Plan Review Details - Permit 05091652
Plan Review Stops For Permit 05091652
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-06-06 Cont ID  
Sent By rmcdouga Date 2006-06-06 Time 11:02 Rev Time 0.00
Received By rmcdouga Date 2006-06-06 Time 11:02 Sent To  
Notes
2006-05-15 00:00:00NEEDS!!!

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-06 Cont ID  
Sent By rmcdouga Date 2006-06-06 Time 11:09 Rev Time 0.00
Received By rmcdouga Date 2006-06-06 Time 11:09 Sent To  
Notes
2006-06-06 00:00:00DENIED
  
 1) THE PLANS MUST BE STAMPED BY PALM
 BEACH COUNTY FOR IMPACT FEES. THE PLAN
 REVIEW NUMBER ON THE PLANS MUST
 CORRESPOND WITH THE P.R. NUMBER ON THE
 IMPACT FEE RECEIPT.
  
 2) SUBMIT FIRE SPRINKLER PLANS FOR THE
 REQUIRED NFPA 13 SYSTEM. THIS IS
 REQUIRED BY FBC 104.3.1.1 OF THE CITY OF
 W.P.B. AMENDMENTS TO THE 2001 FBC.
  
 3) THE GARAGE FLOOR/CEILING ASSEMBLY IN
 DETAIL 17 ON A 10.0.0 DOES NOT
 CORRESPOND TO THE FC 5517 FIRE RATED
 ASSEMBLY LISTED IN THE GYPSUM
 ASSOCIATION MANUAL. PLEASE CORRECT.
  
 4) NUMBER 20 ON THE DOOR SCHEDULE
 SPECIFIES A VENTED GARAGE DOOR. THE
 PRODUCT APPROVAL FOR THE GARAGE DOOR
 DOES NOT INDICATE VENTS IN THE DOOR.
  
 5) REVISE DETAIL 11 ON A 10.0.0 TO
 SPECIFY THE 2001 FBC AND NOT THE CURRENT
 EDITION OF THE STANDARD BUILDING CODE.
  
 6) THE DRAWINGS ATTACHED TO THE STATE
 PRODUCT APPROVAL FOR THE STEEL DOOR FROM
 MASONITE INTERNATIONAL ARE FOR A 6'-8"
 DOOR AND THE PLAN SPECIFIES AN 8'-0"
 DOOR. SEE FL 4940.3 AND DRAWING
 DWG-MA-FLO 133-05.
  
 7) SUBMIT PRODUCT APPROVALS FOR THE
 TRUSS CONNECTORS. (SIMPSON-HETAL 12 &
 16, USP-USC) THE FL COVERSHEET SUBMITTED
 FOR THE USP HANGERS AND COLUMN BASES &
 CAPS HAS A WINDOW MULLION NOA ATTACHED
 TO IT.
  
 8) THE MIAMI-DADE NOA FOR THE SINGLE
 HUNG WINDOWS IS INCOMPLETE. THERE ARE
 SHEETS WITH ANOTHER NOA NUMBER ATTACHED
 AT THE REAR OF THE SH WINDOW NOA.
  
 9) THE DECORATIVE BAHAMA SHUTTERS WILL
 REQUIRE A SEPARATE PERMIT.
  
 10) FS 713.13 IF THE IMPROVEMENT
 DESCRIBED IN THE NOTICE OF COMMENCEMENT
 IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS VOID AND OF NO FURTHER EFFECT.
 (THE NOC WILL NEED TO BE RE-RECORDED
 BEFORE THE PERMIT IS ISSUED.)
  
 11) FBC 13-600.3ABC.1.2 REQUIRES THE
 ENERGY CALCULATION FORMS TO BE SIGNED
 AND SEALED BY AN ARCHITECT OR AN
 ENGINEER.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-30 Cont ID  
Sent By rmcdouga Date 2006-01-30 Time 16:27 Rev Time 0.00
Received By rmcdouga Date 2006-01-30 Time 16:27 Sent To  
Notes
2006-01-30 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE PROPOSED PROJECT APPEARS TO
 COMPRISE MORE THAN ONE PARCEL. PLEASE
 SUBMIT A COPY OF THE REPLAT.
  
