Plan Review Details - Permit 05091639
Plan Review Stops For Permit 05091639
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2006-03-28 Cont ID  
Sent By lursu Date 2006-03-28 Time 15:11 Rev Time 0.00
Received By lursu Date 2006-03-28 Time 15:10 Sent To  
Notes
2006-03-28 00:00:00NEW ADDRESS ASSIGNED TO BLDG 4:
 1596 VANDAN DR. ( EXT #0002 OFF 715 HANK
 AARON DR - MAIN SITE ADDRESS FOR THIS
 DEVELOPMENT: MIZNER LAKES)

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-03-01 Cont ID  
Sent By lursu Date 2006-03-01 Time 14:39 Rev Time 0.00
Received By lursu Date 2006-03-01 Time 14:37 Sent To  
Notes
2006-03-01 00:00:00NEED SITE PLAN AND PROPOSED STREET NAMES
 LIST BEFORE ISSUING AN ADDRESS TO BLDG
 4.CALLED THE CIVIL ENG FIRM"
 CONSULTECH"@ 1954-438-4300 TO FURNISH
 THE INFO .

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-16 Cont ID  
Sent By jwitmer Date 2006-02-16 Time 10:23 Rev Time 4.00
Received By jwitmer Date 2006-02-16 Time 10:23 Sent To  
Notes
2006-02-16 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05091639MIZNER LAKES
  
 ADD: XXXN CONGRESS BLDG# 4
  
 CONT: AVS CONSTRUCTION
 TEL: (954)655-5162
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 ARCH:SLATTERY & ASSOC
 2060 NW BOCA RATON BLVD
 BOCO RATON, FL
 TEL: (561) 392-3848
 FAX: (561) 392-5402
  
 STRUC: CHM STRUCTURAL ENG, LLC
 9200 S DADELAND, SUITE 409
 MIAMI, FL
 TEL (305) 667-1621
 FAX (305) 662-9673
  
 ARCHITECTURAL SHEET A.002, BUILDING
 DATA DOES NOT IDENTIFY TO WHICH CODE
 THIS BUILDING WAS DESIGNED TO. THE
 BUILDING DATA SHEET ALSO DOES NOT
 PROVIDE THE MINIMUM BUILDING DESIGN
 GOVERNED BYINTENDED OCCUPANCYSEE
 503.1.2 AND TABLE 500.
  
 ARCHITECTURAL SHEET A-251 INDICATES THAT
 THIS PLAN WAS DEVELOPED UNDER THE 2001
 FBC, BUT HAS CODE REFRENCES FOR THE 2004
 FBC. S-0.00 ALSO INDICATES THE PLANS
 WERE DEVELOPED UNDER THE 2001 FBC.
 NOTE A-251 OCCUPANCY R-3 IS FOR SINGLE
 FAMILY THIS WILL BE AN R2 OCCUPANCY
 CLASSIFICATION.
  
 THIS REVIEW WILL BE COMPLETED UNDER THE:
 2001 FBC
 TYPE: II, SPRINKLERED NFPA 13
 ---NOTE---
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
 NOTE: FL S S 713.13(2) IF THE NOC IS
 RECORDED AT THE CLERK OF THE COURT AND
 WORK HAS NOT STATED WITH 90 DAYS OF
 RECORDING IT IS NULL & VOID REQUIRING
 RE-RECORDING.
  
 2)FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 3) FBC 13-103.1.2 BEFORE A BUILDING
 PERMIT CAN BE ISSUED, THE SUBMITTED
 ENERGY CODE COMPLIANCE FORMS SHALL BE
 SIGNED BY THE BUILDING OWNER, THE
 OWNER'S ARCHETECT OR OTHER AUTHORIZED
 AGENT LEGALLY DESIGNATED BY THE OWNER.
  
 4) ARCHITECTURAL SHEETS ARE COPIES OF
 SIGNATURE:
 PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6)WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 7) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO
 BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CON- TAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 8) CONTACT LILI URSA FOR ADDRESSING
 REQUIREMENTS @ (561)822-1239.
  
 9) ADDITIONAL INFORMATION REQUIRED FOR
 RECORD KEEPING PURPOSES 104.1.2*:
 10C)A) FLOOD ZONE
 10C)B) FLOOD ELEVATION (IF A ZONE)
 10C)C) LOMAR (IF A ZONE)
 10C)D) NUMBER OF UNITS
 10C)E) NUMBER OF FLOORS
 10C)F) NUMBER OF BEDROOMS
 10C)G) NUMBER OF ROOMS
 10C)H) NUMBER OF BATHROOM
 10C)I) SQ FT LIVING SPACE(TOTAL)
 10C)J) SQ FT FOOT PRINT
 10C)K) SQ FT UNDER ROOF (TOTAL)
  
 10)SHEET A-002
  
 10A) AS NOTED ABOVE PLANS ARE TO
 INDICATE THE MINIMUM BUILDING TYPE,
 503.1.2& TABLE 500.
  
 11) SHEET A-102;
  
 11A)DEFINITION, TERM TOWNHOUSE:A SINGLE
 FAMILY DWELLING CONSTRUCTED IN A SERIES
 OR GROUP OF ATTACHED UNITS WITH PROPERTY
 LINES SEPARATING EACH UNIT. IF TRUELY
 TOWNHOUSE CONSTRUCTION PROVIDE A REPLAT
 OF THE LAND SHOWING INDIVUAL LOT LINES.
 OTHERWISE RENAME THESE UNITS TO SOME
 OTHER TERMINOLOGY. PLANS ARE NOT BUILT
 TO THE TOWNHOUSE STANDARD FOUND UNDER
 SECTION704.4(1-5).
  
 11B) THERE APPEARS TO BE NUMBERS ON
 VARIOUS ITEMS OF THE PLANS AND TO THE
 RIGHT NOTES STATING WITH # 1 BUT NO
 OTHER INFORMATION? COMPLETE.
  
 12 ) SHEET A.300- A.304STAIR TOWER # 1
 ON EACH FLOOR MISSING CLEARENCE AT DOOR
 TO STAIRS.18"X60" LATCH SIDE OF DOOR.
 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARENCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARENCES SHALL BE
 CLEAR & LEVEL.
  
 13) A201/ A202
 13A) PLANS DO NOT PROVIDE A CUT SECTION
 THROUGH STAIRWAYS INDICATING COMPLIANCE
 WITH GUARDRAILS FOR HEIGHT (HEAD
 PROTECTION).COMMON PROBLEM TO ALL
 STAIRWAYS,11-4.4.2 HEAD ROOM. WALKS,
 HALLS, CORRIDORS, PASSAGEWAYS, AILES OR
 OTHER CIRCULATION SPACES SHALL HAVE 80
 INCHES MINIMUM CLEAR HEAD ROOM (SEE
 FIGURE 8(A)). IF VERTICAL CLEARENCE OF
 AN AREA
  
 ADJOINING AN ACCESSIBLE ROUTE IS REDUCED
 TO LESS THAN 80 IN. (NOMINAL
 DIMENSION),
 A BARRIER TO WARN BLIND OR VISUALLY-
 IMPARED PERSONS SHALL BE PROVIDED. (SEE
 FIGURE 8(C-1)).
  
  
 13B ) STAIR TOWER# 4 WINDOWS WITHIN
 10'-0" OF TOWER OPENINGS SEE 1006.1.3.2
  
 13C) GATES OR DOORS BY THE DRIVE-IN
 GATES ARE NOT ON DOOR SCHEDULE ?
  
 13D) PROVIDE THE ACCESSIBLE PATH (MEANS
 OF EGRESS)FROM THE 2 STORY LOFT UNITS ON
 THE FIRST FLOOR AROUND THE PERIMETER OF
 THE PARKING GARAGE. THE PATHWAY THAT
 BACKS UP TO THE COMMERCIAL BUILD OUT
 LATER, RIGHT SIDE OF PAGE HAS 2
 PROBLEMS,
 FIRST THE COLUMNS STICK OUT A FOOT
 MAKING A CLEAR ACCESSIBLE PATH OF ONLY
 36", THE SECOND ISSUE IS THE DOORS SWING
 OUT AS REQUIRED BY CODE BUT THEY SWING
 OVER THE MEANS OF EGRESS 36" ONLY
 LEAVING 12" CLEAR 1/2 OF THE REQUIRED
 44" IS 22" MINIMUM. ALSO SEE DOORS 107,
 108.
  
 13E) ON THE RIGHT SIDE OF 201- 202 THE
 COMMERCIAL AREA, IT APPEARS THERE IS A
 HANDICAPPED RAMP AND STAIRS, BUT NO
 SECTIONS THROUGH FOR FURTHER DETAILS? NO
 ELEVATIONS PROVIDED? IT APPEARS THAT THE
 EXHAUST FROM THE PARKING GARAGE IS
 WITHIN 5'-0" OF THE HANDICAPPED RAMP, IS
 THERE FLARINGS TO DIRECT EXHAUST FROM
 THE RAMP?
  
 13F) HANDICAPPED SPACE WITHIN PARKING
 GARAGE NEEDS TO SHOW VAN ACCESSIBLE
 PARKING.11-4.1.2(5)(B) IN PARKING
 STRUCTURES, ONE IN EVERY EIGHT
 ACCESSIBLE SPACES, BUT NOT LESS THAN
 ONE, SHALL BE "VAN ACCESSIBLE" AND SHALL
 BE DESIGNED AS REQUIRED BY 11-4.6.3.
 THE VERTICAL CLEARANCE AT SUCH SPACES
 SHALL COMPLY WITH ?11-4.6.5.ALL SUCH
 SPACES MAY BE GROUPED ON ONE LEVEL OF A
 PARKING STRUCTURE.WHEN SUCH SPACES ARE
 PROVIDED IN A PARKING STRUCTURE AND ONLY
 ONE IN EIGHT MEET THE HEIGHT REQUIREMENT
 OF 11-4.6.5, THEY SHALL BE DESIGNATED AS
 REQUIRED BY 11-4.6.4.
  
 13G) PROVIDE MORE INFORMATION, PLANS
 INDICATE A TRASH ROOM # 103 BUT THERE IS
 AN AREA # 124 TRAASH AREA? EXPLAIN?THIS
 AREA IS NOT AUTOMOBILE STORAGE BUT A S1
 STORAGE REQUIRING A 3HR SEPERATION. SEE
 TABLE 704.1.
  
