Plan Review Details - Permit 05091653
Plan Review Stops For Permit 05091653
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-05-16 Cont ID  
Sent By lursu Date 2006-05-16 Time 15:18 Rev Time 0.00
Received By rmcdouga Date 2006-06-08 Time 15:02 Sent To  
Notes
2006-05-16 00:00:00PERMIT ATTACHED TO EXT#0020 ,BLDG 7
 :3665 VIANA DR.LU
2006-05-15 00:00:00NEEDS!!!

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-08 Cont ID  
Sent By rmcdouga Date 2006-06-08 Time 15:02 Rev Time 0.00
Received By rmcdouga Date 2006-06-08 Time 15:02 Sent To  
Notes
2006-06-08 00:00:00DENIED
  
 1) THE PLANS MUST BE STAMPED BY PALM
 BEACH COUNTY FOR IMPACT FEES. THE PLAN
 REVIEW NUMBER ON THE PLANS MUST
 CORRESPOND WITH THE P.R. NUMBER ON THE
 IMPACT FEE RECEIPT.
  
 2) SUBMIT FIRE SPRINKLER PLANS FOR THE
 REQUIRED NFPA 13 SYSTEM. THIS IS
 REQUIRED BY FBC 104.3.1.1 OF THE CITY OF
 W.P.B. AMENDMENTS TO THE 2001 FBC.
  
 3) THE GARAGE FLOOR/CEILING ASSEMBLY IN
 DETAIL 17 ON A 10.0.0 DOES NOT
 CORRESPOND TO THE FC 5517 FIRE RATED
 ASSEMBLY LISTED IN THE GYPSUM
 ASSOCIATION MANUAL. PLEASE CORRECT.
  
 4) NUMBER 20 ON THE DOOR SCHEDULE
 SPECIFIES A VENTED GARAGE DOOR. THE
 PRODUCT APPROVAL FOR THE GARAGE DOOR
 DOES NOT INDICATE VENTS IN THE DOOR.
  
 5) REVISE DETAIL 11 ON A 10.0.0 TO
 SPECIFY THE 2001 FBC AND NOT THE CURRENT
 EDITION OF THE STANDARD BUILDING CODE.
  
 6) THE DRAWINGS ATTACHED TO THE STATE
 PRODUCT APPROVAL FOR THE STEEL DOOR FROM
 MASONITE INTERNATIONAL ARE FOR A 6'-8"
 DOOR AND THE PLAN SPECIFIES AN 8'-0"
 DOOR. SEE FL 4940.3 AND DRAWING
 DWG-MA-FLO 133-05.
  
 7) SUBMIT PRODUCT APPROVALS FOR THE
 TRUSS CONNECTORS. (SIMPSON-HETAL 12 &
 16, USP-USC) THE FL COVERSHEET SUBMITTED
 FOR THE USP HANGERS AND COLUMN BASES &
 CAPS HAS A WINDOW MULLION NOA ATTACHED
 TO IT.
  
 8) THE MIAMI-DADE NOA FOR THE SINGLE
 HUNG WINDOWS IS INCOMPLETE. THERE ARE
 SHEETS WITH ANOTHER NOA NUMBER ATTACHED
 AT THE REAR OF THE SH WINDOW NOA.
  
 9) THE DECORATIVE BAHAMA SHUTTERS WILL
 REQUIRE A SEPARATE PERMIT.
  
 10) FS 713.13 IF THE IMPROVEMENT
 DESCRIBED IN THE NOTICE OF COMMENCEMENT
 IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS VOID AND OF NO FURTHER EFFECT.
 (THE NOC WILL NEED TO BE RE-RECORDED
 BEFORE THE PERMIT IS ISSUED.)
  
 11) FBC 13-600.3ABC.1.2 REQUIRES THE
 ENERGY CALCULATION FORMS TO BE SIGNED
 AND SEALED BY AN ARCHITECT OR AN
 ENGINEER.
  
 12) SUBMIT PRODUCT APPROVALS FOR THE
 8 X 8 IMPACT RESISTANT SLIDING GLASS
 DOORS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-01 Cont ID  
Sent By rmcdouga Date 2006-02-01 Time 13:50 Rev Time 0.00
Received By rmcdouga Date 2006-02-01 Time 13:50 Sent To  
Notes
2006-02-01 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE PROPOSED PROJECT APPEARS TO
 COMPRISE MORE THAN ONE PARCEL. PLEASE
 SUBMIT A COPY OF THE REPLAT.
  