 3) IN ORDER TO DETERMINE THE PERCENTAGE
 OF WALL AREA ALLOWED AS OPENINGS BY FBC
 TABLE 600, SUBMIT A SURVEY INDICATING
 THE LOCATIONS OF THE ASSUMED PROPERTY
 LINES BETWEEN THE BUILDINGS.
  
 4) PROVIDE AN AREA CALCULATION TABLE
 LISTING THE FLOOR AREA BREAKDOWNS BY
 FLOOR FOR EACH UNIT AND THE TOTALS FOR
 ALL FOUR UNITS.
  
 5) THE FBC DOES NOT ALLOW HEIGHT AND
 AREA INCREASES FOR NFPA 13R SPRINKLER
 SYSTEMS. SEE FBC TABLE 500 FOOTNOTE (D).
 SPECIFY THE TYPE OF SPRINKLER SYSTEM ON
 THE PLANS. MUST BE A FULL NFPA 13 SYSTEM
 FOR HEIGHT INCREASE. SUBMIT FIRE
 SPRINKLER PLANS PER FBC 104.3.1.1.
  
 6) FBC 2504.4.1 AND GA 216 REQUIRE WOOD
 FURRING TO BE NOT LESS THAN 3/4" X
 1-1/2" ACTUAL SIZE. ALSO, THE SURFACE
 CAN NOT VARY MORE THAN 1/8" FROM THE
 PLANE OF ADJACENT FURRING MEMBERS.
 DETAIL 1 ON A10.0.0 SHOWS THE FURRING
 ATTACHED OVER 3/4" POLYSTYRENE. PLEASE
 REVISE DETAIL TO COMPLY WITH CODE.
  
 7) SPECIFY THE INSULATION THAT WILL BE
 USED IN THE FLOOR/CEILING ASSEMBLY ABOVE
 THE GARAGE.
  
 8) THE GUTTER DOWNSPOUTS ARE REQUIRED TO
 DISCHARGE ONE FOOT AWAY FROM THE
 STRUCTURE PER FBC 1503.4.4.
  
 9) THE DOOR TO THE EXIT STAIRS AT THE
 SECOND FLOOR MUST PROVIDE A 32" CLEAR
 OPENING FROM THE FACE OF THE DOOR TO THE
 STOP WITH THE DOOR OPEN 90 DEGREES. SEE
 FBC 1003.2.1 AND 1003.2.2
  
 10) SHOW COMPLIANCE WITH FBC MECH. TABLE
 403.3 FOR REQUIRED OUTDOOR AIR
 VENTILATION AT GARAGES OF 100 CFM PER
 CAR.
  
 11) WALL SECTION #4 ON A-7.01 IS
 MISLABELED FOR GENERAL NOTES 4 AND 10.
  
 12) SPECIFY THE EXTERIOR FINISH AT THE
 UNDERSIDE OF THE BAY WINDOW SHOWN ON
 A-7.1.1. SPECIFY THE EXTERIOR SHEATHING,
 LATH AND STUCCO. NOTE: SEE ASTM C 926
 FOR REQUIRED STUCCO THICKNESS.
  
 13) ASTM C 926 REQUIRES 7/8" OF STUCCO
 WHEN APPLIED VERTICALLY ON METAL PLASTER
 BASE OVER SOLID BASE. PLEASE REVISE NOTE
 #46 FOR SECTION 3 ON A-7.0.1.
  
 14) SPECIFY THE MEAN ROOF HEIGHT OF THE
 STRUCTURE. THIS IS THE VERTICAL DISTANCE
 FROM FINISHED GRADE TO THE A POINT AT
 THE AVERAGE HEIGHT OF THE ROOF.
  
 15) PROVIDE A DETAIL OF THE BALCONY
 GUARDRAILS. SPECIFY ATTACHMENTS, SPACING
 OF INTERMEDIATE RAILS, ETC.
  