 13H) THE 2 STORY LOFT UNITS DO NOT HAVE
 EXIT ACCESS CORRIDORS TO THESE UNITS.
 EXIT ACCESS CORRIDORS WILL BE REQUIRED
 BECAUSE THE GARAGE ENTRY DOOR IS THE
 PRIMARY ENTRY DOOR COVERED UNDER FAIR
 HOUSING. SEE FAIR HOUSING P. 1.22
 ELEVATORS MUST PROVDE ACCESS TO PRIMARY
 ENTRY FLOORS OF 2-STORY DWELLING IN
 ELEVATOR BUILDINGS. NOTED THE 2-STORY
 LOFT UNITS DO HAVE A FRONT DOOR WHERE
 STAIRS ARE PRESENT, THE ENTERIOR ENTRY
 DOOR IS CONSIDERED THE MAIN OR PRIMARY
 ENTRY DOOR.
 1001.1.3 MEANS OF EGRESS SHALL CONSIST
 OF CONTINUOUS AND UNOBSTRUCTED PATHS OF
 TRAVEL TO THE EXTERIOR OF A BUILDING.
 MEANS OF EGRESS SHALL NOT BE PERMITTED
 THROUGH KITCHENS, CLOSETS, RESTROOMS AND
 "SIMILAR AREAS" NOR THROUGH ADJACENT
 TENANT SPACES.
 THE BUILDING OFFICIAL HAS REVIEWED
 THE LAYOUT OF THIS PLAN AND INTERPRETS
 THROUGH THE GARGE AS SIMILAR AREAS.
 1001.1.4 WHEN UNUSUALLY HAZARDOUS
 CONDITIONS EXIST, THE BUILDING OFFICIAL
 MAY REQUIRE ADDITIONAL MEANS OF EGRESS
 TO ASSURE THE SAFETY OF THE OCCUPANTS.
  
 14) A.203:
  
 14A) STAIRWELL# 3 THERE IS A WALL JUST
 TO THE LEFT OF THE STAIRWELL, PROVIDE A
 SECTION THROUGH IS THIS A HANDRAIL OR A
 WALL ?
  
 14B) BOTTOM LEFT OF PAGE WHERE THE
 MATCHLINE STARTS THERE IS A AREA NO ROOM
 REFRENCE, IT APPEARS POSSIBLY A FENCE
 BLOCKS THIS AREA OFF?
  
 14C) FANS UPPER RIGHT INTAKE OR EXHAUST?
  
 14D) COLUMN LINE RIGHT SIDE OF PAGE NEXT
 TO THE COMMERCIAL AREA, CUTS INTO THE
 ACCESSIBLE ISLE, MEANS OF EGRESS,
 44"MINIMUM.
  
 15) A204:
  
 15A) DOOR 204 SWINGS AGAINST THE TRAFFIC
 FLOW TO THE STAIR TOWER# 1.
 1012.1.2 EGRESS DOORS SHALL BE SIDE
 SWINGING TYPE. DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS.
  
 15B) AREA JUST RIGHT OF STAIR TOWER# 1,
 IS THIS A WINDOW, OPEN, OR HANDRAIL?
  
 15C) LEFT SIDE OF PAGE COMMENT# 14 B),
 THERE IS A PAIR OF DOORS THAT SWING INTO
 THE REQUIRED EGRESS PATH AND A COLUMN
 THAT BLOCKS THE CLEAR AREA TO THE
 COLUMN, ONLY 1'-0" CLEAR. SEE 1012.1.4.
  
 16)A.205;
  
 16A) CONDO UNIT C-4 IT APPEARS THERE MAY
 BE A SHAFT, NO INFO NO CUT SECTION?
  
 16B) POOL EQUIPMEENT ROOM JUST ABOVE
 LEFT & RIGHT IT APEARS TO HAVE MASONARY
 WALLS(M3) WWITH SOME TYPE OF OPENING ,
 RAIL? NO SSECTION?
  
 16C) POOL PAVILION INDICATES A SECTION
 A304 BUT WRONG REFRENCE?PROVIDE SECTION
 OF SINK CABINET.
  
 16D) PROVIDE ADDITIONAL INFORMATION JUST
 TO THE LEFT OF THE POOL PAVILION THERE
 APPEARS TO BE A GRILL? IF GAS:
 SECTION 2808
 BARBECUES - FACTORY-BUILT
 FACTORY-BUILT BARBECUES SHALL BE OF AN
 APPROVED TYPE AND SHALL BE INSTALLED
 IN ACCORDANCE WITH THE MANUFACTURER'S
 INSTRUCTIONS.
  
 16E)POOL DECK PLAN DOES N'T INDICATE
 WHAT TYPE OF FINISH OTHER THAN THE PAVER
 DECK, WHAT ARE THE OTHER AREAS COVERED
 WITH? PLANS DO NOT PROVIDE SLOPE TO DECK
 DRAINS OR DECK DRAINS?
  
 16F) POOL DECK DRAINS WILL BE INSTALLED
 IN A RATED FLOOR, PROVIDE THE TYPE OF
 PIPE TO BE USED AND THE RATED ASSEMBLY
 FOR THIS INSTALATION.
 705.6 PENETRATIONS OF HORIZONTAL
 ASSEMBLIES. ALL PENETRATIONS OF A FLOOR,
 FLOOR/CEILING ASSEMBLY, OR THE CEILING
 MEMBRANE OF A ROOF/CEILING ASSEMBLY
 SHALL BE PROTECTED BY A SHAFT ENCLOSURE
 IN ACCORDANCE WITH 705.2 OR SHALL COMPLY
 WITH ?705.6.1 THROUGH 705.6.4.
 705.6.1 THROUGH-PENETRATIONS.
 THROUGH-PENETRATIONS OF FIRE RATED
 HORIZONTAL ASSEMBLIES SHALL COMPLY
 WITH 705.6.1.1 OR 705.6.1.2.
  
 16G)NOTE: SEE DEPARTMENT OF HEALTH
 [DOH] RULE 64E-9, FLORIDA ADMINISTRATIVE
 CODE AND CHAPTER 514, FLORIDA STATUTES
 FOR SECURITY & REQUIRED FENCING. TO BE
 IN PLACE AT TIME OF BUILDING C.O.
  
 16H) NOTE:13-412.1.ABCD.2.4.2 COVERS
 REQUIRED. SPAS AND HEATED SWIMMING POOLS
 SHALL BE EQUIPPED WITH A COVER DESIGNED
 TO MINIMIZE HEAT LOSS.TO BE IN PLACE AT
 TIME OF BUILDING C.O.
  
 16I) PROVIDE EXITING SIGNAGE FOR POOL
 DECK.1016.1.1 ILLUMINATION OF MEANS OF
 EGRESS SHALL BE PROVIDED IN ACCORDANCE
 WITH THIS SECTION FOR EVERY BUILDING AND
 STRUCTURE.FOR THE PURPOSES OF THIS
 REQUIREMENT, EXIT ACCESS SHALL INCLUDE
 ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS AND
 PASSAGEWAYS LEADING TO AN EXIT.FOR THE
 PURPOSES OF THIS REQUIREMENT, EXIT
 DISCHARGE SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS, WALKWAYS AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
  
 16J) STAIR TOWER# 4, THE DOOR SWINGS THE
 WRONG WAY:1012.1.2EGRESS DOORS SHALL BE
 SIDE SWINGING TYPE.DOORS SHALL SWING
 IN THE DIRECTION OF EGRESS
  
 17)A.206
  
 17A)PAIR OF DOORS # 351 SWING THE WRONG
 WAY AGAINST EXITING PATTERNS.1012.1.2.
  
 17B) RESIDENT STORAGE ROOM 313, TO BE
 CONSIDERED AN S1 REQUIRING 3 HR
 SEPERATION.TABLE 704.1.
  
 17C) SEE A-253 LIFE SAFETY PLAN STAIR
 TOWER# 1 AND DOOR 302 CAN'T ACCOMADATE
 THE OCCUPANT LOAD FOR THE UNITS AND THE
 POOL DECK, 1/2 THE LOAD OR 175 HAVE TO
 GO THROUGH DOOR 302. 175X.2=35" OF CLEAR
 OPENING, A 3'-0" DOOR CLEAR IS 34". THE
 STAIR IS 4'-4"/.3=173.3. DOOR 103 AT THE
 BOTTOM OF THE STAIR ALSO WILL BE TO
 SMALL TO ACCOMADATE THE OCCUPANT LOAD
 FROM THIS FLOOR.
  
 17D) STAIRWELL# 2 IT APPEARS THAT A
 SHAFT IS DIRECTLY IN FRONT OF THE
 STAIRWELL PROVIDE SECTION THROUGH GIVING
 WAAL TYPE AND RATING?705.2.2 SHAFT
 ENCLOSURES. ALL OPENINGS THROUGH A FLOOR
 AND PENETRATIONS THROUGH A FLOOR SHALL
 BE PROTECTED BY A SHAFT ENCLOSURE IN
 ACCORDANCE WITH 705.2.3.
  
 18) A.208:
  
 18A) STORAGE UNITS IN ROOM# 411 WILL
 REQUIRE A 3 HR WALL AROUND THE PERIMETER
 OF THE ROOM.
  
 18B) PROVIDE A CUT SECTION FOR JUST
 OUTSIDE THE FITNESS ROOM AND STORAGE
 ROOM IT APPEARS TO BE A ROOF, NO
 DETAILS.
  
 19) A.300:
  
 19A) STAIR TOWER# 1, DOOR# 103,
 1012.1.3 THE ELEVATION OF THE FLOOR
 SURFACES ON BOTH SIDES OF A DOOR SHALL
 NOT VARY BY MORE THAN 1/2 IN. (13 MM).
 THE ELEVATION SHALL BE MAINTAINED ON
 BOTH SIDES OF THE DOORWAY FOR A DISTANCE
 AT LEAST EQUAL TO THE WIDTH OF THE
 WIDEST LEAF.THRESHOLDS AT DOORWAYS
 SHALL NOT BE MORE THAN 1/2 IN. (13 MM)
 IN HEIGHT.RAISED THRESHOLDS AND FLOOR
 LEVEL CHANGES MORE THAN 1/4 IN. (6.4 MM)
 AT DOORWAYS SHALL BE BEVELED WITH A
 SLOPE NOT STEEPER THAN 1:2.
  
 19B) THE RAMP JUST TO THE LEFT OF THE
 TRASH COMPACTOR ROOM ONLY HAS A 4'-0"
 BOTTOM RAMP.11-4.8.4.(2) LANDINGS. ALL
 LANDINGS ON RAMPS SHALL NOT BE LESS THAN
 60" CLEAR, & THE BOTTOM OF EACH RAMP
 SHALL HAVE NOT LESS THAN 72" OF STRAIGHT
 & LEVEL CLEARENCE.
  
 20)A.403- A.406 ELEVATIONS:
  
 20A) ELEVATIONS, PLEASE PROVIDE THE
 POSITIVE AND NEGATIVE PRESSURES FOR ALL
 OPENINGS, INTERIOR AND END ZONES FOR ALL
 OPENINGS. DESIGN TO ASCE 7-98
  
 20B) PLANS INDICATE THE USE OF FOAM
 BANDS, SEE 1404.1.1 ARCHITECTURAL TRIM
 ON BUILDINGS OF TYPE I, II AND IV
 CONSTRUCTION NOT MORE THAN THREE STORIES
 OR 40 FT (12.2 M) HIGH MAY BE OF TYPE VI
 CONSTRUCTION, AND MAY BE OF TYPE VI
 CONSTRUCTION ON ALL BUILDINGS OF TYPE
 III, V AND VI CONSTRUCTION.TRIM SHALL
 BE SECURED TO THE WALL WITH METAL OR
 OTHER APPROVED BRACKETS OR FASTENERS.
 WHEN ARCHITECTURAL TRIM IS LOCATED ALONG
 THE TOP OF EXTERIOR WALLS, IT SHALL BE
 COMPLETELY BACKED BY THE EXTERIOR WALL
 AND SHALL NOT EXTEND OVER THE TOP OF
 EXTERIOR WALLS.
  