 3) IN ORDER TO DETERMINE THE PERCENTAGE
 OF WALL AREA ALLOWED AS OPENINGS BY FBC
 TABLE 600, SUBMIT A SURVEY INDICATING
 THE LOCATIONS OF THE ASSUMED PROPERTY
 LINES BETWEEN THE BUILDINGS.
  
 4) PROVIDE AN AREA CALCULATION TABLE
 LISTING THE FLOOR AREA BREAKDOWNS BY
 FLOOR FOR EACH UNIT AND THE TOTALS FOR
 ALL FOUR UNITS.
  
 5) THE FBC DOES NOT ALLOW HEIGHT AND
 AREA INCREASES FOR NFPA 13R SPRINKLER
 SYSTEMS. SEE FBC TABLE 500 FOOTNOTE (D).
 SPECIFY THE TYPE OF SPRINKLER SYSTEM ON
 THE PLANS. MUST BE A FULL NFPA 13 SYSTEM
 FOR HEIGHT INCREASE. SUBMIT FIRE
 SPRINKLER PLANS PER FBC 104.3.1.1.
  
 6) FBC 2504.4.1 AND GA 216 REQUIRE WOOD
 FURRING TO BE NOT LESS THAN 3/4" X
 1-1/2" ACTUAL SIZE. ALSO, THE SURFACE
 CAN NOT VARY MORE THAN 1/8" FROM THE
 PLANE OF ADJACENT FURRING MEMBERS.
 DETAIL 1 ON A10.0.0 SHOWS THE FURRING
 ATTACHED OVER 3/4" POLYSTYRENE. PLEASE
 REVISE DETAIL TO COMPLY WITH CODE.
  
 7) SPECIFY THE INSULATION THAT WILL BE
 USED IN THE FLOOR/CEILING ASSEMBLY ABOVE
 THE GARAGE.
  
 8) THE GUTTER DOWNSPOUTS ARE REQUIRED TO
 DISCHARGE ONE FOOT AWAY FROM THE
 STRUCTURE PER FBC 1503.4.4.
  
 9) IN THE OPTION 1 FIRST FLOOR PLAN FOR
 UNIT C, THE PLUMBING FOR THE GUEST BATH
 IS LOCATED IN THE ONE HOUR FIRE RATED
 PARTITION WALL REQUIRED FOR THE GARAGE
 SEPARATION. THIS WILL RESULT IN NUMEROUS
 PENETRATIONS FOR DWV AND WATER SUPPLY
 PENETRATIONS.
  
 10) SHOW COMPLIANCE WITH FBC MECH. TABLE
 403.3 FOR REQUIRED OUTDOOR AIR
 VENTILATION AT GARAGES OF 100 CFM PER
 CAR.
  
 11) PLEASE CLARIFY 90# MINERAL WOOL
 SURFACE FELT. SEE NOTE #11 ON A-7.1.2
 AND DETAIL 18 ON A-10.0.0.
  
 12) SPECIFY THE EXTERIOR FINISH AT THE
 UNDERSIDE OF THE BAY WINDOW SHOWN ON
 A-7.1.2. SPECIFY THE EXTERIOR SHEATHING,
 LATH AND STUCCO. NOTE: SEE ASTM C 926
 FOR REQUIRED STUCCO THICKNESS.
  
 13) ASTM C 926 REQUIRES 7/8" OF STUCCO
 WHEN APPLIED VERTICALLY ON METAL PLASTER
 BASE OVER SOLID BASE. SEE NOTE 14 AT
 WALL SECTION 4 ON A-7.0.2.
  
 14) SPECIFY THE MEAN ROOF HEIGHT OF THE
 STRUCTURE. THIS IS THE VERTICAL DISTANCE
 FROM FINISHED GRADE TO THE A POINT AT
 THE AVERAGE HEIGHT OF THE ROOF.
  
 15) PROVIDE A DETAIL OF THE BALCONY
 GUARDRAILS. SPECIFY ATTACHMENTS, SPACING
 OF INTERMEDIATE RAILS, ETC.
  