 16) SPECIFY THE METHOD OF ATTACHMENT FOR
 THE ROOF TILES. THE PRODUCT APPROVAL
 THAT WAS SUBMITTED HAS AN ATTACHMENT
 RESISTANCE MOMENT OF 24.5 FT-LBF FOR
 MORTAR SET TILE. FOR 140 MPH EXPOSURE B
 WITH 40FT MRH, THE REQUIRED MOMENT IS
 28.3 FT-LBF. PLEASE REVISE ROOF TILE
 DETAILS TO COMPLY WITH CODE.
  
 17) UL ASSEMBLY U 906 HAS A 2 HOUR FIRE
 RATING NOT ONE HOUR AS SPECIFIED ON THE
 PLANS FOR WALL TYPES IN DETAILS 2 AND 6
 ON A-10.00.
  
 18) SPECIFY DRAFTSTOPPING IN THE ROOF
 OVERHANGS IN LINE WITH THE TENANT
 SEPARATION WALLS AS REQUIRED BY FBC
 2305.2.3.
  
 19)705.7.1 JOINTS INSTALLED IN OR
 BE- TWEEN FIRE RESISTANT WALLS, FIRE
 RESIS- TANT FLOORS OR FLOOR/ CEILING
 ASSEMBLIES AND FIRE RESISTANT ROOFS OR
 ROOF/ CEILING ASSEMBLIES SHALL BE
 PROTECTED BY AN APPROVED FIRE RESISTANT
 JOINT SYSTEM DESIGNED TO RESIST THE
 PASSAGE OF FIRE FOR A PERIOD NOT LESS
 THAN THE REQUIRED FIRE RESISTANCE RATING
 OF THE WALL, FLOOR OR FLOOR IN OR
 BETWEEN WHICH IT IS INSTALLED. SPECIFY
 THE JOINT SYSTEM AT THE TOP OF THE
 TENANT SEPARATION WALLS.
  
 20) PROVIDE DETAILS FOR MECHANICAL DUCT
 PENETRATIONS THROUGH FIRE RATED
 ASSEMBLIES.
  
 21) DETAIL 17 ON A-10 DOES NOT
 CORRESPOND TO GA ASSEMBLY FC 5517
 SPECIFIED ON SHEET A 10.2.0.
  
 22) TRUSS LAYOUT AND DRAWINGS ARE
 REQUIRED TO BE REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD FOR THE
 STRUCTURE.
  
 23) THE UPLIFT LOAD VALUES LISTED IN THE
 TRUSS ANCHOR SCHEDULE ON S-3 FOR THE
 SIMPSON HETAL 16 & 20 ARE INCORRECT.THE
 ONE THIRD STRESS INCREASE FOR STEEL
 CALCULATIONS IS NO LONGER ALLOWED. SEE
 THE 2005 SIMPSON CATALOG.
  
 24) THE HUGHES "USC" CONNECTORS ALSO
 HAVE INCORRECT UPLIFT VALUES. HUGHES WAS
 PURCHASED BY USP SEVERAL YEARS AGO AND
 IS LONGER IN BUSINESS. SEE THE 2005 USP
 CATALOG FOR VALUES. UPDATE THE TRUSS
 ANCHOR SCHEDULE.
  
 25) UNDER KEY NOTES/ LEGEND ON A-4.0 AND
 OTHER SHEETS REFERENCE IS MADE TO SHEET
 A-13 FOR THE WALL TYPES. HOWEVER, THERE
 IS NO SHEET A-13.
  
 26) THE ENERGY CALCULATIONS CONTAIN
 SEVERAL ERRORS. THESE ARE CONSIDERED
 MULTIFAMILY NOT SINLE FAMILY. THE
 ADJACENT WALL AT THE GARAGE IS METAL
 FRAME AND THE CEILING INSULATION IS
 SPECIFIED AS R-20 ICYENE.
  
 27)PROVIDE MANUFACTURER'S SPECIFICATIONS
 FOR THE ICYENE INSULATION.
  
 28) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT
 FLORIDA COVER SHEETS FOR ALL PRODUCT
 APPROVALS. IN ADDITION TO THE COVERSHEET
 THE INSTALLATION INSTRUCTIONS OR PRODUCT
 EVALUATION AS LISTED ON THE STATE
 WEBSITE IS ALSO REQUIRED. TWO (2) COPIES
 ARE REQUIRED.
  
