Plan Review Details - Permit 05091648
Plan Review Stops For Permit 05091648
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-05-16 Cont ID  
Sent By lursu Date 2006-05-16 Time 15:45 Rev Time 0.00
Received By lursu Date 2006-05-16 Time 15:45 Sent To  
Notes
2006-05-16 00:00:00PERMIT ATTACHED TO EXT# 0012 FOR BLDG 16
 :4500 BARTOLO LN.LU
2006-05-15 00:00:00NEEDS!!!

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-30 Cont ID  
Sent By rmcdouga Date 2006-05-30 Time 11:23 Rev Time 0.00
Received By rmcdouga Date 2006-05-30 Time 11:23 Sent To P
Notes
2006-05-30 00:00:00DENIED
  
 1) THE PLANS MUST BE STAMPED BY PALM
 BEACH COUNTY FOR IMPACT FEES. THE PLAN
 REVIEW NUMBER ON THE PLANS MUST
 CORRESPOND WITH THE P.R. NUMBER ON THE
 IMPACT FEE RECEIPT.
  
 2) SUBMIT FIRE SPRINKLER PLANS FOR THE
 REQUIRED NFPA 13 SYSTEM. THIS IS
 REQUIRED BY FBC 104.3.1.1 OF THE CITY OF
 W.P.B. AMENDMENTS TO THE 2001 FBC.
  
 3) THE GARAGE FLOOR/CEILING ASSEMBLY IN
 DETAIL 17 ON A 10.0.0 DOES NOT
 CORRESPOND TO THE FC 5517 FIRE RATED
 ASSEMBLY LISTED IN THE GYPSUM
 ASSOCIATION MANUAL. PLEASE CORRECT.
  
 4) NUMBER 20 ON THE DOOR SCHEDULE
 SPECIFIES A VENTED GARAGE DOOR. THE
 PRODUCT APPROVAL FOR THE GARAGE DOOR
 DOES NOT INDICATE VENTS IN THE DOOR.
  
 5) REVISE DETAIL 11 ON A 10.0.0 TO
 SPECIFY THE 2001 FBC AND NOT THE CURRENT
 EDITION OF THE STANDARD BUILDING CODE.
  
 6) THE DRAWINGS ATTACHED TO THE STATE
 PRODUCT APPROVAL FOR THE STEEL DOOR FROM
 MASONITE INTERNATIONAL ARE FOR A 6'-8"
 DOOR AND THE PLAN SPECIFIES AN 8'-0"
 DOOR. SEE FL 4940.3 AND DRAWING
 DWG-MA-FLO 133-05.
  
 7) SUBMIT PRODUCT APPROVALS FOR THE
 TRUSS CONNECTORS. (SIMPSON-HETAL 12 &
 16, USP-USC) THE FL COVERSHEET SUBMITTED
 FOR THE USP HANGERS AND COLUMN BASES &
 CAPS HAS A WINDOW MULLION NOA ATTACHED
 TO IT.
  
 8) THE MIAMI-DADE NOA FOR THE SINGLE
 HUNG WINDOWS IS INCOMPLETE. THERE ARE
 SHEETS WITH ANOTHER NOA NUMBER ATTACHED
 AT THE REAR OF THE SH WINDOW NOA.
  
 9) THE DECORATIVE BAHAMA SHUTTERS WILL
 REQUIRE A SEPARATE PERMIT.
  
 10) FS 713.13 IF THE IMPROVEMENT
 DESCRIBED IN THE NOTICE OF COMMENCEMENT
 IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS VOID AND OF NO FURTHER EFFECT.
 (THE NOC WILL NEED TO BE RE-RECORDED
 BEFORE THE PERMIT IS ISSUED.)
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-03 Cont ID  
Sent By rmcdouga Date 2006-02-03 Time 10:12 Rev Time 0.00
Received By rmcdouga Date 2006-02-03 Time 10:12 Sent To  
Notes
2006-02-03 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE COUNTY IMPACT FEE STAMP DOES NOT
 HAVE THE PLAN REVIEW NUMBER ON THE
 PLANS. PLANS MUST BE RETURNED TO THE
 COUNTY TO HAVE THIS NUMBER NOTED ON THE
 PLANS.
  