 16) SPECIFY THE METHOD OF ATTACHMENT FOR
 THE ROOF TILES. THE PRODUCT APPROVAL
 THAT WAS SUBMITTED HAS AN ATTACHMENT
 RESISTANCE MOMENT OF 24.5 FT-LBF FOR
 MORTAR SET TILE. FOR 140 MPH EXPOSURE B
 WITH 40FT MRH, THE REQUIRED MOMENT IS
 28.3 FT-LBF. PLEASE REVISE ROOF TILE
 DETAILS TO COMPLY WITH CODE.
  
 17) UL ASSEMBLY U 906 HAS A 2 HOUR FIRE
 RATING NOT ONE HOUR AS SPECIFIED ON THE
 PLANS FOR WALL TYPES IN DETAILS 2 AND 6
 ON A-10.00.
  
 18) SPECIFY DRAFTSTOPPING IN THE ROOF
 OVERHANGS IN LINE WITH THE TENANT
 SEPARATION WALLS AS REQUIRED BY FBC
 2305.2.3.
  
 19)705.7.1 JOINTS INSTALLED IN OR
 BETWEEN FIRE RESISTANT WALLS, FIRE
 RESISTANT FLOORS OR FLOOR/ CEILING
 ASSEMBLIES AND FIRE RESISTANT ROOFS OR
 ROOF/ CEILING ASSEMBLIES SHALL BE
 PROTECTED BY AN APPROVED FIRE RESISTANT
 JOINT SYSTEM DESIGNED TO RESIST THE
 PASSAGE OF FIRE FOR A PERIOD NOT LESS
 THAN THE REQUIRED FIRE RESISTANCE RATING
 OF THE WALL, FLOOR OR FLOOR IN OR
 BETWEEN WHICH IT IS INSTALLED. SPECIFY
 THE JOINT SYSTEM AT THE TOP OF THE
 TENANT SEPARATION WALLS.
  
 20) PROVIDE DETAILS FOR MECHANICAL DUCT
 PENETRATIONS THROUGH FIRE RATED
 ASSEMBLIES.
  
 21) DETAIL 17 ON A-10 DOES NOT
 CORRESPOND TO GA ASSEMBLY FC 5517
 SPECIFIED ON SHEET A 10.2.0.
  
 22) TRUSS LAYOUT AND DRAWINGS ARE
 REQUIRED TO BE REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD FOR THE
 STRUCTURE. SUBMIT 2 COPIES WITH EACH
 PERMIT.
  
 23) THE UPLIFT LOAD VALUES LISTED IN THE
 TRUSS ANCHOR SCHEDULE ON S-3 FOR THE
 SIMPSON HETAL 16 & 20 ARE INCORRECT.THE
 ONE THIRD STRESS INCREASE FOR STEEL
 CALCULATIONS IS NO LONGER ALLOWED. SEE
 THE 2005 SIMPSON CATALOG.
  
 24) THE HUGHES "USC" CONNECTORS ALSO
 HAVE INCORRECT UPLIFT VALUES. HUGHES WAS
 PURCHASED BY USP SEVERAL YEARS AGO AND
 IS LONGER IN BUSINESS. SEE THE 2005 USP
 CATALOG FOR VALUES. UPDATE THE TRUSS
 ANCHOR SCHEDULE.
  
 25) UNDER KEY NOTES/ LEGEND ON A-4.6.1
 AND OTHER SHEETS REFERENCE IS MADE TO
 SHEET A-13 FOR THE WALL TYPES. HOWEVER,
 THERE IS NO SHEET A-13. WALL TYPES ARE
 ON A-10.0.0.
  
 26) THE ENERGY CALCULATIONS CONTAIN
 SEVERAL ERRORS. THESE ARE CONSIDERED
 MULTIFAMILY NOT SINLE FAMILY. THE
 ADJACENT WALL AT THE GARAGE IS METAL
 FRAME AND THE CEILING INSULATION IS
 SPECIFIED AS R-20 ICYENE.
  
 27)PROVIDE MANUFACTURER'S SPECIFICATIONS
 FOR THE ICYENE INSULATION.
  
 28) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT
 FLORIDA COVER SHEETS FOR ALL PRODUCT
 APPROVALS. IN ADDITION TO THE COVERSHEET
 THE INSTALLATION INSTRUCTIONS OR PRODUCT
 EVALUATION AS LISTED ON THE STATE
 WEBSITE IS ALSO REQUIRED. TWO (2) COPIES
 ARE REQUIRED.
  
