Plan Review Details - Permit 05091663
| Plan Review Stops For Permit 05091663 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2005-10-17 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-10-17 |
Time |
13:44 |
Rev Time |
2.50 |
| Received By |
alange |
Date |
2005-10-17 |
Time |
10:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2005-10-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2005-10-06 |
Time |
21:20 |
Rev Time |
1.00 |
| Received By |
jleahy |
Date |
2005-10-06 |
Time |
21:20 |
Sent To |
|
|
| Notes |
| 2005-10-06 00:00:00 | PANEL VA IS SHOWN WITH EQUIPMENT IN | | | FRONT.110.26 SHALL APPLY AND 30" W | | | INFRONT BY 36"D IN FRONT SHALL BE | | | MAINTAINED. | | | | | | ALL OUTLETS WITHIN 6' OF A SINK SHALL BE | | | GFCI PROTECTED. | | | | | | JAKE LEAHY 644-7291 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2005-10-07 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2005-10-07 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2005-10-07 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2005-10-07 00:00:00 | ******PROVISO****** | | | | | | 1) EXIT SIGNS SHALL BE VISIBLE FROM ALL | | | COMPONENTS OF REQUIRED MEANS OF EGRESS. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMITS | | | ARE REQUIRED FOR FIRE SPRINKLER AND FIRE | | | ALARM REMODEL. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2005-11-30 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2005-11-30 |
Time |
18:04 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-11-30 |
Time |
18:04 |
Sent To |
P |
|
| Notes |
| 2005-11-30 00:00:00 | TO "P" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2005-10-17 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2005-10-17 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2005-09-30 |
Time |
16:38 |
Sent To |
|
|
| Notes |
| 2005-09-30 00:00:00 | TO "BOB"#3 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2005-10-04 |
|
|
Cont ID |
|
| Sent By |
prafter |
Date |
2005-10-04 |
Time |
09:03 |
Rev Time |
1.50 |
| Received By |
prafter |
Date |
2005-10-04 |
Time |
09:03 |
Sent To |
|
|
| Notes |
| 2005-10-04 00:00:00 | MECH.PLAN REVIEW: | | | | | | PROVISO: ROOF TOP AHU , DUCT SMOKE | | | DETECTOR TO BE TESTED AT FINAL A/C | | | INSPECTION. | | | | | | PAT RAFTER561/805/6728 OR 805/6719 | | | PATTY KRAUSS. | | | | | | PLEASE CALL IF THEAR ANY QUESTIONS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2005-12-07 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-12-07 |
Time |
07:15 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2005-12-07 |
Time |
07:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2005-10-01 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2005-10-01 |
Time |
09:07 |
Rev Time |
1.50 |
| Received By |
jleech |
Date |
2005-10-01 |
Time |
09:07 |
Sent To |
|
|
| Notes |
| 2005-10-01 00:00:00 | DENIED; | | | 1.HORIZONTAL DRY VENTS ARE NOT PERMITED, | | | FBC-2001 SEC 905.3 TD-4 | | | 2.SIZE WATER LINE TO HB-1. | | | 3.SPEC. OUT A HOSE BIB WITH A BUILT IN | | | VACUUM BREAKER. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
|