 3) FL. BLD CODE 1606.1.7 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4) IN ORDER TO DETERMINE THE PERCENTAGE
 OF WALL AREA ALLOWED AS OPENINGS BY FBC
 TABLE 600, SUBMIT A SURVEY INDICATING
 THE LOCATIONS OF THE ASSUMED PROPERTY
 LINES BETWEEN THE BUILDINGS.
  
 5) PROVIDE AN AREA CALCULATION TABLE
 LISTING THE FLOOR AREA BREAKDOWNS BY
 FLOOR FOR EACH UNIT AND THE TOTALS FOR
 ALL SIX UNITS.
  
 6) THE FBC DOES NOT ALLOW HEIGHT AND
 AREA INCREASES FOR NFPA 13R SPRINKLER
 SYSTEMS. SEE FBC TABLE 500 FOOTNOTE (D).
  
 7) THE WALL AND FLOOR/CEILING ASSEMBLIES
 BETWEEN THE GARAGE AND LIVING SPACE ARE
 REQUIRED TO HAVE A ONE HOUR FIRE RATING.
  
 8) THE GUTTER DOWNSPOUTS ARE REQUIRED TO
 DISCHARGE ONE FOOT AWAY FROM THE
 STRUCTURE PER FBC 1503.4.4.
  
 9) THE DOOR TO THE EXIT STAIRS AT THE
 SECOND FLOOR MUST PROVIDE A 32" CLEAR
 OPENING FROM THE FACE OF THE DOOR TO THE
 STOP WITH THE DOOR OPEN 90 DEGREES. SEE
 FBC 1003.2.1 AND 1003.2.2
  
 10) SHOW COMPLIANCE WITH FBC MECH. TABLE
 403.3 FOR REQUIRED OUTDOOR AIR
 VENTILATION AT GARAGES OF 100 CFM PER
 CAR.
  
 11) WALL SECTION #4 ON A-7.01 IS
 MISLABELED FOR GENERAL NOTES 4 AN 10.
  
 12) SPECIFY THE EXTERIOR FINISH AT THE
 UNDERSIDE OF THE BAY WINDOW SHOWN ON
 A-7.1.1. SPECIFY THE EXTERIOR SHEATHING,
 LATH AND STUCCO. NOTE: SEE ASTM C 926
 FOR REQUIRED STUCCO THICKNESS.
  
 13) SPECIFY THE MEAN ROOF HEIGHT OF THE
 STRUCTURE. THIS IS THE VERTICAL DISTANCE
 FROM FINISHED GRADE TO THE A POINT AT
 THE AVERAGE HEIGHT OF THE ROOF.
  
 14) PROVIDE A DETAIL OF THE BALCONY
 GUARDRAILS. SPECIFY ATTACHMENTS, SPACING
 OF INTERMEDIATE RAILS, ETC.
  
 15) SPECIFY THE METHOD OF ATTACHMENT FOR
 THE ROOF TILES. THE PRODUCT APPROVAL
 THAT WAS SUBMITTED HAS AN ATTACHMENT
 RESISTANCE MOMENT OF 24.5 FT-LBF FOR
 MORTAR SET TILE. FOR 140 MPH EXPOSURE B
 WITH 40FT MRH, THE REQUIRED MOMENT IS
 28.3 FT-LBF. PLEASE REVISE ROOF TILE
 DETAILS TO COMPLY WITH CODE.
  
 16) UL ASSEMBLY U 906 HAS A 2 HOUR FIRE
 RATING NOT ONE HOUR AS SPECIFIED ON THE
 PLANS FOR WALL TYPES IN DETAILS 2 AND 6
 ON A-10.00.
  
 17) THE DRYWALL SPECIFIED IN THE RATED
 ASSEMBLY IN DETAIL 5 ON A 10.2.0 SHOULD
 BE FIRE-SHIELD C NOT "D". PLEASE
 CORRECT.
  
 18) PROVIDE INFORMATION FOR MECHINICAL
 DUCT PENETRATIONS THROUGH THE FIRE RATED
 ASSEMBLIES.
  