 20C) EXTERIOR ALUMINIUM RAILINGS TO
 COMPLY WITH1608.2.2.1 GUARDRAIL SYSTEMS
 SHALL BE DESIGNED AND CONSTRUCTED FOR A
 CONCENTRATED LOAD OF 200 LB (890 N)
 APPLIED AT ANY POINT AND IN ANY
 DIRECTION AT THE TOP OF THE GUARDRAIL.
 1608.2.2.4 LOADING CONDITIONS IN
 1608.2.2.1, ?1608.2.2.2 AND 1608.2.2.3
 SHALL NOT BE APPLIED SIMULTANEOUSLY, BUT
 EACH SHALL BE APPLIED TO PRODUCE MAXIMUM
 STRESS IN EACH OF THE RESPECTIVE
 COMPONENTS OR ANY OF THE SUPPORTING
 COMPONENTS.
  
 20D)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 20E)1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 1) GLAZED OPENINGS LOCATED WITHIN 30 FT
 OF GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
 20F) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS FIXED/ STOREFRONT
 B) WINDOWS OPERATABLE
 C) MULLIONS
 D) EXTERIOR DOORS GLAZED, SLIDERS
 E) EXTERIOR LOUVERED DOORS
 F) DOORS STEEL
 G)EXTERIOR OVERHEAD DOORS
 H)HANDRAILS
 I) STORM SHUTTERS
 J) TRUSS ANCHORS
 K) ROOFING ASSEMBLIES
 L) PREMANUFACTURED A/C STANDS
 M) STORM SHUTTERS
  
 20G)) AN INTERPRETATION FROM THE
 BUILDING OFFICIAL ON STORM SHUTTERS THAT
 ARE USED ON LARGE PROJECTS:
 QUESTION# 13) RECOGNIZING SUCH CONCERNS
 AS ABSENTEE OWNERS, OR CASES WHERE
 LONGER TIME AND EFFORT IS NECESSARY TO
 SECURE SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING
 RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING
 IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE EVENT?
  
 IN MATTERS FLORIDA BUILDING CODE, 2004
 EDITION, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT
 REQUIREMENTS FOR ENSURING STABILITY,
 STRENGTH, AND PROPER OPERATION OF
 EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF
 SHUTTERS ON LARGE OR MULTI-STORY
 BUILDING, OR MULTIPLE BUILDINGS ON THE
 SAME PROPERTY, PRE-STORM PREPARATION
 PLANS MUST BE SUBMITTED BY THE PROPERTY
 OWNERS OR MANAGING AGENTS FOR REVIEW BY
 THE CONSTRUCTION SERVICES DEPARTMENT.
 ANY SUCH PLAN SHALL INCLUDE, AT A
 MINIMUM, ON-SITE LOCATION OF SHUTTERS,
 PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS (SAID PARTIES MUST BE LOCATED
 WITHIN PALM BEACH COUNTY), TOTAL NUMBER
 OF OPENINGS TO BE PROTECTED AND TOTAL
 TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE
 ACCOMPLISHED WITHIN TWELVE (12) HOURS OR
 LESS OF THE OFFICIAL NOTIFICATION BY THE
 NATIONAL WEATHER SERVICE OF A HURRICANE
 WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND
 THIS STANDARD) ARE NOT INTENDED TO
 PROHIBIT THE USE OF ALTERNATIVE
 MATERIALS AND METHODS, AND ALLOW THE
 BUILDING OFFICIAL TO REVIEW AND APPROVE
 ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE
 RESISTANCE, DURABILITY AND SAFETY
 PRESCRIBED BY CODE. BASED UPON THIS CODE
 PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON
 A CASE-BY-CASE BASIS AND SHALL REQUIRE
 SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING
 THE ALTERNATE.
  
 QUESTION# 14) ARE REMOVABLE STORM PANELS
 APPROPRIATE FOR USE ON VERY LARGE, MID
 OR HIGH-RISE STRUCTURES?
  
 NO, EXCEPT ON THE GROUND FLOOR. ON
 COMMERCIAL AND MULTI-UNIT RESIDENTIAL
 STRUCTURES, ABOVE THE FIRST LEVEL,
 IMPACT RESISTANT GLAZING OR PERMANENTLY
 AFFIXED PROTECTIVE DEVICES SHALL BE
 INSTALLED. PERMANENTLY AFFIXED
 PROTECTIVE DEVICES SHALL REQUIRE THE
 WRITTEN APPROVAL OF THE BUILDING
 OFFICIAL.
  
 20H) PROVIDE STORM PANEL INFORMATION
 WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.
 FBC 1606.1.4.
  
 20I) FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 20J) PROVIDE ROOF PRESSURE ZONES FOR
 ZONES 1,2& 3. SEE 1606.6/ ASCE 7-98.
  
 21) A.550/ A.650:
  
 21A) THERE ARE VARIOUS
 DETAILS SHOWING ROOF SECTIONS WITH METAL
 STUD FRAMING. THERE IS NO NOTES AS TO
 THE TYPE OF FRAMING MEMBER TO BE USED,
 IF STRUCTURAL, SIZE, GAUGE, DESCRIPTION
 OF TYPE FRAMING , FLANGE WIDTH OR
 MATERIAL THICKNESS. C/C.
 PLANS DO NOT PROVIDE WHAT TYPE OF
 DECKING IS TO BE USED ON THIS PROJECT.
  
 21B)SECTION 06 IS FOR A SUN SHADE, A
 SEPERATE PERMIT IS REQUIRED. PROVIDE
 ENGINEERING FOR FRAME & CANVAS FOR 140
 MPH WIND.
  
 21C) SECTION 07 IS A DESIGN THAT WILL BE
 INCORPORATED INTO THE GUARDRAIL DESIGN.
 1015.3 OPENINGS. OPEN GUARDRAILS SHALL
 HAVE INTERMEDIATE RAILS OR ORNAMENTAL
 PATTERN SUCH THAT A 4-INCH (102 MM)
 DIAMETER SPHERE CANNOT PASS THROUGH ANY
 OPENING UP TO A HEIGHT OF 34 INCHES.A
 BOTTOM RAIL OR CURB SHALL BE PROVIDED
 THAT WILL REJECT THE PASSAGE OF 2-INCH
 (51 MM) DIAMETER SPHERE.
  
  
 22) A.651:
  
 22A) DETAIL# 05 PROVIDE PRODUCT TESTING
 REPORT FOR EXHAUAST FAN FOR PRESURES+/-
 ZONES 1,2 & 3.
  
 22B) DETAIL# 09 IS A BOXED IN RAIN
 LETTER, PLEASE PROVIDE LOCATON ON FLOOR
 PLAN, MORE COMMENTS MAY APPEAR.
  
 22C) DETAIL# 14 RAILING TO MECHANICAL
 PENTHOUSE PROVIDE THE HEIGHT OF
 GUARDRAIL?1015.2 HEIGHT. GUARDRAILS
 SHALL FORM A VERTICAL PROTECTIVE BARRIER
 NOT LESS THAN 42 INCHES (1067 MM) HIGH.
  
 22D) DETAIL# 22 REMOVE THE WORD
 TOWNHOUSE,
  
 23) A.701 ELEVATOR MACHINE ROOMS;
  
 23A) 3003.6.1 VENTS. HOISTWAYS OF ELEVA-
 TORS SERVING MORE THAN 3 FLOORS SHALL BE
 PROVIDED WITH MEANS OF VENTING SMOKE AND
 HOT GASES TO THE OUTER AIR IN CASE OF
 FIRE.
  
 23B)3003.6.2 VENTS SHALL BE LOCATED
 BELOW THE FLOOR OR FLOORS AT THE TOP OF
 THE HOISTWAY, AND SHALL BE EITHER DIR-
 ECTLY TO THE OUTER AIR OR THROUGH NON-
 COMBUSTIBLE DUCTS TO THE OUTER AIR.
  
 23C)3003.6.3 THE AREA OF THE VENTS
 SHALL BE NOT LESS THAN 3 SQ FT FOR EACH
 ELEVATOR CAR, WHICHEVER IS GREATER.
  
 24)SHEET A.704:
  
 24A) TRASH CHUTE PLANS DO NOT INDICATE A
 TWO HR WALL FOR SHAFT.705.2.4.2 REFUSE
 AND LAUNDRY CHUTE ENCLOSURES. A SHAFT
 CONTAINING AREFUSE OR LAUNDRY CHUTE
 SHALL BE USED FOR NO OTHER PURPOSE AND
 SHALL BE PROTECTED BY A SHAFT ENCLOSURE
 IN ACCORDANCE WITH ?705.2.3.
  
 24B)705.2.4.6 AUTOMATIC SPRINKLERS. AN
 APPROVED AUTOMATIC SPRINKLER SYSTEM
 SHALL BE INSTALLED AT THE TOP AND AT
 ALTERNATE FLOOR LEVELS IN REFUSE AND
 LAUNDRY CHUTES AND IN THE TERMINATION
 AND INCINERATOR ROOMS.
  
  
 24E) 705.2.4.2 REFUSE AND LAUNDRY CHUTE
 ENCLOSURES.ALL OPENINGS INTO THE SHAFT
 ENCLOSURE, INCLUDING THOSE FROM ACCESS
 ROOMS AND TERMINATION ROOMS, SHALL BE
 PROTECTED IN ACCORDANCE WITH TABLE
 705.1.2.SUCH OPENING PROTECTIVES SHALL
 BE SELF-CLOSING OR AUTOMATIC-CLOSING
 UPON DETECTION OF SMOKE, EXCEPT THAT
 THE OPENING PROTECTIVE BETWEEN THE SHAFT
 AND THE TERMINATION ROOM MAY BE CLOSED
 BY A HEAT-ACTIVATED DEVICE.
  
 25) SHEET A.801-A807A/ A.903
  
 25A) SEE FAIR HOUSING PRIMARY ENTRY
 DOORS AS WELL AS USABLE DOORS .SEE PAGES
 3.1-3.5
 ACCESSIBLE DOORS- DWELLING UNIT ENTRY
 DOORS ARE TO MEET ANSI 4.13 WITH A 32"
 CLEAR MEAASUREMENT, A 2'-10" DOOR
 REQUIRED.
 USABLE DOORS- 32" NOMINAL CLEAR WIDTH
 IS REQUIRED FOR USABLE DOORS.
  
 25B) A901-A902 DOOR SCHEDULE FOR ALL
 FIRE RATED DOORS THE HARDWARE SCHEDULE
 IS MISSING REQUIRED SILLS. 705.1.3.1
 SILLS, IN ACCORDANCE WITH THE
 REQUIREMENTS OF NFPA 80.
  
