIRED FOOTER STEEL ON THE
 GROUNDING ELECTRODE RISER DETAIL. PLEASE ALSO SHOW ON
 RISER.
 250.50.
  
 21) NOTE: NO, PREVIOUS NOTE REQUESTED A NOTE/DETAIL
 WHICH WOULD ACTUALLY PROVIDE A LITTLE MORE INFORMATION
 FOR THIS REQUIREMENT. PLEASE EXPAND ON NOTE.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE PROVIDE A DETAIL/NOTE FOR ALL RACEWAY SEALS AS
 REQUIRED PER
 230.8
  
 22) NOTE: N/A, HOWEVER SEE NEW NOTES.
  
 23) NOTE: N/A, HOWEVER SEE NEW NOTES.
  
 24) NOTE: N/A.
  
 25) NOTE: OK, HOWEVER SEE NEW NOTES.
  
 26) NOTE: OK.
  
 27) NOTE: OK.
  
 28) NOTE:NO, PLEASE SEE THIS BUILDING DOES NOT SEEM
 TO BE FULLY SPRINKLED. PLEASE SEE LAYOUTS PROVIDED ON
 FP SHEETS DO NOT INDICATE HEADS IN ANY OF THE UNITS ON
 PLANS. THERE ARE NOTES FOR SOME CLOSETS AND BATHROOMS;
 HOWEVER THOSE DO NOT CORRELATE WITH PLANS AS NO HEADS
 ARE SHOWN FOR COVERAGE. PLEASE SEE FIRE MARSHAL'S
 REVIEW AS THE BASE SYSTEM IS REQUIRED UNDER THE
 BUILDING PERMITTED SET OF PLANS EVEN THOUGH THE FS
 PERMIT WILL BE SEPARATE WITH SEPARATE PLANS ETC.
 PLEASE ALSO SEE NOTES PERTAINING TO CIRCUITING AND
 PLEASE SEE NEW NOTES FOR THESE DEVICES AND TYPES
 SHOWN.
 PLEASE SEE 2001 FBC 905.2 WHICH IS MORE RESTRICTIVE AND
 DOES NOT CONTAIN THE EXCEPTION.
 PLEASE REVIEW LOCATIONS.
  
 ** PREVIOUS REVIEW NOTE **
 SMOKE DETECTORS ARE REQUIRED INSIDE AND OUTSIDE ALL
 SLEEPING ROOMS.
 PLEASE SEE 2002 NFPA-72 11.5.3.1
 PLEASE ADJUST NOTE FOR SD'S ON PLANS AS
 SD'S ARE REQUIRED 3' FROM BATH/KITCHEN DOORS, 3' FROM
 SUPPLY AIR DIFFUSERS, 5' FROM R/A GRILLES AND 20' FROM
 KITCHEN COOKING APPLIANCES. W/ EXCEPTIONS FOR DISTANCES
 FROM COOKING APPLIANCES. (PHOTO-ELECTRIC AND RESETTING
 TYPE)
 ** PLEASE SEE PREVIOUS NOTES WITH RESPECT TO ARC FAULT
 PROTECTION OF SD'S AND CIRCUITING.
  
 29) NOTE: N/A PER THIS BUILDING REVIEW.
  
 30) NOTE: NO, AS CIRCUITING IS NOT YET COMPLETE FOR ALL
 COMMON AREAS THIS CAN NOT BE VERIFIED. PLEASE ALSO SEE
 NOTES PERTAINING TO FIXTURES TYPES ETC.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE 700.12E FOR CIRCUITING OF ALL EM/EXT LTS,
 WHICH REQUIRES THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT, SHALL BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA AND CONNECTED
 AHEAD OF ANY LOCAL SWITCHES.
 THIS IS NOTED ON SOME SHEETS, HOWEVER CIRCUITING FOR
 THESE IS NOT SHOWN.
 215.5
  
 31) NOTE: OK.
  
 32) NOTE:NO, PLEASE SE SOME UNITS ARE STILL MISSING
 GFI RECEPTS TO SERVE KITCHEN COUNTER SPACE AS
 REQUIRED.
 UNIT(S) A 1, A-2, C1, C3 ETC. PLEASE GO THROUGH ALL.
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SEE 210.52C1-C5 FOR REQUIRED GFI RECEPTS ALONG
 KITCHEN COUNTER SPACE. PLEASE SEE SOME ARE SHOWN ON
 WHAT APPEARS TO BE A WALL ON THE OTHER SIDE OF THE
 COUNTER SPACE.
 PLEASE SEE B-2, B-4ETC.
 PLEASE SEE OTHER WHICH ARE REQUIRED TO BE WITHIN 2' OF
 THE END OF THE COUNTER SPACE/FROM SINK EDGE ETC. PLEASE
 SEE THESE AREAS REDLINED ON SHEETS.
  
 33) NOTE:NO, PLEASE SEE RESPONSE MENTIONS THIS IS FOR
 SECURITY AND IT IS NOT A PLUG-IN TYPE TRANSFORMER. IF
 THIS IS NOT A PLUG-IN TYPE, PLEASE INDICATE ON PLANS
 WHAT TYPE IT IS AND/OR WILL BE. PLEASESUBMIT OR
 RELOCATE THE RECEPTACLES LOCATED ABOVE CLOTHES CLOSET
 SHELVING OR IN THE NEAR VICINITY AS PREVIOUSLY STATED
 THIS AHJ HAS SEEN TOO MANY INSTANCE WHERE FIRES HAVE
 STARTED BASED ON SOME TYPES OF THESE UNITS AND IN THE
 INTEREST OF LIFE SAFETY AND PROPERTY DAMAGE, THESE WILL
 NOT BE PERMITTED AS SHOWN IN SOME UNITS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE WHAT APPEARS TO BE A RECEPT LOCATED IN THE
 CLOTHES CLOSET FOR PERHAPS A LV PLUG-IN TYPE
 TRANSFORMER?
 PLEASE KNOW, THE ONLY LOCATION A RECEPT IS PERMITTED IN
 A CLOTHES CLOSET FOR THIS PURPOSE, MUST BE LOCATED
 DIRECTLY ABOVE DOOR AWAY FROM COMBUSTIBLES.
 MANY PLUG-IN TYPE TRANSFORMERS BECOME VERY HOT AND
 HAVE MELTED OR CAUSED FIRES IN THIS JURISDICTION.
 PLEASE KNOW, MANY ITEMS IN A CLOTHES CLOSET ARE AN
 ACCELERANT.
 THESE RECEPTS MAY BE MOVED TO UTILITY RM IF SO
 DESIRED.
 110.26, 240.24, 90.4 ETC
  
 34) NOTE: OK.
  
 35) NOTE: OK.
  
 ** NEW NOTES FOR THIS REVIEW **
  
 1) NOTE: PLEASE SUBMIT AND SHOW ALL FIXTURE
 DESIGNATIONS ON PLANS. PLEASE SEE SOME OF THE NOTES
 WHICH MENTION A PARTICULAR FIXTURE DO NOT CORRELATE
 WITH THE FIXTURE SCHEDULE PROVIDED. PLEASE SEE OTHERS
 ARE SHOWN WITH OUT ANY WATTAGE USE OR DESIGNATION(S).
 PLEASE COMPLETE AND COORDINATE ALL AS THESE CAN NOT BE
 REVIEWED FOR COMPLIANCE AT THIS TIME.
  
 2) NOTE: PLEASE SEE PLANS SUBMITTED SEEM TO CONTAIN
 UNITS WHICH ARE NOT PART OF THIS PARTICULAR BUILDING?
 PLEASE SEE C-3. PLEASE SEE THESE DO NOT SEEM TO BE ON
 ARCHITECTURAL PLANS.
 104.2.1.2, ADMIN SECTION
 NEC 408.4, 240.4, 310.16 TO BE VERIFIED.
  
 3) NOTE: PLEASE SEE THE THRESHOLD INSPECTION PLANS
 SUBMITTED ALL CONTAIN A RAISED SEAL OVER A PHOTO-COPIED
 SIGNATURE FROM THE ENGINEER. PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA STATUTES
 471.025 AS AN ORIGINAL SIGNATURE IS REQUIRED. PLEASE
 KNOW THESE MAY BE RETAINED BY THIS OFFICE FOR POSSIBLE
 REVIEW FROM THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS. IF THERE ARE ANY QUESTIONS ON THIS PLEASE
 CONTACT THIS OFFICE OR THE BOARD.
 **THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE.
  
 4) NOTE: PLEASE SEE NFPA-72 DEFINITIONS FOR SMOKE
 DEVICES. IF THESE ARE INDEED (SD) FOR SMOKE DETECTORS
 THEN THEY WOULD DETECT AND CAUSE AN ALARM TO HORN/SIREN
 DEVICE OF SOME TYPE. PLEASE SEE PLANS CALL FOR THESE AS
 120V UNITS, WHICH IF (SA) SMOKE ALARMS WHICH WOULD
 DETECT AND SOUND, THEN THE DESIGNATIONS NEED TO BE
 ADJUSTED ALONE WITH ALL NOTES WHICH CURRENTLY STATE
 SMOKE DETECTORS. PLEASE KNOW THIS WAS NOT A COMMENT ON
 THE PREVIOUS REVIEW, HOWEVER AS INFORMATION WAS GIVEN
 FROM NFPA DIRECTLY, PLANS MUST CONTAIN THE CORRECT
 DESIGNATIONS.
  
 5) NOTE: PLEASE SEE THE BASE FA SYSTEM SHALL BE SHOWN
 AND ALL HORN/STROBE DEVICES SHALL STATE THE MINIMUM
 LEVELS AS REQUIRED PER FBC 11-4.28.1, .2, AND .3(4).
 THIS WAS NOT PART OF THE ELECTRICAL REVIEWERS REVIEW
 WHEN PLANS WERE SUBMITTED PREVIOUSLY HOWEVER THIS HAS
 NOW BECOME PART OF THE ELECTRICAL REVIEWERS REVIEW.
 PLEASE SHOW.
  
 6) NOTE: PLEASE CLARIFY STAIRS SHOWN ON SOME UNITS AS
 NOTED ABOVE IN NOTE #2 FOR NEW REVIEW NOTES.
 PLEASE SEE IF UNIT #C3 IS BEING DONE IN THIS BUILDING ,
 INCLUDE REQUIRED FIRST FLOOR ELECTRICAL.210.52
 PLEASE SEE MISSING WHAT WOULD BE EGRESS LIGHTING AND
 CONTROLS IF INSIDE UNIT AND/OR OUTSIDE UNIT. PLEASE SEE
 NEC 210.70, LS 101 7.8, (7.9 WHERE APPLICABLE).
  
 7) NOTE: PLEASE SEE SEVERAL HOUSE CIRCUITS AS NOTED
 ABOVE WITH RESPECT TO CORRELATION OF CIRCUITING SEEM TO
 BE INDICATE ON THESE PLANS TO PANELS WHICH WOULD BE ON
 OTHER BUILDINGS? PLEASE SEE MISSING WHAT APPEARS TO BE
 A TRASH ROOM(S) AND ANY CIRCUITING FOR LIGHTS,
 COMPACTOR ETC.
 240.4, 310.16, 408.4, ETC
  
 8) NOTE: PLEASE SEE NOTES ABOVE ON PREVIOUS REVIEW AND
 SECOND REVIEW NOTES WITH RESPECT TO ROOM/AREA
 DESIGNATIONS. PLEASE SEE 210.52B1, 210.11C1 AND 220.16
 FOR DINING ROOMS, DINING AREAS, BREAKFAST AREAS,
 KITCHEN AREAS AND THE LIKE. PLEASE SEE THAT SOME
 RECEPTS ARE BEING SHOWN IN AREAS WHICH WOULD APPEAR TO
 BE AREAS OF THE LIKE AS REFERENCED ABOVE, HOWEVER SOME
 OF THESE RECEPTS ARE BEING SHOWN ON LIGHTING CIRCUITS
 OF 15A'S ETC. PLEASE SEE THAT ANY OF THESE AREAS OF THE
 LIKE WILL BE REQUIRED TO CONTAIN THESE RECEPTACLES ON
 THE ONE OR MORE CIRCUITS AS NOTED.
 PLEASE ADJUST PLANS FOR PREVIOUS NOTE AND THIS NOTE.
  
 9) NOTE:PLEASE SEE ELEVATOR CORRIDOR ON 16.06 AND ANY
 POSSIBLEBUILDING CODE COMMENTS BASED ON DEAD-END
 CORRIDORS AND DISTANCES PERMITTED ETC WITH AND/ OR WITH
 OUT BEING SPRINKLED.
 THIS IS ONLY BEING NOTED AS IF THE LAYOUT HAS TO CHANGE
 FOR ANY REASON, THIS WILL AFFECT THE ELECTRICAL PLANS.
  
 10) NOTE: PLEASE PROVIDE NOTE ON FIRST FLOOR MAIN
 ELECTRICAL ROOM PLANS WHICH WILL REQUIRE DOOR TO
 CONTAIN PANIC HARDWARE.
 110.26/90.4
  
 11) NOTE: PLEASE SEE THE VOLTAGE DROP FOR 30A CU'S, AT
 THIS TIME CAN NOT BE VERIFIED. PLEASE SEE SOME UNITS
 INDICATE #10 ALREADY YET THESE WILL BE OVER 75FT AND
 THERE IS NO NOTE FOR THESE UNITS TO UPGRADE TO #8 OR ?
 PLEASE ADJUST AND PROVIDE ADDITIONAL INFORMATION. FBC
 104.2.1.2 FOR ADDITIONAL INFORMATION.
 NEC 310.16, 240.4 ETC.
  
 12) NOTE: PLEASE SEE NOTES ABOVE WHICH REQUESTS FOR THE
 RISER NOTES TO CORRELATE WITH THE DESIGNATIONS ON
 RISER. PLEASE SEE NOTE #1. PLEASE SEE THIS SAME NOTE IS
 PROVIDED FOR METER CENTERS, HOWEVER THE NEW MAINS WILL
 NOT BE METER CENTERS.
 104.2.1.2 FBC ADMIN SECTION.
  
 13) NOTE: PLEASE PROVIDE A DETAIL FOR THE ROOF TOP
 DISCONNECT AS BEING NOTED AND HOW THIS WILL BE MOUNTED?
 (NOT TO UNIT)
 440.11. THIS CAN BE A TYPICAL DETAIL.
  