 19) TRUSS LAYOUT AND DRAWINGS ARE
 REQUIRED TO BE REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD FOR THE
 STRUCTURE.
  
 20) THE UPLIFT LOAD VALUES LISTED IN THE
 TRUSS ANCHOR SCHEDULE ON S-3 FOR THE
 SIMPSON HETAL 16 & 20 ARE INCORRECT.THE
 ONE THIRD STRESS INCREASE FOR STEEL
 CALCULATIONS IS NO LONGER ALLOWED. SEE
 THE 2005 SIMPSON CATALOG.
  
 21) THE HUGHES "USC" CONNECTORS ALSO
 HAVE INCORRECT UPLIFT VALUES. HUGHES WAS
 PURCHASED BY USP SEVERAL YEARS AGO AND
 IS LONGER IN BUSINESS. SEE THE 2005 USP
 CATALOG FOR VALUES. UPDATE THE TRUSS
 ANCHOR SCHEDULE.
  
 22) UNDER KEY NOTES/ LEGEND ON A-4.0 AND
 OTHER SHEETS REFERENCE IS MADE TO SHEET
 A-13 FOR THE WALL TYPES. HOWEVER, THERE
 IS NO SHEET A-13.
  
 23) THE ENERGY CALCULATIONS CONTAIN
 SEVERAL ERRORS. THESE ARE CONSIDERED
 MULTIFAMILY NOT SINLE FAMILY. THE
 ADJACENT WALL AT THE GARAGE IS WOOD
 FRAME AND THE CEILING INSULATION IS
 SPECIFIED AS R-20 ICYENE.
  
 24)PROVIDE MANUFACTURER'S SPECIFICATIONS
 FOR THE ICYENE INSULATION.
  
 25) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. IN
 ADDITION TO THE COVERSHEET THE
 INSTALLATION INSTRUCTIONS OR PRODUCT
 EVALUATION AS LISTED ON THE STATE
 WEBSITE IS ALSO REQUIRED.
  
 26) SUBMIT STATE PRODUCT APPROVALS FOR
 THE TRUSS CONNECTORS AND GARAGE DOORS.
  
 27) THE MIAMI-DADE NOA FOR THE SINGLE
 HUNG WINDOWS HAS THE INFO FROM THE FIXED
 GLASS WINDOWS ATTACHED TO THE NOA
 COVERSHEET.
  
 28) SUBMIT MANUFACTURER'S SPECS. FOR THE
 DOOR CLOSERS.
  
 29) THE CALCULATED VALUE OF THE
 STRUCTURE HAS BEEN INCREASED TO
 $912,590.00. ADDITIONAL PERMIT FEES OF
 $2740.49 ARE REQUIRED.
  
 30) THE FIRST FLOOR PLAN ON SHEETS
 A-4.0.1 AND A-4.3.1 SHOW THE DOOR FROM
 THE GARAGE OPENING DIRECTLY INTO A GREAT
 ROOM. FBC 411.2.8 PROHIBITS OPENINGS
 FROM A PARKING GARAGE DIRECTLY INTO A
 ROOM USED FOR SLEEPING PURPOSES. PLEASE
 INDICATE ON THE PLANS AT THE GREAT ROOM
 THAT THIS ROOM IS NOT TO BE USED FOR
 SLEEPING PURPOSES.
  
 31) FIRE SPRINKLER PLANS ARE REQUIRED TO
 BE SUBMITTED WHEN REQUIRED FOR HEIGHT OR
 AREA INCREASE ALLOWED BY FBC TABLE 500.
 SEE FBC 903.2 AND 104.3.3.1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-05-15 Cont ID  
Sent By dpalmer Date 2006-05-15 Time 20:11 Rev Time 0.00
Received By dpalmer Date 2006-05-15 Time 19:59 Sent To  
Notes
2006-05-15 00:00:00***** NOTES REDLINED *******
  
  
  