 26) A903 :
  
 26A)DOOR NOTES,HURRICANE MISSLE IMPACT
 NOTES , FRENCH DOORS TO COMPLY WITH
 STATEMENT 20G.
  
 26B) BURGLAR INTRUSION NOTES
 3) INDICATE USE OF BOLTS OR PINS FOR
 EXTRA SECURITY DEVICES, SEE FAIR HOUSING
 SECONARY EXTERIOR DOORS, SLIDING GLASS
 DOORS PAGE 3.10-3.12 FOR CLEAR WIDTH AND
 HARDWARE.
  
 (7) INACTIVE LEAF OF A PAIR OF DOORS
 SHALL BE PROVIDED WITH MULTIPLE POINT
 LOCKS AS REQUIRED BY PRODUCT APPROVALS.
 AGAIN THESE LOCKS HAVE TO BE ABLE FOR
 THE HANDICAPPED TO BE ABLE TO OPERATE
 FROM A WHEELCHAIR!!!!!
  
 27) A9.05
  
 27A) DETAILS FOR RATED WALL U-419/ U-423
 WITH A RATED CEILING RAE NOT SHOWN IN
 THE UL DIRECTORY, IN BOTH CASES UL
 STATES THE DRYWALL IS TO GO TO THE FLOOR
 OR ROOF DECK ABOVE.
 704.2.1.3 ALL OTHER PARTITIONS REQUIRED
 TO HAVE A FIRE RESISTANCE RATING SHALL
 EXTEND FROM THE TOP OF THE FLOOR BELOW
 TO THE CEILING ABOVE AND SHALL BE
 SECURELY ATTACHED THERETO.WHERE SAID
 CEILING IS NOT A PART OF AN ASSEMBLY
 HAVING A FIRE RESISTANCE RATING AT LEAST
 EQUAL TO THAT REQUIRED FOR THE
 PARTITION, THE PARTITION SHALL BE
 CONSTRUCTED TIGHT AGAINST THE FLOOR OR
 ROOF DECK ABOVE.
  
 27B) MASONARY WALLS DO NOT GIVE THERE
 MINIMUM EQUAVALENT THICKNESS FOR HOUR
 RATING.
  
 27C) WALL TYPE NOTES:
 ALL PLYWOOD SHEATHING TO BE FIRE
 RETARDANT TREATED PLYWOOD. SEE SECTION
 604 ALL STRUCTURAL MEMBERS ARE TO BE
 NONCOMBUSTIBLE WITH VARYING HR RATINGS
 TABLE 600 PROVIDES THE HR RATINGS
 REQUIRED FOR EACH TYPE OF STRUCTURAL
 COMPONENT. FIRE RETARDANT TREATED
 PLYWOOD WHEN EXPOSED TO FLAME WILL BURN
 AS LONG AS FIRE IS AVAILABLE.
  
 28) S-0.00
  
 28A) CODES INDICATE FBC 2001 BUT ALL
 REFRENCES 02 ACI 318-02 CORRECT
  
 28B)
 WIND LOADS ARE FIGURED 130MPH SHOULD
 READ 140 MPH 3 SECOND GUST,
 AND ASCE 7-98
  
 28C) IMPORTANCE FACTOR 1 IS BUILDINGS
 SUCH AS FARM BUILDINGS RECLASSIFY
  
 28D) EXPOSURE CATEGORY "C" THE CITY IS
 LOCATED IN A "B" ZONE, IF DESIGNING TO
 THE MORE RIGID "C" ZONE THE PRESSURES
 REQUESTED ITEM (20A) WILL HAVE TO
 REFLECT THE HIGHER VALUES FOR WALLS
 OPENINGS AND ROOF PRESSURES.
  
 28E) THRESHOLD BUILDING INSPECTION PLAN:
 WRONG ADDITION TO ASCE7-98 CORRECT
 EDITION FOR FBC 2001.
 28F) BALCONY MOISTURE PROTECTION THIS
 SECTION OF THE CODE IS FOR THE HIGH WIND
 VELOCITY ZONES DADE & BROWARD ONLY!
  
 29) S3.2 FOTTER, COLUMN & BEAM SCHEDULES
 NOT FILED IN MUST COMPLETE FOR REVIEW.
  
 30) M0.2
  
 30A) ROOF TOP CONDENSING UNITS TO MEET
 THE CLEARENCE REQUIREMENTS:
 1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
  
  
 30B) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 PLANS ARE NOT COMPLETE ENOUGH TO DO A
 THOROUGH PLAN REVIEW, ADDITIONAL
 COMMENTS MAY OCCUR ON THE NEXT REVIEW
 WITH THE NEW INFORMATION BEING
 SUBMITTED.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-20 Cont ID  
Sent By dpalmer Date 2005-12-20 Time 10:40 Rev Time 10.00
Received By dpalmer Date 2005-12-19 Time 18:28 Sent To  
Notes
2005-12-20 00:00:00********* UNSAT ************
  
  
 MIZNER LAKES BLDG #4.
  
  
 1)NOTE: PLEASE CORRELATE BLDG PLANS AND
 PERMIT APPLICATION WITH ELECTRICAL
 PLANS. PLEASE SEE BLDG SHEETS INDICATE
 120 UNITS, ALTHOUGH PERMIT APPLICATION
 AND ELECTRICAL PLANS INDICATE 117.
 PLEASE ALSO CORRELATE SQ FT FROM BLDG
 SHEET (A) WITH ELECTRICAL PLANS AS THE
 A/C SQ FT DO NOT SEEM TO MATCH UP.
  
 2)NOTE: PLEASE SEE ALL ARCHITECTUAL
 SHEETS CONTAIN A "RUBBER STAMP" IN LEIU
 OF THE REQUIRED ORIGINAL SIGNATURE FROM
 THE ARCHITECT OF RECORD. FS 481.221
 PLEASE ALSO SEE BLDG REVIEW COMMENTS.
 THIS IS NOT A KAMM CONSULTING COMMENT.
  
 3)NOTE: PLEASE BE SURE ALL ARCHITECTUAL
 AND ELECTRICAL SHEETS CONTAIN REFERENCE
 TO THE 2002 NFPA-70, 2003 NFPA-101,
 2002 NFPA-72, NFPA-20 2002 WITH ANY
 OTHER CODES CURRENTLY IN EFFECT NEEDED.
  
 4)NOTE: PLEASE SEE FP SHEETS AND A
 SHEETS INDICATE A FIRE PUMP AND FIRE
 HOUSE, HOWEVER THERE IS NOT INDICATION
 OF THIS ON ELECTRICAL RISER ETC.
 PLEASE KNOIW, AS PER DISCUSSION WITH
 CHIEF ELECTRICAL INSPECTOR AND FIRE
 MARSHAL'S OFFICE, GENERATOR BACK UP MAY
 BE REQUIRED IF ELECTRIC FIRE PUMP AND
 NOT DIESEL.
 IT WAS ALSO MENTIONED THERE MAY BE ONE
 FOR EACH BLDGOR ONE FOR BOTH?
 PLEASE SEE NFPA-20 FOR MIN REQUIREMTNS
 AND 695 OF NEC.(2002).
  
 5)NOTE: IF AN ELECTRICAL FIRE PUMP IS
 INSTALLED, PLEASE SUBMIT ALL
 SPECS/MANUFACTURES CUT SHEETS FOR PUMP,
 FIRE PUMP CONTROLLER, GENERATOR AND ANY
 SUB-BASE FUEL TANKS.
 PLEASE BE SURE ALL SPECS/CUT SHEETS
 CONTAIN A LISTING FROM A NRTL.
  
 6)NOTE: PLEASE PROVIDE COMPLETE
 PHOTOMETRICS FOR ALL EGRESS PATHS,
 CORRIDORS, GARAGES, STAIRS TOWERS.
 PLEASE SEE 101, 7.8 WHICH REQUIRES A MIN
 OF 10 FT CANDLES UNDER NORMAL POWER AND
 1 FT CANDLE MIN UNDER EMERGENCY POWER OR
 BATTERY BACK UP.
  
 7)NOTE: PLEASE KNOW, A MIN BATTERY BACK
 UP FIXTURE OF SOME TYPE WILL ALSO BE
 REQUIRED IN MAIN ELECTRICAL RM,
 ELECTRICAL RMS, FIRE PUMP RM/HOUSE,
 ELEVATOR EQUIPMENT RMS.
 700.16,7.8,7.9 ETC.
  
 8)NOTE:PLEASE SEE 620.23 WHICH ALSO
 REQUIRESDEDICATED BRANCH CIRCUIT(S)
 FOR RECEPT IN ELEVATOR MACHINE ROOM.
  
 9)NOTE: PLEASEIDENTIFY THE FIXTURE
 TYPES IN STAIR TOWERS. PLEASE LABEL.
  
 10)NOTE: PLEASE PROVIDE DETAIL FOR
 DISCONNECT(S) FOR ROOF TOP UNITS.
 440.11, MAY BE A "TYPICAL" DETAIL FOR
 CU'S.
  
 11)NOTE: PLEASE COMPLETE ALL CIRCUITING
 ON PLANS, INCLUDING ALL COMMON AREAS ,
 PLEASE ALSO SEE UNITS WHICH ARE MISSING CIRCUITING.
 MOST ARE ON PLANS SOME ARE
 MISSING. SEE SOME REDLINED.
  
 12)NOTE: PLEASE PROVIDE ALL AREA AND
 ROOM DESIGNATIONS ON PLANS. NEED TO
 VERIFY FOR CIRCUITING OF DINING AREAS
 ETC.
  
 13)NOTE: PLEASE SEE 210.52B1 WHICH
 REQUIRES RECEPTS IN DINING AREAS/ROOMS T
 BE ON THE ONE OR MORE SMALL APPLIANCE
 CIRCUITS. PLEASE SEE LIGHTING ETC MAY
 NOT BE ON THESE CIRCUITS. THIS WOULD
 ALSO INCLUDE ANY BREAKFAST NOOKS/AREAS.
  
 14)NOTE: PLEASE SEE SOME UNITS WHICH
 INDICATE "J-BOX" FOR HABITABLE
 RMS/EGRESS PATHS WILL BE REQUIRED TO
 CONTAIN SOME SORT OF LIGHT FIXTURE TO
 MEET 210.70, LS101 7.8
 PLEASE SEE REDLINED PLANS.
  
 15)NOTE: PLEASE BE SURE FIXTURE SCHEDULE
 CORRELATE WITH PLANS AND "LABELING" OF
 SOME SORT ALSO CORRELATES.
  
 16)NOTE: PLEASE SEE NFPA-72 11.5.1.1
 WHICH REQUIRES ALL SMOKE DETECTORS TO BE
 WIRED "INLINE", HOWVER PLEASE SEE
 REDLINED PLANS WHERE SD'S IN THE SAME
 UNITS ARE ON MORE THAN ONE CIRCUIT.
  