 29) SUBMIT STATE PRODUCT APPROVALS FOR
 THE TRUSS CONNECTORS.
  
 30) THE MIAMI-DADE NOA FOR THE SINGLE
 HUNG WINDOWS HAS THE INFO FROM THE FIXED
 GLASS WINDOWS ATTACHED TO THE NOA
 COVERSHEET.
  
 31) THE DESIGN PRESSURES LISTED IN THE
 GARAGE DOOR PRODUCT APPROVALS DO NOT
 MEET THE PRESSURES SPECIFIED ON THE
 PLANS. SEE S-7.
  
 32) SUBMIT MANUFACTURER'S SPECS. FOR THE
 DOOR CLOSERS.
  
 33) SUBMIT PRODUCT APPROVALS FOR THE
 EXTERIOR STEEL PANEL DOOR WITH 3/4 HOUR
 FIRE RATING.
  
 34) SUBMIT PRODUCT APPROVALS FOR THE
 8' X 8' IMPACT RATED SLIDING GLASS
 DOOR.
  
 35) PROVIDE A ROOF SHEATHING NAILING
 FIGURE WHICH SPECIFIES THAT THE GABLE
 ENDS REQUIRE NAILING PER ZONE 3.
  
 36) THE CALCULATED VALUE OF THE
 STRUCTURE HAS BEEN REVISED TO
 $911,984.00.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-05-15 Cont ID  
Sent By dpalmer Date 2006-05-15 Time 10:02 Rev Time 0.00
Received By dpalmer Date 2006-05-15 Time 07:52 Sent To  
Notes
2006-05-15 00:00:00**** UNSAT ****
  
 1) NOTE: PLEASE SEE BUILDING IS SHOWN AS
 A FIVE UNTI BUIDING, HOWEVER SERVICE AS
 SHOWN IS FOR FOUR UNITS ONLY.?
 PLEASE CORRELATE SIZE OF SERVICE.215.5
  
 2)NOTE: PLEASESEE #4 GEC SHOWN, WHERE
 A 3/0 MIN IS REQUIRED PER 250.66 FOR THE
 SEC'S SHOWN.
  
 ** PLEASE SEE ALL OTHER ELECTRICAL
 SHEETS ARE STAMPED IN BOTH SETS. BOTH
 SETS WITH THESE STAMPED SHEETS MUST BE
 RETURNED IN SETS WHEN RESUBMITTING
 PALNS.
 PLEASE SEE SHEET 6.1 WAS VOIDEDIN BOTH
 SETS AS THIS WAS STAMPED IN ERROR.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-10-17 Cont ID  
Sent By dpalmer Date 2005-10-17 Time 10:00 Rev Time 0.50
Received By dpalmer Date 2005-10-17 Time 10:00 Sent To  
Notes
2005-10-17 00:00:00********* UNSAT *********
  
  
 1)NOTE: PLEASE SEE PROJECT IS SUBMITTED
 AS CONDO'S YET ELECTRICALSERVICES
 PROVIDED IS SHOWN AS EACH WOULD BE A
 TOWNHOUSE (FEE SIMPLE).
 PLEASE SEE WATER SERVICE SHOWS
 MULTI-FAMILY BLDG.
 PLEASE KNOW, IF THESE AS MULTI-FAMILY
 CONDO BLDGS; ONE SERVICE FOR EACH BLDG
 IS PERMITTED,230.2,230.70MAINS WILL BE
 REQUIRED TO BE GROUPED PER 230.72.
 MCB'S SHOWN IN EACH GARAGE PANEL IS
 PERMITTED.
 PLEASE ADJUST SERVICE FOR BLDG.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 AIC RATINGS ARE SHOWN FOR EACH PANEL,
 BUT WILL ALSO BE REQUIRED FOR MAINS.(NEW
 SERVICE).
  
 3)NOTE: PLEASE CLARIFY LOCATION OF
 DISHWASHER RECEPT. APPEARS TO BE SHOWN
 BEHIND UNIT? THIS IS ONLY A NOTE:
  
 4))NOTE: PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
 PLEASE BE SURE TO CHECK "C" UNITS, NONE
 READLIY VISABLE ON "D".
  
 5)NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52D IN BATHRMS. PLEASE SEE UNIT "D"
 3RD FLR. PLEASE EITHER MOVE GFI TO
 CENTER OF LAVS', OR ADD AN ADDITIONAL.
  