  
 ** PLEASE SEE #1 GEC SHOWN, WHERE A 2/0
 MIN IS REQUIRED PER 250.66BASED ON THE
 SEC'S SHOWN ON RISER.
  
 ** PLEASE SEE 424.3B FOR MIN OCP SHALL
 BE 125% FOR AHU'S. PLEASE SEE OCP HAS
 NOW BEEN DECREASED TO 40A'S???
  
 PLEASE KNOW, THE ABOVE NEED ONLY BE
 REVISED IF MAKING OTHER ELECTRICAL
 REVISIONS. ALL ELECTRICAL REVISIONS,
 MUST BE SUBMITTED FOR REVIEW BEFORE
 ROUGH ELECTRICAL INSPECTION.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-10-17 Cont ID  
Sent By dpalmer Date 2005-10-17 Time 07:18 Rev Time 1.00
Received By dpalmer Date 2005-10-14 Time 17:59 Sent To  
Notes
2005-10-17 00:00:00********* UNSAT *********
  
  
 1)NOTE: PLEASE SEE PROJECT IS SUBMITTED
 AS CONDO'S YET ELECTRICALSERVICES
 PROVIDED IS SHOWN AS EACH WOULD BE A
 TOWNHOUSE (FEE SIMPLE).
 PLEASE SEE WATER SERVICE SHOWS
 MULTI-FAMILY BLDG.
 PLEASE KNOW, IF THESE AS MULTI-FAMILY
 CONDO BLDGS; ONE SERVICE FOR EACH BLDG
 IS PERMITTED,230.2,230.70MAINS WILL BE
 REQUIRED TO BE GROUPED PER 230.72.
 MCB'S SHOWN IN EACH GARAGE PANEL IS
 PERMITTED.
 PLEASE ADJUST SERVICE FOR BLDG.
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 AIC RATINGS ARE SHOWN FOR EACH PANEL,
 BUT WILL ALSO BE REQUIRED FOR MAINS.(NEW
 SERVICE).
  
 3)NOTE: PLEASE CLARIFY LOCATION OF
 DISHWASHER RECEPT. APPEARS TO BE SHOWN
 BEHIND UNIT? THIS IS ONLY A NOTE:
  
 4))NOTE: PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
 PLEASE SEE PLANS REDLINED FOR SOME
 MISSING W/IN 2' OF THE END OF A COUNTER
 OR 4' SPACING.
 UNIT "A"/STANDARD 2FLR,,,
  
 5)NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
 PLEASE SEE THESE HAVE BEEN REDLINED AT
 LOCATIONS OF NOTES.
 UNIT "B",3RD FLR OPT 6 2'OF WALL, UNIT
 "A"2ND FLR, WALL APPEARS TO BE OVER 12'?
 PLEASE SEE A COUPLE OF OTHER LOCATIONS.
  
 6)NOTE: PLEASE SEE LOCATION OF A
 RECESSED LT FIXTURE IN CLOSET
 WASHER/DRYER LOCATION. THESE LOCATIONS
 TYPICALLY CONTAIN SHELVING ABOVE THE
 WASHER/DRYER'S. PLEASE SEE 410.8 FOR MIN
 CLEARENCE FROM LT AND FIXTURE TYPES.
 (WALL MOUNT)? AS SHOWN IN OTHER CLOSETS?
  
 7 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS NEEDS
 TO BE SHOWN ABOVE THE GEN. KT/RECEPT
 LOADS. THIS SHOULD BE ABOVE THE FIGURED
 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 8)NOTE: PLEASE LIST ALL THE REQUIRD ARC
 FAULT PROECTED CIRCUITS AS REQUIRED PER
 2002 210.12
 PLEASE KNOW, SD'S ARE BEING SHOWN
 CIRCUITED TO KITCHEN LIGHTING CIRCUIT,
 THIS IS OK, HOWEVER PLEASE KNOW, THIS
 WOULD ALSO REQUIRE ARC FAULT PROTECTION
 FOR THIS ADDITIONAL CIRCUIT.
 THIS IS ONLY A NOTE:
  
 9)NOTE: PLEEASE SEE NFPA-72 (2002)
 EDITION,11.8.3.5.
 PLEASE PLACE NOTE ON PLANS WHICH STATES
 LOCATIONS OF SD'S TO BE A MIN OF 3' FROM
 BATH(S) AND KITCHEN DOORS AND 20' FROM
 KITCHEN COOKING APPLIANCES.
 ** PLEASE SEE EXCEPTION TO 20' FROM
 COOKING WITH TYPE OF SD USED.**
 PLEASE SEE PLANS SHOWS A SD IN KITCHEN
 AREA AT THIS TIME.
  