 17)NOTE: PLEASE CORRELATE ALL CIRCUITING
 OF SD'S ON PLANS WITH PANEL SCHEDULES.
 PLEASE SEE THERE ARE MANY SD'S SHOWN ON
 DIFFERENT CIRCUITS OTHE THAN WHAT IS
 LISTED ON PANEL SCHEDULE.
  
 18)NOTE: PLEASE SEE MANY SD'S WHICH DO
 NOT INDICATE THE REQUIRED ARC FAULT
 PROTECTION AS MANY OTHERS ARE SHOWN.
 MAY ALSO INDICATE LISTING OF REQUIRED
 ARC FAULT CIRCUITS IN PANEL SCHEDULES.
 210.12, 2002 NEC.
  
 19)NOTE: PLEASE SEE 210.11C, 220.16B
 WHICH REQUIRES A MIN OF 1.5KW FOR
 LAUNDRY/WASHER CIRCUITS.
 PLEASE SEE MOST SHOWN AS 1.2KW, AND SOME
 SHOWN WITHOUT LOADS.
  
 20)NOTE: PLEASE SEE ONLY ONE UNIT PANEL
 SCHEDULE CONTAINS THE "**" AT LOAD
 LOCATIONS.(REDLINED)
  
 21)NOTE: PLEASE CORRELATE ALL SQ FT
 CALCULATIONS ON ELECTRICAL PLANS WITH
 "A" SHEETS WHICH DOES NOT CORRELATE WITH ELECTRICAL SQ
 FT.
  
 22)NOTE: PLEASE MOVE MANY SD'S INTO
 BEDRM AREAS. PLEASE SEE MANY UNITS SEEM
 TO INDICATE SOME SORT OF CEILING HEIGHT
 CHANGE LINE.
 PLEASE SEE NFPA-72 11.8.3.5 WHICH
 REQUIRES ALL SD;S TO BE LOCATED WITHIN
 12" OF A FLAT CEILING, AND WITHIN 3' OF
 THE PEAK OF A SLOPED CEILING.
 PLEASE ADJUST LOCATIONS.
 PLEASE SEE REDLINED PLANS. C3,C4 ETC
  
 23)NOTE: PLEASE SEE PANEL SCHEDULES NOTE
 SD'S AND KITCHEN LTS, HOWEVER MANY UNITS
 SHOWS SD'S TO OTHER BEDRM CIRCUITS.
 PLEASE ALSO SEE PREVIOUS NOTE LISTED
 ABOVE WITH RESPECT TOARC FAULT AND
 CIRCUIITNG.
  
 24)NOTE: PLEASE SEE LOCATIONS ON PLANS
 FOR MISSING RECEPTS PER 210.52, DINING
 RM WALL C-2, RAIL AREAS,WALLS BY STAIRS
 ETC.SEE OTHERS REDLINED.
  
 25)NOTE: PLEASE INDICATE THE REQUIRED
 GFI PROTECTION FOR JACUZZI TUB, RECEPT/BRKR.680.71
  
 26)NOTE: PLEASE IDENTIFY THE PANELS IF
 THEY ARE "TYPICAL" FOR MULTIPLE UNIT
 TYPES, (A,B, C ETC).
  
 27)NOTE: PLEASE SEE SOME CIRCUITING
 MISSING ON PLANS FOR BATH ETC C-5
  
 28)NOTE: PLEASE SEE 210.70 FOR MIN LT
 REQUIRED FOR A/C CLOSETS.
  
 29)NOTE: PLEASE SEE CLOTHES CLOSET FOR
 MIN CLEARENCE REQUIRED FOR LT
 FIXTURE(S).
 410.8, SEE REDLINED.
  
 30)NOTE: PLEASE SEE POSSIBLE MISSING
 RECEPT FOR KITCHEN COUNTERSPACE PER
 210.52C1, C-4
  
 31)NOTE: PLEASE VERIFY TYOE OF CONTROLS
 LABLED AS FUTURE FOR J-BOX RIGHT ON THE
 EDGE OF THE JACUZZI???
 PLEASE SEE 680 FOR MIN CLEARENCES FOR
 ANY PROPOSED DEVICES.
  
 32)NOTE: PLEASE SEE 210.52D FOR MISSING
 BATH GFI RECEPT(S) REQUIRED. TH3 ETC
  
 33)NOTE: PLEASE SEE 210.11C3 WHICH ONLY
 PERMITS TWO WAYS OF CIRCUITING FOR
 DEDICATED BATH CIRCUIT(S).
 PLEASE SEE PLANS INDICATE MORE THAN ONE
 BATH ON THE SAME CIRCUIT.
 TH3 ETC, PLEASE ADJUST ANY OTHERS AS
 NEEDED.
  
 34)NOTE: PLEASE PROVIDE MIN CURB DETAIL
 FOR THROUGH FLOOR PENETRATIONS.368.6
 FOR BUS-DUCT RISER.
  
 35)NOTE: PLEASE SEE MANY A/C HEAT LOADS
 ARE SHOWN AS "0"??
 PLEASE ALSO SEE OTHERS WHICH INDICATE
 65% OF 4KW AS 20KW? PLEASE RE-FIGURE
 LOADS FOR A/C'S AND PLEASE ADJUST PANELS
 AND LOAD CALCULATIONS.
  
 36)NOTE: PLEASE PLACE NOTE ON "ROOF TOP"
 PLANS WHICH WILL BE WORDED TO MENTION:
 ANY PROPOSED LIGHTNING PROTECTION
 SYSTEM, SHALL BE INSTALLEDPER
 NFPA-780" OR WORDS TO THAT AFFECT.
  
 37)NOTE: PLEASE VERIFY FEEDER CONDUCTOR
 TYPES FOR UNITS. COPPER, ALUMINUM.
  
 38)NOTE: PLEASE VERIFY WHY MSB AND SBA
 BOTH INDICATE GFP PROTECTION, WHEN
 240.13, 230.95 ETC DOES NOT SEEM TO
 TRIGGER THE REQUIREMENT. THIS IS NOT A
 CODE COMPLIANCE VIOLATION AND MAY BE
 DONE, IT IS ONLY NOTED, AS IF THIS IS
 SHOWN ON PLANS, THEN THIS WILL BE
 REQUIRED.
  
 39)NOTE: PLEASE SEE 200A OPC FROM MSB TO
 PANEL L1HB WHICH IS SHOWN AS A 125A
 PANEL.
  
 40)NOTE: PLEASE VERIFY MSB SCHEDULE
 INDICATES A "HOUSE PUMP" ON MSB-8,
 HOWEVER RISER DIAGRAM DOES NOT CORRELATE
 WITH THIS?
  
 41) NOTE:PLEASE VERIFY THE LAUNDRY
 CIRCUIT ON KITCHEN WALL? TH1
 SHOWN IN WHAT APPEARS TO BE LIVING RM IN
 TH2? PLEASE SEE OTHER LOCATIONS AND
 CORRELATE WITH ACTUAL LOCATIONS OF ANY
 SUCH WASHER/LAUNDRY UNITS.
  
 ** PLEASE SEE MANY OF THE ABOVE ITEMS
 HAVE BEEN REDLINED AT LOCATIONS OF
 COMMENTS ON ONE SET OF THE PLANS
 SUBMITTED.
  
 **PLEASE SEE ANY POSSIBLE COMMENTSFROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL PLANS/DESIGN.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 FROM SETS COMPLETELY AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING. ONE SET OF ALL
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-12-19 00:00:00PLANS WILL GO INTO "F" STATUS,
 NOTES TO FOLLOW UPON COMPLETION OF
 REVIEW.
2005-12-15 00:00:00IN ELECTRICAL FOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2005-10-19 Cont ID  
Sent By mamini Date 2005-10-19 Time 09:53 Rev Time 1.00
Received By mamini Date 2005-10-19 Time 09:53 Sent To  
Notes
2005-10-19 00:00:00FAILED:
  
 1. PLEASE SUBMIT CALCULATION FOR THE
 PROPOSED STORM WATER SYS.
 2.PLEASE SUBMIT A COPY OF THE SFWMD
 PERMIT FOR OUR RECORD.
 3. PLEASE NOTE THAT A POLLUTION
 PREVENTION PLAN MUST BE INCLUDED IN
 CIVIL, SILT FENCE, TURBIDITY BARRIER,
 ETC. IT MUST BE IN PLACED PRIOR TO ANY
 CONSTRUCTION ACTIVITIES.
 4. A SEPARATE PERMIT AT NO COST FOR ALL
 THE WORK WITHIN PUBLIC R.O.W FROM PUBLIC
 UTILITIES AND ENG. IS REQUIRED, CONTACT
 WINDEL PALMER AT 494-1086, MOT MUST BE
 PROVIDED AT THE TIME OF APPLICATION.
 5. SHEET C-8 SHOWSADDITIONAL WATER
 CONNECTION FROM EXISTING 10" WM IN HANK
 ARRON TO THE BUILDING 5, PLEASE VRIFY.
 6. SHEET C-8, COULD NOT FIND ANY WATER
 SUPPLY CONNECTION FOR BUILDING 4, PLEASE
 VERIFY.
 7. A CLEAN OUT FOR EACH SEWER LATERAL
 MUST BE PROVIDED.
 8. PLEASE NOT THAT CIVIL PLAN MUST BE
 APPROVED FOR ALL THE CONNECTIONS TO THE
 CITY SERVICES BY THE PUBLIC UTILITIES &
 ENG.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-11-30 Cont ID  
Sent By mwennerg Date 2005-11-30 Time 15:29 Rev Time 0.00
Received By mwennerg Date 2005-11-30 Time 15:29 Sent To  
Notes
2005-11-30 00:00:00******DENIED******
  
 1) NFPA 101, 2003 EDITION SHALL BE
 REFERENCED AFTER JAN. 1, 2005.
  
 2) PERMIT APPLICATION INDICATES 117
 UNITS AND SHT A-002 SHOWS 120. PLEASE
 CORRULATE.
  
 3) DO THE TURN AROUNDS MEET THE 50'
 RADIUSREQUIREMENTS OF NFPA 1?
  
 4) PARKING GARAGE TO MEET SEPARATION AND
 ALL OTHER REQUIREMENTS OF FBC AND NFPA
 88A.
  
 5) PLEASE INDICATE TYPE AND QUANTITY OF
 STORAGE PLANNED FOR POOL EQUIPMENT AREA.
  
  
 6) THE LOBBY ENTRANCE DOORS AT END OF
 CORRIDERS APPEAR TO SWING AGAINST THE
 DIRECTION OF TRAVEL.
  
 7) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENT FOR HANDRAILS AND GUARDS.
  
 8) STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 9) THE DOORS LEADING FROM POOL AREA TO
 CORRIDOR SWING AGAINST THE DIRECTION OF
 TRAVEL BASED ON OCCUPANT LOAD OF >50.
  
 10) OCCUPANT LOADS SHOWN AT STAIRS AND
 LIVING UNITS DON'T CORRULATE.
  
 11) WILL CARD READING DEVICES IMPACT
 REQUIRED EXITING?
  
 12) PLEASE REVIEW ALL DOOR SWINGS THAT
 SERVE AREAS WITH OCCUPANT LOADS GREATER
 THAN 50.
  