 29) SUBMIT STATE PRODUCT APPROVALS FOR
 THE TRUSS CONNECTORS.
  
 30) THE MIAMI-DADE NOA FOR THE SINGLE
 HUNG WINDOWS HAS THE INFO FROM THE FIXED
 GLASS WINDOWS ATTACHED TO THE NOA
 COVERSHEET.
  
 31) THE DESIGN PRESSURES LISTED IN THE
 GARAGE DOOR PRODUCT APPROVALS DO NOT
 MEET THE PRESSURES SPECIFIED ON THE
 PLANS. SEE S-6.
  
 32) SUBMIT MANUFACTURER'S SPECS. FOR THE
 DOOR CLOSERS.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-05-15 Cont ID  
Sent By dpalmer Date 2006-05-15 Time 15:06 Rev Time 0.00
Received By dpalmer Date 2006-05-15 Time 13:03 Sent To  
Notes
2006-05-15 00:00:00***** UNSAT*******
  
 1) NOTE: PLEASE SEE PLANS ARE FOR A FOUR
 UNIT BUILDING, HOWEVER THE ELECTRICAL
 SERVICE SUBMITTED IS FOR A 6 UNIT
 BUILDING.
 PLEASE CORRELATE. PLEASE ALSO SHOW THE
 "SITE KEY PLAN" FOR LOCATION OF SERVICE
 AS SHOWN ON OTHER PLANS.
  
 2) NOTE:PLEASE SEE NO, SERVICE
 ENTRANCE CONDUIT OR SERVICE ENTRANCE
 CONDUCTORS ARE SHOWN ON RISER FROM FPL
 TO 1000A SERVICE MAIN.
 PLEASE SEE SEC'S ARE NOTED IN FAULT
 CURRENT CALCS ONLY.
 215.5
  
 3) NOTE: PLEASE SEE #4 GEC SHOWN, WHERE
 A 3/0 MIN IS REQUIRED PER 250.66 BASED
 ON THE SEC'S SHOWN ON THE ELECTRICAL
 RISER IN FAULT CURRENT CALCS.
  
 4) NOTE: PLEASE SEE 424.3B FOR MIN OCP
 SHALL BE 125% FOR AHU'S. PLEASE SEE OCP
 HAS NOW BEEN DECREASED TO 40A'S???
  
 ** PLEASE SEE SHEET 6.1 HAS BEEN VOIDED
 AS THIS WAS STAMPED IN ERROR. PLEASE
 KNOW, ALL OTHER ELETRICAL SHEETS WERE
 STAMPED AND THOSE SHEETS MUST BE LEFT IN
 THE COMPLETED ROLL S TO AVOID A FULL
 REVIEW OF ALL SHEETS WHEN RESUBMITTING
 PLANS.
 ONLY SHEET 6.1, SHOULD BE CHANGED OUT.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-10-17 Cont ID  
Sent By dpalmer Date 2005-10-17 Time 13:03 Rev Time 0.33
Received By dpalmer Date 2005-10-17 Time 13:03 Sent To  
Notes
2005-10-17 00:00:00********* UNSAT *********
  
  
 1)NOTE: PLEASE SEE PROJECT IS SUBMITTED
 AS CONDO'S YET ELECTRICALSERVICES
 PROVIDED IS SHOWN AS EACH WOULD BE A
 TOWNHOUSE (FEE SIMPLE).
 PLEASE SEE WATER SERVICE SHOWS
 MULTI-FAMILY BLDG.
 PLEASE KNOW, IF THESE AS MULTI-FAMILY
 CONDO BLDGS; ONE SERVICE FOR EACH BLDG
 IS PERMITTED,230.2,230.70MAINS WILL BE
 REQUIRED TO BE GROUPED PER 230.72.
 MCB'S SHOWN IN EACH GARAGE PANEL IS
 PERMITTED.
 PLEASE ADJUST SERVICE FOR BLDG.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 AIC RATINGS ARE SHOWN FOR EACH PANEL,
 BUT WILL ALSO BE REQUIRED FOR MAINS.(NEW
 SERVICE).
  