 10)NOTE: PLEASE SEE MECHANICAL NOTES
 PERTAINING TO "DRYER BOOSTER FANS".
 AS PER MECHANICAL THESE MAY NOT BE
 PERMITTED AND ANY COMMENT THEY MAY HAVE
 WILL DIRECTLY AFFECT ELECTRICAL PLANS.
 THIS IS A NOTE, AS IT IS NOT AN NEC
 ISSUE.
 PLEASE SEE ALL SYSTEMS DO HAVE BE
 LISTED.110.3,90.7
  
 11)NOTE: PLEASE SEE SHEET 0.0.0, WHICH
 REFERENCES THE 2000 NFPA-101. PLEASE
 KNOW, AS OF JAN 1ST, 2005, WE ARE
 CURRENTLY UNDER THE 2003 NFPA-101.
  
  
 12)NOTE: PLEASE VERIFY OCP FOR AHU,
 HEAT, MIN 125%. 424.3B.
  
 13)NOTE: PLEASE SEE PLANS DO NOT
 INDICATE ANY ACCESIBLITY TO GFI RECEPTS
 SHOWN FOR JACUZZI/WHIRLPOOL TUB.
  
 14)NOTE: PLEASE SEE 406.2B,210.21B3&4
 WHICH REQUIRES THE MAX OCP FOR A 50A
 RANGE RECEPT TO BE 50A'S. PLEASE SEE A
 2P-60A BRKR IS SHOWN.
  
 15)NOTE: PLEASE PROVIDE AREA AND ROOM
 DESIGNATIONS ON PLANS. PLEASE SEE SOME
 ARE MISSING.
 THIS WILL ALSO BE REQUIRED TO DETERMINE
 CIRCUITING FOR DINING AREAS.
  
  
 ** PLEASE KNOW, MANY ITEMS HAVE BEEN
 REDLINED ON PLANS FOR LOCATIONS OF
 NOTES.
  
 ** PLEASE KNOW, A REVIEW OF MAIN
 ELECTRICAL SERVICECAN NOT BE DONE AT
 THIS TIME, AS SERVICE WILL BE CHANGING.
  
 PLEASE SEE ANY OTHER POSSIBLE COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLF/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 ** PLEASE SEE THIS MAY BE CONSIDERED A
 "THRESHOLD" PROJECT. IF SO, THREE SETS
 OF PLANS WILL BE REQUIRED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2005-10-04 Cont ID  
Sent By mamini Date 2005-10-04 Time 08:54 Rev Time 0.50
Received By mamini Date 2005-10-04 Time 08:54 Sent To  
Notes
2005-10-04 00:00:00PASSED:
  
 1. SEE PERMIT # 04120439 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-11-18 Cont ID  
Sent By mwennerg Date 2005-11-18 Time 13:06 Rev Time 0.00
Received By mwennerg Date 2005-11-18 Time 13:06 Sent To  
Notes
2005-11-18 00:00:00******PROVISO******
  
 1) LIFE SAFETY TO COMPLY WITH NFPA 101,
 2003 EDITION.
  
 2) SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED FOR FIRE SPRINKLER SYSTEM, THAT
 SHALL BE MONITORED BY CENTRAL STATION
 SERVICE.
  
 3) MULTI-PURPOSE FIRE EXTINGUISHERS ARE
 REQUIRED FOR EACH UNIT.
  
 4) AN ADDRESS IS REQUIRED FOR EACH UNIT.
  