 13) AN ADDRESS IS REQUIRED ON BUILDING
 THAT SHALL BE A MINIMUM OF 3" IN HEIGHT
 AND CONTRASTING TO BACKGROUND.
  
 14) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION OF WALL AND CEILINGS IN
 TERMS OF CLASS A,B OR C.
  
 15) IN ACCORDANCE WITH LOCAL
 REQUIREMENTS, DUCT SMOKE DETECTORS SHALL
 BE WIRED TO CAUSE A GENERAL FIRE ALARM
 WHEN ACTIVATED.
  
 16) EXIT SIGNS ARE MISSING IN CORRIDORS
 ON SHT E-2.3.2
  
 17) EXIT SIGNS TO BE MOUNTED AT
 DISTANCES NOT TO EXCEED 100' APART.
  
 18) COOLING TOWERS TO COMPLY WITH NFPA
 214.
  
 19) FIRE ALARM SYSTEM TO BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE.
  
 20) FIRE ALARM TO BE CLASS A, STYLE D OR
 FULLY ADDRESSABLE.
  
 21) PLANS DON'T SHOW SMOKE DETECTORS IN
 CORRIDORS. PLEASE EXPLAIN.
  
 22) ARE AUDIBLE DEVICES PLANNED FOR
 LIVING UNITS?
  
 23) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS.
  
 24) FIRE PUMP TO COMPLY WITH NFPA 20,
 2003 EDITION.
  
 25) SEPARATE SHOP DRAWINGS AND PERMITS
 WITH MANUFACTURER SPEC SHEETS REQUIRED
 FOR FIRE PUMP.
  
 26) A 1000 GPM FIRE PUMP IS PROPOSED.
 PLEASE PROVIDE INFORMATION REGARDING THE
 MEETING WITH THE CITY FIRE MARSHAL AND
 WHAT ARRANGEMENT HAS BEEN ACCEPTED BY
 THIS OFFICE. PLEASE PROVIDE TOTAL OF
 WHAT BUILDINGS THE FIRE PUMP WILL
 SUPPLY.
  
 27) FDV'S ON STANDPIPES ARE REQUIRED TO
 BE 2 1/2" TO 1 1/2" REDUCER WITH CHAIN.
  
 28) IN ADDITION TO ELECTRONIC SWITCHES,
 THE DOUBLE CHECK DETECTOR ASSEMBLY SHALL
 BE SECURED WITH A LOCK AND CHAIN.
  
 29) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 30) PLANS INDICATE THAT THE BUILDING
 HEIGHT IS LESS THAN 75'. THAT WOULD NOT
 MEET THE REQUIREMENTS FOR HIGHRISE.
 PLEASE VERIFY.
  
 31) KNOX BOX WILL BE REQUIRED ON
 BUILDING AT FRONT ENTRANCE.
  
 32) NO CUTTING OR WELDING OPERATIONS TO
 OCCUR WITHOUT APPROVAL OF THE BUREAU OF
 FIRE PREVENTION AND COMPLIANCE WITH NFPA
 51B.
  
 33) LOCKING KNOX BOX CAPS REQUIRED ON
 FIRE DEPARTMENT CONNECTION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-03-03 Time   Rev Time 0.00
Received By adarroug Date 2005-09-30 Time 13:40 Sent To  
Notes
2005-10-04 00:00:00TO "COMM" BD#48/PLANS ON RACK 4 ROLLS
2005-09-30 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-01-12 Cont ID  
Sent By hmoser Date 2006-01-12 Time 09:48 Rev Time 0.00
Received By hmoser Date 2006-01-12 Time 09:48 Sent To  
Notes
2006-01-12 00:00:00PLAN DENIED BLDG. #4
 1)PLEASE MARK DUCT SIZE ON THE PLANS FOR
 FLEX DUCT.
 2) NEED RETURN GRILL SIZE ON THE PLANS
 FOR UNIT C-2 PAGE M4.1.IN THE MASTER
 BEDROOM.
 3) MISSING BATHROOM EXHAUST IN GUEST
 BATHROOM.UNITS C-1 AND C-3 PAGE M4.1
 4) PLEASE REFER TO SECTION 504.6
 DONESTIC DRYERS.(25 FT.RUN)
 5) PLEASE EXPLAIN MECHANICAL PLANS FOR
 LOBBY PAGE M4.4
 6) PLEASE REFER TO TABLE 403.3 2001 FBC
 (M) PRIVIT GARAGE.
 7) PLEASE PROVIDE TYPE OF METRIALS USED
 CONDENSER WATER PIPING ON THE PLANS.
 8) PLEASE REFER TO SECTION 602.2.1
 MATERIALS EXPOSED WITHIN PLENUMS.
 (DOORS ONMECHANICAL CLOSETS MUST BE
 NONCOMBUSTIBLE)
 9) PLEASE SUBMIT MANUFACTURERS
 INSTRUCTIONS ON AHU,CCC,AND RTU WITH
 THE PLANS.
 10)PLEASE REFER TO SECTION 306.1
 CLEARANCE FOR MAINTENANCE AND
 REPLACEMENT.
 11)PLEASE REFER TO SECTION 307.2.3
 AUXILIARY DRAIN PANS.
 12)PLEASE INDECATE ON PLANS WITCH RTU IS
 NUMBER TWO.
 13)PLEASE SUBMIT DETAIL ON AHU ON THE
 PLANS.
  
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-01-09 Cont ID  
Sent By kstevens Date 2006-01-09 Time 07:36 Rev Time 0.00
Received By kstevens Date 2006-01-09 Time 07:36 Sent To  
Notes
2006-01-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 CITY WPB CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS: THE
 PERSONAL SEAL, SIGNATURE, AND THE DATE
 THE ARCHITECT SHALL APPEAR ON ALL
 DOCUMENTS TO BE FILED FOR PUBLIC RECORD.
 THE SIGNATURE IS A "STAMP OF THE
 SIGNATURE" AND AS SUCH IS NOT APPROVED.
 THERE IS NOT DATE ON THE SEAL WHEN IT
 WAS AFFIXED TO THE PLANS. FAC
 61G1-16.003 61G1-16.004(5) & FS 481.2055
 2. SHT A.003 DETAILS 1(A)(B)(C)(D),
 2(A)(B), & 4(A)(B(C)(D), WATER CLOSETS
 ADJACENT TO WALLS SHALL BE 1'6", NOT
 1'6" MINIMUM. THIS IS AN ABSOLUTE
 MEASUREMENT. SEE PAGES 6.3 & 6.5 FHA
 DESIGN MANUAL.
 3. SHT A.003 SUBMIT DETAILS FOR SHOWERS
 PER REQUIREMENTS #6 & 7B FHA DESIGN
 MANUAL. THE CLEAR FLOOR SPACE FOR THE
 SHOWERS SHALL BE PARALLEL WITH THE
 FIXTURE AND FLUSH WITH THE CONTROL WALL.
 SEE PAGE 7.56 FHA DESIGN MANUAL.
 4. SHT A.003 UNIT DETAILS INDICATE
 "APPLICABLE TO UNITS A, B, C, D ETC. BUT
 FLOOR PLANS INDICATE UNITS C1, C2, C3,
 C4 ETC. PLEASE CORRELATE FLOOR PLANS
 WITH TYPICAL DETAILS. SECTION 104.2.1.
 5. SHT A.003 INDICATE WHICH POWDER ROOM
 DETAILS APPLY TO WHICH "TH" UNITS.
 SECTION 104.2.1.
 6. SHT A.003 DETAIL 1(C) PER HUD, THE
 BIDET HAS NO REQUIREMENTS, BUT THE BIDET
 SHALL NOT ENCROACH INTO THE CLEAR FLOOR
 SPACE OF THE WATER CLOSET.
 7. SHT A-106 BUSINESS OFFICE (553)
 ACCESS TO TOILET FACILITIES SHALL BE
 LOCATED NOT MORE THAN ONE STORY ABOVE OR
 BELOW THE EMPLOYEES REGULAR WORK AREA.
 SECTION 403.4.
 8. SHT A-108 SUBMIT CALCULATION FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 THE SF FOR EACH AREA DRAINED, ALONG WITH
 1/2 AREA OF ALL VERTICAL WALLS AND ANY
 AREA OF ROOF THAT DRAINS ONTO THE ROOF
 FROM ABOVE. SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS.
 9. SHTS A-801 THRU A-802C & A-808 ALL
 "TH" UNITS: PRIMARY LEVEL TO BE COVERED
 PER FHA DESIGN MANUAL. SHOW THE FLOOR
 PLAN FOR EACH TYPE OF "TH" UNIT WITH
 CLEAR FLOOR SPACE REQUIRED BY PAGES 7.43
 & 7.47. ALSO SHOW MAX HIEGHT FOR LAV AT
 34" REQUIRED ON PAGE 7.52 FHA DESIGN
 MANUAL.
 10. SHTS A-803 THRU A-807A INDICATE
 SPECIFICATION "A" OR "B" FOR EACH UNIT -
 BATHROOM AS REQUIRED ON PAGES 7.34 &
 7.44 OF THE FHA DESIGN MANUAL.
 11. SUBMIT A FINISH SCHEDULE FOR PUBLIC
 - COMMON USE TOILET FACILITIES ON THE
 THIRD FLOOR. SECTIONS 1204.2 & 104.2.1.
 12. SHT PO.1 PLUMBING SHEET INDEX: SHTS
 P2.6.1, P2.6.2, P2.7.1, P2.7.2, P2.8.1,
 P2.8.2, & P3.6.1 SHOWN ON THE INDEX HAVE
  