 3)NOTE: PLEASE CLARIFY LOCATION OF
 DISHWASHER RECEPT. APPEARS TO BE SHOWN
 BEHIND UNIT? THIS IS ONLY A NOTE:
  
 4))NOTE: PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
 PLEASE SEE PLANS REDLINED FOR SOME
 MISSING W/IN 2' OF THE END OF A COUNTER
 OR 4' SPACING.
 UNIT "A"/STANDARD 2FLR,,,
  
 5)NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 PLEASE SEE THESE HAVE BEEN REDLINED AT
 LOCATIONS OF NOTES.
 UNIT "B",3RD FLR OPT 6 2'OF WALL, UNIT
 "A"2ND FLR, WALL APPEARS TO BE OVER 12'?
 PLEASE SEE A COUPLE OF OTHER LOCATIONS.
  
 6)NOTE: PLEASE SEE LOCATION OF A
 RECESSED LT FIXTURE IN CLOSET
 WASHER/DRYER LOCATION. THESE LOCATIONS
 TYPICALLY CONTAIN SHELVING ABOVE THE
 WASHER/DRYER'S. PLEASE SEE 410.8 FOR MIN
 CLEARENCE FROM LT AND FIXTURE TYPES.
 (WALL MOUNT)? AS SHOWN IN OTHER CLOSETS?
  
 7 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS NEEDS
 TO BE SHOWN ABOVE THE GEN. KT/RECEPT
 LOADS. THIS SHOULD BE ABOVE THE FIGURED
 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 8)NOTE: PLEASE LIST ALL THE REQUIRD ARC
 FAULT PROECTED CIRCUITS AS REQUIRED PER
 2002 210.12
 PLEASE KNOW, SD'S ARE BEING SHOWN
 CIRCUITED TO KITCHEN LIGHTING CIRCUIT,
 THIS IS OK, HOWEVER PLEASE KNOW, THIS
 WOULD ALSO REQUIRE ARC FAULT PROTECTION
 FOR THIS ADDITIONAL CIRCUIT.
 THIS IS ONLY A NOTE:
  
 9)NOTE: PLEEASE SEE NFPA-72 (2002)
 EDITION,11.8.3.5.
 PLEASE PLACE NOTE ON PLANS WHICH STATES
 LOCATIONS OF SD'S TO BE A MIN OF 3' FROM
 BATH(S) AND KITCHEN DOORS AND 20' FROM
 KITCHEN COOKING APPLIANCES.
 ** PLEASE SEE EXCEPTION TO 20' FROM
 COOKING WITH TYPE OF SD USED.**
 PLEASE SEE PLANS SHOWS A SD IN KITCHEN
 AREA AT THIS TIME.
  
 10)NOTE: PLEASE SEE MECHANICAL NOTES
 PERTAINING TO "DRYER BOOSTER FANS".
 AS PER MECHANICAL THESE MAY NOT BE
 PERMITTED AND ANY COMMENT THEY MAY HAVE
 WILL DIRECTLY AFFECT ELECTRICAL PLANS.
 THIS IS A NOTE, AS IT IS NOT AN NEC
 ISSUE.
 PLEASE SEE ALL SYSTEMS DO HAVE BE
 LISTED.110.3,90.7
  
 11)NOTE: PLEASE VERIFY OCP FOR AHU HEAT,
 PER 424.3B, MIN 125%.
  
 12)NOTE: PLEASE SEE "SHIFT" IN PLANS FOR
 ELECTRICAL DEVICES IN UNIT "A"-1 FST
 FLR(REV).
 PLEASE ALSO SEE SOME OTHER UNITS MISSING
 LAYOUT OF BATH RM AREA.
 3RD FLR, OPT 7 (REV).
  
 13)NOTE: PLEASE SEE PLANS DO NOT
 INDICATE ANY ACCESIBLITY TO GFI RECEPTS
 SHOWN FOR JACUZZI/WHIRLPOOL TUB.
  
 14)NOTE: PLEASE SEE 406.2B,210.21B3&4
 WHICH REQUIRES THE MAX OCP FOR A 50A
 RANGE RECEPT TO BE 50A'S. PLEASE SEE A
 2P-60A BRKR IS SHOWN.
  