 5) PLANS INDICATE THAT SHOP DRAWINGS FOR
 PRE-ENGINEERED STAIRS WILL BE PROVIDED,
 THAT SHALL BE IN COMPLIANCE WITH NFPA
 101, AND FBC REQUIREMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-17 Cont ID  
Sent By adarroug Date 2006-03-17 Time 17:09 Rev Time 0.00
Received By adarroug Date 2006-03-17 Time 17:09 Sent To  
Notes
2006-04-11 00:00:00TO "COMM" BD#4
2006-03-17 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-03 Cont ID  
Sent By rmcdouga Date 2006-02-03 Time 10:13 Rev Time 0.00
Received By rmcdouga Date 2005-10-03 Time 16:05 Sent To  
Notes
2005-10-03 00:00:00TO "COMM" BD#46/PLANS ON RACK/17 ROLLS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-05-24 Cont ID  
Sent By pkrauss Date 2006-05-23 Time 11:18 Rev Time 0.00
Received By pkrauss Date 2006-05-23 Time 09:41 Sent To  
Notes
2006-05-23 00:00:00PROVISO:2001 FBC/BUILDING 16/6 UNITS
 RESPONSE TO COMMENTS FROM REVIEW DATED
 11/29/05:
  
 PLEASE REVISE PLANS TO REFLECT THE
 IMPLEMENTATION OF THE PROVISO'S.
  
 COMMENT #4:OUTSIDE AIR CALCULATIONS
 ARE INDICATED ON PLAN SHEET M0.1. PLEASE
 NOTE, INFLITRATION RATES ARE "MAXIMUM"
 RATES AND MAY NOT ACTUALLY EXIST. PLEASE
 SHOW COMPLIANCE WITH 2001 FMC 402.2,
 402.2.1 OR TABLE 403.3.PLEASE NOTE,
 PLAN SHEET M2 ALSO INDICATES O.A. DUCT.
 PROVIDE CALCULATIONS.
  
 COMMENT #5:RESPONSE TO COMMENT
 INDICATES DRYER DUCT WILL BE ABOVE THE
 AHU CLOSET.PLAN SHEET M0.1 THE AHU
 MOUNTING DETAIL ALSO STATES NO
 COMBUSTIBLES ALLOWED IN THE AHU CLOSET
 AS IT SERVES AS A PLENUM.THE DOOR
 SCHEDULE INDICATES THE LOUVERED DOOR IS
 WOOD.PLEASE CLARIFY IF THIS WILL MEET
 THE 25 FLAME/50 SMOKE INDEX WHEN TESTED
 IN ACCORDANCE WITH ASTM 84.
  
 COMMENT 6:OK. PLEASE NOTE, SPECIFIC
 DRYERS ARE TO BE INSTALLED FOR FINAL
 INSPECTION.
  
 COMMENT #7: OK.PLEASE NOTE, PLAN SHEET
 M1 UNIT #46 A(R) DOES NOT REFLECT THE
 ARCHITECTURAL PLAN SHOWN ON A-2.0.1 &
 A-4.0.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-11-29 Cont ID  
Sent By pkrauss Date 2005-11-29 Time 15:57 Rev Time 0.00
Received By pkrauss Date 2005-11-29 Time 15:15 Sent To  
Notes
2005-11-29 00:00:00DENIED:BUILDING 16 / 2001 FBC
 1.PLAN SHEET A-0.0.0 PROJECT
 INFORMATION INDICATES TYPE VI,
 UNPROTECTED SPRINKLERED.PLEASE
 INDICATE WHICH SYSTEM WILL BE UTILIZED
 (13, 13R, 13D, ETC).PLEASE NOTE,
 ADDITIONAL COMMENTS MAY BE GENERATED BY
 THE RESPONSE GIVEN.
  
 2.PLAN SHEET A-4.0.1 KEY NOTES/LEGEND,
 ITEM #25 '1HR CHASE REFER TO 11/A-13'.
 PLAN SHEET A-13 WAS NOT SUBMITTED FOR
 REVIEW.
  
 3.PLAN SHEET M1 PLEASE CLARIFY RATING
 OF THE WALL BETWEEN THE GARAGE & THE
 RESIDENCE.THE ARCHITECTURAL PLANS ARE
 NOT CLEAR AS TO WHERE THE 1HR RATING
 ENDS (AT THE SLAB OR AT THE RATED
 CEILING).PLEASE NOTE DUCTS PENETRATING
 RATED WALL SHALL COMPLY WITH 2001 FMC
 607.1.3.
  