 NOT BEEN SUBMITTED. - P1.1 NOT SHOWN ON
 THE INDEX. P5.1.5 & P5.1.6 DO NOT
 REFLECT THE INDEX SHEETS. - SHTS P5.1.4,
 P5.1.5, & P6.1.4 HAVE BEEN SUBMITTED BUT
 ARE NOT ON THE PLUMBING SHEET INDEX. -
 SHT P5.1.3 ARE SANT. RISERS, BUT ARE
 INDICATED AS STORM. PLEASE CLARIFY.
 SECTION 104.2.1.
 13. ALL PLUMBING SHEETS: INDICATE RISER
 NUMBER FOR EACH SYSTEM THROUGH ALL
 FLOORS IN ORDER TO TRACE RISERS THROUGH
 BUILDING. SECTION 104.2.1.
 14. SHT P2.1.1 SD UP RISER NEXT TO 4"
 SAN DOWN (70DFU) SHOWS NO PIPING TO
 BUILDING DRAIN. SECTION 104.2.1.
 15. P2.1.2 FLOOR DRAINS IN THE TRASH
 ROOM/AREA AND IN THE CORRIDOR SHALL BE
 VENTED. SECTION 901.2.1. - 3/4"
 CONDENSATE UP NOT SHOWN ON THE FLOOR
 ABOVE. - SANT. UP NOT SHOWN ON THE
 FLOOR ABOVE. (S.W. CORNER). - RISERS
 STATE "DOWN" BUT PLUMBING LEGEND SHOWS
 "UP". (THIS IS ALSO SHOWN ON SHT P2.1.2)
 PLEASE CLARIFY SECTION 104.2.1.
 16. SHT P2.2.2 SANT. RISERS #24 & #26
 ARE NOT SHOWN ON FLOOR PLAN. - TWO SETS
 OF STORM RISERS SHOWN ON THE FLOOR PLAN
 WERE NOT SHOWN ON PREVIOUS LEVEL FLOOR
 PLAN. - ONE SET OF STORM RISERS SHOWN ON
 THE FLOOR PLAN WERE NOT SHOWN ON THE
 FOLLOWING LEVEL FLOOR PLAN. PLEASE
 CLARIFY. SECTION 104.2.1.
 17. SHT P2.3.1 SHOW THE LOCATION OF ALL
 SECONDARY DRAINS REQUIRED BY SECTION
 1107. SUBMIT CALCULATION FOR PRIMARY AND
 SECONDARY DRAINS PER 1106 & 1107. SEE
 COMMENT NUMBER 8.
 18. RETAIL SPACES ARE SHELL ONLY THIS
 PERMIT. SEPARATE PERMITS ARE REQUIRED
 FOR THE BUILDOUT FOR THE TENANT SPACES.
 THIS IS INFORMATIONAL ONLY.
 19. SHT P2.3.2 INDICATES 1-1/2" CD
 RISER, (NEXT TO LOBBY), BUT NOT SHOWN ON
 FLOOR PLAN ABOVE. PLEASE CLARIFY.
 SECTION 104.2.1.
 20. SHT P2.4.2 CONDENSATE LINE BETWEEN
 ROOMS 433 & 407 IS NOT SHOWN.
 21. SHT P2.5.1 INDICATE CONDENSATE PLAN
 NOTE NUMBER FOR AHU IN UNIT C-5A(720) -
 CONDO UNIT C-2(515) INDICATES PLAN NOTE
 #3. PLEASE CLARIFY. SECTION 104.2.1.
 22. SHT P2.5.2 CONDENSATE RISER IN
 UNIT C-1(730) INDICATES PLAN NOTE #2.
 PLEASE CLARIFY. SECTION 104.2.1.
 23. FIRST SHT P2.5.1 DOES NOT INDICATE A
 FLOOR LAVEL, SECOND SHT P2.5.1 SHOW THE
 LOCATION FOR ALL VENTS THRU ROOF AND
 INDICATE RISER NUMBER FOR EACH. -
 SUBMIT CALCULATION FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SEE COMMENT #8.
 SECTIONS 1106 & 1107 AND ALL SUBSECTONS.
 24.SECOND SHT P2.5.2 SUBMIT CALCULATIONS
 FOR PRIMARY AND SECONDARY ROOF DRAINS.
 SEE COMMENT #8. SECTIONS 1106 & 1107. -
 DRAINS FOR CCC UNITS SHALL BE LOCATED
 UNDER THE UNITS TO PREVENT TRIPPING
 HAZARDS AND TO KEEP STORM WATER FROM
 DRAINING INTO THE SANT. SYSTEM. ONE
 DRAIN FOR EACH UNIT REQUIRED. CITY CODE
 90-125(5).
 25. SHT P3.1.2 COLD WATER UP TO CHUTE
 WASHDOWN REQUIRES BACKFLOW PROTECTION.
 INDICATE METHOD OF PROTECTION. SECTION
 608.
 26. PLEASE CHECK SHEET NUMBERS AS THERE
 ARE REPEAT NUMBERS. ALSO CHECK THE SHEET
 NUMBERS AGAINST THE PLUMBING SHEET INDEX
 TO MAKE SURE ALL SHEETS ARE SUBMITTED
 AND TO MAKE SURE ALL SHEETS SUBMITTED
 ARE ON THE INDEX. SECTION 104.2.1.
 27. SHT P3.3.1 SEPARATE BACKFLOW
 PROTECTION REQUIRED FOR POOL FILL LINE.
 AN RPZV BACKFLOW IS REQUIRED. SECTION
 608.13.2.
 28. SHEET INDICATING WATER SUPPLY PLAN
 4TH FLOOR-NORTH SECTION MIS-NUMBERED.
 PLEASE CLARIFY/CORRELATE WITH PLUMBING
 SHEET INDEX. SECTION 104.2.1.
 29. SHT INDICATING WATER SUPPLY PLAN 5TH
 FLOOR "SOUTH" SECTION, PREVIOUS SHEETS
 WERE DESIGNATED AS "EAST" OR "WEST".
 THIS IS ALSO THE THIRD SHEET NUMBERED
 P3.4.2. - INDICATE WHAT DESIGNATION WSCB
 & WSH ETC STANDS FOR. - NOTE STATES "SEE
 UNIT LAYOUTS ON SHEET P4.1". SHT P4.1
 NOT SUBMITTED. SECTION 104.2.1.
 30. SHT P4.1.1INDICATES TWO "TYPICAL
 UNIT "C2" FOR THE WATER SUPPLY. ONLY ONE
 C2 FLOOR PLAN FOUND. PLEASE CLARIFY.
 SECTION 104.2.1.
 31. PLEASE SUBMIT WATER SUPPLY PLANS AND
 FLOOR PLANS FOR THE FOLLOWING UNITS:
 C-1A, C-2A, C-2B, C-2C, C-2D, C-2E,
 C-2F, C-2G, C-2H, C-5A, TH-1A, TH-1B,
 TH-1C, TH-1D, TH-2A, TH-2B, TH-2C.
 32. SHT P5.1.1 VENTS ARE REQUIRED ON THE
 FLOOR DRAINS IN THE TRASH ROOM/AREA &
 CORRIDOR. SECTION 901.2.1. - CLEANOUTS
 REQUIRED IN BLDG PLUMBING DRAIN MAXIMUM
 100' SECTION 708.3.2. - DFU'S FOR SOME
 RISERS DO NOT RELFECT THE FLOOR PLANS. -
 RISER DOES NOT REFLECT THE FLOOR PLAN
 WHERE RISER #13 CONNECTS TO THE BUILDING
 DRAIN. - INDICATE RISER # FOR VENT
 CONNECTION FOR M/B IN UNIT UPSTREAM OF
 RISER #12. PLEASE CLARIFY. SECTION
 104.2.1.
 33. CLEANOUTS FOR BUILDING DRAIN SHALL
 BE INSTALLED A MAXIMUM OF 100'. SECTION
 708.3.2. - CLEANOUT AT END OF RUN BY
 SANT. RISER #8 NOT SHOWN. - BLDG DRAIN
 DOES NOT REFLECT THE FLOOR PLAN WHERE
 THE DRAIN SPLITS TOWARD RISERS #1 &
 RISERS 4 THRU 8. SECTION 104.2.1.
 34. SHTS P5.1.3 THRU P5.1.5, EVERY VENT
 STACK SHALL CONNECT TO THE BASE OF THE
 DRAINAGE STACK. ALL RISERS WITH VENT
 STACKS SHALL COMPLY. SECTION 903.4.
 35. SHT P5.1.3 SANT RISER #2 DOES NOT
 REFLECT THE FLOOR PLAN. AN EXTRA LAV IS
 SHOWN. SECTION 104.2.1.
 36. SHT P5.1.3 SANT RISER #4 DOES NOT
 REFLECT THE FLOOR PLAN. SHOWS A SHOWER,
 BUT A TUB IS ON FLOOR PLAN.- A VENT IS
 REQUIRED ON LAV IN THE MASTER BATH.
 SECTIONS 104.2.1 & 901.2.1.
 37. SHT P5.1.3 SANT RISER #6 DOES NOT
 REFLECT THE FLOOR PLAN WHERE THE RISERS
 & BRANCH LINES CONNECT TO THE BUILDING
 DRAIN. SECTION 104.2.1.
 38. SHT P5.1.3 SANT. RISER #8 DOES NOT
 REFLECT THE FLOOR PLAN FOR 2 BATHROOM
 GROUPS ALL FLOORS, AND THE FIRST
 BATHROOM GROUP 3RD FLOOR. SECTION
 104.2.1.
 39. SHT P5.1.4 SANT. RISER #9 DOES NOT
 REFLECT THE FLOOR PLAN WHERE THE RISERS
 AND BRANCH LINES CONNECT TO THE BUILDING
 DRAIN. SECTION 104.2.1.
 40. SHT P5.1.4 SANT. RISER #10 DOES NOT
 REFLECT THE FLOOR PLAN AT LAV ARMS BY
 JAC2. SECTION 104.2.1.
 41. SHT P5.1.4 SANT. RISER #12 DOES NOT
 REFLECT THE FLOOR PLAN AT LAV ARMS BY
 JAC2, NOR WHERE THE RISERS & BRANCH
 LINES CONNECT TTO THE BUILDING DRAIN.
 SECTION 104.2.1.
 42. SHT P5.1.4 SANT. RISER #13 DOES NOT
 REFLECT THE FLOOR PLAN. 1ST & 2ND FLOORS
 ARE NOT SHOWN ON RISER. SECTION 104.2.1.
 43. SHT P5.1.4 SANT. RISER #14 DOES NOT
 REFLECT THE FLOOR PLAN AT LAV ARM NEXT
 TO JAC2. SECTION 104.2.1.
 44. SHT P5.1.4 SANT. RISERS #'S 16 & 20
 DRAIN REQUIRED FOR EACH CCC UNIT ON THE
 ROOF LOCATED UNDERNEATH THE UNITS TO
 PREVENT A TRIPPING HAZARD AND TO PREVENT
 STORM WATER FROM ENTERING THE SANT.
 SYSTEM.
 45. SHT P5.1.4 SANT RISER #17 BATHROOM
 GROUPS DO NOT REFLECT THE FLOOR PLAN 3RD
 THRU 7TH FLOORS. SECTION 104.2.1.
 46. SHT P5.1.5 SANT. RISER #18 DOES NOT
 REFLECT THE FLOOR PLAN. SECTION 104.2.1.
 47. SHT P5.1.5 SANT. RISER #21 DOES NOT
 REFLECT THE FLOOR PLAN WHERE THE RISERS
 AND BRANCH LINES CONNECT TO THE BUILDING
 DRAIN. SECTION 104.2.1.
 48. SHT P5.15 SANT. RISER #22 DOES NOT
 REFLECT THE FLOOR PLAN ON THE 1ST FLOOR
 AT TH W/C AND LAV. SECTION 104.2.1.
 49. SHT P5.1.5 SANT. RISER #23 DOES NOT
 REFLECT THE FLOOR PLAN. SECTION 104.2.1.
 50. SHTS P5.2.1, P5.2.2 & P5.2.3 -
 SECONDARY DRAINS ARE NOT SHOWN FOR THE
 POOL DECK LEVEL AS REQUIRED BY SECTION
 1107. DISCHARGE SHALL BE ABOVE GRADE IN
 A LOCATION WHICH WOULD NORMALLY BE
 OBSERVED BY THE BUILDING OCCUPANTS OR
 MAINTENANCE PERSONAL, AND SEPARATE
 SYSTEMS ARE REQUIRED FOR PRIMARY AND
 SECONDARY DRAINS. SECTION 1107.2-
 SIZING OF STORM SYSTEM TO BE CHECKED
 AFTER CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS ARE SUBMITTED.
 SECTION 1106 & 1107.
 51. SUBMIT STORM BLDG. DRAIN ISOMETRIC
 RISER DIAGRAM SHOWING ALL PIPE SIZES,
 I.D. ALL RISERS & SHOW SF AS IT
 ACCUMULATES IN THE SYSTEM.
 52. SHT P6.1.3 TYPICAL UNIT "C1" WATER
 HAMMER ARRESTORS ARE REQUIRED ON ICE
 MAKER LINE, AND ON BOTH HOT & COLD LINES
 FOR THE W/M & KITCHEN SINK. SECTION
 604.9.
 53. SHT P6.1.3 TYPICAL UNIT "C2" WATER
 HAMMER ARRESTOR REQUIRED ON COLD WATER
 AT KITCHEN SINK FOR ICE MAKER. SECTION
 604.9.
 54. SHT P6.1.3 TYPICAL UNIT "C3" WATER
 HAMMER ARRESTOR REQUIRED ON HOT WATER
 AT KITCHEN SINK & FOR ICE MAKER LINE. -
 RISER DOES NOT REFLECT THE FLOOR PLAN AT
 THE SHOWER IN M/B. SECTIONS 104.2.1 &
 604.9.
 55. SHT P6.1.3 TYPICAL UNIT "TH-1" WATER
 HAMMER REQUIRED ON ICE MAKER LINE.
 SECTION 604.9.
 56. SHT P6.1.3 SHOWS 2 OTHER "TYPICAL
 UNITS C1". THESE DO NOT REFLECT ANY
 FLOOR PLAN. PLEASE CLARIFY. SECTION
 104.2.1.
 57. SUBMIT WATER ISOMETRICS FOR THE
 FOLLOWING UNITS: C-1A, C-1B, C-2A, C-2B,
 C-2C, C-2D, C-2E, C-2F, C-2G, C-2H,
 C-5A, TH-1A, TH-1B, TH-1C, TH-1D, TH-2,
 TH-2A, TH-2B, TH-2C.
 58.SHT P6.1.4 GAS PIPING ISOMETRIC:
 SUBMIT APPROVED TABLES FOR SIZING PIPE
 PER FBC-2001 FUEL GAS CODE.
 59. INFORMATIONAL: PLANS DO NOT APPEAR
 TO BE COMPLETE AT THIS TIME. MORE
 COMMENTS MAY BE FORTHCOMING UPON NEXT
 SUBMITTAL OF PLAN AND DEPENDING UPON
 COMMENT RESPONSES.
 60. SUBMIT A DETAIL FOR THE BOILERS.
 SHOW ALL PIPING WITH PIPE SIZES, VALVES,
 ETC. PIPING SHALL INDICATE THAT ALL
 BOILERS SHALL BE DRAWN FROM
 SIMULTANEOUSLY. SECTION 104.2.1.
 61. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS APPLICATION FOR
 PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGHTS PER FBC-2001
 FUEL GAS.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 G. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 H. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
 I. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 J. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 K. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 L. IF REGULATORS ARE USED, SUBMIT MANUF.
 SPECIFICATIONS FOR THE REGULATORS. IF
 REGULATORS ARE VENTED, SUBMIT ISOMETRICS
 SHOWING SIZE, MATERIAL, AND LOCATION OF
 VENT TERMITATIONS. SECTION 104.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2006-03-03 Cont ID  
Sent By eschneid Date 2006-03-03 Time 13:49 Rev Time 0.00
Received By eschneid Date 2006-03-03 Time 13:49 Sent To  
Notes
2006-03-03 00:00:001) PER ORDINANCE NO. 3914-05, PRIOR TO
 THE ISSUANCE OF THE FIRST BUILDING
 PERMIT, THE APPLICANT/OWNER SHALL:
  