 14) NOTE: PLEASE SEE ATTACHED COPY OF FLORIDA STATUTES
 553.80(2)(B) WITH RESPECT TO REPEAT CODE COMPLIANCE
 COMMENTS. THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
 ** PLEASE KNOW ONE SET OF EACH OF THE PLANS FOR EACH
 BUILDING WILL BE RETAINED BY THIS OFFICEE.
  
 15) NOTE: PLEASE SEE COMPLETE CLUBHOUSECIRCUITING AS
 NOTED IN OTHER REVIEW COMMENTS, HOWEVER THIS IS BEING
 NOTED FOR THE CLUBHOUSE TO EMPHASIZE THIS AND ALL ROOM
 AND AREA DESIGNATIONS.
 FBC 104.2.1.2 ADMIN SECTION AND NEC FOR REVIEW OF
 AREAS. 700.12E AS NOTED ABOVE ETC.
  
 16) NOTE: PLEASE SEE 2ND FLOOR EXIT LIGHT OUTSIDE ON
 THE BUILDING IC SIDE WHICH PLACES THIS EXIT SIGN AT THE
 EGRESS DOORS FROM CLUBHOUSE. AN OCCUPANT IN THIS
 CORRIDOR WOULD READ THIS AS AN EXIT IN WHICH DOORS OPEN
 IN THE DIRECTION OF TRAVEL ETC.
 PLEASE REVIEW THE LOCATIONS AS SHOWN AND SEE POSSIBLE
 FIRE REVIEW NOTES.
  
 17) NOTE: PLEASE SEE FIRE REVIEW COMMENTS WITH RESPECT
 TO ADDRESSING OF BUILDING AND THE LOCATION OF THE
 REQUIRED FIRE ALARM CONTROL PANEL. PLEASE SEE THE
 LOCATIONS WILL BE REQUIRED BY THE FIRE MARSHAL'S
 OFFICE. PLEASE SEE PLANS CURRENTLY SEEM TO SHOW
 MULTIPLE LOCATIONS WHICH ARE UNCLEAR AT THIS TIME. THIS
 COMMENT IS BEING MADE AS THIS WILL AFFECT THE
 ELECTRICAL PLANS.
  
 18) NOTE: PLEASE NOTE/INDICATE THE FEEDERS ON THE RISER
 FROM THE NEW MAINS OUT TO THE METER CENTERS. PLEASE
 KNOW AS THE METER CENTER SCHEDULE SEEMS TO INDICATE
 GROUNDING ELECTRODE AND NOT EQUIPMENT GROUNDING
 CONDUCTOR, IT IS UNCLEAR WHICH TO USE. A NOTE OF WHICH
 TO USE AND WHEN, OR ADJUSTING THE RISER AND RISER NOTES
 WOULD PROVIDE MORE DETAILS FOR THIS.
 PLEASE SEE NOTES WHICH WILL REQUIRE A "FLOATING
 NEUTRAL" AFTER THE FIRST MEANS OF DISCONNECT WILL BE
 REQUIRED ON RISER SHEETS. PLEASE SEE 250.6 AND 250.24B
 AS NEW MAINS ARE INSTALLED AND THE METERS WHICH CONTAIN
 NEUTRALS MAY NOT BE BONDED AFTER THE FIRST MEANS OF
 DISCONNECT.
 FBC 104.2.1.2 ADMIN SECTION.
  
 19) NOTE: PLEASE SEE POWER FOR ELEVATOR IS BEING NOTED
 ON THE FORTH FLOOR PLANS? PLEASE ALSO SEE SEVERAL
 LOCATIONS WHICH PLACE THIS NOTE FOR POWER AND EQUIPMENT
 IN THE EGRESS CORRIDORS?
 PLEASE ALSO CORRELATE WITH THE FIFTH FLOOR PLANS AS
 THIS SEEMS TO BE THE LOCATION(S) IN WHICH EQUIPMENT
 WILL BE INSTALLED IN A ELEVATOR EQUIPMENT CLOSET.
 PLEASE SEE PREVIOUS NOTES WITH RESPECT TO CIRCUITING
 FOR BRANCH CIRCUITS WHICH COULD NOT BE LOCATED AS
 REQUIRED.
 NEC 620
 FBC ADMIN SECTION 104.2.1.2 FOR CLARIFICATION.
  
 20) NOTE: PLEASE INDICATE CLARIFY LOCATION OF THE PANEL
 "P".
 110.26, 240.24, 408.7 ETC
  
  
 *** PLEASE KNOW THAT THERE MAY BE NEW COMMENTS ON THE
 NEXT REVIEW DUE TO INFORMATION NOT SUBMITTED OR
 COORDINATION OF PLANS/INFORMATION SUBMITTED FOR REVIEW
  
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY HAVE AN AFFECT ON ELECTRICAL PLANS.
  
 ** PLEASE KNOW, A TYPE WRITTEN RESPONSE LETTER FROM
 DESIGN PROFESSIONAL(S) FOR EACH COMMENT ON HOW/WHERE
 CORRECTIONS ARE MADE OR IF COMMENTS ON REVIEW WILL HELP
 IN EXPEDITING THE PLAN REVIEW PROCESS. THIS WAS DONE,
 AND SHOULD BE DONE FOR THIS REVIEW AS WELL.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
2007-01-01 09:16:542007-01-01 09:16:54
 IN ELEC FOR REVIEW, IN PROGRESS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-26 Cont ID  
Sent By dpalmer Date 2005-12-26 Time 13:15 Rev Time 0.00
Received By dpalmer Date 2005-12-25 Time 17:52 Sent To  
Notes
2005-12-26 00:00:00REVIEW IN PROGRESS
 ************ UNSAT ************
  
 COURTNEY LAKES
 N. CONGRESS.
  
  
 1)NOTE: PLEASE SUBMIT COMPLETED PLANS
 BOUND TOGETHER IN APPROPRIATE FASHION.
 PLEASE SEE ALL SHEETS WERE SUBMITTED
 LOOSELY AND NOT IN BOUND STES.
  
 2)NOTE: PLEASE BE SURE ALL PLANS ARE
 SIGNED, DATED AND SEALED BY ALL DESIGN PROFESSIONALS AS
 REQUIRED UDNER FS
 481.221 AND 471.025.
 (PLEASE SEE A-SHEETS, ONLY SIGNED).
  
 3)NOTE: PLEASE BE SURE TO CORRECT THE
 CURRENT NEC/ NFPA-70 IN EFFECT.
 PLEASE KNOW, AS OF JULY 1ST, 2003 THE
 STATE OF FLORIDA ADOPTED THE 2002
 NFPA-70 (NEC). PLANS REFERENCE 1999.
 PLEASE SEE SOME ELECTRICAL COMMENTS
 WHICH WILL AFFECT THIS.
 PLEASE SEE NEXT COMMENT WITH RESPECT TO
 PERMITS APPLIED FOR UNDER THE 2001 FBC
 BEFORE OCT 1ST, 2005 AND PERMITS ON OCT
 1ST, 2005.
  
 4)NOTE: PLEASESEE THAT THREE SEPARATE
 PERMIT APPLICATIONS WERE SUBMITTED AND
 NOTED FOR BLDG'S 1,2 AND 3, HOWEVER
 PLANS SHOWS BLDG TYPES 1.2&3 STRUCTUALLY
 ONLY ONE BUILDING.
 PLEASE SEE PERMIT APPLICATIONS ALL
 REFLECT THIS ONE 450 UNIT BLDG.
 PLEASE SEE THIS CONTRADICTS THE "PHASING
 PLAN" SUBMITTED ON A1.04 AS THIS PHASING
 PLAN INDICATES WORK ON BLDGS 4 AND 5
 BEFORE COMPLETION OF BLDGS 1, 2 AND 3.
 PLEASE SEE COMMENTS FROM BLDG, FIRE AND
 OTHER REVIEWERS, ASCERTIFICATES OF
 OCCUPANCY(CO'S) FOR THESE CAN NOT BE
 GRANTED IN THIS ORDER AS THE FIRST
 "STRUCTURED BLDG"(1,2&3) WOULD NOT BE
 COMPLETE.
 PLEASE ALSO SEE COMMENTS WITH RESPECT TO "TEMPORARY
 CO'S" WHICH MAY ALLOW
 OCCUPANCY OF SOME PARTS OF BLDGS,
 HOWEVER THESE TCO'S ARE ONLY GOOD FOR 30
 DAYS AND A MAX OF 3 TCO'S MAY ONLY BE
 GRANTED BY THE BLDG OFFICAL.
 PLEASE KNOW, IN ANY CASE, ALL LIFE
 SAFTEY, FIRE PROTECTION SYSTEMS, FIRE
 SPRINKLERS (FULLY CHARGED),ELECTRICAL
 SYSTEMS ETC SHALL BE COMPLETE IN THE
 BASE BLDG FOR BLDG TYPE 1, 2& 3 BEFORE A
 TCO,/CO CAN BE GRANTED.
  
 *************************************
 ALSO NOTED THAT BLDG'S TYPE 4 AND 5
 WHICH ARE SEPARATE STRUCTURES AND
 INDEPENDANT OF EACH OTHER WERE NOT
 SUBMITTED FOR PERMIT.
 PLEASE SEE ALL PERMITS SUBMITTED AFTER
 OCT. 1ST, 2005 SHALL FALL UNDER THE
 2004 FBC, WITH ALL OTHER CODES ADOPTED
 BY SAID CODE AND STATE OF FLORIDA.
  
 ************************************
 PLEASE SEE COMMENTS FROM OTHER
 REVIEWER(S) WITH RESPECT TO THIS.
  
 *************************************
 PLEASE ALSO SEE NEXT COMMENT WITH
 RESPECT TO THE MAINS, SERVICES, AND
 METER RMS AS PROPOSED.
 ** SEE ALL NOTES FROM ALL REVIEWERS
 WHICH MAY ALSO AFFECT THIS SEQUENCE OF CONSTUCTION.
  
 5)NOTE: PLEASE SEE METER RMS AS SHOWN
 WOULD BE OK, HOWEVER STRUCTURE AS SHOWN
 FOR BLDG TYPE 1,2 AND 3 (ONE BLDG) WOULD
 REQUIRE MAINS TO BE GROUPED.
 90.4,230.2,230.70,230.72,230.76,230.79
 ETC.
 BLDG'S LARGE ENOUGH TO CONTAIN MORE THAN
 ONE SERVICE AT SEPARATE LOCATIONS SHALL
 BE DIVIDED INTO SECTIONS AND SHALL HAVE
 THOSE SECTIONS DIVIDED BY "FIRE WALLS".
 PLEASE SEE FBC FOR DEFINITION OF "FIRE
 WALLS".
 PLEASE KNOW, STRUCTURE CONSTRUCTED AS
 SHOWN IN PLANS, WOULD REQUIRE MAIN
 DISCONNECTS GROUPED, WHICH WOULD THEN
 IN-TURN FEED METER ROOMS.
 OTHER DESIGN CHANGES IN THE "ONE BLDG"
 MAY ALSO PERMIT INDIVIDUAL SERVICES.
 PLEASE SEE BLDG TYPE #4 AND #5 ARE SHOWN
 AS SEPARATE BLDGS WITH STAND ALONE
 SERVICES AND ALL MAINS ARE GROUPED.
 PLEASE KNOW THAT BLDGS 4 AND 5 WILL HAVE
 REVIEWS DONE UNDER THOSE PERMIT
 APPLICATIONS.
 ** PLEASE SEE SOME OF THESE COMMENTS
 WOULD ALSO APPLY.
  
 6)NOTE: PLEASE COMPLETE ALL CIRCUITING
 ON PLANS IN ORDER TO REVIEW CODE
 COMPLIANCEFOR AREAS OF UNITS AND
 COMMON AREAS.
  
 7)NOTE: PLEASE PROVIDE ROOM AND AREA
 DESIGNATIONS ON PLANS, INCLUSIVE OF ALL
 UNITS AND COMMON AREAS.
 REVIEW FOR SOME CODE COMPLIANCE ITEMS
 CAN NOT BE DONE AT THIS TIME.
  
 8)NOTE: PLEASE PROVIDE COMPLETE
 PHOTOMETRICS FOR ALL COMMON AREAS,
 GARAGE AREA,COMMON AREA CORRIDORS,
 STAIR TOWERS ETC.
 PLEASE SEE 2003 NFPA-101 7.8.1.3 AND
 7.9.2 WHICH REQUIRES A MIN OF 10FT
 CANDLES FOR STAIR TOWERS UNDER NORMAL
 OPERATION AS WALK SURFACE AND A MIN OF
 1FT CANDLE AT WALK SURFACE UNDER
 EMERGENCY CONDTIONS. PLEASE ALSO SEE
 OTHER WALK AREAS, GARAGE, CORRIDORS ETC
 AND THE MIN OF 1FT CANDLE.
 **PLEASE SEE PALM BEACH COUNTY SECURITY
 CODE ORDIANCE WITH RESPECT TO MIN DESIGN
 OF PARKING LOT LIGHTING LEVELS UNDER
 NORMAL CONDITIONS. (ONLY NOTED FOR
 DESIGN)NOT REQUIRED. PLEASE SEE ANY
 REQUIREMENTS FROM INS CARRIER WHICH
 REQUIE A MIN LEVEL OF LIGHTING.
 ** PLEASE SEE PHOTOMETRICS OR SITE PLAN
 WAS NOT SUBMITTED FOR PROPOSED POOL
 AREA. THE POOL STRUCTURE IS REQUIRED TO
 BE UNDER A SEPARATE PERMIT. PLEASE KNOW,
 THE PHOTOMETRICS FOR POOL AREA WILL BE
 REQUIRED AND WILL ALSO BE REQUIRED TO BE
 REVIEWED AND STAMPED BY THE PALM BEACH
 COUNTY HEALTH DEPT FOR ANY PROPOSED
 NIGHT-TIME SWIMMING.
  