 4.PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2001 FMC
 TABLE 403.3.
  
 5.PLAN SHEET M2, THE DRYER EXHAUST
 APPEARS TO RUN THROUGH THE AHU.PLEASE
 NOTE, EXHAUST DUCTS SHALL NOT PASS
 THROUGH A PLENUM PER 2001 FMC 601.3.
  
 6.DRYER EXHAUST EXCEEDS THE 25 FT
 MAXIMUM REQUIRED LENGTH PER 2001 FMC
 504.6.PLAN SHEET E2.2 INDICATES BF
 (BOOSTER FAN?).PLEASE NOTE,
 INSTALLATION OF BOOSTER FANS WILL BE
 REVIEWED BY THE BUILDING OFFICIAL UNDER
 "ALTERNATE MATERIALS & METHODS" 2001 FMC
 103.7.1.PLEASE PROVIDE THE FOLLOWING
 INFORMATION FOR REVIEW 1) A LETTER FROM
 ENGINEER EMPLYED BY THE DRYER
 MANUFACTURER STATING THE INSTALLATION OF
 THE BOOSTER FAN IS ACCEPTABLE AND WILL
 NOT VOID THE WARRANTY OF THE DRYER.2)
 MEANS OF NOTIFYING THE OWNER SHOULD THE
 BOOSTER FAN.3) MANUFACTURER'S
 SUBMITTAL & INSTALLATION DATA FOR THE
 BOOSTER FAN.4) PROVIDE ALL PERTINENT
 INFORMATION FOR ALL TRAADES MECHANCIAL,
 ELECTRICAL, FIRE, ETC. FOR THE
 INSTALLATION OF BOOSTER FANS.
  
 7.TRANSFER GRILLES SHALL BE SIZED IN
 ACCORDANCE WITH 2001 FMC 601.4 EXCEPTION
 2 & 3.
  
 IF YOU HAVE ANY QUESTISONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-05-31 Cont ID  
Sent By kstevens Date 2006-05-31 Time 08:29 Rev Time 0.00
Received By kstevens Date 2006-05-31 Time 08:29 Sent To  
Notes
2006-05-31 00:00:00 
  
  
  
 **************PASSED/PROVISO************
  
  
 SANITARY BUILDING DRAIN SHALL BE A
 MINIMUM OF 4 FT OFF THE FOOTER PER
 SECTION 307.4.
  
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-11-29 Cont ID  
Sent By kstevens Date 2005-11-29 Time 08:06 Rev Time 0.00
Received By kstevens Date 2005-11-29 Time 08:06 Sent To  
Notes
2005-11-29 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1. SHTS P2.1.1, P-2.2, P-3.1.1, AND
 P-3.2.4 WATER HAMMER ARRESTORS ARE
 REQUIRED AT THE WASH MACHINES OF ALL
 UNITS. PER SECTION 604.9. - ALL WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE",
 NOT IN THE CEILING AS SHOWN IN SOME
 CASES. PDI-WH 201 AND MANUF INSTALLATION
 INSTRUCTIONS.
 2. IF INDIVIDUAL METERS NO BACKFLOW
 DEVISE IS REQUIRED, BUT IF SINGLE METER
 AN RPZV BACKFLOW WILL BE REQUIRED ON THE
 WATER SERVICE. PLEASE CLARIFY. SECTION
 608.13.2.
 3. SHT P3.2.4 RISER AND FLOOR PLAN FOR
 UNIT B. RISER DOES NOT REFLECT THE FLOOR
 PLAN, AND AS SHOWN, KITCHEN SINK ARMS
 ARE RUNNING IN FRONT OF THE RANGE ABOVE
 THE FLOOR. PLEASE CLARIFY. SECTION
 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2006-01-20 Cont ID  
Sent By mmclean Date 2006-01-20 Time 17:33 Rev Time 0.00
Received By mmclean Date 2006-01-20 Time 17:33 Sent To  
Notes
***NONE***