Plan Review Details - Permit 05091663
Plan Review Stops For Permit 05091663
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-10-17 Cont ID  
Sent By alange Date 2005-10-17 Time 13:44 Rev Time 2.50
Received By alange Date 2005-10-17 Time 10:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-10-06 Cont ID  
Sent By jleahy Date 2005-10-06 Time 21:20 Rev Time 1.00
Received By jleahy Date 2005-10-06 Time 21:20 Sent To  
Notes
2005-10-06 00:00:00PANEL VA IS SHOWN WITH EQUIPMENT IN
 FRONT.110.26 SHALL APPLY AND 30" W
 INFRONT BY 36"D IN FRONT SHALL BE
 MAINTAINED.
  
 ALL OUTLETS WITHIN 6' OF A SINK SHALL BE
 GFCI PROTECTED.
  
 JAKE LEAHY 644-7291

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-10-07 Cont ID  
Sent By mwennerg Date 2005-10-07 Time 10:28 Rev Time 0.00
Received By mwennerg Date 2005-10-07 Time 10:28 Sent To  
Notes
2005-10-07 00:00:00******PROVISO******
  
 1) EXIT SIGNS SHALL BE VISIBLE FROM ALL
 COMPONENTS OF REQUIRED MEANS OF EGRESS.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-11-30 Cont ID  
Sent By adarroug Date 2005-11-30 Time 18:04 Rev Time 0.00
Received By adarroug Date 2005-11-30 Time 18:04 Sent To P
Notes
2005-11-30 00:00:00TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-10-17 Cont ID  
Sent By alange Date 2005-10-17 Time 13:45 Rev Time 0.00
Received By alange Date 2005-09-30 Time 16:38 Sent To  
Notes
2005-09-30 00:00:00TO "BOB"#3

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2005-10-04 Cont ID  
Sent By prafter Date 2005-10-04 Time 09:03 Rev Time 1.50
Received By prafter Date 2005-10-04 Time 09:03 Sent To  
Notes
2005-10-04 00:00:00MECH.PLAN REVIEW:
  
 PROVISO: ROOF TOP AHU , DUCT SMOKE
 DETECTOR TO BE TESTED AT FINAL A/C
 INSPECTION.
  
 PAT RAFTER561/805/6728 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2005-12-07 Cont ID  
Sent By jleech Date 2005-12-07 Time 07:15 Rev Time 1.00
Received By jleech Date 2005-12-07 Time 07:15 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-10-01 Cont ID  
Sent By jleech Date 2005-10-01 Time 09:07 Rev Time 1.50
Received By jleech Date 2005-10-01 Time 09:07 Sent To  
Notes
2005-10-01 00:00:00DENIED;
 1.HORIZONTAL DRY VENTS ARE NOT PERMITED,
 FBC-2001 SEC 905.3 TD-4
 2.SIZE WATER LINE TO HB-1.
 3.SPEC. OUT A HOSE BIB WITH A BUILT IN
 VACUUM BREAKER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695