 7)NOTE: PLEASE SEE NO "ELECTRICAL
 SITE-PLAN" WAS SUBMITTED FOR ANY SITE
 LIGHTING, LANDSCAPE LIGHTING ETC.
 PLEASE KNOW, IF NOT SUBMITTED UNDER THIS
 PERMIT AND VALUES ADJUSTED ACCORDINGLY,
 SSEPARATE PERMIT , PLANS AND FEES WILL
 BE REQUIRED FOR ALL SITE LIGHTING,
 LANDSCAPE LIGHTING WORK.
 ** ALSO NOTE: IN THAT COMPLETE WIND
 LOADING CALCULATIONS FOR LT POLES
 INCLUSIVE FO THE ATTACHMENT OF LT
 FIXTURES WILL BE REQUIRED TO BE
 SUBMITTED WITH PLANS AND PERMIT
 APPLICATION FOR REVIEW.
  
 8)NOTE: PLEASE INCLUDE AN EMERGENCY
 BATTERY BACK UP LT OF SOME SORT IN ALL
 ELECTRICAL ROOMS, FIRE PUMP ROOM,
 ELEVATOR MACHINE RMS. SOME ARE SHOWN,
 BUT NOT ALL.
 7.8,7.9,700.16 ETC
  
 9)NOTE: PLEASE SEE 620.23, AND 620.24
 FOR REQUIRED DEDICATED BRANCH CIRCUITS
 FOR ELEVATOR PITS, AND ELEVATOR MACHINE RMS/EQUIPMENT
 AREAS.
 PLEASE ADJUST HOUSE PANELS AS NEEDED.
  
 10)NOTE: PLEASE SEE ELECTRICAL RISER
 SHOULD "NOTE" FIRE PUMP AS DIESEL AS
 NOTED ON FP SHEETS.
 PLEASE SUBMIT ALL MANUAFCTURES SPEC/CUT
 SHEETS FOR FIRE PUMP CONTROLLER AS
 REVIEW FOR CODE COMPLIANCE UNDER 2002
 NFPA-20 IS REQUIRED.
 PLEASE ALSO SUBMIT ALL MANUFACTURES
 SPECS/CUT SHEETS FOR FUEL TANK.
 PLEASE SEE NFPA-20 9.6.2.2 AS THE FUEL
 CAPACITY IS REQUIRED TO BE SIZED BASE ON
 THE 100% RATED LOAD FOR A MIN OF 8HRS,
 OT TIME SO DETERMIND BY THE FIRE
 MARSHAL'S OFFICE DEPENDING ON OCCUPANCY.
 FUEL SYSTEMS WILL BE UNDER OTHER TRADE
 REVIEW(S). (FIRE AND MECH).
  
 11)NOTE: PLEASE INCLUDE ALL MIN
 CONDUCTOR SIZES ON ALL PANELS,UNITS AND
 HOUSE PANELS. REVIEW FOR THESE ITEMS OF
 CODE COMPLIANCE CAN NOT BE DONE AT THIS
 TIME. 310.16,240.4,215.5
  
 12)NOTE: PLEASE SEE GARAGE/HOUSE
 LIGHTING BEING INDICATED ON 30A AND 50A
 CIRCUITS.
 PLEASE SEE CODE DOES LIMIT THE OCP FOR
 UNIT FIXTURES FOR PROTECTION OF FIXTURES
 ON A BRANCH CIRCUIT.
 PLEASE ADJUST CIRCUITING AS NEEDED.
 PLEASE ALSO SEE A FIXTURE SCHEDULE
 CONTAINING WATTAGES, VOLTAGES ETC WAS
 NOT SUBMITTED.
 PLEASE VERIFY IF THESE UNIT FIXTURES ARE
 RATED TO HAVE OCP AT ABOVE MENTIONED.
 240.4, 310.16 ETC
  
 13)NOTE: PLEASE CORRELATE ALL OCP
 DEVICES FOR UNITS AND FEEDERS BEING
 LISTED IN "RISER NOTES".
 PLEASE SEE SOME FEEDERS SHOWN AS #4'S ON
 125A BREAKER?
 SEE 310.16,240.4
 PLEASE SEE OCP FOR ALL UNITS IS LISTED
 AS 125A'S.
 SEE NEXT COMMENT.
  
 14)NOTE: PLEASE SEE MAX OCP TO BE SIZED
 FOR PANELS/EQUIPMNET BEING FED BY SAID
 OCP.
 PLEASE SEE MANY UNIT PANELS ARE SHOWN AS
 100A MLO, WITH 125A OCP AS LISTED ON
 RISER ETC.
 PLEASE ALSO SEE RISER NOTE #4 WHICH
 INDICATES 125A 2-POLE ETC, HOWEVER
 PLEASE SEE RISER AS THIS NOTE #4 COULD
 NOT BE LOCATED. (APPEARS TO BE
 MISPRINTED FOR "NOTE#7" ON RISER)
 240.4,408,310.16,215.5 ETC.
  
 15)NOTE: PLEASE SEE 16.26 AND 16.27
 WHICH CONTAIN THE SAME EXACT "HOUSE
 PANELS" ?? H1, H1A , H2, AND H2A.
 PLEASE SEE SHEET 16.27 MAY BE DELETED IF
 PANELSCHEDULES FOR "CA" AND"CB" ARE
 MOVED TO 16.26.
  
 16)NOTE: PLEASE CORRELATE LOADS SHOWN
 FOR H1A WITH LOAD SHOWN ON H1.
 THIS DOES NOT MATCH.
  
 17)NOTE: PLEASE CORRELATE LOADS ON PANEL
 H2A WITH LOADS SHOWN ON H2>
 THESE ALSO DO NOT MATCH.
  
 18)NOTE: PLEASE SEE THESE SHEETS ALSO
 REFERENCE "ARC FAULT" PROTECTION FROM
 THE 1999 NEC, WHICH ONLY REQUIRED
 PROTECTION OF RECEPTS.
 PLEASE SEE 2002 NEC WHICH REQUIRES
 PROTECTION FOR ALL "OUTLETS" IN BEDRMS.
 THIS IS INCLUSIVE OF RECEPTS, LTS, FANS,
 SMOKE DETECTORS ETC.
 PLEASE SEE NOTE ON UNIT PLANS AND
 ADJUST.
  
 19)NOTE: PLEASE CORRELATE LOADS , UNITS,
 PANELS, AND BUILDING/METER LOAD
 CALCULATIONS:
 A) PLEASE SEE PANEL SCHEDULE/LOAD
 CALCULATIONS FOR UNIT "B-3" SHOWN ON
 16.26, HOWEVER THIS UNIT TYPE OR LOADS
 COULD NOT BE LOCATED ON BLDG LOAD
 CALCULATIONS ON 16.25?
 B)PLEASE ALSO SEE THE SAME COMMENT ABOVE
 FOR UNIT "C-2" WHICH IS ALSO SHOWN ON
 16.26 BUT NOT IN CALCS ON 16.25??
 ** PLEASE ADJUST ALL AS NEEDED.
  
 20)NOTE: PLEASE INCLUDE THE REQUIRED
 FOOTER STEEL ON THE GROUNDING ELECTRODE
 RISER DETAIL.
 PLEASE ALSO SHOW ON RISER.
 250.50.
  
 21)NOTE: PLEASE PROVIDE A DETAIL/NOTE
 FOR ALL RACEWAY SEALS AS REQUIRED PER
 230.8
  
 22)NOTE: PLEASE SEE RISER WHICH SHOWS A
 POOL PANEL BEING FED FROM PANEL "CA",
 HOWEVER PANEL "CA" , DOES NOT SHOW SUCH
 PANEL.
 215.5
  
 23)NOTE: PLEASE PROVIDE "FUTURE" POOL
 PANEL ON RISER AND PANEL SCHEDULE.
 215.5
  
 24)NOTE: PLEASE SEE RISER NOTE #12 WHICH
 IS SHOWN FOR FEED FROM PANEL "CA" TO
 PANEL "CB". THIS IS SHOWN AS 500MCM'S,
 ALTHOUGH OCP ON CA IS ONLY SHOWN AS
 200A'S? THIS IS PERMITTED, HOWEVER THE
 200A DEVICE MAY NOT ACCEPT 500MCM'S.
 215.5
  
 25)NOTE: PLEASE SEE REDLINED ITEMS ON
 PLANS FOR "EQUIPMENT GROUNDING
 CONDUCTORS" BEING SHOWN BEFORE THE FIRST
 MEANS OF DISCONNECT.
 PLEASE SEE 250.6, 250.24.
 PLEASE SEE HOUSE METER #2, SEE RISER
 NOTE #12 AND #13 SHOWS AN "EQUIPMENT
 GROUNDING" CONDUCTOR WHICH IS
 PARALLELING THE NEUTRAL.
  
 26)NOTE: PLEASE SEE MIN OCP FOR WATER
 HEATERS TO BE SIZED AT 125%.424.13
 PLEASE SEE UNITS CONTAINING 5KW WH @
 208V'S WOULD INCREASE THIS BRKR TO A
 2-P35A. PLEASE ALSO ADJUST ANY AWG PER 310.16,240.4
  
 27)NOTE: PLEASE SEE UNIT LOAD
 CALCULATIONS SHOWS THE LOADS FOR A/C'S
 AFTER THE PERMITTED DERATING, HOWEVER
 PLEASE SHOWLOADS FOR THESE BEFORE
 DERATING.
 PLEASE BE SURE TO CORRELATE WITH LOADS
 FOR COOLING AND HEAT ON MECHANICAL PLAN.
 215.5
  
 28)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 PLEASE SEE 2002 NFPA-72 11.5.3.1
 PLEASE ADJUST NOTE FOR SD'S ON PLANS AS
 SD'S ARE REQUIRED 3' FROM BATH/KTICHEN
 DOORS, 3' FROM SUPPLY AIR DIFFUSERS, 5'
 FROM R/A GRILLES AND 20' FROM KITCHEN
 COOKING APPLIANCES. W/ EXCEPTIONS FOR
 DISTANCES FROM COOKING APPLIANCES.
 (PHOTOELECTRIC AND RESETTING TYPE)
 ** PLEASE SEE PRIVIOUS NOTES WITH
 RESPECT TO ARC FAULT PROTECTION OF SD'S
 AND CIRCUTING.
  
 29)NOTE: PLEASE SEE ALL RECEPTS IN
 CLUBHOUSE KITCHEN PER 210.8B3 WHICH
 REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT RECEPTACLES IN
 NONDWELLING-TYPE KITCHENS
 TO BE GFCI PROTECTED. THIS REQUIREMENT
 APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE,
 WHETHER OR NOT THE RECEPTACLE SERVES
 COUNTERTOP APPLIANCES.
  
 30)NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF ALL EM/EXT LTS, WHICH
 REQUIRES THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 THIS IS NOTED ON SOME SHEETS, HOWEVER
 CIRCUITING FOR THESE IS NOT SHOWN.
 215.5
  
 31)NOTE: PLEASE CLARIFY THE "CT" AS
 LABLED ALONG KITCHEN RECEPTS. THIS
 ABBREVIATION COULD NOT BE LOCATED ON
 SYMBOL LEGEND?
  
 32)NOTE: PLEASE SEE 210.52C1-C5 FOR
 REQUIRED GFI RECEPTS ALONG KTICHEN
 COUNTERSPACE. PLEASE SEE SOME ARE SHOWN
 ON WHAT APPEARS TO BE A WALL ON THE
 OTHER SIDE OF THE COUNTERSPACE.
 PLEASE SEE B-2, B-4ETC.
 PLEASE SEE OTHER WHICH ARE REQUIRED TO
 BE WITHIN 2' OF THE END OF THE
 COUNTERSPACE/FROM SINK EDGE ETC.
 PLEASE SEE THESE AREAS REDLINED ON
 SHEETS.
  
 33)NOTE: PLEASE SEE WHAT APPEARS TO BE A
 RECEPT LOCATED IN THE CLOTHES CLOSET FOR
 PERHAPS A LV PLUG-IN TYPE TRANSFORMER?
 PLEASE KNOW, THE ONLY LOCATION A RECEPT
 IS PERMITTED IN A CLOTHES CLOSET FOR
 THIS PURPOSE, MUST BE LOCATED DIRECTLY
 ABOVE DOOR AWAY FROM COMBUSTIBLES.
 MANY PLUG-IN TYPE TRANSFORMERS BECOME
 VERY HOT AND HAVE MELTED OR CAUSED FIRES
 IN THIS JURISTICTION. PLEASE KNOW, MANY
 ITEMS IN A CLOTHES CLOSET ARE AN
 ACCELERANT.
 THESE RECEPTS MAY BE MOVED TO UTILITY RM
 IS SO DESIRED.
 110.26, 240.24, 90.4 ETC
  
 34)NOTE: PLEASE SEE RELDINED PLANS FOR
 ANY RECEPTS WHICH MAY BE REQUIRED PER
 210.52 (A-2). MOST ALL SPACING IS OK.
  
 35)NOTE: PLEASE MAKE NOTE FOR ALL MIN
 FAIR HOUSING ACT REQUIREMENTS FOR DEVICE
 HEIGHTS.
 24 CFR 100.205
 ** PLEASE KNOW, SOME REVIEW OF CODE
 COMPLIANT ITEMS MAY NOT BE DONE AT THIS
 TIME DUE TO SOME INFORMATION NOT ON
 PLANS.
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY HAVE AN AFFETC ON
 ELECTRICAL PLANS.
  
 ** PLEASE KNOW, A TYPE WRITTEN RESPONSE
 LETTER FROM DESIGN PROFESSIONL(S) FOR
 EACH COMMENT ON HOW/WHERE CORRECTIONS
 ARE MADE OR IF COMMENTS ON REVIEW WILL
 HELP IN EXPEDITING THE PLAN REVIEW
 PROCESS.
  