 A) RECORD PUBLIC ACCESS EASEMENTS FOR
 ROADWAYS AND ADJACENT SIDEWALKS
 THROUGHOUT THE SITE.THIS MAY BE DONE
 ON A PLAT OR SEPARATE INSTRUMENT.
  
 B) RECORD A RESTRICTIVE DEED OR COVENANT PREVENTING THE
 GATING OF ANY OF THE
 ROADWAYS IN THE MIZNER PARK RPD.
  
 C) RECORD A MAINTENANCE AGREEMENT FOR
 THE PAVERS AND LANDSCAPING IN THE HANK
 AARON DRIVE TRAFFIC OVAL.
  
 D) RECORD A MAINTENANCE AGREEMENT FOR
 THE LAKE PATH AND LANDSCAPING ADJACENT
 TO THE MIZNER LAKES RPD.
  
 2) THE MONUMENT SIGN HAS CHANGED
 LOCATION AND CONFIGURATION FROM THE
 PLANS APPROVED BY ORDINANCE NO. 3914-05.
 APPROVAL OF A MINOR AMENDMENT IS
 REQUIRED FOR THE NEW LAYOUT.
  
 3) THE DETENTION AREAS HAVE CHANGED
 CONFIGURATION FROM THE PLANS APPROVED BY
 ORDINANCE NO. 3914-05.APPROVAL OF A
 MINOR AMENDMENT IS REQUIRED FOR THE NEW
 LAYOUT.
  
 4) THE DISABLED PARKING SPACE DETAIL
 DOES NOT APPEAR TO PROVIDE ADEQUATE
 DEPTH TO PREVENT A CAR TO INTRUDE INTO
 THE DROVE AISLE.VERIFY GRAPHICALLY
 THAT THE DEPTH IS ADEQUATE.
  
 5) THE PARKING SPACE DETAILS SHALL STATE
 THAT WHEEL STOPS BE LOCATED TWO (2) FEET
 FROM THE FRONT OF THE SPACE.
  
 6) THE LANDSCAPE PLAN DOES NOT MATCH THE
 SITE AND ENGINEERING PLANS.THE
 ON-STREET PARKING AT THE NORTHWEST
 CORNER OF THE BUILDING HAS BEEN CHANGED
 FROM WHAT WAS APPROVED BY ORDINANCE NO.
 3914-05 ON THE SITE AND ENGINEERING
 PLANS BUT NOT THE LANDSCAPE PLAN.
 APPROVAL OF A MINOR AMENDMENT IS
 REQUIRED FOR THE NEW LAYOUT.
  
 7) THE LAYOUT OF THE PARKING STRUCTURE
 HAS CHANGED FROM WHAT WAS APPROVED BY
 ORDINANCE NO. 3914-05.APPROVAL OF A
 MINOR AMENDMENT IS REQUIRED FOR THE NEW
 LAYOUT.
  
 8) IS THE SPACE IN THE NORTHWEST CORNER
 OF THE GARAGE A LOADING ZONE OR A
 PARKING SPACE?IT IS LABELED
 DIFFERENTLY ON THE SITE, LANDSCAPE AND
 ENGINEERING PLANS AND SHEETS WITHIN THE
 PLANS.
  
 9) THE PARKING CALCULATION TABLE ON
 SHEET A-002 IS INCORRECT.IT SHOWS THE
 WRONG NUMBER OF UNITS COMPARED TO THE
 UNIT BREAKDOWN TABLE.IT SHOULD ONLY
 LIST THE PARKING PROVIDED WITH THE
 PERMIT FOR BUILDING NO. 4 LIMITS OF
 WORK.THE SPACES PROVIDED SHALL EQUAL
 OR EXCEED THE SPACES REQUIRED. WHILE NO
 LOADING SPACES ARE REQUIRED FOR BUILDING
 NO. 4, ENUMERATE ANY THAT ARE PROVIDED.
  
 10) PROVIDE VERIFICATION FROM THE CITY?S ENGINEERING
 AND PARKING DEPARTMENTS THAT
 THE CITY RECOGNIZES THE SAME NUMBER OF
 PARALLEL PARKING SPACES ON HANK AARON
 DRIVE AS SHOWN ON THE SUBMITTED PLANS.
 SOME OF THE SPACES ON THE PLAN SCALE OUT
 AS TOO SHORT AND THUS MAY NOT COUNT
 TOWARD THE PROVIDED PARKING.
  
 11) THE FOOTPRINT OF THE BUILDING, TO
 INCLUDE ENTRYWAYS AND SIDEWALKS, HAS
 CHANGED FROM WHAT WAS APPROVED BY
 ORDINANCE NO. 3914-05.APPROVAL OF A
 MINOR AMENDMENT IS REQUIRED FOR THE NEW
 LAYOUT.
  
 12) THE LAYOUT OF THE POOL/AMENITY DECK
 HAS CHANGED FROM WHAT WAS APPROVED BY
 ORDINANCE NO. 3914-05.APPROVAL OF A
 MINOR AMENDMENT IS REQUIRED FOR THE NEW
 LAYOUT.
  
 13) THE LAYOUT OF THE PERIMETER AND POOL
 AMENITY DECK LANDSCAPING HAS CHANGED
 FROM WHAT WAS APPROVED BY ORDINANCE NO.
 3914-05.APPROVAL OF A MINOR AMENDMENT
 IS REQUIRED FOR THE NEW LAYOUT.
  
 14) THE WATER FEATURE SHOWN ON THE PLANS
 APPROVED BY ORDINANCE NO. 3914-05 IS
 SHOWN AS A PUMP HOUSE ON THE SUBMITTED
 PLANS.WHILE STAFF PREFERS TO SEE A
 COMMUNITY AMENITY AT THIS LOCATION, A
 MINOR AMENDMENT APPROVAL IS REQUIRED FOR
 THE NEW LAYOUT.THE PUMP HOUSE NEEDS TO
 BE SCREENED BY LANDSCAPE.
  
 15) SHOW THE HANK AARON DRIVE PROPERTY
 LINE ON THE SHEETS WITH THE FLOOR AND
 ROOF PLANS INCLUDING A DIMENSION LINE TO
 SHOW THE SETBACK OF THE BUILDING,
 BALCONIES AND ROOF FROM THE PROPERTY
 LINE.
  
 16) REMEMBER THAT THE DEVELOPER IS
 RESPONSIBLE FOR CONSTRUCTING THAT
 PORTION OF THE LAKE PATH ADJACENT TO THE
 SUBJECT SITE TO CITY STANDARDS AT THE
 OWNER?S EXPENSE AND WILL CONTINUE THE
 THEME THAT HAS BEEN ESTABLISHED ADJACENT
 TO THE HOME DEPOT DEVELOPMENT PRIOR TO
 THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY FOR THE FIRST RESIDENTIAL UNIT
 IN THE MIZNER LAKES RPD. THE DEVELOPER
 OR PROPERTY OWNER?S ASSOCIATION IS
 RESPONSIBLE FOR THE MAINTENANCE OF SAID
 PORTION OF THE LAKE PATH.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.