 7 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS NEEDS
 TO BE SHOWN ABOVE THE GEN. KT/RECEPT
 LOADS. THIS SHOULD BE ABOVE THE FIGURED
 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 8)NOTE: PLEASE LIST ALL THE REQUIRD ARC
 FAULT PROECTED CIRCUITS AS REQUIRED PER
 2002 210.12
 PLEASE KNOW, SD'S ARE BEING SHOWN
 CIRCUITED TO KITCHEN LIGHTING CIRCUIT,
 THIS IS OK, HOWEVER PLEASE KNOW, THIS
 WOULD ALSO REQUIRE ARC FAULT PROTECTION
 FOR THIS ADDITIONAL CIRCUIT.
 THIS IS ONLY A NOTE:
  
 9)NOTE: PLEEASE SEE NFPA-72 (2002)
 EDITION,11.8.3.5.
 PLEASE PLACE NOTE ON PLANS WHICH STATES
 LOCATIONS OF SD'S TO BE A MIN OF 3' FROM
 BATH(S) AND KITCHEN DOORS AND 20' FROM
 KITCHEN COOKING APPLIANCES.
 ** PLEASE SEE EXCEPTION TO 20' FROM
 COOKING WITH TYPE OF SD USED.**
 PLEASE SEE PLANS SHOWS A SD IN KITCHEN
 AREA AT THIS TIME.
  
 10)NOTE: PLEASE SEE THE WASHERCOULD
 NOT BE LOCATED ON PLANS FOR UNIT "C, YET
 THIS IS INDICATE ON PANEL SCHEDULE.
 PLEASE SEE MECHANICAL NOTES
 PERTAINING TO "DRYER BOOSTER FANS".
 AS PER MECHANICAL THESE MAY NOT BE
 PERMITTED AND ANY COMMENT THEY MAY HAVE
 WILL DIRECTLY AFFECT ELECTRICAL PLANS.
 THIS IS A NOTE, AS IT IS NOT AN NEC
 ISSUE.
 PLEASE SEE ALL SYSTEMS DO HAVE BE
 LISTED.110.3,90.7
  
 11)NOTE: PLEASE VERIFY OCP FOR AHU HEAT,
 PER 424.3B, MIN 125%.
  
 12)NOTE:
  
 13)NOTE: PLEASE SEE PLANS DO NOT
 INDICATE ANY ACCESIBLITY TO GFI RECEPTS
 SHOWN FOR JACUZZI/WHIRLPOOL TUB.
  
 14)NOTE: PLEASE SEE 406.2B,210.21B3&4
 WHICH REQUIRES THE MAX OCP FOR A 50A
 RANGE RECEPT TO BE 50A'S. PLEASE SEE A
 2P-60A BRKR IS SHOWN.
  
 15)NOTE: PLEASE PROVIDE AREA AND ROOM
 DESIGNATIONS ON PLANS. PLEASE SEE SOME
 ARE MISSING.
 THIS WILL ALSO BE REQUIRED TO DETERMINE
 CIRCUITING FOR DINING AREAS.
  
 16)NOTE: PLEASE SEE PLANS REFERENCE THE
 2000 NFPA 101, WHEN AS OF JAN 1ST 2005,
 THE 2003 NFPA-101 IS IN EFFECT.
  
 17)NOTE: PLEASE SEE THAT THE RECEPT
 SHOWN FOR LV PANEL IN CLOSET MAY NOT BE
 IN ANY SHELF AREA. THIS RECEPT MAY BE
 ABOVE DOOR ONLY, OR PANEL SHALL BE MOVED
 TO OUTSIDE CLOTHES CLOSET. PLEASE KNOW
 THIS IS A FIRE HAZARD FOR THE LV
 TRANSFORMER CLOSE TO EASILY IGNITIBLE
 MATERIALS.
  