 ** PLEASE KNOW THAT A MEETING TO GO OVER
 FIRST COMMENTS FOR DESIGN/PHASING OF
 BLDGWITH ALL REVIEWERS IS SUGGESTED
 BEFORE PERHAPS SUBMITTING PLANS BACK FOR
 REVIEW.
 PLEASE KNOW, ALL REVIEWS AFTER THE 1ST
 FREE "RE-SUB" IS SUBJECT TO A 10% RESUB
 FEE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-12-25 00:00:00ONE ROLL IN ELECTRIC FOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2007-09-28 Cont ID  
Sent By rchokshi Date 2007-09-28 Time 14:20 Rev Time 0.00
Received By rchokshi Date 2007-09-28 Time 13:54 Sent To  
Notes
2007-09-28 14:19:55****FAILED*****
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
 2. PLEASE SHOW ON CIVIL DRAWING THE EXACT MAILING
 ADDRESS, BUILDING NAME, OR NUMBER, YOU TALKING ABOUT 3
 PERMITS, PLEASE IDENTIFY EACH BUILDING ON THE DRAWING.
 3.PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 4.PLEASE SHOW FINISH FLOOR ELEVATION ON DRAWING .
 PLEASE EXPLAIN IN DETERMINING FIRST FLOOR ELEVATION,
 PLEASE SHOW IN YOUR CALCULATION THAT YOU CONSIDERED
 CENTER LINE OF ROAD , FLOOD ZONE OF THIS SITE,& 5,10,
 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST
 FLOOR ELEVATION, PLEASE SHOW ALL THESE IN YOUR STORM
 WATER CALS.PLEASE ALSO SHOW ON DRAWINGS THE MAXIMUN
 AND MINIMUM PARKING LOT ELEVATIONS.
  
 5. PLEASE SHOW ON DRAWINGTHE SITE AREA, YOU ARE
 DEVELOPING FOR THIS PROJECT . PLEASE ALSO SHOW TOTAL
 PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT,
 LAKE,SIDEWALK, PARKING,BUILDING AREA ETC. MAKE SURE
 THESE AREAS SHOWN ON DRAWINGS MUST MATCH WITH AND USED
 IN STORM WATER QUALITY CALCULATIONS.
 6. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS.AFTER CONTROL
 STRUCTURE WHERE STORM WATER GOES??
 7. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN.
 8. PLEASE RESUBMIT A COPY OF SFWMD PERMIT,, & GEO TECH
 REPORT,STORM WATER CALS MUST BE APPROVED FROM 1000
 45TH STREET ENGINEERING SERVICES.
 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED.
 10. PLEASE KEEP SEPARATE CIVIL DRAWINGS SO I CAN REVIEW
 QUICK.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-01-19 Cont ID  
Sent By rchokshi Date 2007-01-19 Time 09:56 Rev Time 0.00
Received By rchokshi Date 2007-01-19 Time 09:52 Sent To  
Notes
2007-01-19 09:56:42PLEASE SUBMIT CIVIL PLANS FOR OUR REVIEW ALON WITH A
 COPY OF SFWMD PERMIT, GEO TECH REPORT, WATER QUALITY
 STORM WATER CALCULATIONS.
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2005-10-31 Cont ID  
Sent By mamini Date 2005-10-31 Time 10:51 Rev Time 0.50
Received By mamini Date 2005-10-31 Time 10:51 Sent To  
Notes
2005-10-31 00:00:00FAILED:
  
 1. PLEASE SUBMIT CIVIL PLANS FOR OUR
 REVIEW AND APPROVAL.NOTE THAT CIVIL
 PLANS FOR THIS WERE REVIEWED UNDER OLD
 PERMIT APPLICATIONS # 04021308,04021305,
 04021300 WHICH EXPIRED.COPY OF THE
 REVIEW NOTES INCLUDED FOR YOUR USE.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-11-07 Cont ID  
Sent By mwennerg Date 2007-11-07 Time 14:28 Rev Time 0.00
Received By mwennerg Date 2007-11-07 Time 14:28 Sent To  
Notes
2007-11-07 14:32:47***DENIED***
  
 COMMENTS FROM FIRST REVIEW HAVE NOT BEEN ADDRESSED.
 RESPONSE LETTER INDICATES COMMENT RESPONSES BELOW,
 HOWEVER NONE WERE PROVIDED. PLEASE REFER TO PAGE 35 OF
 RESPONSE LETTER.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-02-27 Cont ID  
Sent By mwennerg Date 2007-02-27 Time 15:20 Rev Time 0.00
Received By mwennerg Date 2007-02-27 Time 15:20 Sent To  
Notes
2007-02-27 15:30:33***DENIED***
  
 IN ORDER TO HELP EXPEDITE THE PLAN REVIEW PROCESS,
 PLEASE SEE THE FOLLOWING:
  
 1) PLEASE REFER TO THE FIRST FIRE REVIEW COMMENTS. MANY
 COMMENTS WERE ANSWERED OR ADDRESSED WITH COMMENT NOTED.
 THIS DOES NOT DEMONSTRATE THAT COMPLIANCE WILL BE MET.
 IT WOULD BE HELPFUL IF THE CHANGE OR ADDED NOTE IS
 CLEARLY SHOWN ON DRAWINGS, AND THE CORRECT SHEET NUMBER
 IS INDICATED. SOME RESPONSES WERE FOUND ON SHEETS THAT
 WERE DIFFERENT FROM WHAT WAS INDICATED IN THE RESPONSE
 LETTER. FOR EXAMPLE, COMMENT #1 INDICATES THAT
 REFERENCE HAS BEEN ADDED TO FP13.17, BUT WAS ACTUALLY
 FOUND ON A 1.02. PLEASE KNOW THAT IT IS UNDERSTOOD THAT
 SOME COMMENTS MAY BE ACKNOWLEDGED, BUT SHOULD BE SHOWN
 ON PLANS TO ELLIMINATE CONFUSION IN THE FUTURE DURING
 THE INSPECTION PROCESS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW(561) 805-6722
 FIRE PREVENTION(561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-12-27 Cont ID  
Sent By mwennerg Date 2005-12-27 Time 12:58 Rev Time 0.00
Received By mwennerg Date 2005-12-27 Time 12:58 Sent To  
Notes
2005-12-27 00:00:00******DENIED******
  
 1) NFPA 101 AND NFPA 1, 2003 EDITION
 SHALL BE REFERENCED.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER SYSTEM
 WHICH SHALL BE UL CERTIFIED FOR CENTRAL
 STATION SERVICE.
  
 3) PLEASE NOTE THAT INTENDED SCOPE OF
 WORK FOR THIS PROJECT IN RELATION TO THE
 PERMIT APPLICATIONS IS CONFUSING.
  
 4) WHENS PLANS ARE RESUBMITTED, PLEASE
 ASSURE THAT ALL SHEETS ARE BOUND
 TOGETHER AND ORGANIZED.
  
 5) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 6) STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 7) TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES 3 STORIES OR
 30' IN HEIGHT.
  
 8) IN REGARDS TO PHASING, PLEASE BE
 ADVISED THAT ALL LIFE SAFETY COMPONENTS
 MUST BE INSPECTED, TESTED AND APPROVED
 PRIOR TO OCCUPANCY OF BUILDINGS.
  
 9) PARKING AREAS MUST BE IN COMPLIANCE
 WITH APPLICABLE BUILDING CODES AND NFPA
 88A. MINIMUM TWO HOUR SEPARATION TO
 OTHER PARTS OF BUILDING IS REQUIRED.
  
 10) WET FIRE HYDRANTS TO BE OPERATION
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
  
 11) PLEASE NOTE THAT ALL LIFE SAFETY
 EQUIPMENT, FIRE SPRINKLER AND FIRE ALARM
 AND ALL OTHER BUILDING SERVICES SHALL BE
 SEPARATE IF BUILDINGS MEET THE CRITERIA
 FOR SEPARATE STRUCTURES.
  
 12) ALL ACCESS ROADS SHALL BE AT LEAST
 20' IN CLEAR , UNOBSTRUCTED WIDTH FOR
 EMERGENCY VEHICLES, AND SHALL MEET ALL
 OTHER REQUIREMENTS OF NFPA 1.
  
 13) PLEASE INDICATE ALL LOCATION OF FIRE
 HYDRANTS.
  
 14) NFPA 13, 2002 EDITION SHALL BE
 REFERENCED. SHT. A5.01.
  
 15) LOCKING KNOX BOX CAPS ARE REQUIRED
 ON FIRE DEPARTMENT CONNECTIONS.
  
 16) IN ADDITION TO ELECTRONIC SWITCHES,
 THE DOUBLE CHECK DETECTOR ASSEMBLIES
 SHALL BE SECURED WITH A CHAIN AND LOCK.
  
 17) AS NOTED ON SHT, A5.02, FIRE
 EXTINGUISHERS SHALL BE MOUNTED AT
 DISTANCES TO SATISFY THE 75' TRAVEL
 DISTANCE REQUIREMENT.
  
 18) ALL DOORS SHALL SWING IN THE
 DIRECTION OF TRAVEL WHEN SERVING AREAS
 WITH OCCUPANT LOADS OF GREATER THAN 50.
  
 19) ELEVATORS TO COMPLY WITH ASME A17.1.
  
 20) PENETRATIONS INTO , AND OPENINGS
 THROUGH STAIRWELLS SHALL BE LIMITED TO
 AND IN COMPLIANCE WITH NFPA 101, SECTION
 7.1.3.2.1 (6).
  
 21) PLEASE CLARIFY ALL EXIT DISCHARGING
 FROM STAIRWELLS THAT LEAD DIRECTLY TO
 THE OUTSIDE.
  
 22) SOME ACHITECTUAL DRAWINGS SHOW
 STAIRWELL DOORS, AND OTHERS DON'T.???
  
 23) THIS PERMIT APPLICATION PROCESS
 ILLUSTRATES 3 BUILDINGS AND OTHER
 BUILDINGS, 4&5 ARE SHOWN ON PLANS.
 PLEASE CLARIFY.
  
 24) PLEASE ILLUSTRATE THE TOTAL OCCUPANT
 LOAD FOR THE CLUBHOUSE.
  
 25) IN ADDITION TO THE ALREADY NOTED
 REQUIREMENTS FOR ADDRESSING, PLEASE NOTE
 THAT THE HEIGHT OF THE ADDRESS SHALL BE
 AT LEAST 3" IN HEIGHT FOR RESIDENTIAL
 BUILDINGS.
  
 26) PLEASE REFER TO DOOR SCHEDULE AND
 VERIFY CORRECT AMOUNT OF FIRE RATED
 DOORS. DOORS SERVINGS AREAS WITH
 OCCUPANT LOADS GREATER THAN 100 SHALL
 HAVE PANIC HARDWARE.
  
 27) FIRE PROTECTION SITE PLAN DOESN'T
 APPEAR COMPLETE ON SHT FP13.01.
  
 28) FIRE DEPARTMENT VALVES SHALL BE 2
 1/2" TO 1 1/2" REDUCER WITH CHAINS.
  
 29) MORE INFORMATION AND MANUFACTURER
 SPEC SHEETS REQUIRED FOR FIRE PUMP AND
 ASSOCIATED EQUIPMENT.
  
 30) FIRE PROTECTION SHEETS DON'T SHOW
 ANY FIRE SPRINKLER SYSTEM. ???? FIRE
 SPRINKLER DESIGN AND LAY OUT MUST BE
 ILLUSTRATED.
  
 31) IF A FIRE HYDRANT FLOW TEST HASN'T
 BEEN DONE WITHIN ONE YEAR, ANOTHER TEST
 WILL BE REQUIRED FOR FIRE SPRINKLER
 CALC. PLEASE CONTACT THE BUREAU OF FIRE
 PREVENTION AT (561) 805-4724.
  
 32) PLEASE INDICATE ALL SMOKE DETECTOR
 LOCATIONS IN ACCORDANCE WITH NFPA 101,
 SECTION 30.3.4.5.
  
 33) EXIT LIGHTS TO BE MOUNTED AT
 DISTANCES NOT TO EXCEED 100'. IT APPEARS
 THAT MORE EXIT SIGNS ARE NEEDED IN
 CORRIDORS.
  
 34) FIRE ALARM SHALL BE CLASS A, STYLE D
 OR FULLY ADDRESSABLE.
  
 35) ARE SMOKE DETECTORS TIED INTO THE
 FIRE ALARM SYSTEM PLANNED FOR CORRIDORS?
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-08-05 Cont ID  
Sent By amckenzi Date 2008-08-05 Time 09:28 Rev Time 0.00
Received By amckenzi Date 2008-08-05 Time 09:28 Sent To  
Notes
2008-08-05 09:29:13TO EXTEND APPLICATION UNTIL 11/5/08 PER NKM/AMM

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-14 Cont ID  
Sent By adarroug Date 2007-08-14 Time 14:25 Rev Time 0.00
Received By adarroug Date 2007-08-14 Time 14:25 Sent To  
Notes
2007-09-07 16:15:56TO "COMM" BD#55/PLANS ON RACK--15 ROLLS
2007-08-14 14:25:47WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-29 Cont ID  
Sent By spalmer Date 2006-11-29 Time 19:31 Rev Time 0.00
Received By spalmer Date 2006-11-29 Time 19:31 Sent To  
Notes
2006-12-08 15:28:00TO "COMM" BD#41--3 APPL. PLANS ON RACK--7 ROLLS
2006-11-29 19:32:05WAITING FOR "COMM" BOARD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-31 Cont ID  
Sent By adarroug Date 2006-08-31 Time 11:32 Rev Time 0.00
Received By adarroug Date 2006-08-31 Time 11:32 Sent To  
Notes
2006-08-31 00:00:00WAITING FOR "COMM" BD-ROLLS BY MIRELLE'S
 CUBE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-03-03 Time   Rev Time 0.00
Received By adarroug Date 2005-10-03 Time 16:33 Sent To  
Notes
2005-10-12 00:00:00TO "COMM" BD#49/PLANS ON RACK
2005-10-03 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-10-04 Cont ID  
Sent By rregueir Date 2007-10-04 Time 18:15 Rev Time 0.00
Received By rregueir Date 2007-09-25 Time 14:43 Sent To  
Notes
2007-10-04 17:42:29REVIEW #: 3
 ACTION: DENIED
  
 FBC 2001 CODE FAMILY
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NOTE: THERE HAVE BEEN SIGNIFICANT CHANGES AS WELL AS
 PAGES ADDED TO PLANS. THE LEVEL OF CHANNGES REQUIRES A
 THOROUGH REVIEW OF MECHANICAL PLANS IN THEIR ENTIRETY.
 ANY COMMENT FROM PREVIOUS REVIEWS NOT REPEATED IN THIS
 REVIEW SHALL BE CONSIDERED TO HAVE BEEN ADEQUATELY
 ADDRESSED.
  