 15)NOTE: PLEASE PROVIDE AREA AND ROOM
 DESIGNATIONS ON PLANS. PLEASE SEE SOME
 ARE MISSING.
 THIS WILL ALSO BE REQUIRED TO DETERMINE
 CIRCUITING FOR DINING AREAS.
  
 16)NOTE: PLEASE SEE PLANS REFERENCE THE
 2000 NFPA 101, WHEN AS OF JAN 1ST 2005,
 THE 2003 NFPA-101 IS IN EFFECT.
  
 ** PLEASE KNOW, MANY ITEMS HAVE BEEN
 REDLINED ON PLANS FOR LOCATIONS OF
 NOTES.
  
 ** PLEASE KNOW, A REVIEW OF MAIN
 ELECTRICAL SERVICECAN NOT BE DONE AT
 THIS TIME, AS SERVICE WILL BE CHANGING.
  
 PLEASE SEE ANY OTHER POSSIBLE COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 ** PLEASE SEE THIS MAY BE CONSIDERED A
 "THRESHOLD" PROJECT. IF SO, THREE SETS
 OF PLANS WILL BE REQUIRED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-10-04 Cont ID  
Sent By mamini Date 2005-10-04 Time 09:07 Rev Time 0.50
Received By mamini Date 2005-10-04 Time 09:07 Sent To  
Notes
2005-10-04 00:00:00PASSED:
  
 1. SEE PERMIT # 04120439 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-11-21 Cont ID  
Sent By mwennerg Date 2005-11-21 Time 16:17 Rev Time 0.00
Received By mwennerg Date 2005-11-21 Time 16:17 Sent To  
Notes
2005-11-21 00:00:00******PROVISO******
  
 1) LIFE SAFETY TO COMPLY WITH NFPA 101,
 2003 EDITION.
  
 2) SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED FOR FIRE SPRINKLER SYSTEM, THAT
 SHALL BE UL CERTIFIED FOR CENTRAL
 STATION SERVICE.
  
 3) MULTI-PURPOSE FIRE EXTINGUISHERS ARE
 REQUIRED FOR EACC UNIT.
  
 4) AN ADDRESS IS REQUIRED FOR EACH UNIT,
 AND SHALL BE AT LEAST 3" IN HEIGHT AND
 CONTRASTING TO BACKGROUND.
  
 5) PLANS INDICATE THAT SHOP DRAWINGS FOR
 PRE-ENGINEERED STAIRS WILL BE PROVIDED,
 THAT SHALL BE IN COMPLIANCE WITH NFPA
 101 AND FBC REQUIREMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-05 Cont ID  
Sent By adarroug Date 2006-04-05 Time 15:12 Rev Time 0.00
Received By adarroug Date 2006-04-05 Time 15:12 Sent To  
Notes
2006-04-11 00:00:00TO "COMM" BD#4
2006-04-05 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-30 Cont ID  
Sent By rmcdouga Date 2006-01-30 Time 16:41 Rev Time 0.00
Received By rmcdouga Date 2005-10-03 Time 16:07 Sent To  
Notes
2005-10-03 00:00:00TO "COMM" BD#46/PLANS ON RACK/17 ROLLS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-05-26 Cont ID  
Sent By pkrauss Date 2006-05-26 Time 09:30 Rev Time 0.00
Received By pkrauss Date 2006-05-26 Time 09:30 Sent To  
Notes
2006-05-26 00:00:00PROVISO:2001 FBC/BUILDING 19/4 UNITS
 RESPONSETO REVIEW COMMETNS OF 11/28/05
  
 PLEASE REVISE PLANS TO REFLECT THE
 IMPLEMENTATION OF THE PROVISO'S.
  
 COMMENT #6:SPECIFIC DRYER TO BE
 INSTALLED WHICH WILL ELIMINATE THE NEED
 OF THE BOOSTER FAN.PLEASE NOTE,
 SPECIFIC DRYER IS TO BE INSTALLED FOR
 FINAL INSPECTION 2001 FMC 504.6.
  
 COMMENT #7:PLAN SHEET M0.1 THE OUTSIDE
 AIR CALCULATIONS ARE BASED ON
 "INFILTRATION RATES".THE INFILTRATION
 RATES ARE "MAXIMUM RATES" ALLOWED BY
 CODE AND MAY NOT ACTUALLY EXIST.THE
 "ACTUAL" RATE IS NOT KNOWN UNLESS
 TESTED.OUTSIDE AIR CALCULATIONS ARE TO
 BE PER 2001 FMC 402.2, 402.2.1 OR TABLE
 403.3.PLEASE PROVIDE CALCULATIONS.
 PLEASE NOTE, PLAN SHEET M2 INDICATES 6"
 OUTSIDE AIR DUCT, PLEASE REMOVE FROM THE
 PLANS IF THIS DUCT IS NOT GOING TO BE
 INSTALLED.
  
 COMMENT #8:AHU CLOSET IS USED AS A
 RETURN AIR PLENUM.PLAN SHEET M0.1 AHU
 DETAIL 15 ANNOTATES "NO COMBUSTIBLES
 ALLOWED IN THE RETURN AIR PLENUM".
 HOWEVER, PLAN SHEETS A-4.0.2 THROUGH
 A-4.5.3, THE DOOR SCHEDULE INDICATES THE
 AHU CLOSET DOOR WILL BE A WOOD LOUVERED
 DOOR.PLEASE NOTE, THE DOOR AND FRAME
 ARE REQUIRED TO MEET THE 25 FLAME/50
 SMOKE INDEX WHEN TESTED UNDER ASTM 84.
 PLEASE VERIFY THE DOOR & FRAME MEET THIS
 REQUIREMENT PER 2001 FMC 602.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-11-28 Cont ID  
Sent By pkrauss Date 2005-11-28 Time 07:13 Rev Time 0.00
Received By pkrauss Date 2005-11-28 Time 07:13 Sent To  
Notes
2005-11-28 00:00:00DENIED:BUILDING 19 / 2001 FBC
 1.PLAN SHEET A-0.0.0 PROJECT
 INFORMATION INDICATES TYPE VI,
 UNPROTECTED SPRINKLERED.PLEASE
 INDICATE WHICH SYSTEM WILL BE UTILIZED
 (13, 13R, 13D ETC).PLEASE NOTE
 ADDTIONAL COMMENTS MAY BE GENERATED BY
 THE RESPONSE GIVEN.
  
 2.PLAN SHEET A-4.0.2 KEY NOTES/LEGEND,
 ITEM #25 '1HR CHASE REFER TO 11/A-13'.
 PLAN SHEET A-13 WAS NOT SUBMITTED FOR
 REVIEW.
  
 3.PLAN SHEET M-1 INDICATES 8" SUPPLY
 DUCT & 3" EXHAUST PENETRATING THE RATED
 WALL BETWEEN THE GARAGE AND THE
 RESIDENCE.THE ARCHITECTURAL PLANS ARE
 NOT CLEAR IF THE WALL CONTINUES PAST THE
 RATED CEILING.PLEASE NOTE, EXHAUST
 DUCTS PENETRATING A FIRE RATED WALL
 SHALL COMPLY WITH 2001 FMC 607.1.3 #3.
  
 4.PLAN SHEET M2 DRYER EXHAUST EXCEEDS
 THE 25 FT REQUIREMENT WITH REDUCTIONS
 FOR 90'S PER 2001 FMC 504.6.PLAN SHEET
 E2.2 INDICATES 'BF' (BOOSTER FAN?).
 PLEASE NOTE, INSTALLATION OF BOOSTER
 FANS WILL BE REVIEWED BY THE BUILDING
 OFFICIAL UNDER "ALTERNATE MATERIALS &
 METHODS" 2001 FMC 103.7.1.PLEASE
 PROVIDE THE FOLLOWING INFORMATION FOR
 REVIEW:1) A LETTER FROIM AN ENGINEER
 EMPLOYED BY THE DRYER MANUFACTURER
 STATING THE INSTALLATION OF THE BOOSTER
 FAN IS ACCEPTABLE AND WILL NOT VOID THE
 WARRANTY OFTHE DRYER.2) MEANS OF
 NOTIFYING THE OWNER SHOULD THE BOOSTER
 FAN FAIL.3) MANUFACTURER'S SUBMITTAL &
 INSTALLATION DATA FOR THE BOOSTER FAN.
 4) PROVIDE ALL PERTINENT INFORMATION FOR
 ALL TRADES MECHANICAL, ELECTRICAL, FIRE
 ETC. FOR THE INSTALLATION OF BOOSTER
 FANS.
  
 5.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH TABLE
 403.3 OF THE 2001 FMC.
  
 6.PLEASE PROVIDE DETAIL FOR THE AHU
 LOCATED IN THE CLOSET.PLEASE NOTE,
 MECHANICAL CLOSET SHALL BE CONSTRUCTED
 PER 2001 FMC 603.9 & 610.1.ABC.3.7 OF
 CHAPTER 13 OF THE 2001 FBC.
  
 7.PLAN SHEET M.2 DRYER EXHAUST APPEARS
 TO RUN THROUGH THE PLENUM IN THE AHU
 CLOSET.PLEASE CLARIFY.PER 2001 FMC
 601.3, EXHAUST DUCTS SHALL NOT EXTEND
 INTO OR PASS THROUGH RETURN AIR PLENUMS.
  
 8.PLEASE NOTE, TRANSFER GRILLES FROM
 THE BEDROOM AREAS SHALL COMPLY WITH 2001
 FMC 601.4 EXCEPTION 2 & 3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-05-30 Cont ID  
Sent By kstevens Date 2006-05-30 Time 07:38 Rev Time 0.00
Received By kstevens Date 2006-05-30 Time 07:38 Sent To  
Notes
2006-05-30 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 FROM PREVIOUS REVIEW:
  
 3. SHT P3.2.4 RISER AND FLOOR PLAN FOR
 UNIT B. RISER DOES NOT REFLECT THE FLOOR
 PLAN, AND AS SHOWN, KITCHEN SINK ARMS
 ARE RUNNING IN FRONT OF THE RANGE ABOVE
 THE FLOOR. PLEASE CLARIFY. SECTION
 104.2.1.
 ***RESPONSE NOTED, BUT NOW THE RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN.
  
  
 ****************NEW COMMENT*************
  
 1B. SHTS P2.1.1, & P3.1.1, THE SANITARY
 BUILDING DRAIN SHALL BE A MINIMUM OF 4
 FT. OFF THE FOOTER PER SECTION 307.4.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-11-29 Cont ID  
Sent By kstevens Date 2005-11-29 Time 07:14 Rev Time 0.00
Received By kstevens Date 2005-11-29 Time 07:14 Sent To  
Notes
2005-11-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SHTS P-2.2, P-3.1.1, P3.2 AND
 P-3.2.4 WATER HAMMER ARRESTORS ARE
 REQUIRED AT THE WASH MACHINES OF ALL
 UNITS. PER SECTION 604.9. - ALL WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE",
 NOT IN THE CEILING AS SHOWN IN SOME
 CASES. PDI-WH 201 AND MANUF INSTALLATION
 INSTRUCTIONS.
 2. IF INDIVIDUAL METERS NO BACKFLOW
 DEVISE IS REQUIRED, BUT IF SINGLE METER
 AN RPZV BACKFLOW WILL BE REQUIRED ON THE
 WATER SERVICE. PLEASE CLARIFY. SECTION
 608.13.2.
 3. SHT P3.2.4 RISER AND FLOOR PLAN FOR
 UNIT B. RISER DOES NOT REFLECT THE FLOOR
 PLAN, AND AS SHOWN, KITCHEN SINK ARMS
 ARE RUNNING IN FRONT OF THE RANGE ABOVE
 THE FLOOR. PLEASE CLARIFY. SECTION
 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2006-01-20 Cont ID  
Sent By mmclean Date 2006-01-20 Time 17:34 Rev Time 0.00
Received By mmclean Date 2006-01-20 Time 17:34 Sent To  
Notes
***NONE***