  
 ** PLEASE KNOW, MANY ITEMS HAVE BEEN
 REDLINED ON PLANS FOR LOCATIONS OF
 NOTES.
  
 ** PLEASE KNOW, A REVIEW OF MAIN
 ELECTRICAL SERVICECAN NOT BE DONE AT
 THIS TIME, AS SERVICE WILL BE CHANGING.
  
 PLEASE SEE ANY OTHER POSSIBLE COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 ** PLEASE SEE THIS MAY BE CONSIDERED A
 "THRESHOLD" PROJECT. IF SO, THREE SETS
 OF PLANS WILL BE REQUIRED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-10-04 Cont ID  
Sent By mamini Date 2005-10-04 Time 08:58 Rev Time 0.50
Received By mamini Date 2005-10-04 Time 08:57 Sent To  
Notes
2005-10-04 00:00:00PASSED:
  
 1. SEE PERMIT # 04120439 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-11-22 Cont ID  
Sent By mwennerg Date 2005-11-22 Time 10:06 Rev Time 0.00
Received By mwennerg Date 2005-11-22 Time 10:06 Sent To  
Notes
2005-11-22 00:00:00******PROVISO******
  
 1) LIFE SAFETY TO COMPLY WITH NFPA 101,
 2003 EDITION.
  
 2) SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED FOR FIRE SPRINKLER SYSTEM, THAT
 SHALL BE UL CERTIFIED FOR CENTRAL
 STATION SERVICE.
  
 3) MULTI-PURPOSE FIRE EXTINGUISHERS ARE
 REQUIRED FOR EACH UNIT.
  
 4) AN ADDRESS IS REQUIRED FOR EACH UNIT,
 AND SHALL BE AT LEAST 3" IN HEIGHT AND
 CONTRASTING TO BACKGROUND.
  
 5) PLANS INDICATE THAT SHOP DRAWINGS ARE
 BEING PROVIDED FOR PRE-ENGINEERED
 STAIRS, THAT SHALL BE IN COMPLIANCE WITH
 NFPA 101, AND FBC REQUIREMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-17 Cont ID  
Sent By adarroug Date 2006-03-17 Time 17:07 Rev Time 0.00
Received By adarroug Date 2006-03-17 Time 17:07 Sent To  
Notes
2006-04-11 00:00:00TO "COMM" BD#4
2006-03-17 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-01 Cont ID  
Sent By rmcdouga Date 2006-02-01 Time 13:51 Rev Time 0.00
Received By rmcdouga Date 2005-10-03 Time 16:05 Sent To  
Notes
2005-10-03 00:00:00TO "COMM" BD#46/PLANS ON RACK/17 ROLLS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-06-07 Cont ID  
Sent By pkrauss Date 2006-06-06 Time 11:03 Rev Time 0.00
Received By pkrauss Date 2006-06-06 Time 11:01 Sent To  
Notes
2006-06-06 00:00:00PROVISO:2001 FBC/BUIDLING 7/5 UNITS
  
 PLEASE REVISE THE PLANS TO REFLECT THE
 IMPLEMENTATION OF THE PROVISO'S.
  
 1.PLAN SHEET M0.1, DETAIL ON THE AHU
 MOUNTING NOTE #15 STATES "NO
 COMBUSTIBLES ALLOWED IN THE MECHANICAL
 CLOSET" AS IT SERVES AS A PLENUM.THE
 DOOR SCHEDULE ON PLAN SHEET A-4.7.3
 INDICATES THE AHU CLOSET DOOR AS A WOOD
 LOUVERED DOOR.PLEASE CLARIFYNWITH THE
 DOOR MANUFACTURE THAT THIS DOOR MEETS
 THE 25 FLAME/50 SMOKE INDEX AS SPECIFIED
 IN 2001 FMC 602.2.1.
  
 2.O.A. CALCULATIONS INDICATED ON PLAN
 SHEET M0.1 ARE BASED ON INFILTRATION
 RATES.THE INFILTRATION RATES ARE THE
 MAXIMUM ALLOWED BY CODE AND MAY NOT
 REFLECT A "TRUE" RATE.PLEASE PROVIDE
 CALCS IN ACCORDANCE WTIH 2001 FMC 402.2,
 402.2.1 OR TABLE 403.3.PLEASE NOTE,
 PLAN SHEET M2 INDICATES A 6" O.A. DUCT.
 PLEASE DELETE FROM THE PLAN IF THIS IS
 NOT GOING TO BE INSTALLED.
  