 1. M15.01 THRU M15.03: R/A JUMPERS FROM BEDROOMS ARE
 NOT SIZED TO MEET THE BALANCED R/A EXCEPTIONS OF FBC,M
 601.4. ALL DROPS INTO A MASTER SUITE SHALL BE INCLUDED
 PER EXCEPTION #3. THE MINIMUM SIZE JUMPER NEEDED FOR 7
 INCH AND 4 INCH ROUND DROPS IS 77 SQUARE INCHES. THE 9
 INCH ROUND SHOWN ON PLANS PROVIDES 63.6 SQUARE INCHES.
 A MINIMUM 10 INCH ROUND DUCT IS REQUIRED TO MEET
 EXCEPTION #1. UNLESS JUMPERS AND TRANSFERS ARE DESIGNED
 TO MEET THESE EXCEPTIONS, A FIELD TEST WILL BE REQUIRED
 AT FINAL INSPECTION TO VERIFY A DIFFERENTIAL PRESSURE
 OF 0.01 IN. W.C. OR LESS ACROSS THE CLOSED DOOR IN
 ACCORDANCE WITH THIS SECTION.
  
 2. M15.01 THRU M15.03: NOTE 10 TABLE FOR TRANSFER
 GRLLS, SIZES SHOWN ARE NOT IN COMPLIANCE WITH FBC,M
 601.4 EXCEPTION #2. SEE COMMENT 1 ABOVE FOR
 REQUIREMENTS IF TRANSFERS ARE NOT DESIGNED TO MEET THE
 EXCEPTIONS UNDER THIS SECTION.
  
 3. M15.01 THRU M15.03: KEY NOTE #9, NO INFORMATION WAS
 PROVIDED REGARDING DRYERS OR INSTALLATION INSTRUCTIONS
 AS STATED IN THE NOTE. PROVIDE INFORMATION NEEDED TO
 SHOW COMPLIANCE WITH FBC,M 501.4 AND KEY NOTE #9.
  
 4. M15.01: THE CONFIGURATION OF THE AC CLOSET IN
 APARTMENT A3 IS DIFFERENT FROM THE TYPICAL MOUNTING
 DETAIL SHOWN ON M15.22. PROVIDE DETAIL FOR THIS
 INSTALLATION SHOWING HOW DUCTED RETURN TO GRILL (SEE
 NOTE 6 ON M15.01) WILL WORK WITH A WATER HEATER UNDER
 THE AHU. ALSO, SHOW HOW O.A. DUCT IS TO TERMINATE IN
 CLOSET.
  
 5. M15.01 THRU M15.03: ALL APARTMENTS EXCEPT A3 CALL
 FOR FULLY LOUVERED DOORS ON A/C CLOSETS FOR RETURN AIR.
 ARCHITECTURAL FLOOR PLANS A5.50 THRU A5.53 SHOW DOORS
 AS U02 AND U-18. DOOR SCHEDULE ON A-9.02 SHOWS THESE TO
 BE "J" TYPE DOORS, WHICH ARE SOLID 6-PANEL DOORS.
 COORDINATE PLANS AND SHOW HOW AIR IS TO BE RETURNED TO
 A/C CLOSETS. FBC,M 601.4
  
 6. M15.04: FIRST AND SECOND FLOOR AREAS, BASED ON LIFE
 SAFETY PLANS A1.20 AND A1.21 ALONG WITH FLOOR PLANS
 A5.07 AND A5.71 THERE ARE NUMEROUS LOATIONS WHERE DUCTS
 ARE PENETRATING RATED WALL ASSEMBLIES. SHOW OPENING
 PROTECTIVES AT ALL LOCATIONS WHERE DUCTS PENETRATE
 RATED ASSEMBLIES. BE SURE TO COOORDINATE WITH
 ARCHITECTURAL PLAND. FBC,M 607.1.2 AND 607.6
  
 7. M15.05 THRU M15.08 AND M15.11: KEY NOTE #1 CALLS FOR
 3/4 INCH PVC FROM EACH AHU TO CONDENSATE RISER. PVC
 SHALL NOT BE LOCATED IN A/C CLOSETS USED AS PLENUMS PER
 FBC,M 602.2.1. ALSO, CONDENSATE LINES AS SHOWN ON PLANS
 WILL REQUIRE A SIGNIFICANT CHANGE IN ELEVATION TO
 MAINTAIN A UNIFORM ALIGNMENT AND SLOPE IN ACCORDANCE
 WITH FBC,M 307.2.2 DUE TO THE LONG HORIZONTAL RUNS
 SHOWN IN GARAGE AREA. PROVIDE AN ELEVATION VIEW DETAIL
 SHOWING THE FEASIBILITY OF THIS CONFIGURATION WHILE
 TAKING INTO ACCOUNT STRUCTURAL ELEMENTS AND REQUIRED
 CLEARANCES IN THE GARAGE. THE AREA CHOSEN FOR THIS
 DETAIL SHOULD INCORPORATE A "WORST CASE" CONDITION. FBC
 104.2.1.2
  
 8. M15.22: CONDENSATE TRAP DETAIL FOR NON-DUCTED RETURN
 UNITS, THE SECONDARY DRAIN LINE FROM THE AUXILIARY
 DRAIN PAN SHALL NOT BE CONNECTED TO THE PRIMARY
 CONDENSATE RISER. A SEPARATE DRAIN LINE SHALL EXTEND
 FROM THE PAN TO A CONSPICUOUS POINT AND SERVE AS AN
 ALARM WHICH INDICATES THAT THE PRIMARY DRAIN IS
 RESTRICTED.AS AN ALTERNATIVE TO A SEPARATE DRAIN
 LINE, AN APPROVED WATER LEVEL DETECTOR OR FLOAT SWITCH
 DEVICE SHALL BE USED TO CONTROL OVERFLOW BY
 AUTOMATICALLY SHUTTING DOWN THE EQUIPMENT OR APPLIANCE
 THAT PRODUCES THE CONDENSATE. THE FLOAT SWITCH ON THE
 SECONDARY DRAIN OUTLET AT THE AHU MAY BE INSTALLED
 (ALTHOUGH IT'S NOT NECESSARY) BUT IT CAN NOT REPLACE
 THE SEPARATE SECONDARY DRAIN LINE OR THE FLOAT SWITCH
 REQUIRED ON THE AUXILIARY DRAIN PAN. THE FLOAT SWITCH
 ON THE SECONDARY DRAIN OUTLET AT THE AHU IS ACCEPTABLE
 AS OVERFLOW PROTECTION ONLY ON THE DUCTED RETURN UNITS
 WHERE AN AUXILIARY DRAIN PAN CAN NOT BE INSTALLED UNDER
 THE AHU. FBC,M 307.2.3 AND 307.2.4
  
 9. M15.22: DUCT SUPPORT DETAIL INDICATES 1/2 INCH WIDE
 22GA SUPPORTS ON FLEX DUCT. THE MATERIAL SUPPORTING
 FLEX DUCT SHALL NOT BE LESS THAN 1 1/2 INCHES WIDE.
 FBC,M 603.5.6.6(6).
  
 10. M15.22: CONDENSING UNIT DETAIL CALLS FOR 1/4 INCH
 CABLES TIED TO THE CONDENSER AND THE BEAM WITH 3/8 INCH
 LAG BOLTS. LAG BOLTS ARE FOR USE IN WOOD. PLEASE
 SPECIFY A FASTENER WHICH IS APPROPRIATE FOR THIS
 APPLICATION. ALSO, INDICATE ON PLANS THE WIND SPEED TO
 WHICH THIS CONNECTION DETAIL IS DESIGNED. FBC,M 301.13
 AND FBC CH.16
  
 11. M15.22: TYPICAL AHU DETAIL, PROVIDE MANUAL VOLUME
 DAMPER AT OUTDOOR AIR DUCT IN CLOSET PER FBC
 13-409.1.ABCD.2.
  
 12. M15.23: PROVIDE OUTDOOR AIR CALCULATIONS FOR
 DWELLING UNITS IN ACCORDANCE WITH FBC,M TABLE 403.3.
  
 13. M15.21: FIRE PUMP ROOM, PROVIDE SUBMITTAL AND
 INSTALLATION DETAIL FOR THE DIESEL STORAGE TANK. ALSO,
 PROVIDE DETAIL FOR THE DIESEL ENGINE EXHAUST WITH
 DISCHARGE LOCATION. STATIONARY LIQUID FUELED INTERNAL
 COMBUSTION ENGINES, INCLUDING FUEL STORAGE AND PIPING
 SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 37-94. SEE
 FBC,M 915.1 AND 915.2.
  
 14: ENERGY: THERE WERE TWO DIFFERENT SETS OF
 CALCULATIONS SUBMITTED. FORM 400A-2004 V2.5 IS NOT
 VALID AS THIS PROJECT IS UNDER THE 2001 FBC. THE 2004
 FORM IS DISREGARDED AND THE 2001 FORM IS BEING REVIEWED
 FOR CODE COMPLIANCE. FBC 13-400.3.A.
  
 15. ENERGY: SEVERAL ITEMS LISTED ON THE INPUT DATA
 REPORT DO NOT CORRELATE WITH WHAT IS SHOWN ON PLANS.
 EXAMPLE: THE REPORT INDICATES EXTERIOR WALL ASSEMBLES
 WITH R-VALUE OF 11.94. THE WALL AS DESCRIBED IN THE
 REPORT IS NOT SHOWN ON ARCHITECTURAL PLANS. THE
 INFORMATION USED IN THE INPUT DATA REPORT SHALLL
 CORRELATE WITH PLANS. PLEASE VERIFY ALL ASSEMBLIES,
 R-VALUES, U-FACTORS AND INFILTRATION RATES ARE IN
 COMPLIANCE AND CORRESPOND WITH WHAT IS ON ARCHITECTURAL
 PLANS. FBC 13-400.3.A
  
 16. ENERGY: COOLING LOAD CALCS, DATA USED TO PERFORM
 COOLING LOAD CALCULATIONS AS SHOWN ON THE SYSTEM SIZING
 SUMMARY DO NOT MATCH THE VALUES SHOWN ON PLAN. EXAMPLE:
 AHU CH-3 ON SUMMARY SHOWS 120 CFM OF OUTDOOR AIR.
 EQUIPMENT SCHEDULEON M15.23 SHOWS 200 CFM, PLEASE
 CORRELATE PLANS AND CALCULATIONS. FBC 13-407.1.ABCD.1
  
 17. ENERGY: PROVIDE AUTOMATIC SETBACK OR SHUTDOWN
 CONTROLS IN ACCORDANCE WITH FBC 13-407.1.ABCD.2.4.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status   Date 2006-12-21 Cont ID  
Sent By pkrauss Date 2006-12-21 Time 15:18 Rev Time 0.00
Received By pkrauss Date 2006-12-21 Time 15:18 Sent To  
Notes
2006-12-21 15:18:48DENIED:2001 FLORIDA BUILDING CODE
  
 BUILDING #1:PLEASE NOTE, PAGES HAVE CHANGED SINCE
 PREVIOUS REVIEW DATED 1-31-06
  
 RESPONSE TO COMMENT 1:RESPONSE INDICATES VENTILATION
 CALCULATIONS ON SHEET M15.23. PLAN SHEET M15.23 IS
 WAS NOT SUBMITTED FOR REVIEW, BUT THE CALCULATION DOES
 APPEAR ON PLAN SHEET M15.07,CALCULATIONS WERE NOT
 GIVEN THE THE UNITS.
  
 RESPONSE TO COMMENT 2:OKAY
  
 RESPONSE TO COMMENT 3:RESPONSE INDICATES THE AHU
 CLOSET DOOR WAS CHANGED ON THE DOOR SCHEDULE A9.02 TO A
 NON-COMUSTIBLE DOOR.THIS IS NOT THE CASE, THE DOOR
 SCHEDULE INDICATES A WOOD DOOR.PLEASE ALSO NOTE ON
 PLAN SHEET M15.01, M15.02, & M15.03KEY NOTE #11
 INDICATES A "FULL HEIGHT LOUVERED DOOR" WHICH IS NOT
 REFLECTED ON THE DOOR SCHEDULE.PLEASE CORRELATE.
 PLEASE ALSO NOTE, THE CONDENSATE LINE SHALL ALSO BE OF
 NON-COMBUSTIBLE MATERIAL.
  
 RESPONSE TO COMMENT 4:RESPONSE INDICATES CLEARANCE
 AROUND THE AHU EXCEEDS THE MINIMUM OF 4" AS REQUIRED IN
 2001 FMC 603.1.3.THIS NOT WHAT IS DEPICTED IN THE
 DETAIL OF THE AHU MOUNTING DETAIL ON PLAN SHEET M15.09.
 PLEASE REVISE PLAN TO REFLECT PROPER CLEARANCE.PLEASE
 ALSO NOTE THE AFOREMENTIONED DETAIL SHOWS OUTSIDE AIR
 DUCT.THIS IS NOT INDICATED ON ANY OF THE PLANS,
 PLEASE PROVIDE DUCT SIZE, LAYOUT, MATERIAL AND INTAKE.
  
 RESPONSE TO COMMENT 5:RESPONSE INDICATES "CONDENSATE
 TRAP DETAIL" ON SHEET M15.22.SHEET M15.22 WAS NOT
 SUBMITTED.PLEASE NOTE, THE ORIGINAL COMMENT REQUESTED
 INFORMATION ON THE AUXILIARY DRAIN PAN & OVERFLOW
 PROTECTION AS REQUIRED IN 2001 FMC 307.2.3.COMMENT
 WAS NOT ADDRESSED.
  
 RESPONSE TO COMMENT 6:RESPONSE STATES "TYPICAL
 CONDENSING UNIT INSTALLATION DETAIL" ON SHEET M15.22.
 THIS SHEET WAS NOT SUBMITTED.
  
 RESPONSE TO COMMENT 7 ALSO REFERS TO SHEET M15.22 WHICH
 WAS NOT SUBMITTED FOR REVIEW.
  
 RESPONSE TO COMMENT 8:OKAY
  
 RESPONSE TO COMMENT 9:RESPONSE REFERS TO PLAN SHEETS
 M15.05 THROUGH M15.08.KEY NOTE ON SHEETS INDICATES
 M15.05 THROUGH M15.08 3/4 PVC CONDENSATE TO TERMINATE
 BEUOND EXTERIOR WALL.PLEASE ANNOTATE THE FOLLOWING:
  
  
 A) EXTERIOR TERMINATION SHALL BE A MINIMUM OF 12"
 FROM BUILDING STRUCTURE PER 2001 FBC 1503.4.4.
  
 B) PVC IS COMBUSTIBLE AND SHALL NOT BE INSTALLED
 IN THE PLENUM OF THE AHU CLOSET.
  
 RESPONSE TO COMMENT 10: OKAY
  
 *******************NEW COMMENT********************
  
 11. PLAN SHEET A8.20 INDICATES THE TRASH CHUTE.PER
 2001 FBC 705.2.4.6, AN APPROVED AUTOMATIC SPRINKLER
 SYSTEM SHALL BE INSTALLED AT THE TOP AND AT ALTERNATE
 FLOOR LEVELS IN REFUSE AND LAUNDRY CHUTES AND IN THE
 TERMINATION & INCINERATOR ROOMS.
  
 *****REVIEW IN PROGRESS*********

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-01-30 Cont ID  
Sent By pkrauss Date 2006-01-30 Time 10:13 Rev Time 0.00
Received By pkrauss Date 2006-01-30 Time 08:37 Sent To  
Notes
2006-01-30 00:00:00DENIED:2001 FLORIDA BUILDING CODE
  
 1.PLAN SHEET AP A6.01 THROUGH A701, IT
 APPEARS THE COORIDORS HAVE OPENINGS AT
 CERTAIN POINTS.PLEASE INDICATE TOTAL
 SQUARE FOOTAGE AS REQUIRED FOR 'NATURAL
 VENTILATION'.THE OUTSIDE AIR
 CALCULATIONS INDICATED ON PLAN SHEET
 M15.13 DO NOT SHOW TOTAL SQUARE FOOTAGE.
  
 2.PLANS INDICATE RETURN AIR JUMPERS
 FROM THE BEDROOM AREAS.PLEASE NOTE,
 THE RETURN AIR JUMPERS ARE TO BE SIZED
 IN ACCORDANCE WITH 2001 FMC 601.4
 EXCEPTION 1 & 3.PLEASE REVISE RETURN
 TO INCREASE TO THE REQUIRED MINIMUM.
  
 3.PLANS INDICATE LOUVERED DOOR.THE
 DOOR SCHEDULE INDICATES THIS AS BEING A
 WOOD DOOR.THE AHU CLOSET IS CONSIDERED
 A RETURN AIR PLENUM.THE DOOR MUST ALSO
 MEET THE REQUIREMENT OF NON-COMBUSTIBLE
 OR SHALL HAVE A FLAME SPREAD INDEX OF
 NOT MORE THAN 25 AND A SMIKE DEVELOPED
 INDEX OF NOT MORE THAN 50 WHEN TESTED IN
 ACCORDANCE WITH ASTM E 84.PLEASE
 PROVIDE DOCUMENTATION ON THE DOORS.
  
 4.PLEASE NOTE, PER 2001 FMC 603.1.3 4"
 CLEARANCE AROUND THE AIR HANDLER IS
 REQUIRED.
  
 5.PLAN SHEET M15.12 DETAILS FOR THE
 AHUDOES NOT INDICATE AN AUXILIARY
 DRAIN PAN WITH OVERFLOW PROTECTION AS
 REQUIRED BY 2001 FMC 307.2.3.PLEASE
 REVISE.
  
 6.CONDENSING UNIT STANDS SHALL COMPLY
 WITH 2001 FBC 1511.7 FOR HEIGHT
 REQUIREMENT ABOVE FINISHED ROOF.
  
 7.CONDENSING UNIT STANDS SHALL COMPLY
 WITH 2001 FMC 301.13 & CHAPTER 15 OF THE
 FBC FOR WIND PRESSURES.
  
 8.PLEASE PROVIDE LINE SIZES FOR THE
 REFRIGERANT LINES AS WELL AS THE
 CONDENSATE.
  
 9.PLEASE INDICATE TERMINATION OF THE
 CONDENSATE.
  
 10. PLEASE PROVIDE ENERGY AND MANUAL J
 CALCULATIONS IN ACCORDANCE WITH 2001 FBC
 CHAPTER 13.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (5610805-6719.

Review Stop P PLUMBING
Rev No 4 Status   Date   Cont ID  
Sent By kstevens Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-11-15 Cont ID  
Sent By kstevens Date 2007-11-14 Time 07:16 Rev Time 0.00
Received By kstevens Date 2007-11-10 Time 16:37 Sent To  
Notes
2007-11-15 07:28:38DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW. THE COMMENT NUMBER
 SHALL STAY THE SAME AS THE FIRST REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
 (NOTE STATING "SUBSTANITAL MODIFICATIONS INCLUDING BUT
 NOT LIMITED TO BUILDING DEPARTMENT COMMENTS II" HAS
 CAUSED THE COMPLETE REVIEW OF EACH SHEET AND ADDED MANY
 HOURS OF REVIEW TIME AS SOME SHEETS ONLY HAD MINOR
 CHANGES BUT THE WHOLE SHEET WAS INDICATED IN THE
 REVISION CLOUD. NEW COMMENTS HAVE BEEN ORIGINATED
 BECAUSE OF CHANGES AND RE-REVIEW).
  
 A. OK
 B. OK
 1. OK
 2. OK
  
 3. SHT AP/A5.12 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. SHOW SF DRAINED FOR EACH
 AREA ALONG WITH 1/2 AREA OF ALL VERTICAL
 WALLS, INCLUDING PARAPETS, AND THE AREA
 OF ANY ROOFS THAT DRAIN ONTO THE ROOF
 AREAS FROM ABOVE. - SHOW THE LOCATION OF
 ALL SECONDARY ROOF DRAINS OR SCUPPERS.
 IF SCUPPERS ARE USED, SUBMIT A DETAIL
 SHOWING HEIGHT, WIDTH, AND DISTANCE TO
 FLOW LINE OFF THE ROOF. SECTION 1503.4.2****RESPONSE
 NOTED, BUT SHEET A5.25 WAS
 NOT SUBMITTED, AND NO CALCULATIONS
 WITH INFORMATION REQUESTED HAS BEEN
 LOCATED.
 ******RESPONSE NOTED, BUT THE INTENT OF THE CODE
 SECTION THAT REQUIRES SEPARATE PRIMARY AND SECONDARY
 ROOF DRAINS HAS NOT BEEN MET. IF THERE IS BLOCKAGE IN
 THE DOWNSPOUT, THEN AS INTENDED THE STORM WATER CAN
 DRAIN OVER THE TOP OF THE COLLECTOR HEAD, BUT IF THE
 SCUPPER OPENING IS COVERED/BLOCKED, THEN NEITHER THE
 PRIMARY, NOR THE SECONDARY DRAIN WILL WORK. SCUPPERS
 WILL BE REQUIRED IN THE PARAPET WALLS SIZED PER SECTION
 1107.3 AND A DETAIL WILL BE REQUIRED SHOWING THE
 LENGTH, HEIGHT & WIDTH AND INDICATING THE HEIGHT OFF
 THE ROOF AS REQUIRED IN SECTION 1503.4.2.
  
 4. SHTS AP/A5.61 & AP/A5.62 INDICATE
 SPECIFICATION "A" OR "B" FOR EACH UNIT
 OR BATHROOM AS REQUIRED IN FHA DESIGN
 MANUAL PAGES 7.34 & 7.35. - LAVS SHALL
 BE A MINIMUM OF 2' OFF THE WALL IN ORDER
 TO BE CENTERED ON THE 48" LENGTH OF THE
 CLEAR FLOOR SPACE. PLEASE INDICATE ON
 PLANS. FHA DESIGN MANUAL PAGES 7.47 AND
 7.48. - WATER CLOSET OPENING SHALL BE A
 MINIMUM OF 33" WITH THE WATER CLOSET 18"
 OFF ONE FIXTURE AND 15" OFF THE OTHER
 FIXTURE TO THE CENTER OF THE W/C. FHA
 DESIGN MANUAL PAGES 7.43, 7.44, & 7.45. ****RESPONSE
 NOTED, BUT SPECIFICATION
 "A" OR "B" HAS NOT BEEN INDICATED. ALSO
 THE WATER CLOSET OPENING MEASUREMENTS
 HAS NOT BEEN SHOWN ON THE FLOOR PLAN. ******RESPONSE
 NOTED, BUT SPECIFICATION "A" OR "B" IS NOT INDICATED ON
 THE PLANS.
  
 5. OK
 6. OK
 7. OK
  
 8. SUBMIT A DETAIL FOR THE COMMON USE
 TOILET ROOMS SHOWING COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.19, & 11-4.22 AND
 ALL SUBSECTIONS.
 ****RESPONSE NOTED, BUT THE FOLLOWING
 INFORMATION IS STILL REQUIRED ON PLANS
 TO SHOW COMPLIANCE:
 A. 11-4.19.3 CLEAR FLOOR SPACE (FORWARD
 APPROACH REQUIRED).
 ******RESPONSE NOTED, BUT PARALLEL APPROACH IS SHOWN.
 FORWARD APPROACH IS REQUIRED.
 B. 11-4.19.4 EXPOSED PIPES & SURFACES. ******RESPONSE
 NOTED, BUT NOTE WAS NOT FOUND.
 C. 11-4.19.5 FAUCETS
 ******RESPONSE NOTED, BUT NOTE WAS NOT FOUND.
  
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
  
 14. AN RPZV BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING. SECTION
 608.13.2.
 ****RESPONSE NOTED, BUT COMMENT NOT
 ADDRESSED. EACH BUILDING IS REQUIRED TO
 HAVE ITS OWN RPZV BACKFLOW. INDICATE ON
 PLANS AT THE WATER SERVICE TO THE
 BUILDING.
 ******RESPONSE NOTED, BUT THE RPZV BACKFLOW WAS NOT
 FOUND ON THE CIVIL SHEET #10. PLEASE CLARIFY.
  
 15. SUBMIT A WATER LAYOUT FOR BUILDING
 AND WATER RISER DIAGRAMS. SHOW ALL PIPE
 SIZES, VALVES, WATER HAMMER ARRESTORS,
 (INSTALLED IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING). SECTIONS 104.3.1.1,
 606.1, 606.2, 608.13.2 & PDI-WH 201.
 ****RESPONSE NOTED, BUT THE WATER RISER
 DIAGRAM SHALL BE SUBMITTED IN ISOMETRIC
 FORM. WATER HAMMER ARRESTORS AND
 REQUIRED VALVES CAN NOT BE SHOWN ON A
 FLAT PIPING LAYOUT.
 ******RESPONSE NOTED, BUT THE WATER DISTRIBUTION SYSTEM
 RISERS SHALL BE SHOWN IN ISOMETRIC FORM FROM THE
 ENTRANCE OF THE BUILDING THRU THE 5TH FLOOR. SHT
 AP/P14.26 AS INDICATED WAS THE STORM WATER RISER
 DIAGRAM, NOT THE POTABLE WATER RISER DIAGRAM.
  
 16. SUBMIT A BUILDING SANITARY DRAIN
 ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE
 SIZES, TRAPS, OFFSETS, RISER LOCATIONS
 WITH RISER NUMBERS, DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM ETC. SECTION
 104.3.1.1.
 ***COMMENT RESPONSE NOTED, BUT COMMENT
 NOT ADDRESSED.
 ******RESPONSE NOTED, BUT SHT AP/P14.23 ONLY SHOWS
 RISERS, NOT THE BUILDING DRAIN ISOMETRIC, AND SHTS
 AP/P14.24 & AP/P14.25 DO NOT SHOW THE RISER LOCATIONS
 WITH THE RISER DESIGNATION NUMBERS.
  
 17. SUBMIT A BUILDING STORM DRAIN
 ISOMETRIC RISER DIAGRAM, SHOWING ALL
 PIPE SIZES, RISER LOCATIONS WITH RISER
 NUMBERS, AND SQUARE FEET AS IT
 ACCUMULATES IN THE SYSTEM. SECTION
 104.3.1.1.
 ****RESPONSE NOTED, BUT NOT ADDRESSED.
 SEE COMMENT RESPONSE TO COMMENT #10.
 RISER REQUIRED FOR ALL HORIZONTAL
 STORM DRAINAGE.
 ******RESPONSE NOTED, BUT SHT AP/P14.22 SHOWS NO STORM
 BUILDING DRAIN ISOMETRIC.--SHT AP/P14.26 SHOW ALL
 CLEANOUTS REQUIRED BY SECTION 1101.8.--P-TRAPS ARE
 NOT REQUIRED ON THE STORM SYSTEM.--5S, A MINIMUM 5"
 PIPE IS REQUIRED FOR THE 4" GD-1 1720SF OR INDICATE
 MINIMUM 1/4"/FT SLOPE. TABLE 1106.3.--1S, PIPE SIZE
 IS DECREASED IN SIZE IN THE DIRECTION OF FLOW
 DOWNSTREAM OF1858SF. UPSTREAM SHOWS 8" BUT DOWNSTREAM
 IS SHOWN AS 6". SECTION 704.2. 8" PIPE REQUIRED.
  
 18. OK
  
 **************NEW COMMENTS**************
  
 1B. OK
 2B. OK
 3B. OK
  
 4B. SUBMIT A DETAIL FOR THE DOWNSPOUTS
 AND THE COLLECTOR HEAD AT THE TOP.
 INDICATE SIZE OF DOWNSPOUT, LENGTH,
 WIDTH & HEIGHT OF COLLECTOR HEAD.
 INDICATE ON ROOF PLAN SQUARE FOOTAGE
 DRAINING INTO EACH DOWNSPOUT.
 ******RESPONSE NOTED, BUT LENGHT, WIDTH & HEIGHT ARE
 NOT SHOWN FOR THE COLLECTOR HEAD. A CUT VIEW ONLY WAS
 SUBMITTED, PLEASE PROVIDE AN ELEVATION DETAIL TO SHOW
 ALL MEASUREMENTS.
  
 5B. SECONDARY DRAINAGE AND SEPARATE
 SYSTEMS ARE REQUIRED FOR THE ROOF
 DRAINAGE PER SECTIONS 1107.1 & 1107.2.
 PLEASE INDICATE THE LOCATION AND SIZE OF
 THE SECONDARY ROOF DRAINAGE. SUBMIT A
 DETAIL FOR THE SECONDARY ROOF DRAINS. ******RESPONSE
 NOTED, BUT THE INTENT OF THE CODE SECTION THAT REQUIRES
 SEPARATE PRIMARY AND SECONDARY ROOF DRAINS HAS NOT BEEN
 MET. IF THE DOWNSPOUT BACKS UP THEN AS INTENDED THE
 STORM WATER CAN DRAIN OVER THE TOP OF THE COLLECTOR
 HEAD, BUT IF THE SCUPPER OPENING IS COVERED/BLOCKED,
 THEN NEITHER THE PRIMARY, NOR THE SECONDARY DRAIN WILL
 WORK. SCUPPERS WILL BE REQUIRED IN THE PARAPET WALLS
 SIZED PER SECTION 1107.3 AND A DETAIL WILL BE REQUIRED
 SHOWING THE HEIGHT & WIDTH AND INDICATING THE HEIGHT
 OFF THE ROOF AS REQUIRED IN SECTION 1503.4.2.
  
 6B. SHTS AP A5.05, AP A5.13, AND AP A5.24
 ROOF PLAN SHOWS UNITS AND FIXTURES.
 PLEASE CLARIFY. SECTION 104.2.1.
  
 ********NEW COMMENTS 3RD REVIEW********
  
 1C. SHT AP/P14.01 UNIT A3 NOTE STATES "1/2IN CW/HW
 DOWN, BUT ONLY SHOWS C/W. PLEASE CLARIFY. SECTION
 105.2.1.
  
 2C. SHT AP/P14.03 UNITS C2 & C3 WERE DELETED FROM THE
 SHEET, BUT NO REVISION IS INDICATED. PLEASE CLOUD AND
 INDICATE REVISION WITH A NUMBERED DELTA TRIANGLE.
 SECTION 104.2.1.3.
  
 3C. SHT AP/P14.04 BOTH UNITS, IDENTIFY ALL STACK RISERS
 AND INDICATE WHICH MAIN STACK THEY CONNECT TO.--2ND
 FLOOR CLUBHOUSE PLUMBING PLAN. THE KITCHEN SINK SHALL
 DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT FOR THE
 TOILET ROOM FIXTURES. SECTION 909.1.--INDICATE ON
 WHAT PAGE THE SANITARY LINE CONTINUES.
  
 4C. SHT AP/P14.05 IDENTIFY ALL STACKS. INDICATE WHICH
 SHEET THE PIPE CONTINUES AT THE COMMON AREAS.--4"
 GD-1, BY THE TRASH ROOM SQUARE FOOTAGE IS NOT LEGIBLE.
 SECTION 104.2.1.--THE BUILDING STORM DRAIN LINE HAS
 BEEN DELETED ON ONE SIDE OF THE SHEET. WAS IT RELOCATED
 TO ANOTHER SHEET? PLEASE CLARIFY. SECTION 104.2.1.--
 INDICATE THE RISER NUMBERS SO THEY CAN BE LOCATED ON
 THE NEXT LEVEL. (MANY RISERS HAVE THE SAME NUMBER. EACH
 RISER SHALL HAVE ITS OWN NUMBER SO IT CAN BE TRACED
 FROM THE GROUND FLOOR THRU THE ROOF. (SEE RISERS S-10,
 S-11 & S-12 FOR EXAMPLE). (IF THERE ARE TYPICAL RISERS,
 THEN INDICATE THAT IT IS A TYPICAL RISER, SUCH AS RISER
 S-11 AND THEN SHOW WHICH RISER NUMBERS ARE TYPICAL).
  
 5C. SHT AP/P14.06 INDICATE THE RISER NUMBERS SO THEY
 CAN BE LOCATED ON THE NEXT LEVEL. (MANY RISERS HAVE THE
 SAME NUMBER. EACH RISER SHALL HAVE ITS OWN NUMBER SO IT
 CAN BE TRACED FROM THE GROUND FLOOR THRU THE ROOF. (SEE
 RISER S-33 FOR EXAMPLE). (IF THERE ARE TYPICAL RISERS,
 THEN INDICATE THAT IT IS A TYPICAL RISER, SUCH AS RISER
 S-11 AND THEN SHOW WHICH RISER NUMBERS ARE TYPICAL).
  
 6C. SHT AP/P14.07 IDENTIFY ALL RISERS. SECTION 104.2.1.
 --MINIMUM 5" REQUIRED DOWNSTREAM OF 4" GD-1 1200SF &
 DOWNSTREAM OF 4" GD-1 836SF. (MANY RISERS HAVE THE SAME
 RISER NUMBER). TABLE 1106.3.
  
 7C. SHT AP/P14.08 IDENTIFY ALL RISERS. SECTION 104.2.1.
 (MANY RISERS HAVE THE SAME RISER NUMBER).
  
 8C. SHT AP/P14.09 SHOW THE PIPE SIZES TO W/1 RISERS.
 TABLES 604.3 & 604.5.
  
 9C. SHT AP/P14.10 SHOW THE PIPE SIZES TO W/1 RISERS.
 TABLES 604.3 & 604.5.
  
 10C. SHT AP/P14.11 SHOW THE PIPE SIZES TO W/1 RISERS.
 TABLES 604.3 & 604.5.--INDICATE WHERE THE NEW 4" CW
 FEEDS FROM AND CONTINUES ON TO. SECTION 104.2.1.
  
 11C. SHT AP/P14.12 FULL OPEN VALVES ARE REQUIRED PER
 SECTION 606.1(3). PLEASE INDICATE ON PLANS.
  
 12C. SHT AP/P14.13 PLAN KEY NOTES 3 & 4 WERE NOT
 LOCATED. PLEASE CLARIFY & CORRELATE. SECTION 104.2.1.
 --SHOW ALL RISER DESIGNATION NUMBERS .
  
 13C. SHT AP/P14.14 PLAN KEY NOTES 3 & 4 WERE NOT
 LOCATED. PLEASE CLARIFY & CORRELATE. SECTION 104.2.1.
 --ONE RISER DESIGNATION S/2 NOT INDICATING WHERE THE
 RISER IS LOCATED.--ONE RISER (2), THE 4" SANT.
 STACK FITTING APPEARS TO BE GUIDING THE THE WASTE
 AGAINST THE FLOW. SECTION 706.3.--SHOW ALL RISER
 DESIGNATION NUMBERS .
  
 14C. SHT AP/P14.15 NO REVISION NUMBER IS INDICATED IN
 THE DELTA TRIANGLE.--NO PLAN KEY NOTES NUMBERS ARE
 INDICATED AT THE UNITS NEXT TO THE MATCHLINE. SECTION
 104.2.1.--SHOW ALL RISER DESIGNATION NUMBERS .
  
 15C. SHT AP/P14.16 NO REVISION NUMBER OR DELTA
 INDICATED.--PLAN KEY NOTES 3 & 4 NOT LOCATED.--
 SHOW ALL RISER DESIGNATION NUMBERS .SECTION 104.2.1.
  
 16C. SHT AP/P14.17 NO PLAN KEY NOTES INDICATED FOR
 NUMBERS 1 & 2. PLEASE CLARIFY & CORRELATE. SECTION
 104.2.1.
  
 17C. SHT AP/P14.19 NO PLAN KEY NOTES INDICATED FOR
 NUMBERS 1 & 2. PLEASE CLARIFY & CORRELATE. SECTION
 104.2.1.
  
 18C. SHT AP/P14.21SANITARY RISERS 1, 4, 5, 6 & 7 EVERY
 VENT STACK SHALL CONNECT TO THE BASE OF THE DRAINAGE
 STACK AT OR BELOW THE LOWEST HORIZONTAL BRANCH. SECTION
 903.4. PLEASE CORRECT ON RISERS.--SANT RISER 7
 TOTAL DFU'S IS 24, NOT 20. (BATHROOM GROUP IS 5, PLUS
 ONE FOR THE EXTRA LAV) TABLE 709.1 (SEE DEFINITION OF
 BATHROOM GROUP).--DETAIL #4, A FULL OPEN VALVE IS
 REQUIRED ON THE SUPPLY LINE TO THE WATER HEATER.
 SECTION 606.1(7).
  
 19C. SHT AP/P14.22 ALL UNITS. A WATER HAMMER ARRESTOR
 IS REQUIRED AT THE DISHWASHER LINE PER SECTION 604.9.
 --UNITS B1, B2, B3 & B4 DO NOT REFLECT THE FLOOR
 PLAN. SECTION 104.2.1.--UNITS C2 & C3. NO FLOOR
 PLANS ARE SUBMITTED FOR THESE UNITS. PLEASE CLARIFY.
 SECTION 104.2.1.
  
 20C. SHT AP/P14.23 SANITARY RISERS 1 THRU 9 & 19 ARE
 NOT SUBMITTED. PLEASE CLARIFY. SECTION 104.2.1.
  
 21C. SHTS AP/P14.24 & AP/P14.25 INDICATE THE RISER
 DESIGNATION NUMBERS AT THE BASE OF EACH RISER TO BE
 ABLE TO TRACK THE RISERS FROM FLOOR TO FLOOR. SECTION
 104.2.1.
  
 22C. SHT AP/P14.26 SHOW THE CLEANOUTS REQUIRED IN
 SECTION 1101.8.--P-TRAPS ARE NOT REQUIRED IN THE
 STORM SYSTEM.--MINIMUM 5" REQUIRED AT 4" GD-1
 17720SF OR SHOW SLOPE MINIMUM 1/4"/FT.--8" REQUIRED
 AT 7176SF. 6" WAS SHOWN. PIPE WAS REDUCED IN THE
 DIRECTION OF FLOW AND IS NOT ALLOWED PER SECTION 704.2.
 8" PIPE IS REQUIRED. TABLE 1106.3.
  
 23C. SHT AP/P14.27 SHOW THE CLEANOUTS REQUIRED IN
 SECTION 1101.8.--P-TRAPS ARE NOT REQUIRED IN THE
 STORM SYSTEM.
  
 24C. NOTE: REVISION #1 HAS BEEN DELETED FROM THE TITLE
 BLOCK REVISION INDEX FROM MOST ALL PLUMBING SHEETS. ALL
 REVISIONS SHALL BE INDICATED IN THE REVISION INDEX FOR
 RECORD KEEPING. PLEASE SHOW ALL REVISIONS THROUGHOUT
 THE LENGTH OF THE PROJECT. SECTION 104.2.1.3.
  
 25C. THERE IS NO KEY PLAN OR COLUMN LINES TO INDICATE
 WHAT SECTION OF THE BUILDING IS LOCATED ON WHICH SHEET.
 MATCH LINES DO NOT INDICATE INFORMATION TO DIRECT
 INFORMATION FROM ONE SHEET TO ANOTHER. IT IS TIME
 CONSUMING WHEN ONE SECTION OF THE PLANS HAS NO RELATION
 TO ANOTHER WITH INFORMATION SUBMITTED. PLEASE SUBMIT A
 KEY PLAN ON EACH SHEET OF THE FLOOR PLANS AS HAS BEEN
 SUBMITTED ON THE ARCHITECTURAL SHEET IN ORDER TO
 EXPEDITE THE PLAN REVIEWS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6713
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-10-11 Cont ID  
Sent By kstevens Date 2006-10-11 Time 13:48 Rev Time 0.00
Received By kstevens Date 2006-10-11 Time 13:48 Sent To  
Notes
2006-10-11 15:00:48DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW. THE COMMENT NUMBER
 SHALL STAY THE SAME AS THE FIRST REVIEW:
  
 A. OK
 B. OK
 1. OK
 2. OK
  
 3. SHT AP/A5.12 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. SHOW SF DRAINED FOR EACH
 AREA ALONG WITH 1/2 AREA OF ALL VERTICAL
 WALLS, INCLUDING PARAPETS, AND THE AREA
 OF ANY ROOFS THAT DRAIN ONTO THE ROOF
 AREAS FROM ABOVE. - SHOW THE LOCATION OF
 ALL SECONDARY ROOF DRAINS OR SCUPPERS.
 IF SCUPPERS ARE USED, SUBMIT A DETAIL
 SHOWING HEIGHT, WIDTH, AND DISTANCE TO
 FLOW LINE OFF THE ROOF. SECTION 1503.4.2****RESPONSE
 NOTED, BUT SHEET A5.25 WAS
 NOT SUBMITTED, AND NO CALCULATIONS
 WITH INFORMATION REQUESTED HAS BEEN
 LOCATED.
  
 4. SHTS AP/A5.61 & AP/A5.62 INDICATE
 SPECIFICATION "A" OR "B" FOR EACH UNIT
 OR BATHROOM AS REQUIRED IN FHA DESIGN
 MANUAL PAGES 7.34 & 7.35. - LAVS SHALL
 BE A MINIMUM OF 2' OFF THE WALL IN ORDER
 TO BE CENTERED ON THE 48" LENGTH OF THE
 CLEAR FLOOR SPACE. PLEASE INDICATE ON
 PLANS. FHA DESIGN MANUAL PAGES 7.47 AND
 7.48. - WATER CLOSET OPENING SHALL BE A
 MINIMUM OF 33" WITH THE WATER CLOSET 18"
 OFF ONE FIXTURE AND 15" OFF THE OTHER
 FIXTURE TO THE CENTER OF THE W/C. FHA
 DESIGN MANUAL PAGES 7.43, 7.44, & 7.45. ****RESPONSE
 NOTED, BUT SPECIFICATION
 "A" OR "B" HAS NOT BEEN INDICATED. ALSO
 THE WATER CLOSET OPENING MEASUREMENTS
 HAS NOT BEEN SHOWN ON THE FLOOR PLAN.
  
 5. SHT AP/A5.56 INDICATE MATERIAL FOR
 GRAB BAR BLOCKING. SECTION 104.2.1.
 ***RESPONSE NOTED, (SEE AP A5.56), BUT
 SHT AP/A5.56 HAS NOT BEEN SUBMITTED.
 PLEASE CLARIFY.
  
 6. OK
 7. OK
  
 8. SUBMIT A DETAIL FOR THE COMMON USE
 TOILET ROOMS SHOWING COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.19, & 11-4.22 AND
 ALL SUBSECTIONS.
 ****RESPONSE NOTED, BUT THE FOLLOWING
 INFORMATION IS STILL REQUIRED ON PLANS
 TO SHOW COMPLIANCE:
 A. 11-4.19.3 CLEAR FLOOR SPACE (FORWARD
 APPROACH REQUIRED).
 B. 11-4.19.4 EXPOSED PIPES & SURFACES.
 C. 11-4.19.5 FAUCETS
  
 9. SHTS AP/P14.02 UNITS B3 & B4 MAXIMUM
 4 FU ON A 2" WET VENT IN MASTER BATH.
 TABLE 909.3.
 ****RESPONSE NOTED, BUT THE RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN
 AS THE FLOOR PLAN SHOWS 3" AND THE RISER
 DIAGRAM SHOWS 2-1/2" FOR THE WET VENT.
 CORRELATE RISER AND FLOOR PLAN. SECTION
 104.2.1. (INFORMATION NOT INDICATED ON SHT
 P14.06 AS INDICATED IN RESPONSE).
  
 10. OK
  
 11. SHT AP/P14.26 OFFSETS IN THE SANT.
 SHALL BE SHOWN ON EITHER BLDG. DRAIN
 ISOMETRIC RISER DIAGRAM, OR SANT. RISER
 DIAGRAMS. SECTION 104.2.1.
 ****RESPONSE NOTED, BUT WHEN THE SANT.
 RISER FROM UNDERGROUND IS ABOVE THE
 CEILING OF THE FIRST FLOOR, THE RISER
 SPLITS AND OFFSETS INTO OTHER RISERS.
 (EXAMPLE RISER 2,3,6 COMES OUT OF THE
 GROUND AND OFFSETS ABOVE THE CEILING AND
 SPLITS INTO THREE SEPARATE RISERS.
 BUILDING DRAIN ISOMETRIC RISER SHALL
 REFLECT THIS PIPING. SECTION 104.3.1.1.
  
 12. OK
 13. OK
  
 14. AN RPZV BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING. SECTION
 608.13.2.
 ****RESPONSE NOTED, BUT COMMENT NOT
 ADDRESSED. EACH BUILDING IS REQUIRED TO
 HAVE ITS OWN RPZV BACKFLOW. INDICATE ON
 PLANS AT THE WATER SERVICE TO THE
 BUILDING.
  
 15. SUBMIT A WATER LAYOUT FOR BUILDING
 AND WATER RISER DIAGRAMS. SHOW ALL PIPE
 SIZES, VALVES, WATER HAMMER ARRESTORS,
 (INSTALLED IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING). SECTIONS 104.3.1.1,
 606.1, 606.2, 608.13.2 & PDI-WH 201.
 ****RESPONSE NOTED, BUT THE WATER RISER
 DIAGRAM SHALL BE SUBMITTED IN ISOMETRIC
 FORM. WATER HAMMER ARRESTORS AND
 REQUIRED VALVES CAN NOT BE SHOWN ON A
 FLAT PIPING LAYOUT.
  
 16. SUBMIT A BUILDING SANITARY DRAIN
 ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE
 SIZES, TRAPS, OFFSETS, RISER LOCATIONS
 WITH RISER NUMBERS, DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM ETC. SECTION
 104.3.1.1.
 ***COMMENT RESPONSE NOTED, BUT COMMENT
 NOT ADDRESSED.
  
 17. SUBMIT A BUILDING STORM DRAIN
 ISOMETRIC RISER DIAGRAM, SHOWING ALL
 PIPE SIZES, RISER LOCATIONS WITH RISER
 NUMBERS, AND SQUARE FEET AS IT
 ACCUMULATES IN THE SYSTEM. SECTION
 104.3.1.1.
 ****RESPONSE NOTED, BUT NOT ADDRESSED.
 SEE COMMENT RESPONSE TO COMMENT #10.
 RISER REQUIRED FOR ALL HORIZONTAL
 STORM DRAINAGE.
  
 18. OK
  
 **************NEW COMMENTS**************
  
 1B. ALL ARCHITECTURAL SHEETS. THE TITLE
 BLOCK SHALL CONTAIN THE PRINTED NAME OF
 THE PERSON SEALING THE DOCUMENT. FAC 61G1-16.004(6) &
 FS F81.2055.
  
 2B. SHTS AP/P14.09 THRU AP/1412 PIPING FOR
 THE FIXTURES ON THE SECOND THRU 4TH FLOORS
 SHALL BE SHOWN ON THE FLOOR PLAN WITH
 THE FIXTURES, (SHTSP14.13 THRU P14.16).
 SECTION 104.2.1.3.
  
 3B. SHTS AP A5.60, AP A5.61, AP A5.62
 REFER TO SHEET A5.58. THIS SHEET HAS NOT
 BEEN SUBMITTED. PLEASE CLARIFY. SECTION
 104.2.1.
  
 4B. SUBMIT A DETAIL FOR THE DOWNSPOUTS
 AND THE COLLECTOR HEAD AT THE TOP.
 INDICATE SIZE OF DOWNSPOUT, LENGTH,
 WIDTH & HEIGHT OF COLLECTOR HEAD.
 INDICATE ON ROOF PLAN SQUARE FOOTAGE
 DRAINING INTO EACH DOWNSPOUT.
  
 5B. SECONDARY DRAINAGE AND SEPARATE
 SYSTEMS ARE REQUIRED FOR THE ROOF
 DRAINAGE PER SECTIONS 1107.1 & 1107.2.
 PLEASE INDICATE THE LOCATION AND SIZE OF
 THE SECONDARY ROOF DRAINAGE. SUBMIT A
 DETAIL FOR THE SECONDARY ROOF DRAINS.
  
 6B. SHTS AP A5.05, AP A5.13, AND AP A5.24
 ROOF PLAN SHOWS UNITS AND FIXTURES.
 PLEASE CLARIFY. SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6713
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-01-18 Cont ID  
Sent By kstevens Date 2006-01-18 Time 07:18 Rev Time 0.00
Received By kstevens Date 2006-01-17 Time 19:00 Sent To  
Notes
2006-01-18 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 A. PLANS WERE SUBMITTED AS LOOSE SHEETS
 AND AS SUCH IS NOT ACCEPTABLE. PLEASE
 SUBMIT PLANS IN BOUND SETS. SECTION
 104.2.1.3.
 B. PERMITS INDICATE 3 SEPARATE
 BUILDINGS, BUT PLANS INDICATE ONE
 BUILDING. PLEASE CLARIFY. SECTION
 104.2.1.
 1. ALL ARCHITECTURAL SHEETS, (EXCEPT FOR
 STRUCTURAL), ARE NOT SEALED AS REQUIRED
 IN SECTION 104.2.2 & FAC 61G1-16.003
 61G1-16.004(5) & FS 481.2055.
 2. SHTS AP/A1.02 & AP/A1.03 SHOWN IN
 DRAWING INDEX ON SHT AP/A1.01 HAVE NOT
 BEEN SUBMITTED. SECTION 104.2.1.
 3. SHT AP/A5.04 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. SHOW SF DRAINED FOR EACH
 AREA ALONG WITH 1/2 AREA OF ALL VERTICAL
 WALLS, INCLUDING PARAPETS, AND THE AREA
 OF ANY ROOFS THAT DRAIN ONTO THE ROOF
 AREAS FROM ABOVE. - SHOW THE LOCATION OF
 ALL SECONDARY ROOF DRAINS OR SCUPPERS.
 IF SCUPPERS ARE USED, SUBMIT A DETAIL
 SHOWING HEIGHT, WIDTH, AND DISTANCE TO
 FLOW LINE OFF THE ROOF. SECTION 1503.4.2
 4. SHTS AP/A5.61 & AP/A5.62 INDICATE
 SPECIFICATION "A" OR "B" FOR EACH UNIT
 OR BATHROOM AS REQUIRED IN FHA DESIGN
 MANUAL PAGES 7.34 & 7.35. - LAVS SHALL
 BE A MINIMUM OF 2' OFF THE WALL IN ORDER
 TO BE CENTERED ON THE 48" LENGTH OF THE
 CLEAR FLOOR SPACE. PLEASE INDICATE ON
 PLANS. FHA DESIGN MANUAL PAGES 7.47 AND
 7.48. - WATER CLOSET OPENING SHALL BE A
 MINIMUM OF 33" WITH THE WATER CLOSET 18"
 OFF ONE FIXTURE AND 15" OFF THE OTHER
 FIXTURE TO THE CENTER OF THE W/C. FHA
 DESIGN MANUAL PAGES 7.43, 7.44, & 7.45.
 5. SHT AP/A5.56 INDICATE MATERIAL FOR
 GRAB BAR BLOCKING. SECTION 104.2.1.
 6. SHTS AP/A5.50 THRU AP/A5.55 LAV SHALL
 BE 34" TO TOP OF FIXTURE RIM, NOT 36" AS
 SHOWN. FHA DESIGN MANUAL PAGE 7.52.
 7. SHTS AP/A6.01 THRU AP/A6.04 INDICATE
 THE BLDG. NUMBERS FOR EACH OF THE
 BUILDING ELEVATIONS.
 8. SUBMIT A DETAIL FOR THE COMMON USE
 TOILET ROOMS SHOWING COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.19, & 11-4.22 AND
 ALL SUBSECTIONS.
 9. SHTS AP/P14.02 UNITS B3 & B4 MAXIMUM
 4 FU ON A 2" WET VENT IN MASTER BATH.
 TABLE 909.3
 10. SHT AP/P14.05 VENTS ARE REQUIRED FOR
 THE FLOOR DRAINS. SECTION 901.2.1. -
 CLEANOUTS ARE REQUIRED IN THE SANT.
 BUILDING DRAIN AT ALL CHANGES OF
 DIRECTION OVER 45 DEGREES. SECTION
 708.3.3.
 11. SHT AP/P14.26 OFFSETS IN THE SANT.
 SHALL BE SHOWN ON EITHER BLDG. DRAIN
 ISOMETRIC RISER DIAGRAM, OR SANT. RISER
 DIAGRAMS. SECTION 104.2.1.
 12. SHT AP/P14.27 SANT. RISER S/9,
 PLEASE INDICATE FIXTURE TYPE FOR FIXTURE
 L-3. THIS IS NOT SHOWN ON PLUMBING
 FIXTURE SCHEDULE. SECTION 104.2.1.
 13. SHT AP/P14.27 WATER HEATER PIPING
 DETAIL, THERMAL EXPANSION CONTROL IS
 REQUIRED PER SECTION 607.3.2. PLEASE
 INDICATE METHOD. - DIELECTRIC UNIONS ARE
 NOT APPROVED FOR WATER SUPPLY.
 DIELECTRIC COUPLING TO BE USED.
 14. AN RPZV BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING. SECTION
 608.13.2.
 15. SUBMIT A WATER LAYOUT FOR BUILDING
 AND WATER RISER DIAGRAMS. SHOW ALL PIPE
 SIZES, VALVES, WATER HAMMER ARRESTORS,
 (INSTALLED IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING). SECTIONS 104.3.1.1,
 606.1, 606.2, 608.13.2 & PDI-WH 201.
 16. SUBMIT A BUILDING SANITARY DRAIN
 ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE
 SIZES, TRAPS, OFFSETS, RISER LOCATIONS
 WITH RISER NUMBERS, DFU'S AS THEY
 ACCUMULATE IN THE SYSTEM ETC. SECTION
 104.3.1.1.
 17. SUBMIT A BUILDING STORM DRAIN
 ISOMETRIC RISER DIAGRAM, SHOWING ALL
 PIPE SIZES, RISER LOCATIONS WITH RISER
 NUMBERS, AND SQUARE FEET AS IT
 ACCUMULATES IN THE SYSTEM. SECTION
 104.3.1.1.
 18. SUBMIT STORM RISER DIAGRAMS SHOWING
 ALL PIPE SIZES, OFFSETS, AND SQUARE
 FOOTAGE DRAINED FOR EACH RISER.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  

Review Stop X PERMIT EXTENSION
Rev No 1 Status N Date 2008-11-05 Cont ID  
Sent By dfulcher Date 2008-11-05 Time 09:23 Rev Time 0.00
Received By dfulcher Date 2008-11-05 Time 09:20 Sent To  
Notes
2008-11-05 09:22:46APP EXTENDED TO 2/3/09 PER RAB

Review Stop Z ZONING
Rev No 2 Status F Date 2006-12-22 Cont ID  
Sent By lfranco Date 2006-12-22 Time 19:39 Rev Time 0.00
Received By lfranco Date 2006-12-22 Time 19:18 Sent To I
Notes
2006-12-22 19:34:16PLANNING AND ZONING**** FAILED ****
  
  
 1.PROVIDE RESPONSES TO COMMENTS IN WRITING AND
 INDICATE THE REVISIONS ON SITE PLAN.
  
 2.A MINOR AMENDMENT TO THE COURTNEY LAKES PB 1402
 PLANNED DEVELOPMENTIS REQUIRED TO REFLECT NUMBER OF
 HANDICAP PARKING SPACES REQUIRED.AN APPLICATION WILL
 NEED TO BE FILED TO THE PLANNING AND ZONING DEPARTMENT
 AND APPROVED PRIOR TO SIGN-OFF OF BUILDING PERMIT.
  
 3.PURSUANT TO SECTION 94-485(O)PAGE CD 94:273 OF THE
 CODE, THE AMOUNT OF DISABLED PARKING SPACES PROPOSED
 DOES NOT COMPLY.THERE ARE TWENTY (20) REQUIRED
 PARKING SPACES THAT NEED TO BE PROVIDED.IN ADDITION,
 THE LOCATION OF THE SPACES SHALL BE LOCATED SO THAT
 USERS ARE NOT COMPELLED TO WALK OR OTHERWISE MOVE
 BEHIND PARKED VEHICLES.WHY ARE THESE SPACES LOCATED
 ACROSS DRIVE AISLES INSTEAD OF CLOSE PROXIMITY TO THE
 BUILDING ACCESS? REVISE ACCORDINGLY.
  
 SHOULD YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1435
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2006-03-03 Cont ID  
Sent By lfranco Date 2006-03-03 Time 15:59 Rev Time 0.00
Received By lfranco Date 2006-03-03 Time 15:05 Sent To  
Notes
2006-03-03 00:00:00FAILED:
 PLANNING AND ZONING DEPARTMENT
  
 1. A SITE PLAN WAS NOT PROVIDED IN THE
 SUBMITTAL PACKET. PLEASE SUBMIT A SITE
 PLAN FOR ZONING REVIEW AND APPROVAL.
  
  


Account Summary | Usage Policy | Privacy Policy