 3.SPECIFICDRYERS AS TO BE INSTALLED
 BY FINAL INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-11-29 Cont ID  
Sent By pkrauss Date 2005-11-29 Time 08:49 Rev Time 0.00
Received By pkrauss Date 2005-11-29 Time 08:49 Sent To  
Notes
2005-11-29 00:00:00DENIED:BUILDING 7 / 2001 FBC
 1.PLAN SHEET A-0.0.0 PROJECT
 INFORMATION INDICATES TYPE VI,
 UNPROTECTED SPRINKLERED.PLEASE
 INDICATE WHICH SYSTEM WILL BE USED
 (13,13R, 13D ETC).PLEASE NOTE,
 ADDITIONAL COMMENTS MAY BE GENERATED BY
 THE RESPONSE GIVEN.
  
 2.PLAN SHEET A-4.6.2 KEY NOTES/LEGEND,
 ITEM #25 '1HR CHASE REFER TO 11/A-13'.
 PLAN SHEET A-13 WAS NOT SUBMITTED FOR
 REVIEW.
  
 3.PLAN SHEET M0.1 EQUIPMENT SCHEDULE
 INDICATES AHU-1 AS A 5 TON UNIT.NOTE
 #2 INDICATES AREA SMOKE DETECTORS TO
 SHUT DOWN AHU.PLEASE INDICATE THIS ON
 THE ELECTRICAL PLANS FOR UNITS 97D &
 93D.
  
 4.PLEASE CLARIFY RATING OF THE WALL
 BETWEEN THE GARAGE & THE RESIDENCE.THE
 ARCHITECTURAL PLANS ARE NOT CLEAR AS TO
 WHERE THE 1HR RATING ENDS (AT THE SLAB
 OR AT THE RATED CEILING).
  
 5.PLAN SHEET M1 R/A JUMPER FROM THE
 GUEST SUITE IN UNITS 97D & 93D IS NOT
 SIZE IN ACCORDANCE WITH 2001 FMC 601.4
 EXCEPTION 1 & 3. R/A JUMPER FROM THE
 GUEST SUITE SHALL BE A MINIMUM OF 12".
  
 6.PLAN SHEET M3 R/A TRANSFER GRILLES
 ARE NOT SIZED PROPERLY.SHOW COMPLIANCE
 WITH 2001 FMC 601.4 EXCEPTION 2 & 3.
  
 7.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2001 FMC
 TABLE 403.3.
  
 8.PLAN SHEET M3, THE DRYER EXHAUST
 EXCEEDS THE REQUIRED 25FT MAXIMUM
 DISTANCE PER 2001 FMC 504.6.
  
 9.PLEASE PROVIDE A DETAIL FOR THE AHU
 LOCATED IN THE 2ND FLOOR CLOSET.SHOW
 COMPLIANCE WITH 2001 FMC 603.9 &
 610.1.ABC.3.7 OF THE 2001 FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-05-27 Cont ID  
Sent By kstevens Date 2006-05-27 Time 13:21 Rev Time 0.00
Received By kstevens Date 2006-05-27 Time 13:21 Sent To  
Notes
2006-05-27 00:00:00 
  
  
  
  
 *************PASSED PROVISO*************
  
 SANITARY BUILDING DRAIN SHALL BE A
 MINIMUM OF 4FT OFF THE FOOTER PER
 SECTION 307.4.
  
  
  
  
  
  
  
  
  
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-11-29 Cont ID  
Sent By kstevens Date 2005-11-29 Time 06:46 Rev Time 0.00
Received By kstevens Date 2005-11-28 Time 18:59 Sent To  
Notes
2005-11-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SHTS P2.1.1, P2.2.2,P-2.3.1,
 P3.1.1, P-3.2, & P3.3.2 WATER HAMMER
 ARRESTORS ARE REQUIRED AT THE WASH
 MACHINES OF ALL UNITS. PER SECTION
 604.9. - ALL WATER HAMMER ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE", NOT IN THE CEILING AS
 SHOWN IN SOME CASES. PDI-WH 201 AND
 MANUF INSTALLATION INSTRUCTIONS.
 2. IF INDIVIDUAL METERS NO BACKFLOW
 DEVISE IS REQUIRED, BUT IF SINGLE METER
 AN RPZV BACKFLOW WILL BE REQUIRED ON THE
 WATER SERVICE. PLEASE CLARIFY. SECTION
 608.13.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2006-01-20 Cont ID  
Sent By mmclean Date 2006-01-20 Time 17:33 Rev Time 0.00
Received By mmclean Date 2006-01-20 Time 17:33 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved